HVDC Unit 1
HVDC Unit 1
HVDC Unit 1
In recent years, a no. of developments have taken place in the power systems field.
The basic function of a transmission system is to transfer electrical power from
one area to another area or from one network to another network.
The present trend is to transmit larger amounts of power at very high voltages.
The voltages above 300KV are termed as Extra High Voltage, (EHV).
The voltage exceed 750 KV are termed as Ultra High Voltages (UHV).
Now-a-days larger amount of power are transmitted over long distances from
generating stations to load centers.
Alternating current power is used as a power source as well as for
transmission purposes because it can be conveniently generated and also converted
from one voltage to another voltage.
Why we go for EHV/UHV range for transmission purposes is
i) Reduction of electrical losses and hence transmission efficiency increases
ii) It improves voltage regulation because of reduction of line drop.
iii) Because of high voltage, the size of conductor is less because size of the conductor
is inversely proportional to the square of transmission voltage.
iv) The installation cost of the transmission line per km decreases by increasing in
voltage level.
v) It is possible to interconnecting of power systems.
vi) Less right-of-way is required.
Vii) Load carrying capacitor is expressed in terms of Surge Impedance Loading(SIL) for
transmission line, The surge impedance is given by Zc =
where L is the series
inductance and C is the shunt capacitance per unit length of the time. L / C
2
Surge Impedance loading (SIL) for a transmission line is given by SIL = 3V / Z c
Where V is line to neutral voltage.
From the above equation SIL varies as the square of the operating voltage. That
means for increase in transmission voltage level SIL increases, thus power
transfer capability of the line increases.
In view of above advantages many technical problems involved in EHV
transmission. The major problems are
i)Corona loss and Radio interference
The EHV transmission corona loss and radio interference is
high because line voltage level being a governing factor in the corona loss.
Corona loss can be minimized either by increasing the
conductor size or by increasing the spacing between the conductors. But the
spacing between the conductors cannot be increased to a large extent because
if the spacing is increased, the cost of the supports generally becomes very
high. Large diameter conductors have been used to bring down the corona loss
and radio interference.
But for increasing the diameter hollow and ACSR conductor
are used. But the cost of manufacturing for such conductor is high and their
handling is both difficult and expensive. Therefore bundled conductor after an
economical solution for minimizing corona loss and radio interference for EHV.
ii) EHV line needs heavy supporting structures because of use of bundled
conductors.
iii) Erection is difficulty.
iv) It requires high level of insulation
In view of these problems with ac, the dc transmission has staged a come
back in the form of high voltage dc transmission to supplement the AC transmission
system.
The first DC link was setup in 1954 between Swedish mainland and the
island of Gotland. This was a monopolar, 100KV, 20 MW, cable system making use
of sea return.
In 1961 an underwater dc link was setup between England and France.
This was bipolar + 100KV, 160 MW cable system over a distance of about 65 KM.
HVDC transmission has also been introduced in India. +500 KV has been
selected as the voltages for HVDC transmission.
A +500 KV, 1500 MW, 810 KM bipolar HVDC line has already been set up
between Rihand and Delhi.
At present the world has over 50 HVDC schemes in operation for a total
capacity of more than 50,000 MW and the capacity is increased by about 2000MW
every year.
Step-up
transformer
Generating
Station
Step-down
transformer
HVDC
Transmission
Rectifier
Station (R)
filter
filter
Inverter
Station (I)
Receiving
end
HVDC link
Rectifier
Inverter
AC
Supply
AC Grid
I
Converter Station
Converter station consists the following equipments and as shown in fig
i.Converter unit
ii.Converter transformer
iii.Filters
iv.Reactive power
v.Smoothing reactor
vi.Switch gear
i.Converter Station:
ii.Converter transformer:
The converter transformer can have the different configurations, they are
a)Three phase, two winding transformer
b)Single phase, three winding transformer
c)Single phase, two winding transformer
The above of (a) and (b) type of transformer can be installed at the
valve side & winding are stator and delta with neutral point ungrounded.
The configuration (c) can be used on the AC side and the transformer
are connected in parallel with neutral grounded.
Note:
The leakage reactance of the transformer is chosen to limit the short circuit
currents through any value.
