Load Calculation
Electrical System Design
Voltage Drop Calculation
Per Unit Calculation
Short Circuit Calculation
ELECTRICAL DIAGRAM
San Jose line 2
MDP-B /BUS-B, 480V, 3Ø, 60Hz
Motor Load Calculation
5.1.1 Governor oil Pump, 20HP 480V, 3Phase, 60Hz, 0.8PF,
0.90 Efficiency
From PEC 2009 page 350
From PEC 2009 Page 241 & 1541
Motor Load Calculation
From PEC 2009 page 691 & 169
Branch Circuit No. 2, 480V, 3Ø, 60Hz
BC No. 2: Power Distribution Center 1; 480V, 60Hz, 3Phase (back-up BUS A)
Thermal Size of Wire and Grounding
Size of Size of
Overload Conductor, THW (Color coded):
Item Full Load Disconnec Circuit
Equipment Description Power Rating Setting A= Black, B = Red, C = Yellow
No. Current t Switch Breaker
= + Ground = Green @ RSC
(Amperes) (Amperes)
115%xIfl Conduit
HP kW kVA Amperes Amperes mm2 3C mm2G mm RSC AT AF AT AF
1 Governor Oil Pump no. 1 20 16.578 20.722 24.926 28.665 8.0 8.0 32 40 100 70 100
2 Governor oil pump no. 2 20 16.578 20.722 24.926 28.665 8.0 8.0 32 40 100 70 100
3 Main Unit Transformer Cooling Unit 20 16.578 20.722 24.926 28.665 8.0 8.0 32 40 100 70 100
4 Rotating Amplifier 15 12.433 15.542 18.694 21.498 8.0 8.0 32 30 100 60 100
5 Generator Heater 12.000 15.000 20.047 23.055 8.0 8.0 32 30 100 50 100
6 Turbine Drain Pump 3/4 0.622 0.777 0.935 1.075 3.5 3.5 20 20 100 20 100
7 Genrator Cooling Water Valve 1/2 0.414 0.518 0.623 0.717 3.5 3.5 20 20 100 20 100
8 Turbine Grease Pump 1/2 0.414 0.518 0.623 0.717 3.5 3.5 20 20 100 20 100
9 Hydraulic Jack Pump 1/2 0.414 0.518 0.623 0.717 3.5 3.5 20 20 100 20 100
10 115kV Switch Gear Heater 6.000 7.500 10.024 11.527 5.5 5.5 25 20 100 30 100
11 Power Outlet 3.000 3.750 5.012 5.764 3.5 3.5 25 20 100 20 100
12 Spare
13 Total kVA Load 106.290 131.359 50.00 14.00 65 175 200
2 Foundation Sump Pump No. 2 30 24.867 31.083 37.389 44.973 22 8.0 40 100 100 150
50
3 Bat. Charger No. 1 3 3.750 5.012 5.764 3.5 3.5 20 20 100 20 100
4 Bat. Charger No. 2 3 3.750 5.012 5.764 3.5 3.5 20 20 100 20 100
5 Power Outlet 3 3.750 5.012 5.764 3.5 3.5 20 20 100 20 100
6 Bearing Drain Oil Pump 1 0.829 1.036 1.246 1.433 3.5 3.5 20 20 100 20 100
7 Transformer 480/240V LP # 1 12 15 18.043 20.749 8 8.0 32 100 50 100
30
8 Transformer 480/240V LP # 2 12 15 18.043 20.749 8 8.0 32 100 50 100
30
9 Transformer 480/240V LP # 3 12 15 18.043 20.749 8 8.0 32 100 50 100
30
10 Transformer 480/240V LP # 4 12 15 18.043 20.749 8 8.0 32 100 50 100
30
11 Transformer 480/240V LP # 6 12 15 18.043 20.749 8 8.0 32 100 50 100
30
12 Spare
Total kVA Load 139.092 168.810 125.00 30.00 100 225 250
2 2
