0% found this document useful (0 votes)
221 views16 pages

s71200 System Manual en-US en-US

1) Analog modules are used to process analog signals from sensors and send analog control signals to actuators. 2) Analog input modules convert physical quantities such as pressure, temperature, or flow into standard analog signals that can be read by the CPU. Analog output modules convert values from the CPU into analog signals to control physical quantities. 3) Analog values are represented numerically with a resolution of up to 16 bits allowing for measurement ranges to be scaled and represented accurately in the CPU for processing.

Uploaded by

josimar vargas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
221 views16 pages

s71200 System Manual en-US en-US

1) Analog modules are used to process analog signals from sensors and send analog control signals to actuators. 2) Analog input modules convert physical quantities such as pressure, temperature, or flow into standard analog signals that can be read by the CPU. Analog output modules convert values from the CPU into analog signals to control physical quantities. 3) Analog values are represented numerically with a resolution of up to 16 bits allowing for measurement ranges to be scaled and represented accurately in the CPU for processing.

Uploaded by

josimar vargas
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 16

Analog Value Processing

High level

Level
transmitter
Low level

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.1
Use of Analog Modules
Process Analog input module CPU

Physical Standard :
quantity analog signal Result :
memory :
:
PIW ... :
PIW ... :
MR L PIW 352
ADC :::
module
Sensor Transducer PIW ... ..
..
..
..
• Pressure ± 500mV ..
• Temperature ± 1V ..
• Flow ± 5V ..
• Speed ± 10V ..
• pH value ± 20mA ..
• Viscosity 4...20mA ..
• etc. etc. Analog output module ..
..
..
..
..
..
..
..
PQW ... ..
Physical Analog PQW ...
DAC ::: T PQW 368
quantity actuator
PQW ... :

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.2
Measuring Range Module

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.3
Analog Module SM335 (Inputs)

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.4
Analog Input Module SM331

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.5
Analog Module SM335 (Outputs)

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.6
Analog Value Representation and Measured Value Resolution

Bit no. Units 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Bit value Dec. Hex. VZ 214 213 212 211 210 29 28 27 26 25 24 23 22 21 20

8 128 80 * * * * * * * * 1 0 0 0 0 0 0 0

9 64 40 * * * * * * * * * 1 0 0 0 0 0 0

10 32 20 * * * * * * * * * * 1 0 0 0 0 0
Reso-
lution
11 16 10 * * * * * * * * * * * 1 0 0 0 0
in bits
+ sign
12 8 8 * * * * * * * * * * * * 1 0 0 0

13 4 4 * * * * * * * * * * * * * 1 0 0

14 2 2 * * * * * * * * * * * * * * 1 0

15 1 1 * * * * * * * * * * * * * * * 1

* = 0 or 1

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.7
Analog Value Representation of Different Measuring Ranges

Voltage Current Resistance Temperature


e.g.: e.g.: e.g.: e.g. Pt100
Range
Meas.range Units Meas.range Units Meas.range Units Meas.range Units
± 10V 4 .. 20mA 0...300Ohm -200...+850ºC

Overflow >= 11.759 32767 >= 22.815 32767 >=352.778 32767 >= 1000.1 32767

Overrange 11.7589 32511 22.810 32511 352.767 32511 1000.0 10000


: : : : : : : :
10.0004 27649 20.0005 27649 300.011 27649 850.1 8501

10.00 27648 20.000 27648 300.000 27648 850.0 8500


7.50 20736 16.000 20736 225.000 20736 : :
Rated range : : : : : : : :
-7.5 -20736 : : : : : :
-10.00 -27648 4.000 0 0.000 0 -200.0 -2000

Underrange - 10.0004 - 27649 3.9995 -1 -1 - 200.1 - 2001


Negative
: : : : : : :
values
- 11.759 - 32512 1.1852 - 4864 - 4864 - 243.0 - 2430
not
Underflow <= - 11.76 - 32768 <= 1.1845 - 32768 possible - 32768 <= - 243.1 - 32768

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.8
Analog Value Representation for the Analog Outputs

Voltage Current
Units
Range Output ranges: Output ranges:
0 to 10V 1 to 5V ± 10V 0 to 20mA 4 to 20mA ± 20mA

Overflow >=32767 0 0 0 0 0 0

Overrange 32511 11.7589 5.8794 11.7589 23.515 22.81 23.515


: : : : : : :
27649 10.0004 5.0002 10.0004 20.0007 20.005 20.0007

27648 10.0000 5.0000 10.0000 20.000 20.000 20.000


: : : : : : :
0 0 1.0000 0 0 4.000 0
: 0 : 0 :
Rated range - 6912 0.9999 : 3.9995 :
: :
- 6913 0 : 0 :
: : :
: 0 : 0 :
: : :
- 27648 -10.0000 -20.000

Underrange - 27649 - 10.0004 - 20.007


: : :
- 32512 - 11.7589 - 23.515

Underflow <=- 32513 0 0

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.9
Analog Module Addresses with S7-300

Rack 3 Power IM 640 656 672 688 704 720 736 752
Supply
(Receive)
to to to to to to to to
654 670 686 702 718 734 750 766

Rack 2 Power IM 512 528 544 560 576 592 608 624
Supply
(Receive) to to to to to to to to
526 542 558 574 590 606 622 638

Rack 1 Power IM 384 400 416 432 448 464 480 496
Supply
(Receive) to to to to to to to to
398 414 430 446 462 478 494 510

R Power IM 256 272 288 304 320 336 352 368


0
Supply CPU (Send) to to to to to to to to
270 286 302 318 334 350 366 382

Slot 2 3 4 5 6 7 8 9 10 11

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.10
Scaling Analog Input Values

500,0

0,0
0 27648

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.11
Unscaling a Real Number for Analog Output

27648

0
0,0 100,0

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.12
Exercise: Assigning Parameters to the Analog Module SM335

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.13
Exercise: Assigning Parameters to the Analog Module SM331

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.14
Exercise: Hardware Diagnostics with Diagnostic Interrupt

2x

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.15
Exercise: Recording and Displaying the Weight of the Transported
Parts
CPU
Simulator AI module

0
10 PIW 352
0 ... 10V (PIW 304) 0 ... 27648
V

AI1 AI2 AO1 -15V...+15V


AO2

AI1 AI2

Weight: 0 ... 500kg

DO module
BCD Display
QW 12
0 1 2 3 0 ... 500 kg
(QW 6)

SIMATIC S7 Date: 06.02.2019


SITRAIN Training for
Automation and Drives
Siemens AG 2000. All rights reserved. File: PRO1_13E.16

You might also like