The converter transformers are designed to withstand DC voltage
stresses and increased eddy current losses due to harmonic currents.
iii.Filters:
Three types of filters can be used in the converter station, they are
a)AC filter
b)DC filters
c)High frequency (RF/PLC) filters
iv. Reactive power source:
Converter stations require reactive power supply that is dependent on the
active
Power loading [about to 60% of the active power]. Fortunately, part of this reactive
power requirement is provided by AC filters. For addition of above the shunt
(switched) capacitor, synchronous condensers and static Var systems are used. On
the dependency of speed of control is desired.
v. Smoothing reactor:
Generally a sufficiently large series reactor is used on DC side to get the
smooth DC current and also for the protection. The reactor is designed as a linear
reactor and is connected on the line side, neutral side or at intermediate location.
vi. DC switch gear:
The DC switch gear is usually a modified AC equipment used to interrupt
small DC currents [employed as disconnecting switches]. DC breakers or metallic
return transfer breakers (MRTB) are used, if required for interruption on rated load
currents.
In addition to the equipment described above, AC switch gear and
associated equipment for protection and measurement are also part of the converter
station.
However, the voltage rating of individual thyristor is small as compared to line voltage.
Thus a large number of thyristors are connected in series to obtain required voltage
rating.
The valves are of indoor design, air insulated and air (or) water-cooled.
Generally the thyristor always fail to an internal short circuit, a thyristor valve is always
equipped with a number of extra thyristors in series so that even if any one of thyristor
fails, the operation of the valve is not effected. As thyristor produce heat of 30-40 W/cm2
hence effective cooling system is required in practical installation. Water cooling in
recommended for high power applications. Thyristors are protected from dv/dt, dI/dt,
forward over voltage firing, over temperature and forward recovery protection.
iii) Converter transformers:
The modern HVDC scheme six pulse or twelve pulse converters are used.
Generally 12-pulse converters are more preferred as it contains high ripple frequency.
There are two 3 phase transformers connecting each 12-pulse converter to the ac bus
bars. One of the 3 phase transformer is star/star (Y-Y) connected and the other is
star/delta (Y-) connected so as to give a phase shift of 30 degrees between the two 6pulse bridge of the converter. Converter transformer serves the following fuctions:
Short circuit currents are controlled by suitable impedance value of these transformer.
Converter transformer reactance will suppress the harmonics.
Reactive power is supplied to the converter through tap changing.
A converter transformer has a some what different design than that of normal power
transformer because in the converter transformer the currents have high harmonic
content so that special care has to be taken with regard to eddy current losses. To
reduce the reactive power demand in steady state operation on load tap changing is
normally used. Proper quality control of tap change is needed in HVDC systems
because the number of tap changer operation are high in HVDC system.
iii) Converter Unit:
The 12-pulse converter is formed by connecting two 3-ph 6-pulse
converters connected in series. A 12-pulse converter unit is shown in fig. The use of
four valve units per phase of a 12-phase converter configuration is common. A typical
quadrivalve comprises from valves placed vertically one above the other to form on
limb of the converter. Such an arrangement provides the most compact and
economical layout of the valves and the valve housing. Three quadrivalve consists of
12-pulse converter. Valve firing signals are generated in the converter control at
ground potential and are transmitted to each thyristor in the valves through a fiber
optic light guide system. Snubber circuit, gapless surge arresters are used to
protection of valves.
iv) Smoothing reactors:
A smoothing reactor is connected in series with each pole of a converter
station. The valve of inductance is between the 0.4H to 1.0H. The DC reactor is
usually of air core and oil-cooled type and has the non linear magnetic
characteristics. By increasing the value of inductance the current waveform on the
DC side improves but control response slows down and the resonance frequency
reduces making the stabilization of current control more difficult.
The size of the filter represents the reactive power that the filter supplies at
fundamental frequency and the quality of the filter represents the sharpness of
tuning which increases with the ratio of its resonance inductance or capacitance to
its resistance for resonant filters.
In case of high pass filter, the sharpness increases is inversely propotional
to that ratio. AC filters used in HVDC systems are tuned filter which is sharply tuned
to a harmmic frequency, damped filter which, is shunt connected, offer low
impedance over a broad band of frequencies. Now in 12-pulse valve group
operation only two damped filters are used. Damped filters are simple to design and
have lower rate of the resonant over voltage and currents are compared to tunned
filter.
