Insulators must be tested to ensure they can withstand over-voltages from sources like lightning. There are two types of high voltage tests: power frequency voltage tests and impulse voltage tests. These tests are done to determine the disruptive discharge voltage, withstand voltage, and flashover voltages of insulators under dry and wet conditions. Similar types of tests are also done on other electrical equipment like transformers.
Insulators must be tested to ensure they can withstand over-voltages from sources like lightning. There are two types of high voltage tests: power frequency voltage tests and impulse voltage tests. These tests are done to determine the disruptive discharge voltage, withstand voltage, and flashover voltages of insulators under dry and wet conditions. Similar types of tests are also done on other electrical equipment like transformers.
Insulators must be tested to ensure they can withstand over-voltages from sources like lightning. There are two types of high voltage tests: power frequency voltage tests and impulse voltage tests. These tests are done to determine the disruptive discharge voltage, withstand voltage, and flashover voltages of insulators under dry and wet conditions. Similar types of tests are also done on other electrical equipment like transformers.
Insulators must be tested to ensure they can withstand over-voltages from sources like lightning. There are two types of high voltage tests: power frequency voltage tests and impulse voltage tests. These tests are done to determine the disruptive discharge voltage, withstand voltage, and flashover voltages of insulators under dry and wet conditions. Similar types of tests are also done on other electrical equipment like transformers.
Download as PPTX, PDF, TXT or read online from Scribd
Download as pptx, pdf, or txt
You are on page 1of 46
High voltage
measurement and testing
Chapter-7 Why do we need to test the insulators It is essential to ensure that the electrical equipment is capable of withstanding the over-voltages that are met with in service.
The over-voltages may be either due to natural
causes like lightning or system originated ones such as switching or power frequency transient voltages.
Hence, testing for over-voltages is necessary
TESTING OF INSULATORS The overvoltage tests are classified into two groups: (i) power frequency voltage tests; and (ii) impulse voltage tests. These tests together ensure the over-volt-age withstand capability of an apparatus.
Commonly used technical terms.
Disruptive Discharge Voltage: This is defined as the voltage
which produces the loss of dielectric strength of an insulation. It is that voltage at which the electrical stress in the insulation causes a failure which includes the collapse of voltage and passage of current. In solids, this causes a permanent loss of strength, and in liquids or gases only temporary loss may be caused. When a discharge takes place between two electrodes in a gas or a liquid or over a solid surface in air, it is called flashover. If the discharge occurs through a solid insulation it is called puncture Withstand Voltage: The voltage which has to be applied to a test object under specified conditions in a withstand test is called the withstand voltage [as per IS: 73 1 and IS: 2099-1963]. Fifty Percent Flashover Voltage: This is the voltage which has a probability of 50% flashover, when applied to a test object. This is normally applied in impulse tests in which the loss of insulation strength is temporary. Hundred Per Cent Flashover Voltage: The voltage that causes a flashover at each of its applications under specified conditions when applied to test objects is specified as hundred per cent flashover voltage. Creepage Distance: It is the shortest distance on the contour of the external surface of the insulator unit or between two metal fittings on the insulator. A.C. Test Voltages: Alternating test voltages of power frequency should have a frequency range of 40 to 60 Hz and should be approximately sinusoidal. The deviation allowed from the standard sine curve is about 7%. The deviation is checked by measuring instantaneous values over specified intervals and computing the rms value, the average value, and the form factor. Impulse Voltages : Impulse voltages are characterized by polarity, peak value, time to front (tf), and time to half the peak value after the peak (tt). The time to front is defined as 1.67 times to the time between 30% and 90% of the peak value in the rising portion of the wave. According to IS: 2071 (1973), standard impulse is defined as one with tf = 1.2 s, tt =50 s (called 1/50 s wave). The tolerances allowed are 3% on the peak value, 30% in the front time (tf), and 20% in the tail time (tt). Reference Atmospheric Conditions: The electrical characteristics of the insulators and other apparatus are