0% found this document useful (0 votes)
460 views59 pages

Power System Operation and Control: by DR Sai Ram Inkollu Professor

This document discusses economic operation of power systems through six units: 1. It introduces the economic operation of power systems by discussing different generation technologies and costs. 2. It covers hydrothermal scheduling which coordinates hydro and thermal generation to minimize costs while meeting demand. 3. It discusses unit commitment which determines which generators should be online to meet the next day's load at minimum cost. 4. It describes load frequency control which maintains system frequency within acceptable limits during normal operation and system disturbances. 5. It examines load frequency controllers which are used in load frequency control to regulate frequency deviations. 6. The final unit discusses reactive power control which aims to keep voltages within limits for reliable and efficient system operation.

Uploaded by

i sai ram
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
460 views59 pages

Power System Operation and Control: by DR Sai Ram Inkollu Professor

This document discusses economic operation of power systems through six units: 1. It introduces the economic operation of power systems by discussing different generation technologies and costs. 2. It covers hydrothermal scheduling which coordinates hydro and thermal generation to minimize costs while meeting demand. 3. It discusses unit commitment which determines which generators should be online to meet the next day's load at minimum cost. 4. It describes load frequency control which maintains system frequency within acceptable limits during normal operation and system disturbances. 5. It examines load frequency controllers which are used in load frequency control to regulate frequency deviations. 6. The final unit discusses reactive power control which aims to keep voltages within limits for reliable and efficient system operation.

Uploaded by

i sai ram
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 59

POWER SYSTEM OPERATION

AND CONTROL

By
DR SAI RAM INKOLLU
Professor
UNIT-1

Economic Operation of Power


Systems

2
Power System Economic Operation
• Different generation technologies vary in the:
– capital costs necessary to build the generator
– fuel costs to actually produce electric power

• For example:
– nuclear and hydro have high capital costs and low operating costs.
– Natural gas generators have low capital costs, and (with gas available
from fracking) moderate operating costs.

3
Power System Economic Operation
• Fuel cost to generate a MWh can vary widely from technology to
technology.

• For some types of units, such as hydro, “fuel” costs are zero but the limit
on total available water gives it an implicit value.

• For thermal units it is much easier to characterize costs.

• We will focus on minimizing the variable operating costs (primarily fuel


costs) to meet demand.

4
Power System Economic Operation
• Power system loads are cyclical.

• Therefore the installed generation capacity is usually much greater than the
current load.

• This means that there are typically many ways we could meet the current
load.

• Since different states have different mixes of generation, we will consider


how generally to minimize the variable operating costs given an arbitrary,
specified portfolio of generators.

5
Thermal versus Other Generation
 The main types of generating units are thermal and hydro, with wind and
solar rapidly growing.

 For hydro the fuel (water) is free but there may be many constraints on
operation:
– fixed amounts of water available,
– reservoir levels must be managed and coordinated,
– downstream flow rates for fish and navigation.

 Hydro optimization is typically longer term (many months or years).

 We will concentrate on dispatchable thermal units, looking at short-term


optimization:
 Non-dispatchable wind and solar can be incorporated by subtracting from
load.

6
Generator types
 Traditionally utilities have had three broad groups of generators:
– “Baseload” units: large coal/nuclear; almost always on at max.
– “Midload,” ‘intermediate,” or “cycling” units: smaller coal or gas that cycle
on/off daily or weekly.
– “Peaker” units: combustion turbines used only for several hours. during
periods of high demand

7
Block Diagram of Thermal Unit

•To optimize generation costs we need to develop cost relationships


between net power out and operating costs.

•Between 2-10% of power is used within the generating plant; this is known
as the auxiliary power.
8
Thermal generator Cost Curves
 Thermal generator costs are typically represented by one or other of the
following four curves
– input/output (I/O) curve
– fuel-cost curve
– heat-rate curve
– incremental cost curve

 For reference
- 1 Btu (British thermal unit) = 1054 J
- 1 MBtu = 1x106 Btu
- 1 MBtu = 0.29 MWh

9
I/O Curve
 The IO curve plots fuel input (in MBtu/hr) versus net MW output.

10
Fuel-cost Curve
 The fuel-cost curve is the I/O curve multiplied by fuel cost.
 A typical cost for coal is $ 1.70/MBtu.

11
Heat-rate Curve
• Plots the average number of MBtu/hr of fuel input needed per MW of output.

• Heat-rate curve is the I/O curve divided by MW.

Best heat-rate for most efficient coal


units is around 9.0

12
Incremental (Marginal) cost Curve
 Plots the incremental $/MWh as a function of MW.

 Found by differentiating the cost curve.

13
Mathematical Formulation of Costs
 Generator cost curves are usually not smooth. However the curves can
usually be adequately approximated using piece-wise smooth,
functions.

 Two approximations predominate:


– quadratic or cubic functions
– piecewise linear functions

 We'll assume a quadratic approximation:

Ci ( PGi )  i  i PGi   i PGi2 $/hr (fuel-cost)


dCi ( PGi )
ICi ( PGi )   i  2 i PGi $/MWh
dPGi
14
Coal Usage Example
•A 500 MW (net) generator is 35% efficient. It is being supplied with coal
costing $1.70 per MBtu and with heat content 9000 Btu per pound. What is
the coal usage in lbs/hr? What is the cost?