IMFAC = (125%BM+TRM)*70%DF IMFCA = ((20.047 x 1.25) + (27.751))*(0.70) = 36.967 A Use: 3-22mm +8mm G THW @ 40mm Ø RSC
IMBOP = (250%BM+TRM)*70%DF IMBOP = ((20.047 x 2.50) + (27.751))*(0.70) = 54.508 A Use: 70AT/100AF, 3P trip Breaker
Given;
Phase = 3 Phase
SSTB
to
MDP
Voltage Drop Calculation
Voltage Drop Calculation
TABLE 9.1.1.9, PEC 1, 2009
Conductor Size
XL (Reactance for All R Steel Conduit
mm2
Wires ) Resistance
2.0 0.073 3.100
3.5 0.068 2.000
5.5 0.063 1.200
8 0.065 0.780
14 0.064 0.490
22 0.060 0.310
30 0.057 0.200
38 0.057 0.160
50 0.055 0.120
60 0.054 0.100
80 0.052 0.079
100 0.051 0.063
125 0.051 0.054
150 0.051 0.045
175 0.050 0.039
200 0.049 0.035
250 0.048 0.029
325 0.048 0.025
375 0.048 0.021
400 0.048 0.021
500 0.046 0.018
Voltage Drop Calculation
Voltage Drop Calculation
Voltage Drop Calculation
75 1
VD = 3 (131.359) x (0.132) 305 1 = 7.3853 V
Z = R2 + XL2
Voltage Drop (VD) Calculation for Feeder 8mm2, 75M from PPB
BC #2 to Individual Motor with the data from Chapter 4 Table 4.2.3
75 1
VD = 3 (24.926) x (0.7327) 305 1 = 8.3094 V
8.3094
%VD = x 100 = 1.7726 + 2.3490 = 4.1216 %
468.7841
Source
MVAba se = 100 MVAba se
MVASC 3LG = 2530.7 Zpu = ------------ = 0.03951 pu
X/R = 14.9594 MVASC
Rpu = Zpu cos (tan-1 X/R) = 0.00264 pu
Source
MVAba se = 100 MVAba se
MVASC 2LG = 2635.4 Zpu = ------------ = 0.03794 pu
X/R = 15.3744 MVASC
Rpu = Zpu cos (tan-1 X/R) = 0.00246 pu
Source
MVAbase = 100 MVAbase
MVASCLL = 2143.2 Zpu = ------------ = 0.04666 pu
X/R = 14.6317 MVASC
Rpu = Zpu cos (tan-1 X/R) = 0.00318 pu
477,000 CM or
0.212 Ω/mi or
0.430 Ω/mi or
Short Circuit Per Unit Calculation
Short Circuit Per Unit Calculation
Short Circuit Per Unit Calculation
Short Circuit Per Unit Calculation
SC Cable Impedance Calculation
SC Cable Impedance Calculation
SC Motor Impedance Calculation
Utility Per Bus Impedance
Short Circuit Calculation
Short Circuit Calculation
Short Circuit Calculation, Fault Point
Short Circuit Calculation, Fault # 1
Short Circuit Calculation, Fault # 1
Short Circuit Calculation, Fault # 1
Short Circuit Calculation, Fault # 1
Short Circuit Calculation, Fault # 1
Short Circuit Calculation, Fault # 1
Short Circuit Calculation, Fault # 1
Short Circuit Calculation, Fault # 1
Short Circuit Calculation, Fault # 1
=SQRT(3)*13.8*3PF
Short Circuit Calculation, Fault # 2
Short Circuit Calculation, Fault # 2
Short Circuit Calculation, Fault # 2
Short Circuit Calculation, Fault # 2
Short Circuit Calculation, Fault # 2
Short Circuit Calculation, Fault # 2
Short Circuit Calculation, Fault # 2
Short Circuit Calculation, Fault # 2
Short Circuit Summary
Short Circuit Calculation, Fault Detail