normally referred to the reference atmospheric conditions. According to the Indian Standard Specifications, they are: Temperature : 27 C Pressure : 1013 millibars (or 760 torr) Absolute humidity : 17 gm/m3. It is not always possible to do tests under these reference conditions, correction factors have to be applied. In some cases, the following test conditions are also used as reference (British Standard Specifications) conditions. Temperature : 20 C Pressure : 1013 millibars (or 760 torr) Absolute humidity : 11 gm/m3(65% relative humidity at 20 C ) Tests on insulators The tests that are normally conducted are usually subdivided as (i) type tests, and (ii) the routine tests Type tests: Type tests are intended to prove or check the design features and the quality. The routine tests are intended to check the quality of the individual test piece. Type tests are done on samples when new designs or design changes are introduced. Routine tests: The routine tests are done to ensure the reliability of the individual test objects and quality and consistency of the materials used in their manufacture. High voltage tests include (i) the power frequency tests, and (ii) impulse tests. All the insulators are tested for both categories of test Type tests (power frequency) Dry and wet flashover test: A .c. voltage of power frequency is applied across the insulator and increased at a uniform rate of about 2 per cent per second of 75% of the estimated test voltage, to such a value that a breakdown occurs along the surface of the insulator. The test conducted under normal conditions without any rain or precipitation is called "dry flashover test". The test done under conditions of rain is called "wet flashover test. (specification of arrangement in IEC, 1979) Application of 15 positive and 15 negative impulses (IEC 1979). Two in each set are allowed to flashover. If more than two flashovers occur in each set, then the insulator is deemed to have failed the test Wet and Dry Withstand Tests (One Minute): In these tests, the voltage specified in the relevant specification is applied under dry or wet conditions for a period of one minute with an insulator mounted as in service conditions. The test piece should withstand the specified voltage. The characteristics of artificial rain in IEC 168 (IEC,1979). Type tests (Impulse) Impulse Withstand Voltage Test This test is done by applying standard impulse voltage of specified value under dry conditions with both positive and negative polarities of the wave. If five consecutive waves do not cause a flashover or puncture, the insulator is deemed to have passed the test. If two applications cause flashover, the object is deemed to have failed. If there is only one failure ,additional ten applications of the voltage wave are made. If the test object has withstood the subsequent applications, it is said to have passed the test Impulse Flashover Test: The test is done as above with the specified voltage. Usually, the probability of failure is determined for 40% and 60% failure values or 20% and 80% failure values, since it is difficult to adjust the test voltage for the exact 50% flashover values. The average value of the upper and the lower limit s is taken. The insulator surface should not be damaged by these tests, but slight marking on its surface or chipping off of the cement is allowed. Pollution Testing : There is problem of pollution of outdoor electrical insulation and consequent problems of the maintenance of electrical power systems, pollution testing is gaining importance. The pollution tests maybe made either to determine the maximum degree of pollution withstood by the insulator under a given voltage or to determine its withstand voltage for a specified degree of pollution. The pollution tests involve application of the pollution and simultaneous or subsequent application of voltage. The pollution tests fall into two categories: the saline fog method and the pre-deposited pollution method (IEC, 1975) TESTING OF TRANSFORMERS The following tests are required on most power transformers, as recommended by IEC 76- 1 and 2 (IEC, 1976c,d),and 76-3-1 (IEC, 1987a). Routine tests a. Measurement of winding resistance b. Measurement of voltage ratio and check of voltage vector relationship c. Measurement of impedance voltage, short-circuit impedance, and load loss d. Measurement of no-load loss and current e. Tests on tap changers Type tests a. Dielectric tests b. Temperature rise tests Impulse Testing of Transformers The purpose of the impulse tests is to determine the ability of the insulation of the transformers to withstand the transient voltages due to lightning ,etc. Impulse testing of transformers is done using both the full wave and the chopped wave of the standard impulse, produced by a rod gap with a chopping time of 3 to 6 s. To prevent large over voltages