DC filter:
DC side of HVDC converter converter the voltage harmmics generation
harmmic currents, whose amplitude depend on the belong inversion angle and the
impedance of the DC circuit itself. The harmmics on the DC side must also be
limited before entering the line. The dc reactor or smoothing reactor is sufficient to
limit the magnitude of the harmmics on the dc side.
i) Voltage limits:
The normal working voltage and the over voltages caused by switching surges and
lightning must be limited to values that will not cause puncture on flashover of
the insulation. AC line voltage control is complex by the line charging and
inductive voltage drops. On EHV overhead lines switching surges have become
the more serious transient overvoltages, and on ac lines attempts and made to
limit them to peak value of two or three times normal crest voltage. Whereas in
case of DC transmission switching surges are lower than this, say 1.7 times
normal voltages.
Due to corona maximum working voltage or the minimum conductor size is
limited on over head lines. In cables, normal working voltage is usually the
limiting factor. Insulation will withstand a DC voltage higher than the crest of the
alternates voltage( 2 times R.M.S. voltage)
ii) Current limit:
The temperature of a conductor must be limits in order to avoid damage to the
conductor itself permanently increased sag on in the case of a cable to the
installation in contact with it. Hence current in the conductor must be limited in
accordance with its duration and the ambient temperature.
iii) Reactive Power and Voltage Regulation:
On long distance ac over head lines and shorter distance ac cables, the
generation and absorption of reactive power by the line itself a serious problem.
C1 K 0 K1nV K 2 nA
Where
Where
n = number of conductors
A = total cross section of each conductor
V = Voltage level with respect to ground
K 0 , K1 , K 2 are constants
The cost of losses per unit length is given by,
2
p
n
pTLp
nV
C2
A
p= specific resistance (or) resistivity of conductor
T = Total operation time during a year
L = Loss load factor
P = cost per unit energy
p
pTLp
V
C2
nA
2
p
pK 3
V
nA
where K3 = TLp
By minimising the sum of C2 and third term in C1 we have
p
K 3 p
K 2 nA
nA
K 3 nA
nA
p
K 3 p
K 2 p
p
K 3 V
P V
J
nA
K3
P V
K2 p . P V
K 2 K3
C C1 C2
p
K 3 p
K 0 K1nV K 2 nA
nA
K 0 K1nA K 2
K3
p
p
p . K3 . p
K2 A
V
K3
p
p.
K2 A
p
p
K 0 K1nA K 2 K 3 p K 2 K 3 p
A
A
p
K 0 K1nA 2 K 2 K 3 p
A
DC Circuit Breaker:
Recent developments in DC circuit breakers are useful in tapping of existing DC link
parallel operation of converters is allowed rather than series operation shows some
flexibility in the system growth.
In order to limit the fault current the dc breaker current should not to exceed the full
load ratings.
Conversion of Existing AC Lines:
o In certain cases such as to increase the power transfer limits it is necessary to
convert existing AC circuits to DC.
oIn India there is an experimental project of converting single circuit (or) double circuit
220kV line is currently under commissioning stage.
Operation with weak AC systems:
The strength of AC systems connected to the terminals of DC link is
measured in terms of short circuit ratio (SCR)
SCR = short circuit level at the converter bus / Rated DC power
If SCR<3, then it is weak AC system. For a weak AC system, conventional
constant extinction angle control may not be satisfactory.
In order to overcome the problems of weak AC systems constant reactive current control
(or) AC voltage control have been suggested. By using static VAR systems at the
converter bus fast reactive power control can be achieved.
It is necessary to limit the dynamic over voltages during load rejections through
converter control.
The dynamic stability of power systems can be improved by power modulation
techniques in the presence of weak AC systems.
Co-ordinated real and reactive power control must be necessary inorder to overcome the
problems of voltage variations which can limit the power modulation.
HVDC Systems in India:
There are two HVDC systems in India
i)Vindhyachal HVDC back to back systems
This link is for exchange of power between northern and western
regions. Each block consists of 250 MW capacitors, it can operate bidirectional and can
transfer power in the range of 250 MW to 250 MW depending on systems conditions.
