Typical Control / Supervision Circuits: by Y. K. Pandharipande

The document describes several typical control and supervision circuits used in electrical systems, including: 1) A typical control panel layout and circuit arrangement. 2) A local/remote control and protection trip circuit. 3) An anti-pumping circuit for circuit breakers. 4) Metering circuits. 5) Trip circuit supervision using coils to provide pre-close and post-close monitoring. 6) VT fuse supervision circuits to detect secondary fuse failures and block tripping. 7) A VT supervision scheme using voltage balance detection to monitor primary and secondary fuses.

Uploaded by

Viresh Shaunak
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
79 views11 pages

Typical Control / Supervision Circuits: by Y. K. Pandharipande

The document describes several typical control and supervision circuits used in electrical systems, including: 1) A typical control panel layout and circuit arrangement. 2) A local/remote control and protection trip circuit. 3) An anti-pumping circuit for circuit breakers. 4) Metering circuits. 5) Trip circuit supervision using coils to provide pre-close and post-close monitoring. 6) VT fuse supervision circuits to detect secondary fuse failures and block tripping. 7) A VT supervision scheme using voltage balance detection to monitor primary and secondary fuses.

Uploaded by

Viresh Shaunak
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 11

TYPICAL CONTROL / SUPERVISION

CIRCUITS

By
Y. k. Pandharipande.
TYPICAL CONTROL / SUPERVISION
CIRCUITS
TYPICAL CONTROL PANEL LAY OUT (FRONT VIEW)
TYPICAL CONTROL / SUPERVISION
CIRCUITS
TYPICAL CIRCUIT ARRANGEMENT / MIMIC
TYPICAL CONTROL / SUPERVISION
CIRCUITS
LOCAL/REMOTE CONTROL & PROTECTION TRIP CKT
TYPICAL CONTROL / SUPERVISION
CIRCUITS
ANTI-PUMPING CIRCUIT FOR BREAKER

APR – Anti-pumping Relay, PR – Protection Relay Contact


CS – C.B. Remote Control Switch, C/C, T/C – CB Close /Trip Coil
TYPICAL CONTROL / SUPERVISION
CIRCUITS
TYPICAL CONTROL / SUPERVISION
CIRCUITS
TYPICAL CONTROL / SUPERVISION
CIRCUITS
METERING CIRCUITS (TYPICAL)
TYPICAL CONTROL / SUPERVISION
CIRCUITS
TRIP CIRCUIT SUPERVISION

 “A” Coil provides post close supervision while A & B Coil


provide pre-close supervision.
 “C” Element is provided with delay on drop off to prevent
false alarms on mommentary dip in DC Voltage.
TYPICAL CONTROL / SUPERVISION
CIRCUITS
VT FUSE SUPERVISION

P – Protection Burden, M – Metering Burden


R – Fuse Failure relay
 Detects only secondary fuse failure.
 High Speed operation. Used to monitor VT supply to
Distance relay to block tripping & sound alarm on VT Fuse
Failure.
TYPICAL CONTROL / SUPERVISION
CIRCUITS
VT SUPERVISION USING VOLTAGE BALANCE SCHEME

 Relay operates on unbalance voltage detection.


 Monitors Prim. & Secondary fuses using 2 out of 2 logic.