Generator Protection
Generator Protection
Generator Protection
Gen Stator Thermal Protection
Field Thermal Protection
Gen stator fault Protection
Gen rotor field Protection
Gen abnormal operating conditions
System backup Protection
Power transformer Protection
Generator Protection
Stator Thermal protection
Thermal Protection
Direct rotor Body temperature measurement
not possible
Core Monitor may detect overheating
Protection for field over excitation
IDMT/ Definite Time
Excitation limiters
Generator Protection
Typical setting
Voltage Based
V
o
l
Generator Grounding Practices
It is common practice to ground all types of
generators through some form of external
impedance
limit the mechanical stresses and fault damage
in the machine,
to limit transient voltages during faults, and
to provide a means for detecting ground faults
within the machine.
Typical Grounding practices
Ungrounded
Solid Grounding
High-impedance grounding
Low-resistance grounding
Reactance grounding
Grounding-transformer grounding
Generator Grounding Practices
Ungrounded
– Phase to ground fault current limited
– Generators are not often operated ungrounded
as it may produce high transient over-voltages
during faults and makes the fault location
difficult to determine.
Solid Grounding
– Solid grounding of a generator neutral is not
generally used since this practice may result in
high mechanical stresses and excessive fault
damage in the machine.
Generator Grounding Practices
High Impedance Grounding
– High resistance grounding
The high-resistance grounding method utilizes a resistor
connected across the secondary of the distribution transformer
to limit the maximum ground fault current.
For a single-phase-to-ground fault at the machine terminals, the
primary fault current will be limited to a value in the range of
about 3 A to 25 A.
– Ground fault neutralizer grounding
The ground fault neutralizer grounding method utilizes a
secondary tunable reactor to limit the maximum ground fault
current.
Low –resistance grounding
In this method, a resistor is connected directly between the
generator neutral and ground.
For a single-phase-to-ground fault at its terminals the primary
fault current will be limited to a value in the range of about 200
A up to 150% of rated full-load current.
Resistor cost and size usually preclude the use of resistors.
Stator Earth Fault Protection
Typical Setting:
– 5% with 1 Sec TD
100 % Stator E/F Protection
Disadvantages
Relay
U
a I
Neutral
transformer b
Measure
Low frequency injection method
– Modern rotor earth fault protection relay operates on
the principle of low frequency injection into the field
winding via capacitors.
– Corresponding current or resistance during E/F is sensed
Method of detection:
Impedance measurement with Under Voltage
RELAY LINE
Out of step protection
Machine runs out of synchronism with the network
Cyclic variation of rotor angle
Current increases.
Results in the winding stress
It may also damage the auxiliaries of the affected unit
Method of detection
– Variations in impedance measured at Gen Terminal
– Distinguish between the recoverable swing and the
irrecoverable swing
– blinders and a supervisory mho element,
– Trips the machine when imp is inside the mho and
cross the blinders with the specified time.
– Minimum impedance (multiple zone) + counting no
of swings
Out of step protection settings
Typical Over Fluxing Withstand
Capability
Accidental back energisation
Cause
Effects
Typical setting:
U/F O/F
Alarm - 48.5hz 5 sec 51 hz 1 sec
Trip - 47.4 hz 2 sec
Backup impedance protection
Differential
Biased differential used
biased setting 20%
Restricted E/F
High impedance
Set to 5%-10% in high impedance earthing
Backup E/F
Set to 30% rated current with delay of 1 sec
Other Protections
Overall Differential Protection (87GT)
- Covers generator, GT & UT
Typical Generator
protection
scheme
NON GCB SCHEME GCB SCHEME
TRIP LOGIC OF GENERATOR PROTECTION
Two independent channels with independent CT/VT inputs/ DC
supply/ Trip relays
b) based on CB status
and O/C
7. Instantaneous and time A A2
delayed Over Current
protection to be used on
HV side of excitation
transformer.
7. Unit Transformer UT LV UT LV CB
OTI/WTI trip CB Trip Trip &
& signal for
signal change
for over of
change unit
over of board.
unit
board.
8. Unit Transformer A A1
Buchholtz, PRD /other
mechanical Protections
9. 64 GT (For GT LV wdg & A1
UT HV wdg)
10. EHV CB/GCB LBB A A1
11. EHV BB PROTN A A1
ADDITIONAL control/protection interlocks realized through GRP