Wireless 3900 Series Base
Station Hardware Installati
on
www.huawei.com
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Contents
1 Installation Scenarios and Exam
ple
2 Installation Technical key point
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page2
Installation scenarios
Typical
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Antenna Feeder System
Antenna
Jumper cable
Lightning protection ground clip
Feeder cable
Equipment room
Cable ladder
Jumper cable
BTS
Tower
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page 4
Equipment Room Inside
Air
conditioner
Cable
ladder
Equipment
PDF
alert
Battery
Lamp
PGND
Main-attached of
chamber inside
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page5
Products of the 3900 Series Base Statio
n
Outdoor Macro Base Station
Indoor Macro Base Station
Distributed Base Station
Mini Base Station
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page6
HUAWEI Main Base Station Description
Indoor
eNodeB
BTS3900
Outdoor eNodeB
BTS3900A
RFU
Multi-modal RRU
60W/4C
CDMA/WCDMA/LTE
GSM/UMTS/LTE
Distributed
eNodeB
DBS3900
RRU
BBU
Multi-modal BBU
2U 19-in rack mount
design
Use to 2G/3G/4G
operation
Huawei Fourth Generation Base Station
Three standardized modules shared by all Sites portfolio
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page 7
DBS3900 Overview
The DBS3900 consists of the BBU, RRUs and the other eq
uipments.
DBS3900
Antenna
system
Power
Transmissi
on
BBU
RRU
Environme
nt
Monitoring
etc.
Site supplementary equipments
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page8
BBU3900 Physical Structure
[fizikl]
WBBP/UBBP/LBBPUELP WMPT/UMPT
UPEU
FAN
BBU3900 consists of the following subsystems: baseband
subsystem, cabinet subsystem, transmission subsystem,
interconnection subsystem, main control subsystem, monitoring
subsystem, and clock subsystem.
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page 9
BBU3900
Configuration(normal)
BBU layout
In any scenario FAN UPEU UEIU boards are in the fixed slot
( )
(Max)
board type board name) (if integrant)
configuration order priority from left to right)
FAN
FAN
Yes
slot16
Power board
UPEU
Yes
slot19 slot18
monitoring)
EUIU
NO
slot18
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page10
BBU3900 Configuration(GBTS
scenario)
BBU typical configuration
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page11
BBU3900 Configuration(UMTS
scenario)
BBU typical configuration
Slot3 Slot2 UMTS CPRI WBBPd WBBPf UBBPd_U
Slot3 Slot2 UBBPd_U>WBBPf>WBBPd
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page12
BBU3900 Configuration(LTE
scenario)
BBU typical configuration
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page13
BBU3900 Configuration(Single RAN)
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page14
BBU3900 Configuration(Single RAN)
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page15
RRU Physical Structur
e
Indicator
[ndket]
CPRI
interface
Interconnect
interface
Power
connector
RET CONNECTOR
ANT Tx/Rx
PGND
ANT Rx
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page 16
RRU3942
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page17
DBS3900 Typical Installation Scenarios
BBU and RRU centralized
installed in indoor IFS06
rack
BBU installed in indoor cabinets &
RRU mounted on outdoor pole
BBU installed in outdoor cabinets &
RRU mounted on tower
BBU installed on indoor wall &
RRU mounted on outdoor wall
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page18
Installation scenarios
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
BBU Installation scenarios
Outdoor Cabinet
Indoor in the Rack
Inside APM30H
cabinet
on the Wall
Indoor on the Wall
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page 20
RRU Installation scenarios 1
The RRUs can be installed on the pole, on the wall and in
the L-Rack and so on
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page 21
RRU Installation scenarios 2
Para el proyecto RAN 2015-2016, todas las RRU sern
Blade RRU, y sern instaladas en modo concentrado para
ahorrar pipes y espacio.
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page 22
Cable de Energa de la RRU
Se deben usar terminales OT para la conexin de los equipos. En el extremo de
la RRU el blindaje del cable debe ser aterrizado al chasis del equipo, para lo
cual debe ser descubierto segn se muestra en la siguiente figura:
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page23
Solucin del Producto Proyecto RAN
2015 2016.
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page24
Reglas de conexiones de energ
a (Caso ms complejo)
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page25
Consumo de energa y Requerimi
ento de Breakers
Power Scenario
No.