At 35% efficiency required fuel input per hour is


500 MWh 1428 MWh 1 MBtu 4924 MBtu
  
hr  0.35 hr 0.29 MWh hr
4924 MBtu 1 lb 547,111 lbs
 
hr 0.009MBtu hr
4924 MBtu $1.70
Cost =   8370.8 $/hr or $16.74/MWh
hr MBtu
15
Wasting Coal Example
•Assume a 100W lamp is left on by mistake for 8 hours, and that the
electricity is supplied by the previous coal plant and that
transmission/distribution losses are 20%. How much coal has he/she
wasted?

With 20% losses, a 100W load on for 8 hrs requires


1 kWh of energy. With 35% gen. efficiency this requires
1 kWh 1 MWh 1 MBtu 1 lb
    1.09 lb
0.35 1000 kWh 0.29 MWh 0.009MBtu

16
Incremental Cost Example
For a two generator system assume
C1 ( PG1 )  1000 20 PG1  0.01PG21 $/hr
C2 ( PG 2 )  400 15 PG 2  0.03PG22 $/hr
Then
dC1 ( PG1 )
IC1 ( PG1 )   20  0.02 PG1 $/MWh
dPG1
dC2 ( PG 2 )
IC2 ( PG 2 )   15  0.06 PG 2 $/MWh
dPG 2

17
Incremental Cost Example, cont'd
If PG1  250 MW and PG 2  150 MW Then
C1 (250)  1000 20  250  0.01  2502  $ 6625/hr
C2 (150)  400 15  150  0.03  1502  $6025/hr
Then
IC1 (250)  20  0.02  250  $ 25/MWh
IC2 (150)  15  0.06  150  $ 24/MWh

18
UNIT-2

Hydrothermal Scheduling

19
Introduction

From an overall systems view, the single most important attribute of


hydroelectric plants is that there is no fuel cost, therefore production costs,
relative to that of thermal plants, are very small.

There are three basic types of hydroelectric plants: run-of-river, pumped


storage, and reservoir systems. We will just introduce the first two in this
section, and then the remainder of these notes will be dedicated to
understanding reservoir systems.
Hydro-Thermal Scheduling (HTS)
The goal of reservoir plant scheduling depends on the time frame of interest.

1. Long-range (weeks to year): Here we need the load forecast and expected
water flow from a rainfall forecast. Then we can predict the energy availability
from the hydro facilities and compute the necessary thermal energy.

2. Short-range (day to 1 week): Using results from (1) and more precise load
and water information, we can formulate a problem where the solution yields
the minimum cost of running the thermal plants on an hour-to-hour basis.
Hydro Station
Terminology

Forebay: A lake or water impoundment (reservoir) before the entrance to the


power plant.

Afterbay: A lake or water impoundment downstream from the power plant


that receives the water after it has passed through the turbines.

Penstock: The pipe leading from the water intake to the turbine.

Intake: The entrance from the forebay to the penstock.

Spillage: releasing water over the dam rather than through the penstock.
Some dams have spillways, as shown in Fig. 17, which allow smolts
(adolescent salmon) to pass without transiting through the turbines.
UNIT-3

UNIT COMMITMENT
UNIT-4

LOAD FREQUENCY CONTROL


UNIT-5

LOAD FREQUENCY CONTROLLER


UNIT-6

REACTIVE POWER CONTROL


Reactive Power and Voltage Control

Control objectives contributing to efficient and reliable operation of power


system:

• Voltage at terminals of all equipment are within acceptable limits


– both utility and customer equipment designed to operate at certain
voltage rating
– prolonged operation outside allowable range could cause them
damage

• System stability is satisfactory


– voltage levels and reactive power control have significant impact on
stability

• The reactive power flow is minimized so as to reduce I 2R and I 2X losses


to a practical minimum
– ensures transmission system operates efficiently
Production and Absorption of Reactive Power (Q)

• Synchronous Generators
– can generate or absorb Q depending on
excitation
– capability limited by field current, armature
current, and end-region heating limits
– automatic voltage regulator continuously adjusts
excitation to control armature voltage
– primary source of voltage support!

• Overhead lines
– at loads below natural or surge impedance load
(SIL), produce Q
– at loads above SIL, absorb Q
• Underground cables
– have high SIL due to high capacitance
– always loaded below SIL, and hence generate Q

Transformers
absorb Q due to shunt magnetizing reactance and series leakage
inductance

Loads
a typical "load bus" is composed of a large number of devices
composite characteristics are normally such that a load bus absorbs Q
industrial loads usually have shunt capacitors to improve power factor

As power flow conditions vary, reactive power requirements of


transmission network vary

Since Q cannot be transmitted over long distances, voltage control has to


be effected using special devices dispersed throughout the system
Methods of Voltage Control
• Control of voltage levels is accomplished by controlling the production,
absorption, and flow of reactive power at all levels in the system

