Duct Systems
Duct Systems
Duct Systems
CHAPTER 6
JEFFREY C. AVILA
601.0 Scope
602.1
Supply air, return air, and outside
air shall be conducted through duct
system constructed of metal as set
forth in Table 6-1 to 6-10 or metal
ducts complying with UMC
Standards No. 62.
Rectangular ducts in excess of two inches shall comply
with the standard. Ducts, plenums, and fittings may be
constructed of concrete, clay, or ceramics when
installed in the ground or in a concrete slab. Provided
the joints are tightly sealed. Corridors shall not be used
to convey air to or from rooms if the corridor is required
to be of fire resistive construction.
602.2 Combustibles within Ducts or Plenums
Materials exposed within ducts or plenums shall be non-
combustible or shall have flame spread index nit greater than 25
and a smoke developed index not greater than 50.
Exceptions:
1. Air filters meeting the requirement of Section 311.2 and 503.3.
2. Water evaporation media in an evaporative cooler.
3. Charcoal filters when protected with an approved fire suppression
system.
4.Electrical wiring in plenums shall comply with NFPA 70.
5. Non-metallic sprinkler piping in plenums shall be listed and
labelled.
6. Non-metallic tubing in plenums shall be listed and labelled.
602.3 Factory made air ducts
602.5 Metal
Air moving systems supplying air in excess of 2000 cubic feet per
minute (944 L/s) to enclosed spaces within buildings shall be
equipped with an automatic shut-off. Automatic shutoff shall be
accomplished by interrupting the power source of the air moving
equipment upon detection of smoke in the main supply air duct
served by such equipment. Smoke detectors shall be UL
approved for air duct installation and shall be installed in
accordance with the manufacturers approved installation
instructions. Such devices shall be compatible with the operating
velocities, pressures, temperatures, and humidity of the system.
Where fire detection or alarm systems are provided for the
building, the smoke detectors required by this section shall be
supervised by such systems and installed in accordance with
NFPA 72 and the Building and Fire Codes.
Exceptions:
1. When the space supplied by the air moving
equipment is served by a total coverage smoke
detection system complying with the Fire code,
interconnection to such system may be used to
accomplish the required shutoff.
2. Automatic shutoff is not required when all occupied
rooms served by the air handling equipment have direct
exit to the exterior and the travel distance does not
exceed 100 feet (30480 mm).
3. Automatic shutoff is not required the Group R,
Division 3 and Group U Occupancies.
4. Automatic shutoff is not required for approved
smoke control systems or where analysis demonstrates
shutoff would create a greater hazard, such as may be
encountered in air moving equipment supplying
specialized portions of Group H Occupancies. Such
Equipment shall be required to have smoke detection
with remote indication and manual shutoff capability at
an approved location.
5. Smoke detectors that are factory installed in listed
air moving equipment may be used in lieu of smoke
detectors installed in the main supply air duct served by
such equipment.