100% found this document useful (3 votes)
182 views

220KV Protection Logic

The document provides specifications for protection schemes for various equipment in a 220kV and 33kV substation, including: 1. 220kV line bays which include distance protection and busbar protection. 2. 220kV transformer bays which include transformer differential and busbar protection. 3. 220kV bus coupler bays which include breaker failure protection and busbar protection. 4. Requirements for the busbar protection panel and schemes for 33kV transformer LV and bus sectionalizer bays.

Uploaded by

sekaran
Copyright
© © All Rights Reserved
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
100% found this document useful (3 votes)
182 views

220KV Protection Logic

The document provides specifications for protection schemes for various equipment in a 220kV and 33kV substation, including: 1. 220kV line bays which include distance protection and busbar protection. 2. 220kV transformer bays which include transformer differential and busbar protection. 3. 220kV bus coupler bays which include breaker failure protection and busbar protection. 4. Requirements for the busbar protection panel and schemes for 33kV transformer LV and bus sectionalizer bays.

Uploaded by

sekaran
Copyright
© © All Rights Reserved
Available Formats
Download as PPTX, PDF, TXT or read online on Scribd
You are on page 1/ 9

FOR 220 KV LINE

BUS CT
89 52CB 1 2 3 4 5 89L
P1 P2

MFM+BCU+EM

21L2 LINE DISTANCE

21L1 LINE DISTANCE


In case of centralised Architecture
LBB Stand alone 50Z or Spare

Low Impedance Busbar Protection


50Z+87BB
In case of centralised Architecture
LBB Stand alone
FOR 220 KV TRANSFORMER HV

BUS CT
89 52CB 1 2 3 4 5 89T
P1 P2

MFM+BCU+EM

87T2/64 & 51/50/67

87T1 TRF DIFF


In case of centralised Architecture
LBB Stand alone 50Z or Spare

Low Impedance Busbar Protection


50Z+87BB
In case of centralised Architecture
LBB Stand alone
FOR 220 KV BUS COUPLER BAY
BUS-1
BUS-2

P2 CT P1 P1 P2
CT
52CB
89A 4 3 2 1 1 2 3 4 89B

50/51/67 Either one 50/51/67


(BCPU) (BCPU)

MFM
In case of centralised Architecture MFM For
LBB Stand alone 50Z or Spare APTRANSCO
Low Impedance Busbar Protection 50Z+87BB
In case of centralised Architecture
LBB Stand alone
FOR 220 KV METERING BAY
Metering Arrangement
GENERATOR
Either one has to be followed FEEDER
BUS Provision is to be provided BUS

89A 52CB 89B

MAIN & MAIN &


CHECK CHECK
TARIFF TARIFF
METER METER

STANDBY STANDBY
TARIFF TARIFF
METER METER
FOR 220 KV METERING BAY
GENERATOR
BUS FEEDER
BUS
P2 CT P1 P1 P2
CT
52CB
89A 1 2 3 4 5 5 4 3 2 1 89B

50/51/67 Either one 50/51/67


(BCU) (BPU)

MFM for Standby


APTRANSCO ENERGY METER

In case of centralised Architecture


LBB Stand alone 50Z or Spare

Low Impedance Busbar Protection 50Z+87BB


In case of centralised Architecture
LBB Stand alone
FOR Busbar Protection Panel
1. Stand alone DC Supply for Busbar Protection and PUs. So Separate DC
Distribution with MCBs to be Provided in Busbar Protection Panel.
Similarly for PU in Panel also separate MCB to Be provided.
2. Bus PT distribution with MFMs are to be provided. MFMs with RS485
with Modbus to Transfer the data to SAS Bus Voltage & Frequency.
3. Stand alone IEC 61850 V & F relays for each Bus to be provided. ( U/O
Voltage , U/O frequency, dv/dt and df/dt)
4. All MFMs are 0.2 cls, LED Display, 140 X 140 size, 3 or 4 Line Display.
5. MFMs are any one of Accord, Satec, Meco, Conserv, Bitronics
6. Station Level SAS form a ring of ES of Developer & ES of STU and
provision for GPS & Gateway as per developer scope.
7. Separate BCUs are to be provided in BB Panel.
8. Auxiliary BCU Panel standalone for Developer & STU
9. Redundant Gateway & Redudant GPS Connection.
10.Stand alone ethernet switch for BB panel
11. DC Change over facility
12.SAS panel for Developer & STU
13.GPS Time clock 2 nos
14. invertor- 2nos each 3 KVA for Developer & STU on 220V DC & 220V
AC with Distribution
15.Furniture also as per APTRANSCO.
FOR 33 KV TRANSFORMER LV

BUS CT
89 52CB 1 2 3 4 89T
P1 P2

MFM+BCU

87 T2+64T+
51/50/67
87 TRF DIFF
PARTIAL BUSBAR
PROTECTION
FOR 33 KV BUS SECTIONALISER

BUS A CT BUS B
89A 52CB 1 2 3 4 89B
P1 P2

MFM+EM

51/50/67 (BCPU)
PARTIAL BUSBAR
PROTECTION 2
PARTIAL BUSBAR
PROTECTION 1
FOR 33 KV FEEDER

BUS CT
89 52CB 1 2 89F
P1 P2

MFM+EM

51/50/67 (BCPU)

You might also like