Frequency Control and Regulating Reserves

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 38

7.

FREQUENCY CONTROL
AND REGULATING
RESERVES

Asko Vuorinen

1
Purpose of frequency control
and regulating reserves
 Keep the balance between demand
and supply of electricity
 Balance is measured with frequecy of
system

2
Power system differenetial
equation
dWk/dt= Pg – Pc

where
Wk = kinetic energy of all rotating
machines = ½ J ω2
Pg = power generation
Pc = power consumption
J = torque of machines
ω = angular speed (rad/s)

3
Frequency drop without
regulation

df = dPg/Kn ( 1 – e –fNKn/(2Wk) x t)

where
2Wk/(fNKn) = time constant (T) (5 - 10 s)
Kn = natural control gain of the network (Hz/MW)
1/Kn = self regulation power (typically 1-2 % of
total capacity)

4
Deficit causes a frequency drop
without regulation (line 1) and
with regulation (line 2)

5
Without regulation

 Loss of 10 % of generation causes a


frequency drop by 3 – 5 Hz within a
minute
 The maximum allowed deviation is
typically 0.1 – 0.2 Hz (dfs), thus
regualtion is needed

6
Regulation reserves limit the
frequency deviation to dfs

7
Classification of regulating
reserves (UCTE)*

8
UCTE = Union for the Co-ordination of Transmission of Electricity
Sequence of actions of primary,
secondary and tertiary control

9
Primary control reserves

10
Primary control reserves

Actions taken within 5 – 30 seconds


by generator droop control

Generators measure the frequency


and immediately change the output
according the formula:

dP = - Pgn/sG/fn x df

11
Primary control, continued

dP = - Pgn/sG/fn x df = - Rp x df

where
dP = change in generator output (MW)
Pgn = nominal output of generator (MW)
sG = generator droop (%)
fn = nomnal frequency
df = change in power system frequency
Rp = regulating power = - Pgn/SG/fn

12
Primary control, continued
 If the frequency deviation is eleminated the
output becomes the same as it was before
the disturbance (system is then restored)

 The primary control is Proportional control


(P-control), where the output change (dP) is
directly proportional to frequency deviation
(df)

13
Primary control, continued
Two generators (a and b)
with different droop

14
Two generators (a and b)
with different droop

Generator b needs much larger


deviation in frequency (fb) than
generator a (fa) to change the output
by the same relative amount
(Primary control reserve)

15
Need of primary control reserves

 UCTE 3000 MW (Continental Europe)


 3000 MW or equivalent of two 1500 MW
nuclear plants or lines trip at the same time
 Eastern Interconnection (USA)
 3000 MW = largest interconnection
 NORDEL (North Europe)
 Continuous control = 600 MW/0.1 Hz
 Frequency response = 1000 MW, if
frequency drop to 49,5 – 49,9 Hz

16
Primary control reserve
deployment time (UCTE)

17
Primary control reserve
deployment time
 UCTE
 1500 MW in 15 s
 3000 MW in 30 s
 Nordel
 300 MW in 5 s
 1200 MW in 30 s

* Note: the first 5 seconds are critical (see slide 7)


18
Secondary control reserves
(regulating reserves in USA)

19
Secondary control reserves
Functions
 Should reset the primary control
reserves in 5 – 15 minutes to be ready
for next disturbance
 Should correct the frequency
deviation within allowable limit
 +/- 0.1 Hz in Nordel
 +/- 0.2 Hz in UCTE

20
Secondary control reserves
Control formula

dP = - K x ACE – 1/Tr ∫ ACE dt *

where
dP = output set point of secondary controller
K = gain of P – controller
ACE = Area Control Error
Tr = time constant of secondary controller
* Note: The control action dP increases by integral
formula, if the deviation of ACE remains constant (PI-type
controller)

21
Secondary control reserves
Area Control Error (ACE)

ACE = dB + K x df

Where
dB = deviation in power balance (= Generation-
Load + Import - Export)
df = deviation of frequency from (fN)
K = dependency between deviation of power
and system frequency
Note: ACE is calculated in about five to ten second intervals by
computers in the dispatch center
22
Secondary control reserves
Reserve requirements (UCTE)

23
Secondary control reserves
Reserve requirements

 UCTE (Continental Europe)


 3000 MW system 100 MW = 3 %
 10000 MW system 200 MW = 2 %
 60000 MW system 600 MW = 1 %
 PJM (USA)
 Forecasted day peak load 1.1 %
 Forecasted night peak load 1.1 %
 Nordel (North-Europe)
 No specific requirement given

24
Secondary control reserves
Automatic Generation Control (AGC) and
manual control
 AGC (USA and UCTE)
 Dispatch center computers measure
ACE and send setpoints for regulating
power plants automatically
 Manual (Nordel)
 Dispatch center operators call to
regulating power plants by phone and
ask to change the set points

25
Secondary control reserves
Response times

 5 min
 PJM (USA)
 Germany
 10 min
 Nordel
 California (USA)

26
Secondary control reserves
Compliance factor (USA)

CF = ACE/(-10B) x df

Where

CF = compliance factor
ACE = Area Control Error (slide 22)
10B = bias setting of control area (MW/Hz)
df = frequency deviation

27
Secondary control reserves
Compliance factor (USA)

 Compaliance factor is measured in each ten


minute periods for monthly statistics

 If 90 % of compliance factors during a


month are better then required, then
everything is OK

 If not, regulators may demand more new


reserves or faster response times from
existing regulation reserves
28
Secondary control reserves
Power plant actions

 Gas engine plant operates initially at 70 %


output

 It can then change its output +/- 30 % in five


minutes

 Ramp rate = 30 %/5 min = 6 %/min*

*See futher details of ramp rates of various power plants


in presentation Fundamentals of power plants

29
Secondary control reserves
Part load efficiency is important

Efficiency at 70 % load: GE 41 % and GT 34 %


30
Secondary control reserves
Part load efficiency of 80 MW gas engine
plant*

* At high Efficiency Mode engines are started one by one


At Regulation Mode all engines run at same output 31
Secondary control reserves
Summary

 Secondary control systems correct the


frequency deviation using PI-type
regulation
 Regulation can be made automatically
by AGC or mannually by the operator
 The power plants which have highest
part load efficiency can deliver
reguation with the lowest costs
32
Tertiary control reserves
Balance control

33
Tertiary control reserves
Balance control

 Tertiary control is a responsibility of


each Load Serving Entity (LSE)
 LSE should balance its load,
generation, sales and purchases in
each balancing interval
 Balancing interval varies from 15
minutes to 60 minutes depending on
the country
34
Tertiary control reserves
Balance control

 LSE can
 Use selfgeneration for balance control
 By balance difference from balance
provider
 Pay penalties to System Operator
 LSE:s prefer
 Power plants which can be used in
balance control and regulation
35
Critical situations
 Morning ramp
 All resources are needed to increase
power from 50 % to 100 % within two
hours
 Television pickup
 Olympic games or other sport
happenings can increase load by 10 -
20 % in some minutes

36
Summary

 Transmission system operator (TSO) uses


frequency control and regulation to keep
the electricity power balance in control
from seconds to one hour
 Load Service Entities (LSE) try the keep
the their balance by flexible power plants
within one hour and sell regulation services
to TSO

37
For details see reference text book
”Planning of Optimal Power Systems”

Author:
Asko Vuorinen

Publisher:
Ekoenergo Oy

Printed:
2008 in Finland

Further details and


internet orders see:

www.optimalpowersystems.com 38

You might also like