This system is provided air insulated water cooled Thyristor valves designed for 12-pulse
operation, star extended delta, two winding transformer, AC filters, capacitors ( for
reactive power compensation), smoothing reactance etc.
ii)Rihand-Delhi Systems
This is setup between Rihand and delhi to transmit bulk power from
Rihand to Delhi. The capacity of system is +500kv, 1500MW, 810KM bipolar.
For a given pulse number select the configuration such a way that both the valve and
transformer utilization are minimized.
In general converter configuration can be selected by the basic commutation group
and the no. of such groups connected in series and parallel.
Commutation group means set of valves in which only one valve conducts at a time.
Let q be the no of valves in a commutation group,
r be the no of parallel connections,
s be the no of series connections, then
the total no of valves will be = qrs
sq
Vdo Vm .sin
Vdo s.
q
2
V Cost.dt
m
sq
q
Vm Sint q
2
sq
Vm .2.Sin
2
q
If q is even:
then the maximum inverse voltage occurs when the valve
with a phase displacement of radian in conducting and this is given by
PIV = 2Vm
If q is odd:
the maximum inverse voltage occurs when the valve with a
phase shift of +/q in conducting and this is given by
PIV = 2Vm Cos/2q
PIV
2
, for q is even
Vdo
sq.sin
q
sq.sin
2q
, for q is odd
This Graetz circuit utilizes the transformer and the converter unit to atmost level
and it maintains low voltage across the valve when not in conduction.
Due to this quality present in Graetz circuit, it dominates all other alternative
circuits from being implemented in HVDC converter.
The low voltage across the valves is nothing but the peak inverse voltage which
the valve should withstand.
The six-pulse Graetz circuit consists of 6 valves arranged in bridge type and the
converter transformer having tappings on the AC side for voltage control.
AC supply is given for the three winding of the converter transformer connected in
star with grounded neutral.
The windings on the valve side are either connected in star or delta with ungrounded
neutral.
The six valves of the circuit are fired in a definite and fixed order and the DC output
obtained contains six DC pulses per one cycle of AC voltage wave.
a)Operation without overlap:
The six pulse converter without over lapping valve construction sequence are 1-2,
2-3, 3-4, 4-5, 5-6, 6-1.
At any instant two valves are conducting in the bridge. One from the upper group
and other from the lower group.
Each valve arm conducts for a period of one third of half cycle i.e., 60 degrees.
In one full cycle of AC supply there are six pulses in the DC waveform. Hence the
bridge is called as six pulse converter.
when = 0, the commutation takes place naturally and the converter acts as a
rectifier.
when > 60 deg, the voltage with negative spikes appears and the direction of power
flow is from AC to DC system without change in magnitude of current.
when = 90 deg, the negative and positive portions of the voltage are equal and
because of above fact, the DC voltage per cycle is zero. Hence the energy transferred is
zero.
when > 90 deg, the converter acts as an inverter and the flow of power is from DC
system to AC system.
Let valve 3 is fired at an angle of .
the DC output voltage is given by
Vdc = Vdo Cos
From above equation we can say that if firing
angle varies, the DC output voltage varies.
Vd eb ec ebc
6
Vdc
2
3
Vdc
600
ebc .d t
3 2
VLL Cos 600 Cos 1200
3 2
VLL Cos
1.35VLL Cos
DC Voltage waveform:
The dc voltage waveform contains a ripple whose frequency is six times
the supply frequency.
This can be analysed in Fourier series and contains harmonics of the
order
h=np
Where p is the pulse number and n is an integer.
The rms value of the hth order harmonic in dc voltage is given by
2
1 h 2 1 sin 2
Vh Vdo 2
h 1
1/2
Although can vary from 0 to 180 degrees, the full range cannot be utilized. In
order to ensure the firing of all the series connected thyristors, it is necessary to
provide a minimum limit of greater than zero, say 5 deg.
Also in order to allow for the turn off time of a valve, it is necessary to provide an
upper limit less than 180 deg.
The delay angle is not allowed to go beyond 180- where is called the
extinction angle (sometimes also called the marginal angle).
The minimum value of the extinction angle is typically 10 deg, although in normal
operation as an inverter, it is not allowed to go below 15deg or 18deg.
AC current waveform:
It is assumed that the direct current has no ripple (or harmonics) because of
the smoothing reactor provided in series with the bridge circuit.
