CHAPTER 8 - Shunt Capacitor Bank Protection
CHAPTER 8 - Shunt Capacitor Bank Protection
CHAPTER 8 - Shunt Capacitor Bank Protection
1
CONTENT
1. INTRODUCTION
1.1 Overview of Series and Shunt Capacitor banks
2. POWER SYSTEM REACTIVE REQUIREMENTS
3. SHUNT CAPACITOR APPLICATIONS
3
1. Introduction
Capacitor unit rating
IEEE std C37.99 -2000
The capacitor unit is made up of individual capacitor elements, arranged in
series/parallel connected groups within a steel enclosure.
The internal discharge device is a resistor that reduces the unit residual voltage to
8
4. CAPACITOR BANK DESIGNS
Capacitor ‘‘units’’ are the basic building blocks of capacitor
banks. A capacitor unit is enclosed in a case with a number of
9
4. CAPACITOR BANK DESIGNS
Pole-mounted distribution capacitor banks are made up of
one or more parallel connected capacitor units per phase.
11
4. CAPACITOR BANK DESIGNS
The fuseless design is not usually applied for system voltages less than about
34.5 kV. The reason is that there shall be more than 10 elements in series so that 16
the bank does not have to be removed from service for the failure of one element
because the voltage across the remaining elements would increase by a factor of
about E (E – 1), where E is the number of elements in the string.
4. CAPACITOR BANK DESIGNS
4.4 Capacitor Bank configurations (Connections)
Fusing and protection are the two aspects that determine the
17
Fig. shows the four most common wye-connected capacitor
bank configurations
4.4 Capacitor Bank configurations (Connections)
Capacitor bank in Substations – Y
Distribution capacitor banks – Y or ∆
Types of capacitor bank connections shown in Figure below:
18
4.4 Capacitor Bank configurations (Connections)
4.4.1 Grounded/Ungrounded Wye
Most distribution and transmission-level capacitor banks are wye
21
5. DESIGNS AND LIMITATIONS OF LARGE
CAPACITOR BANKS
A typical arrangement for an externally
27
7. Several types of relaying schemes are applied on
large capacitor banks to provide system protection
7.3 Loss of bus voltage protection:
It is sometimes desirable to trip the capacitor when voltage is lost at
29
8. Unbalance Protection Methods
8.1 Unbalance Protection for Ungrounded, Single-Wye Banks
The simplest method for this application is to measure the bank zero-
sequence voltage. (ANSI code 59 Over Voltage Relay)
30
8. Unbalance Protection Methods
8.1 Unbalance Protection for Ungrounded, Single-Wye Banks
Fig. (c) shows a compensated neutral unbalance method.
32
8. Unbalance Protection Methods
8.3 Unbalance Protection for Grounded, Single-Wye Banks
Fig. (a) shows unbalance voltage protection using busbar PTs and PTs connected to tap
points.
33
8. Unbalance Protection Methods
8.3 Unbalance Protection for Grounded, Single-Wye Banks
Voltage Differential Protection
Fig. (a) shows unbalance voltage protection using busbar PTs and
PTs connected to tap points.
Unbalances in the bank change the tap point voltage with respect to
the busbar voltage, causing the relay to operate.
34
8. Unbalance Protection Methods
8.4 Unbalance Protection for Grounded, Double-Wye Banks
Unbalance Protection for Grounded, Double-Wye Banks Fig. (a)
shows unbalance current and Fig. (b) shows unbalance voltage
35
8. Unbalance Protection Methods
8.4 Unbalance Protection for Grounded, Double-Wye Banks
In Fig. (b), the protection uses two PTs per phase connected to
36
(b) Double Grounded Y-Connected Capacitor Banks
9. Mid-Rack Phase to Phase Faults
39
(c) DC Schematic (Backup Tripping)
11. Summary on Shunt Capacitor Protection Methods
44
Bibliography
1. J Lewis Blackburn and Thomas J Domin, Protection Relaying Principles
and Applications, third Edition, CRC press Taylor and Francis group,
2006. (Chapter 9: Transformer, Reactor, and Shunt Capacitor