Lecture 09 - Ex P
Lecture 09 - Ex P
• Standards:
– EN 50016:1995 (‘second edition’)
– EN 50016:1977 (‘first edition’)
• identical to BS 5501:Part 3:1977
Ex p - slide 1 of 8
Typical Ex p arrangement
Pressure Switch
Outlet Control
Ignition-
capable
Protective gas equipment Flow Meter
Fan
Controller
Non-hazardous Hazardous area
area
Ex p - slide 2 of 8
Types of Ex p equipment
• Leakage compensation (air or inert gas)
– flammable gas analysers
– VDUs
– motors
• Continuous circulation (air also acts as coolant)
– motors
• Continuous dilution (usually air)
– control rooms
– analyser houses
• Static pressurisation (inert gas - portable items only)
– torches
Ex p - slide 3 of 8
Required overpressure
• Minimum 50 Pa (0.5 mbar) required
– If pressure falls below this level, the controller can usually
be programmed to react depending on the risk
Ex p - slide 4 of 8
Constructional requirements
• Monitoring of initial purge
• Manual purge over-ride not allowed (except zone 2)
• Monitoring of overpressure throughout enclosure
• Overpressure protection
• Alarm, possibly isolation, if pressure falls <50 Pa
• Avoid ‘dead spots’
• Capacitors, batteries, etc. must be intrinsically safe
Ex p - slide 5 of 8
Maintenance
Ex p - slide 6 of 8
Advantages
Ex p - slide 7 of 8
Disadvantages
Ex p - slide 8 of 8