being induced in the windings not under test, they are short circuited and connected to ground . Impulse testing is done in the following sequence Applying impulse voltage of magnitude 75% of the Basic Impulse Level (BIL) of the transformer under test. one full wave voltage of 100% BIL, two chopped waves of 100% BIL, one full wave of 100% BIL, and one full wave of 75% BIL. It is very important to see that the grounding is proper and the windings not under test are suitably terminated. Test voltages The conventional forms of test voltages in use can be divided into three main groups: (a) direct voltages, (b) power-frequency alternating voltages, and (c)impulse voltages, which are divided into lightning and switching impulses. Also, in the case of testing machine insulation, alternating voltages of low frequency are sometimes used. Tables list the recommended test voltages adopted for testing equipment for rated AC voltages ranging between l and 765kV (IEC, 1976b). For equipment with rated voltages of 1 to 300 kV, performance under power-frequency operating voltage, temporary over-voltages, and switching over-voltages is generally checked by a short-duration power-frequency test. Testing with Direct voltages Direct voltage is used mainly to test equipment used in high-voltage DC transmission systems. It is additionally used in insulation testing of arrangements with high capacitance, such as capacitors and cables. The value of the test voltage is defined by its arithmetic mean, The test voltage, as applied to the test object, should not contain AC components corresponding to a ripple factor of more than 5% when normal current is drawn. During the test it is required that the rate of voltage rise above 75% of its estimated final value should be about 2% per second (IEC, 1973). The requirements of the test are generally satisfied if no disruptive discharge occurs on the test object when under the test voltage for the specified duration. Non destructive testing of Insulation Nondestructive electrical tests are usually carried out on the equipment insulation to ensure that its electrical characteristics comply with the specifications without destroying it. These tests include partial discharges, radio interference, dielectric loss angle, and insulation resistance measurements (Kind, 1978). Di-electric loss measurement Losses always occur in dielectrics due to conduction, polarization, and ionization. Dielectric losses cause certain electrical effects, which can be utilized for nondestructive high-voltage testing. Schering bridge for dielectric loss measurement The Schering bridge, devised by Schering in 1919, has since been widely used to measure the capacitance and loss angle of high-voltage insulators, capacitors, and cable samples. The bridge comprises two high-voltage (HV) arms and two low-voltage (LV) arms. The HV arms are the test piece and a standard capacitor, This capacitor should have no significant losses over the full working range. Both the LV arms and the null detector are shielded from the high-voltage circuit to eliminate any errors in the measurements caused by the effect of stray capacitances. In the power frequency range (25 to 100 Hz) Schering bridge is a very versatile and sensitive bridge and is readily suitable for high voltage measurements. The tan can be readily obtained with this bridge. The lossy capacitor or capacitor with the dielectric between electrodes is represented as an imperfect capacitor of capacitance Cx together with a resistance rx. The standard capacitor is shown as Cs which will usually have a capacitance of 50 to 500 F. The variable arms are R4 and C3R3. Balance is obtained when The lossy capacitor which is made as an equivalent Cx in series with rx can be represented as a parallel combination of C and R where the parallel combination Rx is found to be
The normal method of balancing is by fixing
the value of R3 and adjusting C3 and R4. R is usually an decade resistor box. High voltage measurement Measurement of high voltages d.c., a.c. or impulse voltages involves unusual problems that may not be familiar to specialists in the common electrical measurement techniques. The difficulties are mainly related to the large structures necessary to control the electrical elds, to avoid ashover and sometimes to control the heat dissipation within the circuits. HV Measurement Techniques Peak voltage measurements by spark gaps Simple spark gaps insulated by atmospheric air can be used to measure the amplitude of a voltage above about 10 kV. The complex mechanism of this physical effect, often employed in protecting equipment from over-voltages. The fast transition from an either completely insulating or still highly insulating state of a gap to the high conducting arc state is used to determine a voltage level, the disruptive discharge does not offer a