Motor and Transformer Feeder Protection Using Siperotec Relay
Motor and Transformer Feeder Protection Using Siperotec Relay
MOTOR AND TRANSFORMER
PROTECTION USING
PROTECTION USING
SIEMENS
SIEMENS
SIPROTEC RELAY
SIPROTEC RELAY
MOTOR FEEDER PROTECTION
USING SIPROTEC RELAY
Under Voltage Protection(ANSI 27)
• Under voltage protection detects voltage dips in electrical machines and
avoids inadmissible operating states and possible loss of stability.
• Under voltage protection consists of two stages. A pickup is signaled as
soon as selectable voltage thresholds are undershot. A trip signal is
transmitted if a voltage pickup exists for a selectable time.
Ip Pickup 38A
T Ip Time Dial 2.00 sec
IEC Curve Normal Inverse
IDMT Protection(ANSI 51V)
• The highly sensitive earth fault protection detects earth faults in systems
with isolated or high-impedance earthed star point.
• The residual current is numerically filtered so that only the fundamental
wave of the current is used for the measurement. This makes the
measurement insensitive to short-circuit transients and harmonics.
IEE> Pickup 30 A
T IEE>Time delay 0.45sec
IEE>>Pickup 75 A
T IEE>> Time delay inst
Thermal Over load protection(ANSI 49)
The thermal overload protection prevents thermal overloading of the
stator winding.(Operational miss handling)
The device calculates the over temperature in accordance with a single-
body thermal model. Thermal over load protection consists of two stages.
Negative Sequence Protection
• Unbalanced loads produce a reverse field in motors which
drives the rotor at twice the frequency.
• Eddy currents are induced on the surface of the rotor, leading
to local temperature rises in the rotor.
Internal fault:
Percentage Differential characteristics
Id
% = Y *100%
X
t (% )
n
Perce
Slope Y
X
Minimum
Pickup
(per unit) Ir
Tripping Characteristics of Differential
Protection
Branch “a”
Branch a represent the sensitivity
threshold of the differential protection
and consider constant error current .
For example:
magnetizing current
Branch “b”:
Branch b takes into consideration current-
proportional errors which may result from
transformation errors of the main CTs or
from erroneous current caused by the
position of the tap changer of the voltage
regulator.
Branch “c”:
In the range of high currents which may give rise to current transformer saturation ,
branch c causes stronger stabilization.
Branch “d”:
Differential currents above the branch d cause immediate trip regardless of the restraining
quantity and harmonic content
Tripping Characteristics of Differential
Protection
Slope 2
Slope 1
The inrush current has a high proportion of harmonics having twice the
system frequency, offer possible stability against tripping.
If
I(2*fn)/I(fn) > adjustable constant