33 11KV Substation SLD
33 11KV Substation SLD
33 11KV Substation SLD
Goh GSS 14 Km
(2x20)MVA Terminal Gantry
33 KV Line
33 KV L A
33 KV Lightning arrestor
33 KV fuse
H.G fuse
AB Switch
AB Switch H.G.fuse
AB Switch
11 KV C.T 11 KV C.T 11 KV C.T 11 KV C.T
11 KV PT 100 KVA T/F
11 KV FUSE 11 KV FUSE
11 KV FUSE 11 KV FUSE
55 A 35 A 70A 60A
11KV FEEDER 11 KV FEEDER 11KV FEEDER 11KV FEEDER
DEOHARA R 25 KM TOWN FEEDER 5KM TYAP FEEDER R 35 KM DORHA FEEDER R 26 KM
RABBIT+WEASEL RABBIT+WEASEL RABBIT+WEASEL RABBIT+WEASEL
1.DC SUPPLY TOTALLY FAILED NO BATTERY CHARGER FOUND 2.CONDITION OF CONTROL ROOM IS REALLY HORRIBLE
3.NO PANEL FOUND IN THE CONTROL ROOM 4.MOST OF THE LAS ARE DAMAGED
5.CTS AND PTS ARE SHORT AND FEW ARE DAMAGED 6. NO VCB/OCB FOUND IN WORKING CONDITION ALL ARE DAMAGED
ALL THE CEILING OF CONTROL ROOM IS BROKEN IT NEEDS CIVIL WORK 7..HIGHLY SHORTAGE OF STAFF AND OPERATOR ,HELPER IS INCHARGE
Single Line Diagram of (2X5) MVA 33/11 KV Goh S/S (Proposed)
33 KV PT 33 KV PT
33 KV V.C.T 33 KV V.C.T
H.G fuse
H.G fuse
33 KV LA
33 KV L A
33 /11 KV T/ F 5 MVA
33 /11 KV T/ F 5 MVA
11 KV L A
11 KV L A
11 KV POST INSULATOR
11 KV C.T
11 KV C.T
11 KV VCB
11 KV VCB
Bus isolator
11 KV PT Proposed AB Switch
AB Switch
AB Switch AB Switch
AB Switch AB Switch AB Switch AB Switch
11 KV L A 11 KV L A
11 KV L A 11 KV L A
5MVA
5 MVA
11 kv CT
11 kv CT
11 KV VCB
11 KV PT Bus isolator 11 KV VCB
AB Switch Proposed AB Switch H.G.fuse
AB Switch AB Switch
11 kv CT
11 kv CT 11 kv CT 11 kv CT 11 kv CT 11 kv CT
63 KVA T/F
11 KV VCB
11 KV VCB 11 KV VCB 11 KV VCB