• Generating units provide the basic means of voltage control

• Additional means are usually required to control voltage throughout the


system:

– sources or sinks of reactive power, such as shunt capacitors, shunt


reactors, synchronous condensers, and static var compensators
(SVCs)

– line reactance compensators, such as series capacitors

– regulating transformers, such as tap-changing transformers and


boosters
Methods of Voltage Control
• Shunt capacitors and reactors, and series capacitors provide passive
compensation
– are either permanently connected to the transmission and distribution
system, or switched
– contribute to voltage control by modifying the network
characteristics

• Synchronous condensers and SVCs provide active compensation; the


reactive power absorbed/ supplied by them are automatically adjusted so
as to maintain voltages of the buses to which they are connected
– together with the generating units, they establish voltages at specific
points in the system
– voltages at other locations in the system are determined by active and
reactive power flows through various circuit elements, including the
passive compensating devices
Objectives of Reactive Power Compensation

• To control voltage and/or improve maximum power transfer


capability
• Achieved by modifying effective line parameters:

– characteristic impedance,

– electrical length, θ = βl

• The voltage profile is determined by ZC


• The maximum power that can be transmitted depends on ZC as well
as β
Shunt Reactors

• Used to compensate the undesirable voltage effects associated with line


capacitance
– limit voltage rise on open circuit or light load
• Shunt compensation with reactors:
– increases effective ZC
– reduces the effective natural load , i.e., voltage at which flat voltage
profile is achieved
• They are connected either:
– directly to the lines at the ends, or
– to transformer tertiary windings; conveniently switched as var
requirements vary
• Line reactors assist in limiting switching surges
• In very long lines, at least some reactors are required to be connected to
lines
Shunt Capacitors
• Used in transmission systems to compensate for I 2X losses
• Connected either directly to H.V. bus or to tertiary winding of
transformers
• Normally distributed throughout the system so as to minimize losses and
voltage drops
• Usually switched: a convenient means of controlling voltage
• Shunt capacitor compensation of transmission lines in effect
– decreases ZC
– increases θ, i.e., electrical length
• Advantages: low cost and flexibility of installation and operating
• Disadvantages: Q output is proportional to square of the voltage; hence
Q output reduced at low voltages

• Shunt capacitors are used extensively in distribution systems for power


factor correction and feeder voltage control
Series Capacitors

• Connected in series with the line


• Used to reduce effective inductive reactance of line
– increases maximum power
– reduces I 2X loss
• Series capacitive compensation in effect reduces both:
– characteristic impedance ZC, and
– electrical length θ
• Reactive power produced increases with increasing power transfer
– Self regulating !
• Typical applications
– improve power transfer compatibility
– alter load division among parallel lines
– voltage regulation
Synchronous Condenser

• A synchronous machine running without a prime mover or a


mechanical load

• Depending on field excitation, it can either absorb or generate vars

• With a voltage regulator, it can automatically adjust vars to maintain


constant voltage

• Started as an induction motor and then synchronized

• Normally connected to tertiary windings of transformers

• Unlike a SVC, a synchronous condenser has an internal voltage

• Speed of response not as fast as that of an SVC


Static VAR Compensators (SVC)
• Shunt connected static var generators and/or absorbers whose outputs
are varied so as to control specific power system quantities

• The term static is used to denote that there are no moving or rotating
components

• Basic types of SVCs:

– thyristor-controlled reactor

– thyristor-switched capacitor

– saturated reactor

• A static var system (SVS) is an aggregation of SVCs and mechanically


switched capacitors or reactors whose outputs are coordinated

• When operating at its capacitive limit, an SVC behaves like a simple


capacitor
Static Synchronous Compensator (STATCOM)
• Can be based on a voltage-sourced or current-sourced converter
• Figure below shows one with voltage-sourced converter
– driven by a dc voltage source: capacitor

• Effectively an alternating voltage source behind a coupling reactance


– controllable in magnitude
• Can be operated over its full output current range even at very low
(typically 0.2 pu) system voltage levels
• Requires fewer harmonic filters and capacitors than an SVC, and no
reactors
– significantly more compact
Tap-Changing Transformers
• Transformer with tap-changing facilities constitute an important means
of controlling voltages throughout the power system

• Control of a single transformer will cause changes in voltages at its


terminals
– in turn this influences reactive power flow
– resulting effect on the voltages at other buses will depend on network
configuration and load/generation distribution

• Coordinated control of the tap changers of all transformers


interconnecting the subsystems required to achieve overall desired effect

• During high system load conditions, network voltages are kept at highest
practical level to
– minimize reactive power requirements
– increase effectiveness of shunt capacitors and line charging
• The highest allowable operating voltage of the transmission network is
governed by
– requirement that insulation levels of equipment not be exceeded
– need to take into consideration possible switching operations and
outage conditions

• During light load conditions, it is usually required to lower network


voltages
– reduce line charging
– avoid underexcited operation of generators

• Transformers with under-load tap-changers (ULTC) are used to take care


of daily, hourly, and minute-by-minute variations in system conditions

• Off-load tap-changing transformers used to take care of long-term


variations due to system expansion, load growth, or seasonal changes

You might also like