The AC currents flowing through the valve (secondary) and primary windings
of the converter transformer contain harmonics.
The waveform of the current in a valve winding is shown in fig.
2
Ip
I d .cos .d
/3
/3
2
I p .I d cos .d
/3
2Id
2I
Ip d
Ip
sin /3
/3
sin
sin
/
3
3
3
Q sin sin
2
2
2 3
Ip
2Id
Ip
2Id
Ip
2 3
.I d
Now the rms value of line current of fundamental frequency component is given
by
I RMS
I RMS
Ip
2
2 3
.I d
2
I RMS
I RMS
2 3.I d
2
6
.I d
I
In
n
The harmonics contained in the current waveform are of the order given by
h = np + 1
where n is an integer, p is the pulse number.
For a 6 pulse bridge converter, the order of AC harmonics are 5, 7, 11, 13 and
higher order.
They are filtered out by using tuned filters for each one of the first four harmonics
and a high pass filter for the rest.
The Power Factor:
The AC power supplied to the converter is given by
6
I d , we obtain
Substituting for Vdc = Vdo Cos , and I1=
cos = cos
The reactive power requirements are increased as is increased from 0
When = 90 deg, the power factor is zero and only reactive power is consumed.
In fig
Lc indicates leakage inductance of transfromer
Vd, Id = DC voltage and current flowing in the line
Ld = DC side reactance
V1 = voltage across the thyristors
p,n = positive and negative pole on the line
Due to the leakage inductance of the converter transformers and the
impedance in the supply network, the current in a valve cannot change suddenly and
thus commutation from one valve to the next cannot be instantaneous.
For example, when valve 3 is fired, the current transformer from valve 1 to
valve 3, takes a finite period during which both valves are conducting. This is called
overlap and its duration is measured by the overlap (commutation) angle .
Commutation delay:
The process of transfer of current from one path to another path with both
paths carrying current simultaneously is known overlap.
The time required for commutation or overlapping which is expressed in
electrical degrees is done with commutation angle, denoted by .
During normal operating conditions the overlap angle is in the range of 0 to 60
degrees, in which two (or) three valves are conducting.
However, if the overlap angle is the range of 60 to 120 degrees, then three to
four valves are in conducting state which is known as abnormal operation mode.
During commutation period, the current increases from 0 to Id in the incoming
valve and reduces to zero from Id in the outgoing valve.
The commutation process begins with delay angle and ends with extinction
angle ie., it starts when t = and ends when t = + = , where is known as an
extinction angle.
Timing diagram
In this mode each interval of the period of supply can be divided into two
subintervals.
In the first subinterval, three valves are conducting and in the second
subinterval, two valves are conducting.
ea Em cos | t 600 |
eb Em cos | t 600 |
ec Em cos | t 1800 |
Corresponding line voltages are eac , eba, ecb
eac ea ec
Em cos(t 600 ) Em cos(t 1800 )
Em (cos(t 600 ) cos(t 1800 ))
1
3
Em | cos t. sin t.
cos t |
2
2
3
Em cos t
sin t
2
2
3
1
cos t sin t |
2
2
1
3 Em |
eac
1
3
1
Em cos t. sin t. cos t. sin t.
2
2
2
3
3Em (sin t )
2
3
Em
cos t sin t
2
2
1
3Em
cos t sin t
2
2
Each valve will conduct for 120 degrees and each pair will conduct for 60
degrees, if there is no overlap.
Let us consider non-overlap of only valve 1,2 conducting followed by overlap of 3 with 1.
Ie., 1,2 and 3 conducting.
When only valve 1 and 2 conducting
ia ic I1 I 2 I d
ib I 3 I 4 I 5 I 6 0
Va V p ea Em cos(t 600 )
Vb eb Em cos(t 600 )
Vc Vn ec Em cos(t 1800 )
Vd V p Vn ea ec eac 3Em cos(t 300 )
V1 V2 0
V3 eba 3Em sin t
V4 Vn V p Vd
V5 Vn V p Vd
V6 ec eb ecb 3Em cos(t 1500 )
When valve 3 is fired then 3 will overlap with 1 and it will be 3 valve
conduction periods ie., 1, 2 and 3.
