Protection of Alternators
Protection of Alternators
of
Alternators
Protection of Alternators
1) Failure of Prime-Mover
2) Failure of Field
3) Overcurrent
4) Overspeed
5) Overvoltage
6) Unbalanced Loading
7) Stator Winding Faults
Failure of Prime-Mover
When input to the prime-mover fails, the
alternator runs as a synchronous motor
and draws some current from the supply
system. This motoring conditions is
known as “Inverted running”.
Failure of Field
The chances of field failure of alternators
are undoubtedly very rare. Even if it does
occur, no immediate damage will be
caused by permitting the alternator to
run without a field for a short-period.
It is sufficient to rely on the control room
attendant to disconnect the faulty
alternator manually from the system bus-
bars.
Overcurrent
It occurs mainly due to partial breakdown
of winding insulation or due to Overload
on the supply system.
Overspeed
Overspeed is the sudden loss of all or the
major part of load on the alternator.
Modern alternators are usually provided
with mechanical centrifugal devices
mounted on their driving shafts to trip
the main valve of the prime-mover when
a dangerous overspeed occurs.
Overvoltage
The field excitation system of modern
alternators is so designed that
overvoltage conditions at normal running
speeds cannot occur.
However, overvoltage in an alternator
occurs when speed of the prime-mover
increases due to sudden loss of the
alternator load.
Unbalanced Loading
Unbalanced loading means that there are
different phase currents in the alternator.
Unbalanced loading arises from faults to
earth or faults between phases on the
circuit external to the alternator.
The unbalanced currents, if allowed to
persist, may either severely burn the
mechanical fixings of the rotor core or
damage the field winding.
Unbalanced Loading
Resistances are
usually adjustable in
order to obtain the
exact balance.
Differential Protection of
Alternators
Limitations.
The two circuits for alternator
protection shown above have their own
limitations.
It is a general practice to use neutral
earthing resistance in order to limit the
destructive effects of earth-fault currents.
In such a situation, it is impossible to protect
whole of the stator windings of a star-
connected alternator during earth-faults.
Modified Differential
Protection for Alternators