Gen Prot Islanding
Gen Prot Islanding
protection
Stator Protection
Abnormal operating conditions
System back up protections
Rotor protection
GT protections
UT protections
Over view of type of fault Vs protection
FAULT/ABN EFFECT PROTECTION
ML CONDN
Thermal over Over heating of stator Thermo couples/
loading wdg/insulation failure Over current relays
External Unbalanced loading stress Over load/negative phase
fault sequence relay
Stator faults Wdg burn out Differential prot
ph to ph/ Welding of core lamination 100% E/F prot/95% E/f
Ph to E Inter turn prot
Inter turn
Rotor fault Damage to shaft/bearing 2 stage rotor E/F protection
Motoring LFPR/Rev power Inter lock
A) Unit scheme:
(NON GCB SCHEME)
In this scheme no
switchgear is provided
between the generator and
generator transformer, which
are treated as a unit; a unit
transformer is tapped off the
interconnection for supplying
of power to auxiliary plant.
GCB SCHEME
B) Generator circuit breaker
scheme:
In this scheme a generator
circuit breaker is provided
between the generator and
generator transformer. unit
transformer is tapped off before
the GCB for supplying of
power to auxiliary plant.
Generator grounding practices
Generator grounding practices
Generator grounding practices
Generator grounding practices
Generator earthing practices
TRIP LOGIC OF GENERATOR PROTECTION
CLASS A TRIPS
ALL ELECTRICAL TRIP
TRIP TURBINE , FIELD, GENERATOR,GT,UT
CLASS-B TRIP
MECHANICAL TRIPS
AVOID OVER SPEEDING OF TURBINE DUE TO STEAM
ENTRAPPED IN TURBINE. TURBINE TRIP SIGNAL IS GIVEN
FIRST AND THE ACTIVE POWER, SENSED BY THE LOW
FORWARD RELAY (32G) GIVES THE TRIP SIGNAL TO THE UNIT
BREAKER & FIELD BREAKER AFTER A TIME DELAY.
IN GCB SCHEME, ONLY GCB AND FIELD IS TRIPPED,KEEPING
UAT CHARGED THROUGH GT
IN NON GCB SCHEME, HV CB,FIELD,UT LCV CB ARE TRIPPED.
Class C
Trips only HV CB
Typical gen prot sld
Typical Generator
protection
scheme
RELAY GROUPING.
SL PROTECTION FUNCTION REMARK ON GROUPING
NO OF PROTECTION
1. Generator Differential Protection, 3 pole 87 G AND 87 GT SHALL
(87 G) having operating time of 25 milli BE ON TWO DIFFERENT
sec. or lower at five times the current CHANNELS OF
rating. PROTECTION.
2. Overall Differential Protection (87GT).
FEATURES:
UNIT TYPE PROTECTION
INSTANTANEOUS IN OPERATION.
COVERS THE STATOR WDG FOR PHASE TO PHASE FAULTS.
DUPLICATED DIFFERENTIAL PROT GIVEN USED FOR GCB
SCHEME
TWO TYPES: HIGH IMPEDANCE TYPE/BIASED TYPE.
STABLE FOR THROUGH FAULTS.
HIGH IMP TYPE RELAY contd
CT PARAMETERS
Vk = 2 If (Rct+2Rl)
Vk Min. Knee point voltage of the CT
If - Maximum fault current in the system
(converted to sec side)
Rct- Secondary resistance of the CT
Rl lead resistance of the sec connection
(typ 8.73 ohms per km for 2.5 sq mm cu cable)
CT CONNECTION
BIASED TYPE DIFF RELAY
CTS CAN BE SHARED WITH OTHER PROTECTIONS
PS CLASS CTs REQUIRED.
LESS STRINGENT CT PARAMETERS.
INDIVIDUAL CT INPUTS GIVEN TO THE INDIVIDUAL BIAS COILS.
THROUGH FAULT STABILITY ACHIVED THROUGH BIASING.
CT MISMATCH (TYP OF THE PRDER OF 1:5 ) CAN BE ACCOMODATED.
MORE SUITABLE FOR NUMERICAL INTEGRATED PROTECTION SYSTEMS
AS THE CTs CAN BE SHARED FOR MANY FUNCTIONS.
CT CONNECTION
Biased Differential protection
Modern numerical relays have flexible settings for
Id, b (point of slope change) and the slopes.