For this period the emanation for the voltage and current are different and
thus can be obtained as follows:
Consider that valve 3 is ignited at angle and for overlap angle both 1 and 3 conduct
together.
The duration of overlap 1 and 3 will conduct top with 2 at the bottom as shown in the fig.
Just at the beginning, t =
At t =
i1 I d
i3 0
i1 0
i3 I d
The angle (+) is called extinction angle
During overlap a loop is formed as N-3-1-N
For this loop,
di3
di1
eb ea Lc
Lc
dt
dt
di3
di1
3Em sin t Lc
Lc
dt
dt
i 1 i3 I d
i1 I d i3
So
di3
di
Lc (id i3 )
dt
dt
di3
3Em sin t 2 Lc
dt
3Em sin t Lc
3 Em
sin t.dt 2 L di
c
3Em
t
cos t i3
2 Lc .
i3
3Em
cos cos t I d i1
2 Lc .
At t = (+);
i3 I d
Id
3 Em
cos cos( )
2 Lc
I d I s 2 cos cos( )
(or)
where
i3 I d i1
I s 2
3 Em
cos cos t
2 Lc
3 Em
2 Lc
During overlap the line-line voltage of the short circuited phase is zero and two
line to neutral voltage Va and Vb during which overlapping period.
Half sum of Va and Vb, Va Vb ea eb
2
ec
ec
2
3
Em cos t
2
Similarly sets of equations apply for other overlap period such as between 3 and 5 (or) 4
and 6 (or) between 6 and 2 etc. with only appropriate change in time.
Vd
1, 2, 3 conduct
3 & 2 conduct
3 3Em
3 3 Em
3 3Em
.
(sin sin )
sin 2100 cos cos 210 0 sin sin .cos150 0 cos sin1500
3.3.Em
3 3Em 1
3
3
1
cos
sin
sin
cos
sin sin
2
2
2
2
2
3 3Em
2
3 3Em
2
Vd
3 3E
cos cos
2
3 3E
cos cos
2
V
Vd do cos cos
2
Vd
Vd
If = 0, no overlap
3 3E
Vdo
Vd Vdo cos
cos cos
Id
Is2
2 I s 2
1
3Em
L
c
3Em
2 Lc
3Em
V
do .I d
QI s 2
Vdo
Vdo
2 Lc
Id .
2
3Em
Vd
I d Lc
Lc I d
Vd Rc I d
where
3
2 fLc
Rc 6 fLc
Rc
Rc
DC voltage and valve voltage waveforms for rectifier when =15 deg,
= 15 deg, = 30 deg
Inversion:
In HVDC converters thyristor is used, it is a unidirectional device.
The current in a converter cannot be reversed.
Therefore power reversal can be obtained only by reversal of the average DC
voltage.
Converter will operate as a rectifier for firing angle < 90 deg, and power flows from
AC to DC side.
When firing angle > 90 deg, the average output power Pd becomes negative and
power flows form DC to AC.
For an inverter, it is usal to define an advance angle = -, also =
Vdi
Therefore
Vdoi
cos cos
2
Vdoi
cos cos
2
V
doi cos cos
2
I di I s 2 cos cos
Also
Vdo2 cos B
Rc2
Vd2
Vdo1
RL
Vd1
AC
Vdo1 cos a
Rc1
Rectifier
AC
Vdo2
One of the major advantages of a HVDC link is the rapid controllability of transmitted
power through the control of firing angle of the converters.
Modern converter control are not only fast but also very reliable and they are use for
protection against line and converter faults.
The current in a dc link operating in steady state is given by ohms law
2 1/2
12
I1 I I
2
11
6 cos cos
Id
6 2 sin 2 sin 2
I11 I1 sin
Id
4
cos
cos
I11 I1 cos
where
sin h 1
2 ,B
2
h 1
h 1
sin h 1
1
cos cos
2
Harmonic component with no overlap
n
I ho
6 Id
h
1/ 2
where
Vh 1 2
C D 2 2CD cos 2
Vdo 2
cos h 1
2
C
h 1
cos h 1
2
D
h 1
1
2
Is2
Id
cos 300 cos 300
3
Average Direct voltage
Vd Vdo
3 I d
3 cos 30
2 I s 2
Vdo
cos cos
2
Vdo
cos cos
2
Vd
1
cos cos
Vdo 2
Vd
Id
Similarly
where
Vd
cos cos
2Xl
X l 2 fLc Lc
Vd
Vd 1
Id
Id
1
For fixed value of delay angle , different values of Vd/Vdo can be found for various
values of overlap angle .
