Profibus Networks102
Profibus Networks102
28/04/2003 TEXT
PROFIBUS 1(3)
FIELDBUS
i o
1
P2
4
6
5
7
EN 50170 part 2
Automation in Product Process automation
general automation PROFIBUS-PA
PROFIBUS-FMS PROFIBUS-DP IEC 1158-2
RS 485/FO RS 485/FO Depents on
General use Fast application
• Master-Slave:
– Master (which has the token) can communicate with slave
devices connected to it
– Master can send and receive messages from slaves
i 1o
P
24
576
• 3 different media:
• Type A
– Pair cable (shielded)
– Wave impedance 135 … 165
– Resistance 110 /km
– Cable diameter 0,64 mm
– Area > 0,34 mm2
– Capacitance < 30 pF/m
– Cable length:
Speed, kBit/s 9,6 19,2 93,75 187,5 500 1500 12000
Length of the segment, m 1200 1200 1200 1000 400 200 100
(Segment = PROFIBUS bus which is terminated from both ends with end resistor)
A B A B
Module 2 Module 3
FO FO
coupler coupler
FO FO
2 devices / coupler coupler
measurement point
• Connected devices:
– Active devices, Master (e.x. PLS, PC)
– Passive devices, Slave (e.x. I/O units, drives)
• Transmission speed:
– Is determined by slowest connected device
– In same network all devices have same speed
– from 9,6 kbit/s up to 12 Mbit/s
Slave
… max 126
2. ... 31. 34. ... 63. devices
Bus segment
- max 32 devices in a segment
- repeated is a physical devices (counted into 32 devices), but it does
not have a address
- max. 9 repeaters for one bus
Slave PROFIBUS PA
- speed fixed
Coupler : 31,25 kbit/s
- power supply for PA-bus - max. 10 - 30 devices
- physical device, bus has no
address
- DP-bus speed is 31,25 kbit/s, there
are couplers that can support 93,75
kbit/s bus speed for DP-bus
Slave PROFIBUS PA
DP/PA- DP/PA-
link coupler - speed fixed
Link: 31,25 kbit/s
- requires an address in DP-bus - max. 10 - 30 devices
- max. 96 links in one DP-bus
- speed in DP-bus can be 12 Mbit/s
PROFIBUS - DP
PROFIBUS - PA
SOFTWARE REQUIREMENTS
• Fieldnet Builder Programs
– For fieldbus configuration
• HONEYWELL Files for Fieldnet Builder
– Honeywell programs needed for PROFIBUS fieldbus
configuration
• Device Support Block Sets
– Device Support Blocks for devices used in the project
HARDWARE REQUIREMENTS
• FC, Field Controller (with PROFIBUS fieldbus
interface unit)
Pulp, Paper, and Printing Profibus networks
28 April, 2003 21
System requirements 2(2)
Experion PKS system
FIELDBUS INTERFACE
• Two independent fieldbus interfaces
• Implementation gives possibility to integrate many
different fieldbuses based on different fieldbus
standards
• Protocols supported now:
– Profibus
– Interbus
– DeviceNet
– LON
• One FC can in total handle even 250 fieldbus devices
connected to it’s fieldbusses
BUS 0
3 4 5 Hardware address
3 4 5 Hardware address
NIU
Slave
AI AO BI BO
3
Address in the 3
bus
Device Card Image, S.B. 1 1 1 1 1
- max. 250
NIU
Slave
AI AO BI BO
3
CARD IMAGE (S.B) 1 2 3 4 5 Binary output
application pin
Device Support Block