Current Transformer Sop
Current Transformer Sop
1. Objective.
• This test is to ensure the CT circuits are properly connected with respected cores and there is no mix up in the circuit.
• ingle point grounding shall be verified for CT circuits, before starting this test. Inject 25% of rated primary current between
one phase and earth with all connected burden. Measure secondary current at all points of CT circuits. It shall be done for
other phases.
• Procedure:
• CT ratio is described as the ratio of primary current input to secondary current output at full load. For example, a CT with
a ratio of 100:1 will produce 1 amps of secondary current when 100 amps flow through the primary.
• If the primary current changes, the secondary current output will change accordingly. For example, if 150 amps flow
through a 50 amp rated primary the secondary current output will be 0.5 amps.
Result:(33KV system voltage ct 100/1A)
CT Ratio Primary R Y B
Current (A) 1S1 – 1S2 2S1-2S2 1S1 – 1S2 2S1-2S2 1S1 – 1S2 2S1-2S2