direct reading of the voltage across the gap. A complete short-circuit is the result of a spark, and therefore the voltage source must be capable to allow such a short-circuit, although the currents may and sometimes must be limited by resistors in series with the gap. Sphere gaps Two adjacent metal spheres of equal diameters, with certain separation distance ,form a sphere gap for the measurement of the peak value of either d.c., a.c. or both kinds of impulse voltages. The ability to respond to peak values of voltages, if the duration of the peak region is not too short in time (13sec), is governed by a short statistical time lag. i.e. Time lag is the waiting time for an electron to appear to initiate an electron avalanche and breakdown streamer, and an equally short formative time lag required for the voltage breakdown or fast current increase within the breakdown channel. Standardized construction for sphere gap A and B dene clearances such as to maintain the eld distribution between the points on the two spheres that are closest to each other (sparking points) within narrow limits. The height of the sparking point P above the horizontal ground plane, which can be a conducting network in or on the oor of the laboratory, or a conducting surface on the support in which the sphere gap is placed, must be within given limits related to the sphere diameter D. To be accepted as a standard measuring device, a minimum clearance B around the sphere must also be available, within which no extraneous objects (such as walls, ceilings, transformer tanks, impulse generators) or supporting framework for the spheres are allowed. Disruptive discharge voltages Sphere gap of diameter D and spacing S will spark at a peak voltage whose value will be close to the nominal values. For every sphere diameter the sparking voltage is a non-linear function of the gap distance, which is mainly due to the increasing eld in homogeneity and only less to the physics of breakdown. The calibration data, related to the atmospheric reference conditions (temperature 20C; air pressure 101.3 kPa or 760 mmHg) and the kind and polarity of voltage applied, are a result of joint international measurements within the period 1920 to about 1955. Remarks on the use of the sphere gap The sphere gap represents a capacitance, which may form a series resonant circuit with its leads. Heavy pre discharges across a test object will excite superimposed oscillations that may cause erratic breakdown. To avoid excessive pitting of the spheres, protective series resistances may be placed between test object and sphere gap, whose value may range from 0.1 to 1 M for d.c. and a.c. power frequency voltages. For higher frequencies, the voltage drop would increase and it is necessary to reduce the resistance. For impulse volt- ages such protective resistors should not be used or should not exceed a value of 500 (inductance less than 30 H) The disruptive discharge values of Tables apply to measurements made without irradiation other than random ionization already present, except in The measurement of voltages below 50 kV peak, irrespective of the sphere diameters, The measurement of voltages with spheres of 125 mm diameter and less, whatever the voltage. The application of spark gaps is time consuming. The procedure usually consists of establishing a relation between a high voltage, as measured by the sphere gap, and the indication of a voltmeter, an oscilloscope, or other device connected in the control circuit of the equipment The voltage measured by the sphere gap is derived from the spacing. The procedure in establishing the relationship varies with the type of voltage to be measured, as follows: For the measurement of direct and alternating voltages, the voltage shall be applied with an amplitude low enough not to cause disruptive discharge during the switching transient and it is then raised sufficiently slowly for the l.v. indicator to be read accurately at the instant of disruptive discharge of the gap. The procedure for the measurement of impulse voltages is different: In order to obtain the 50 per cent disruptive discharge voltage, the spacing of the sphere gap or the charging voltage of the impulse generator shall be adjusted in steps corresponding to not more than 2 per cent of the expected disruptive discharge value. Six applications of the impulse should be made at each step. The interval between applications shall not be less than 5 sec. The value giving 50% probability of disruptive discharge is preferably obtained by interpolation between at least two gap or voltage settings, one resulting in two disruptive discharges or less, and the other in four disruptive discharges or more. Another, less accurate, method is to adjust the settings until four to six disruptive discharges are obtained in a series of ten successive applications.