Revision Notes: By: Marta Ihuhwa Peee
Revision Notes: By: Marta Ihuhwa Peee
PEEE
Difference Between Star and Delta Connection
• The terminals of the three branches are connected to a common point.
The network formed is known as Star Connection. The three branches of
the network are connected in such a way that it forms a closed loop
known as Delta Connection.
• In a star connection, the starting and the finishing point ends of the three
coils are connected together to a common point known as the neutral
point. But in Delta connection, there is no neutral point. The end of each
coil is connected to the starting point of the other coil that means the
opposite terminals of the coils are connected together.
• In Star connection, the line current is equal to the Phase current, whereas
in Delta Connection the line current is equal to root three times of the
Phase Current.
• In Star connection, line voltage is equal to root three times of the Phase
Voltage, whereas in Delta Connection line voltage is equal to the Phase
voltage.
Difference Between Star and Delta Connection
• The Speed of the star connected motors is slow as they receive 1/√3 of the voltage but the
Speed of the delta connected motors is high because each phase gets the total of the line
voltage.
• In Star Connection, Phase voltage is low as 1/√3 times of the line voltage, whereas in Delta
Connection Phase voltage is equal to the line voltage.
• Star Connections are mainly required for the Power Transmission Network for longer
distances, whereas in Delta connection mainly in Distribution networks and is used for
shorter distances.
• In Star Connection, each winding receives 230 volts and in Delta Connection, each winding
receives 415 volts.
• Both 3 phase 4 wire and 3 phase 3 wire system can be derived in the star connection,
whereas in Delta Connection only 3 phase 4 wire system can be derived.
• The amount of Insulation required in Star Connection is low and in Delta Connection high
insulation level is required.
Substations
Substations
• What is a Substation?
A substation is a bunch of electrical devices gathered and connected in one place.
• In the single line diagram, the system component is usually drawn in the form of
their symbols. Generator and transformer connections, star, delta and neutral
earthing are indicated by symbols drawn by the side of the representation of these
elements.
single line diagrams
SDL
electrical symbols
Protective Relays
• Protective relay work as a sensing device, it senses the fault, then known its
position and finally, it gives the tripping command to the circuit breaker. The circuit
breaker after taking the command from the protective relay, disconnect the faulted
element.
• The core is laminated to reduce these to a minimum as they interfere with the efficient
transfer of energy from the primary coil to the secondary one.
• The eddy currents cause energy to be lost from the transformer as they heat up the core -
meaning that electrical energy is being wasted as unwanted heat energy.
• Laminated means 'made up of insulated layers of iron 'glued' together' rather than being in a
single solid 'lump'.
• A laminated core has a higher resistance than a non-laminated one with the same number of
domains. It therefore does not get such big a currents induced in it
Auto-transformers
• Autotransformer has only one single voltage winding which is common to both
sides. This single winding is “tapped” at various points along its length to provide a
percentage of the primary voltage supply across its secondary load. Then the
autotransformer has the usual magnetic core but only has one winding, which is
common to both the primary and secondary circuits.
Applications for Autotransformer
• The purpose of the open circuit test is to determine the no-load current and losses
of the transformer and determine the no-load parameter.
• The test is performed on the primary winding of the transformer.
• The wattmeter, ammeter and the voltage are connected to their primary winding.
• The nominal rated voltage is supplied to their primary winding with the help of the
ac source.
• The secondary winding of the transformer is kept open and the voltmeter is
connected to their terminal. This voltmeter measures the secondary induced
voltage.
• As the secondary of the transformer is open the no-load current flows through the
primary winding.
Short Circuit Test
• The short circuit test is performed the copper loss occur on the full load. The
copper loss is used for finding the efficiency of the transformer.
• Determine the equivalent resistance, impedance, and leakage reactance are
known by the short circuit test.
• The short circuit test is performed on the secondary or high voltage winding
of the transformer.
• The measuring instrument like wattmeter, voltmeter and ammeter are
connected to the High voltage winding of the transformer
• The primary winding is shortcircuited by the help of thick strip or ammeter
which is connected to their terminal.
• The low voltage source is connected across the secondary winding because of
which the full load current flows from both the secondary and the primary
winding of the transformer. The full load current is measured by the ammeter
connected across their secondary winding.