Ring Plus Aqua Starter Gear - TERI
Ring Plus Aqua Starter Gear - TERI
Ring Plus Aqua Starter Gear - TERI
Sinnar
Nashik
Areas covered
• Furnace
• Electrical System
• Electrical Drives
• Heat treatment furnace
• Pumps, Air compressors, Fans & Blowers
• Lighting System
Electricity Energy Profile
Load trend deep valleys are observed, during the shift-change over periods & Break time,
(Morning session 7AM, 11.30AM and Evening session 7.00PM, 11.30PM).
Harmonics level at the 33kV level
30 0.30
20 0.20
% %
10 0.10
0 0.0
1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3
Ah5 Ah7 Ah9 Ah17 Ah19 Ah21
12/4/2012 - 2:30:00.000 PM 12/4/2012 - 2:30:00.000 PM
2.0 0.40
% %
1.0 0.20
0.0 0.0
1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3
Ah11 Ah13 Ah15 Ah23 Ah25 Ah27
12/4/2012 - 2:30:00.000 PM 12/4/2012 - 2:30:00.000 PM
Effect's of Harmonics
• False /Nuisance Tripping of Circuit Breaker
• Overheating of Capacitors, series/parallel resonance
• Induction type energy meter reads high/low
• Unpredictable behavior of Protective relays
• Increased losses, Noise & Vibration in Rotating Machines
• Saturation, increased Cu & Iron losses, high temp. rise in
Transformers
• Insulation failure, increased Cu. Losses in Cables
• Ballast failure, flicker in Lighting overheating
• Overheating of fuses & nuisance fuse blow
• Interference in Telecom Lines
Harmonics
• As per IEEE-519, the % voltage distortion should be below 5.0%.
Total harmonic distortion of current (%THD-I) should be below
15.0%. Regulation by State Government law.
The following are suggested to reduce the harmonics levels
25.00
25.00
20.00
20.00
15.00
15.00
%
10.00
10.00
5.000
5.000
12/5/2012
12/5/2012 2:53.000
2:53.000 (M:S)
(M:S) 12/5/2012
3:18:06.000
3:18:06.000PM
PM 34
34 Sec/Div
Sec/Div 3:20:59.000 PM
Trend @ 4505 4506 Unit
Trend @ 4507 4508 Unit
Trend @ 4509 4510 unit
kW
100.00
150.00
200.00
250.00
0.00
50.00
3:28:43 PM
3:28:46 PM
3:28:49 PM
3:28:52 PM
3:28:55 PM
3:28:58 PM
3:29:01 PM
3:29:04 PM
3:29:07 PM
3:29:10 PM
3:29:13 PM
3:29:16 PM
3:29:19 PM
3:29:22 PM
3:29:25 PM
3:29:28 PM
3:29:31 PM
3:29:34 PM
3:29:37 PM
3:29:40 PM
Time
3:29:43 PM
3:29:46 PM
3:29:49 PM
3:29:52 PM
3:29:55 PM
Loading Trend of 4313 Unit
3:29:58 PM
Trend @ 4313 unit
3:30:01 PM
3:30:04 PM
3:30:07 PM
3:30:10 PM
3:30:13 PM
3:30:16 PM
3:30:19 PM
3:30:22 PM
3:30:25 PM
3:30:28 PM
3:30:31 PM
3:30:34 PM
3:30:37 PM
3:30:40 PM
Trend @ 1104 unit
Trend @ 1204 Unit
Trend @ 1309 unit
Trend @ 1610 unit
Trend @ 1705 Unit
Trend @ 3107 Unit
Trend @ 3147 unit
Trend @ 1709 unit
Trend @ 3124 unit
Suggestion
Major Observations
Recommended to install thyrister based temperature controller for all the electric
furnace for better temperature control.
Recommended to switch ON fume suction fans, only during loading & unloading
of stock (Energy saving – 10 kW).
Educate furnace operator for better operation of electric furnace.
Tempering Furnace
50.00
40.00
kW
30.00
20.00
10.00
0.00
3:20:00 3:30:00 3:40:00 3:50:00 4:00:00 4:10:00 4:20:00 4:30:00 4:40:00 4:50:00 5:00:00 5:10:00
PM PM PM PM PM PM PM PM PM PM PM PM
Time
Lighting
Average Best SEC for Air cooled screw compressor – 0.16 to 0.17 kW/cfm
Air compressor
Energy loss, kW 40
Ring forming section
Cooling Water Pump
Parameters Unit Design Operating
Flow rate m3/h 62.4 45.1
Head m 10.5
Motor Power kW 3.7 6.0
Design flow required for the machine – 900 lpm (54 m3/hr)
• It is suggested to replace Aluminum fan blade with FRP type blade. It will
reduce fan power consumption by around 10-15%.