Alternator
Alternator
1. Rotating-Armature Type
The armature winding is on the rotor and the field system
According to the arrangement is on the stator.
of the field and armature 2. Rotating-Field Type
windings
The armature winding is on the stator and the field system
is on the rotor.
• The round rotor is used high speed (3600 rpm) machines. • The poles are bolted to the shaft
• A forged iron core (not laminated, DC) is installed on the shaft. • Each pole has a DC winding.
• Slots are milled in the iron and insulated copper bars are placed in the slots. • The DC winding is connected to the slip-rings(not
• The slots are closed by wedges and re-enforced with steel rings. shown)
• A DC source supplies the winding with DC through
brushes pressed into the slip ring
• A fan is installed on the shaft to assure air
circulation and effective cooling
• Low speed, large hydro-generator may have more
than one hundred poles.
• These generators are frequently mounted vertically.
INDUCED VOLTAGE PRODUCED BY A CHANGING MAGNETIC FIELD IN A CONDUCTOR
As the magnetic field moves past the wire, energy from the
moving magnetic field is transferred to the wire and a potential is
built up in it as it moves. The wire then has the ability to produce
power.
INDUCED VOLTAGE PRODUCED BY A CHANGING MAGNETIC FIELD IN A CONDUCTOR
Transformer Action
By combining the previous two principles, we now have the
basic operation of a transformer:
In the example below, since both coils share the same flux (M)
then the input and output EMF.s are proportional to the number
of turns of conductor around that flux:
E2/E 1 = N2/N1
Poles
It is important to point out that the illustrations presented have
only shown one set of poles. This is purely for analysis and
ease of viewing. The prime mover would have to rotate at 60
revolutions per second or 3600 rpm to produce a 60-cycle
waveform. Water-driven generators at 300 rpm would of course
have 12 sets of poles. It is enough to say that the number of
poles only affects the required rotor speed. The general theory
remains the same.
Field Excitation and Exciters
• DC current in the field winding produces the main flux, ϕ𝑓 jXAR jXA RA IA
• ϕ𝑓 induces an emf, 𝐸𝐺 , in the armature winding. Field Winding Armature Reaction Armature winding
effect modeled as parameter
• Depending on the load condition, the armature current 𝐼𝐴 is a voltage drop
established. In the following discussions, it is assumed to be
a lagging power factor. DC VT
• I𝐴 produces its own flux due to armature reaction, 𝐸𝐴𝑅 is the EG (=EA)
induced emf by ϕ𝐴𝑅 .
• The resulting phasor, 𝐸𝑟𝑒𝑠𝑢𝑙𝑡𝑎𝑛𝑡 = 𝐸𝐺 + 𝐸𝐴𝑅 is the “true”
induced emf that is available.
A 3 ø, 5 kVA, 208V, four-pole, 60 Hz, star-connected synchronous machine has negligible stator winding resistance and a synchronous
reactance of 8 ohms per phase at rated terminals voltage.
Determine the excitation voltage and the power angle when the machine is delivering rated kVA at 0.8 pf lagging. Draw the phasor
diagram for this condition.
Solution
• The flux produced by the armature winding reacts with the flux
set up by the poles on the rotor, causing the total flux to
change.
Figure.1 (a) The per-phase equivalent circuit of a
synchronous generator without armature reaction while
depicting the revolving field produced by the rotor.
Figure.1 (a) The phasor diagrams for a (b) lagging pf, (c) unity pf, and (d) leading pf.
Armature Reaction in Synchronous Machines
(a) If 𝜙𝑃 is the flux per pole in the generator under no load, then
the generated voltage 𝐸𝑎 must lag 𝜙𝑃 by 90˚, as shown in
Figure 2.
(b) Since the power factor is unity, the phase current 𝐼ሚ𝑎 is in phase
with the terminal phase voltage 𝑉෩𝑎 .
(c) As the phase current 𝐼ሚ𝑎 passes through the armature winding,
its magnetomotive force (mmf) produces a flux 𝜙𝑎𝑟 which is in
phase with 𝐼ሚ𝑎 . The effective flux 𝜙𝑒 per pole in the generator
is the algebraic sum of the two fluxes; that is, 𝜙𝑒 = 𝜙𝑝 + 𝜙𝑎𝑟
,as shown in the figure. Figure 2: Phasor diagram depicting the effect of
(d) The flux 𝜙𝑎𝑟 , in turn, induces an emf 𝐸෨𝑎𝑟 in the armature armature reaction when the power factor is unity.
winding. 𝐸෨𝑎𝑟 is called the armature reaction emf. The
armature reaction emf 𝐸෨𝑎𝑟 lags the flux 𝜙𝑎𝑟 by 90˚ . Hence the
effective generated voltage per-phase 𝐸෨𝑒 is the algebraic sum
of the no-load voltage 𝐸෨𝑎 and the armature reaction emf 𝐸෨𝑎𝑟 .
