6th Sem Power System
6th Sem Power System
EE610
Associate Professor
Dept. of Electrical and Electronics Engineering
JSS Science and Technology University
(Sri Jayachamarajendra College of Engineering )
UNIT I
1.Alternator
2.Power transformer
3.Transmission lines
4.Substation transformer
5.Distribution transformer
6.Loads
E2 N 2 I
K 1
E1 N1 I 2
R2
R01 R1 R2 ' R1 =Equivalent resistance referred to 1o
K2
X
X 01 X 1 X 2 ' X 1 22 =Equivalent reactance referred to 1o
K
04/01/2016 Dept of EEE, SJCE 6
MODELLING OF GENERATOR AND
SYNCHRONOUS MOTOR
Π type T type
kVb kVb
2 2
Zb
MVAb KVAb
1000
Z Z Z * MVAb
Z p.u
Z b kVb 2
kVb
2
MVAb
Let kVb ,old & MVBb ,old represent old base values
Z * MVAb ,new
Z p.u ,new (3)
kV
2
b , new
2
kV MVAb ,new
Z p.u ,new Z p.u ,old
b , old
* *
kV
2
b , new
MVAb ,old
kV
2
MVAb ,new
X p.u ,new X p.u ,old
b , old
* *
kV
2
b , new
MVAb ,old
2
1
Zt Z ps Z pt Z st '
'
Yij yij
SYMMETRICAL COMPONENTS
Three-phase system
Single-line diagram
Vb2 Vb
Va2
Vc2
And Inverse of A is 1 1 1
A-1 = 31 1 a a2
1 a2 a
va 1 1 1 va 0
v 1 a 2 a v
b a1
vc 1 a a
2
va 2
va 0 1 1 1 va
v 1 2 v
a1 3 1 a a b
va 2 1 a 2
a vc
Solution:
Solution:
Ia0 = 1/3 (Ia + Ib + Ic) =0A
Ia1 = 1/3 (Ia + a Ib + a2Ic) = 10<600 A
Ia2 = 1/3 (Ia + a2 Ib + a Ic) = 0 A
UNSYMMETRICAL FAULT
ANALYSIS
UNSYMMETRICAL FAULTS
o One or two phases are involved
o Voltages and currents become unbalanced and each phase is to be treated
individually
o The various types of faults are
Shunt type faults
1.Line to Ground fault (LG)
2. Line to Line fault (LL)
3. Line to Line to Ground fault (LLG)
Series type faults
Open conductor fault (one or two conductor open fault)
IA VA
If
E ~
~ ~
If IB VB
IC VC
Figure 9
I0 1 1 1 Ia
1
I1 1 2 Ib (12)
3
1
2
I2 Ic
IA 1 1 1 I0
IB 1
2
I1 (13)
IC 1 2 I2
IB = IC = 0
IA = If (14)
VA = 0 (short-earth)
VA = 0 and since the generator is only able to generate positive sequence components,
E0 = E2 = 0
Also, since IB = IC = 0, I0 = I2 = 0
E1
I1
Z1 Z2 Z0
3E
f (14) and (15)
The fault current If = IA = 3II1 from
Z1 Z2 Z0
3E
If (18)
Z1 Z2 Z0
where E is the generated phase voltage.
where E is the generated phase voltage.
The equivalent
The equivalent circuitcircuit is given
is given by 10
by Figure
Z0 Z1 Z2
Figure 10
33 kV
X1 = X2 = 3j
~ X0 = 4j B
30 MVA
X1 = 02j pu
X2 = 01j pu
X0 = 005j pu
75
X1 0 2j 0 5j
30
75
X2 0 1j 0 25 j
30
75
X0 0 05 j 0 125 j
30
Line:
VL 2 33 2 10 6
ZB 14 5
MVA b 75 10 6
3j
X1 X2 0 207 j pu
14 5
4j
X0 0 276 j pu
14 5
1·1275j
1pu
75 10 6
I f 3 ( j0 887) = -j3·49 kA
3 33 10 3
The fault current may be reduced by increasing the impedance to the fault. Using the data of
the above example, consider the effect of earthing only one generator.
1·19j I1 I2 I0
~
1
j 84
j1 19
A
IA0
IB0
~ IC0
~ ZN ~
If
B
C
Figure 12
Z0
3ZN
Figure 13
~ 3
3 Earthing resistance = = 0 207 pu
14 5
0·5j 0·25j
0·207j 0·207j 3x0·207 0·125j 0·276j
~ 0·5j 0·25j
changed
unchanged unchanged
zero
+ve -ve
Z = ·621 + 1·19j
~ |Z| = 1·342
I0 = I1 = I2
1
I1 = (0621 - 119j)
1 342
75 106
If = 3 x (0621 - 119j) x = 293(0621 - 119j) kA
3 33 103
STABILITY STUDY
Dynamic stability
Ability of the power system to regain synchronism after small disturbances
occurring for a long time (like changes in turbine speed, change in load)
Transient stability
This concern with sudden and large changes in the network conditions i.e. .
sudden changes in application or removal of loads, line switching operating
operations, line faults, or loss of excitation.
H system d 2
pa pm pe p.u
f dt 2
Smachine
H system H machine
S system
Multiplying both sides of the above equation by dt and then integrating between two arbitrary angles δ0 and δc
If the two areas are equal, i.e., A1 = A2, then the power system will be stable