The curves are plotted with Vd/Vdo on y-axis and Id/2Is on X-axis.
It is possible to change operating point on Vd/Id characteristic by changing
Inverter:
The Inverter characteristics are similar to the rectifier characteristics.
Inverter operation requires a minimum commutation margin angle during which the
voltage across the valve is negative.
Hence the operating region of an Inverter is different from that for a rectifier.
Voltage:
i)Average voltage is
1
Voltage Vd Em Sint.d t
0
Em
Cost 0
2E
Vd m
Em Vd
2
Em 1.57Vd
PIV 2 Em 2. Vd
2
Vd
3.142Vd
Currents:
For half of secondary winding
I davg
I dRMS
Id
0.5 I d
2
I d2
2
1/ 2
V A rating:
VA rating of valve PIV I avg
For 1- full wave converter
2 PIV I avg
2 Vd
.Vd I d
.Pd
VA rating
3.142 Pd
Id
2
Id
0.707 I d
2
Transformer rating:
Transformer secondary rating 2 I rms Erms
Id
Vd
2 2 2
I dVd
2
1.571Pd
Transformer primary rating 1.111TVd
Id
1.111Pd
T
Q Primary voltage has crest value Tem and RMS value 0.707TEm
1.111TVd
Bridge Rectifiers:
During positive half cycle of AC supply valve 1 and 2 are conduct , load side
voltage is same as source.
During negative half cycle valve 3 and 4 are conducting the load voltage and
valve voltage are shown in fig.
Although the bridge circuit may appear more complicated then the full wave
circuit because it has four valves instead of two, the secondary winding is used more
effectively and the PIV of each valve has been halved for a given DC output voltage.
Therefore Peak Inverse Voltage, PIV = Em
Voltage
i)Average voltage,
1
Vd
Sint.d t
2 Em
Em Vd
2
Em 1.57Vd
Vd
ii)
PIV Em 1.57Vd
Currents:
I davg
I drms
Id
0.5 I d
2
I d2
2
1/ 2
0.707 I d
VA rating:
VA rating of valve
PIV I davg
4 PIV I davg
4 Vd I davg
2
I dVd
3.14 Pd
Transformer rating:
VA rating of secondary winding = primary winding = 1.111Pd
Three-Phase Rectifier:
For large amount of power is required we go for three-phase rectifier.
In this rectifier ripple is smalls in magnitude and higher in frequency than in 1-
Converters.
In this circuit direct current in the secondary winding saturates the transformer
cores. To avoid saturation Y-connection is replaced by the zig-zag connection, in which
the DC mmfs of the two secondary winding on the same core canal out.
i)Average voltage,
1500
E Sint.d t
2 300 m
3
3E
1500
m Cost 300
2
3E 2 3
3 3Vm
m
0.826 Em
2 2
2
Vd 0.826 Em
Em 1.209Vd
3 1.209Vd
2.094Vd
I davg
1500
30
id .d t
1
1500
id 300
2
I
I davg d 0.333I d
3
I dRMS
1500
300
1/2
I d2 d t
Id
3
0.5773I d
3 I rms Erms
3
Id
E
m
3
2
2
Pd
3
1.481Pd
3- Bridge Rectifier:
In the 3- mid point rectifier load voltage is equal to line to neutral voltage and it
is line to line voltage.
The circuit is shown in fig. is a 3- full wave bridge rectifier (or) 3- six-pulse
bridge rectifier .
In this circuit upper group device will conduct when supply voltage is most
positive where as lower group devices will conduct when supply voltage is most
negative.
i) Average voltage:
6
Vd
2
90
900
30
AB
d t
3
3Em sin t 300 dt
300
3 3Em
cos t 300
900
300
3 3 Em
Em
Vd 0.604Vd
3 3
Vd
1500
300
5 /6
/6
2
Id
3
0.816 I d
PIV I avg
3Em
Vd I d
9
I d d t
Id
3
Id
0.333I d
3
I d2t I d2 dt
7 /6
11 /6