DISADVANTAGES
relay accessory
FIELD
NGT
COMPARISION BETWEEN E/F PROTECTIONS
INTER TURN PROTECTION
CURRENT BASED SYSTEM
FOR GENERATORS WITH SPLIT NEUTRALS WITH ALL SIX
TERMINALS BROUGHT OUT ON NEUTRAL SIDE
DELAYED LOW-SET O/C RELAY WHICH SENSES THE CURRENT
IN THE CONNECTION BETWEEN THE NEUTRALS OF THE STATOR
WINDINGS
TYPICAL SETTING:
U/F O/F
ALARM - 47.8HZ 1 SEC 51 Hz 1 SEC
TRIP - 47.4 HZ 2 SEC 51.5Hz 2.5 SEC
SETTING NEED TO BE CO-ORDINATED WITH THE
RESPECTIVE GRID AGENCY AND THE ISLANDING
SCHEME SETTINGS AND THE M/C CAPABILITY.
NEGATIVE SEQUENCE PROTECTION
Negative sequence protection
NEGATIVE SEQUENCE PROTECTION FOR GENERATOR PROTECTS
THE GENERATOR FROM EXCESSIVE HEATING IN THE ROTOR
RESULTING FROM UNBALANCED STATOR CURRENTS
CAUSED DUE TO
ONE POLE OPEN IN LINE
ONE POLE OPEN OF A CIRCUIT BREAKER
CLOSE IN UNCLEARED UNBALANCED FAULTS
METHOD OF DETECTION:
RELAY LINE
OUT OF STEP PROTECTION
MACHINE RUNS OUT OF SYNCHRONISM WITH THE NETWORK
CYCLIC VARIATION OF ROTOR ANGLE
CURRENT INCREASES HEAVILY
FREQUENCY DEPEND ON THE RATE OF SLIP
RESULT IN THE WINDING STRESS
IT MAY ALSO DAMAGE THE AUXILIARIES OF THE AFFECTED
UNIT
DETECTED BY SENSING THE VARIATIONS IN IMP
DISTINGUISH BETWEEN THE RECOVERABLE SWING AND THE
IRRECOVERABLE SWING
BLINDERS + A SUPERVISORY MHO ELEMENT,TRIP WHEN
IMP IS INSIDE THE MHO AND CROSE THE BLINDERS WITH
THE SPECIFIED TIME.
MINIMUM IMPEDANCE(MULTIPLE ZONE) + COUNTING NO OF
SWINGS
TYPICAL POLE SLIPPING RELAY
CHARACTERISTICS
TYP SETTING:
:
MHO RELAY SETTING
FORWARD: ZT+Z SYS,
REVERSE : GEN XD
OVER CURRENT SETTING
TYP 115%
DISTANCE BETWEEN THE
BLINDERS = HALF OF
VECTOR SUM OF
ZG,ZT,ZSYS
(APPROXIMATELY)
TIME TYP 50-55 MSEC
TYPICAL OUT OF STEP/POWER SWING LOCUS
ACCIDENTAL BACK ENERGISATION
CAUSE:
EFFECTS
DETECTED BY
CRITERIA:
UNDER FREQUENCY / RATE OF CHANGE OF
FREQUENCY
ACTION:
STAGGERED TRIPPING OF GRID LINES AT
PREDTERMINED LOGIC AT THE PRE DECIDED
SEQUENCE.
ISLANDING SCHEME FOR GRID
CONNECTED GENERATORS.
KEY FEATURES
INTEGRATED SCHEME FOR THE WHOLE
PLANT
FREQUENCY BASED
TRIGGERING BASED ON THRESHOLD AND
RATE OF CHANGE OF FREQUENCY
U/F RELAYS CONNECTED TO BUS CVT
BASED ON 2 OUT OF 3 LOGIC
INDIVIDUAL TRIP RELAYS FOR EACH FEEDER
STAGGERED TRIPPING SCHEME TO BE
ENGINERED IN COORDINATION WITH
RESPECTIVE GRID AGENCY DEPENDING ON
THE SYSTEM CONDITIONS AND THE POWER
NUMBER OF THE CONNECTED GRID.
CVT SUPPLY FOR U/F
RELAYS
CONNECTED TO THE SELECTED
BUS CVT SUPPLY
OR