That is, 𝐸෨𝑒 + 𝐸෨𝑎 + 𝐸෨𝑎𝑟 . An equivalent circuit showing the
armature reaction emf is given in Figure 3.
(e) The per-phase terminal voltage 𝑉෨𝑎 in obtained by subtracting
the voltage drops 𝐼ሚ𝑎 𝑅𝑎 + 𝑗෩𝐼𝑎 𝑋𝑎 from 𝐸෨𝑒 . In other words,
𝐸෨𝑒 = 𝑉෨𝑎 + 𝐼ሚ𝑎 (𝑅𝑎 + 𝑗𝑋𝑎 )
From the phasor diagram, it should be obvious that the armature reaction
has reduced the effective flux per pole when the power factor of the load is
unity. Also, the terminal voltage is smaller than the generated voltage.
By following the above sequence of events, we can obtain the phasor
diagrams for the lagging (figure 4) and the leading (Figure 5) power factors.
From these figures it is evident that the resultant flux is (smaller/larger) with
armature reaction for the (lagging/leading) power factor that without it. In
addition, the terminal voltage 𝑉෨𝑎 is (higher/lower) than the generated voltage
𝐸෨𝑎 when the power factor is (leading/lagging). Since the flux per pole 𝜙𝑃 is
different for each of the three load conditions, the field current 𝐼𝑓 must be
adjusted each time the load is changed.
Since the armature reaction emf 𝐸෨𝑎𝑟 lags the current 𝐼ሚ𝑎 by 90 ˚, we can also Figure 4: The phasor diagram showing the effect of
express it as armature reaction when the power factor is lagging.
𝐸෨𝑎𝑟 = − 𝑗𝐼ሚ𝑎 𝑋𝑚
Where, 𝑋𝑚 , a constant of proportionality, is known as the magnetization
reactance.
Both the magnetization reactance and the leakage reactance are present at
the same time. It is rather difficult to separate one reactance from the other.
For this reason, the two reactances are combined together and the sum
𝑋𝑠 = 𝑋𝑚 + 𝑋𝑎
is called the synchronous reactance. The synchronous reactance is usually
very large compared with the resistance of the armature winding. We can
now define the synchronous impedance on a per-phase basis as 𝑍෨𝑠 = Figure 5: The phasor diagram showing the effect of armature
𝑅𝑎 + 𝑗𝑋𝑠 reaction when the power factor of the load is leading.
Synchronous Generator Tests
With the terminals open, 𝐼𝐴=0, so 𝐸𝐴 = 𝑉𝜑. It is thus possible to Circuit diagram to perform open-circuit test.
construct a plot of 𝐸𝐴 or 𝑉𝑇 vs 𝐼𝐹 graph. This plot is called open-circuit
characteristic (OCC) of a generator. With this characteristic, it is
possible to find the internal generated voltage of the generator for any
given field current.
𝐸𝐴
𝐼𝐴 =
𝑅𝐴2 + 𝑋𝑆2
Short-circuit characteristic (SCC) of a generator
Synchronous Generator Tests
From both tests, here we can find the internal machine impedance
(𝐸𝐴 from OCC, 𝐼𝐴 , from SCC):
𝐸𝐴
𝑍𝑆 = 𝑅𝐴2 + 𝑋𝑆2 =
𝐼𝐴
Since 𝑋𝑆 ≫ 𝑅𝐴 , the equation reduces to:
𝐸𝐴 𝑉𝜙𝑂𝐶
𝑋𝑆 ≈ =
𝐼𝐴 𝐼𝐴
The following are the three methods which are used to determine the
voltage regulation of smooth cylindrical type Alternators
• Often two or more generators are connected in parallel to supply a common load in large utility systems
Connecting a generator to other generators is called paralleling
many paralleled generators behave like an infinite bus
• voltage and frequency are constant and cannot be easily altered
before connecting a generator to an electrical grid, it must be synchronized
• the generator frequency is equal to the system frequency
• the generator voltage is equal to the system voltage
• the generator voltage is in phase with the system voltage
• the phase sequence of the generator is the same as that of the system
Synchronizing may be achieved with the help of synchronizing lamps, the rotary lamp method being the most popular.
Alternatively, a device known as the synchroscope may conveniently be used to facilitate synchronizing.
• To synchronize a generator
adjust the speed regulator of the prime mover so that frequencies are close
adjust the excitation so that generator voltage and system voltage are equal
observe the phase angle by means of a synchro scope, which indicates the phase angle between two voltages
• the pointer rotates proportional to the frequency difference
• a zero mark indicates a zero degree phase angle
• the speed regulator is adjusted so that the pointer barely creeps across the dial
on the zero mark, the line circuit breaker is closed
Parallel Operation of Synchronous Generators (Connecting to an Infinite Bus)