Specifying Optical Fiber Cable: Ch5 Fiber Optics Technician's Manual, 3 - Ed Jim Hayes
Specifying Optical Fiber Cable: Ch5 Fiber Optics Technician's Manual, 3 - Ed Jim Hayes
Specifying Optical Fiber Cable: Ch5 Fiber Optics Technician's Manual, 3 - Ed Jim Hayes
Cable
Ch 5
Fiber Optics Technician’s
Manual, 3rd. Ed
Jim Hayes
Cable Parameters and
Typical Values
Installation v. Environmental
Specifications
Installation Specifications
• Ex: Installation Load (Pulling force)
Environmental Specifications
• Determine the cable’s long-term
performance
• Ex: Temperature range of operation
Installation Specifications
Maximum installation load
• Force in lb. (or kg-force or N)
• Pulling with more than this force will
permanently change the attenuation of
the fiber
• Typical values:
67-125 lb. for 1-fiber cables
250-500 lb. for cables with 6-12 fibers
600 lb. for self-supporting aerial cables
Installation Specifications
Minimum installation bend radius
• Don’t bend the cable under tension
through a corner sharper than this
• If you violate the bend radius, you may
damage some part of the cable
structure
• Typical value: 20 times cable diameter
Installation Specifications
Diameter
• Important when fitting the cable into a
crowded conduit
Temperature range for installation
and storage
Environmental
Specifications
Temperature range
• Outside this range, the plastic may
crack, or
• Expansion cycles will create
microbends in the fiber, increasing
attenuation
Indoor, typically -10 to 50 Centigrade
Outdoor, typically -20 to 60 Centigrade
Military: -55 to 85 Centigrade
• Image: a Teflon-coated fiber optic thermometer
that operates down to 5 degrees Kelvin (link Ch
5i)
Environmental
Specifications
Minimum long-term bend
radius
• With the cable not under tension
• Typically 10 diameters
Image: Japanese fiber with bend radius
under 1 cm (link Ch 5h)
NEC (National Electrical Code)
• Three cable fire ratings:
No letter or G: General use—least
stringent fire test
R: Riser—can be used in vertical shafts
P: Plenum—most strict test
Environmental Specifications
Long-term use load
• Important for long vertical installations
• Aerial installation
Vertical rise distance
• Must put in strain-relief loops
Flame resistance
• Non-building applications
UV stability
Environmental Specifications
Resistance to Rodent Damage
• Inner ducts are an alternative to armor
Steel armor
Copper tape armor
Braided armor
Dielectric armor
• Image from arcelect.com
• Armor makes the cable much less
flexible
Environmental Specifications
Resistance to water damage
• Filled and Blocked
Each loose buffer tube is filled (with gel or
tape)
A blocking material fills the space between
the tubes
Crush load
• Short-term v. long-term
Environmental Specifications
Abrasion resistance
Resistance to chemicals
Environmental Specifications
Resistance to conduction under high
voltage
Toxicity
• “Halogen-free” cables produce less
harmful smoke
• Required in Japanese and European
buildings
High flexibility
• If constantly bending, like an elevator
Environmental Specifications
Hermetically sealed fiber
• Protect it from water pressure, etc.
Radiation resistance
• Nuclear reactors or satellites
Impact Resistance
• Dropping heavy objects on the cable
Gas permeability
• Preventing gas from escaping through
the cable
Environmental Specifications
Stability of filling compounds
• Temperature cycles can pump filling
compounds out the end of the cable
Vibration
Design Shortcuts
Future-Proofing a System
Include extra fibers in cables
• It costs very little more to get a cable
with more fibers in it
Include singlemode fibers in
multimode cables
• Allows enormous bandwidth increases
later
Use dual-wavelength multimode fiber
• Or even laser-optimized fiber
Multimode Fibers
Early multimode systems used
62.5/125 micron fiber
• LED light sources at 850 or 1300 nm
• 10 Mbps or 100 Mbps
• Huge installed base
50/125 micron fiber
• Faster with VCSEL sources at 850 nm
Laser-optimized 50/125 micron fiber
• Fastest, using VCSEL sources
Singlemode Fibers
Usually 1300 nm singlemode fiber is
good enough
Cheaper than 1550 nm or two-
wavelength systems
Cable Types
Indoor
• Short distance – Break-out cable
• Longer distance – Distribution cable
• Rugged environment – Break-out cable
• Use all-dielectric cable
• Plenum-rated PVC is recommended
Cable Types
Outdoor
• Cable should be water-blocked and gel-
filled
• Many fibers (>36) – consider ribbon
cable
• For midspan access, use stranded loose-
tube cable
• Use all-dielectric cable
Stranded Loose-Tube
Same as loose-tube table
• Image from Corning (Link Ch 5f)
Cable Types
Indoor/Outdoor
• You could splice
indoor to
outdoor at the
building
entrance
• Or use indoor-
outdoor cable
like Corning’s
FREEDM
• Image from Corning
(Link Ch 5g)