Description
Scenario
Scenario_P1
Scenario_P2
3*RRU+1*BBU
6*RRU+1*BBU
Scenario_P3
9*RRU+1*BBU
Scenario_P4
12*RRU+1*BBU
850M
850M+1900M
850M+1900M+2
600M
850M+1900M+2
600M+700M
Typical Power(W)
Maximum
Power(W)
883.71
1723.37
1440.59
2722.18
2543.96
3772.6
3263.96
4732.6
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page26
RUTEO DE CABLES OPTICOS Y ELEC
TRICOS
La fijacin de cables y ductos a la escalerilla debe realizarse con abrazaderas
metlicas galvanizadas o de acero inoxidables. Est prohibido el uso de
amarras plsticas, ya que se vuelven quebradizas ante la exposicin prolongada a
la luz solar.
Los cables de fibra ptica y de alimentacin DC instalados en los feeder clamp en la
estructura vertical deben seguir la distribucin indicada en la figura siguiente. Los
feeder clamps slo deben ser utilizados en la torre, luego del conduit y corta gota (3
metros sobre el nivel de piso). En caso que la torre sea del tipo mono poste o
ventada no utilizar clamps en la parte superior de la torre (Plataforma, usar
amarra metlica).
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page27
RUTEO DE CABLES OPTICOS Y ELEC
TRICOS
NOTA: Para sitios colocalizados en infraestructura de CLARO, la subida de cables
DC y FO por una torre auto-soportada debe realizarse por las cantoneras. Est
prohibido utilizar la escalerilla de subida o perfiles que estn definidos como de
exclusividad de Claro.
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page28
RUTEO DE CABLES OPTICOS Y ELEC
TRICOS
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page29
Connection Practice
Connection
Practice
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page30
Power On a Base Station
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page31
Contents
2 Installation Referenced Technical p
oint
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page32
Technical point - Assemble the
antenna
Assemble the
support
Install the upper
support on the
antenna.
Install the lower
support on the
antenna.
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Technical point - Assemble the
antenna
Adjust the down-tilt of the antenna by referring to the scales on
the upper support or by using the inclinometer.
Antennas should be in the 45-degree protected area of lightning
rod.
Adjust the tilt of the inclinometer according to the requirement in
the engineering design
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Antenna M-Tilt and E-Tilt Adjustm
entAdjust the E-Tilt
Note:
Adjust the E-Tilt for each sector according to the planning.
Take the Photo for each sector after adjustment.
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page 35
Technical pointinstall the
antenna
on the tower
There need lifting rope and traction rope, to prevent the feeder hitting
from tower
Feeder connector should be wrapped to protect it
Do not tightly
secure the
screws on the
upper and
lower ,
convenient
azimuth
adjustment of
the antenna.
And also avoid
the antenna
drop from the
pole.
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Antenna Mechanical Down Tilt Adjustment
Adjust the M-Tilt
Note:
Adjust the M-Tilt
for each Antenna
according to the
planning.
Take the Photo for
each Antenna after
adjustment.
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page 37
Technical point - Lift the RRU and
the holding pole
1
When lifting the RRU to the tower, avoid collision of the RRU
with the tower
When lift the RRU, bind the whole RRU but not only the handle
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
of the RRU
Technical point - Lift the Fibers
Lifting
rope
Pulley
Tensile
rope
Steering
rope
Lifting
rope
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page39
Steering
rope
Technical point - Lift the Power
Cables
Pulley
Lifting
rope
Steering
rope
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page40
Attentions for the cabinet installatio
n
When cabinets installed
side by side, the space
should be within 3 mm
offset between the two
cabinets, and within 5
mm offset parallel in
front.
The base and the
cabinet must be screwed
each other tightly, and
the steady.
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Technical point --Lay and bind t
he Cables
Lay and bind the Cables
Use the cable tie with white color indoor
and black color outdoor.
The distant between two cable tie is
between 20cm to 40cm (less than 25cm
[p:pn
in perpendicular direction), and the
tie
should be in the same direction. dkjl]
Smoothly cut the redundancy of the
cable tie
Power cable:
[rdndnsi:]
The space between a power cable/ground
cable and a signaling cable outside the
good
cabinet should be more
than 3 cm
Without
appearan
fixed
straight
cross
ce
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Technical point Make Waterproof Con
nector
Step1
Connect
jumpers
to RRU,
tighten
the
connecto
rs;
wrapped
spirally
insulatio
n tape in
one
layers
Step2
The
waterproof
tape is
wrapped
spirally
upwards,
downwards
, and then
upwards
again in
three
layers
Step3
Step4
The
insulatio
n tape is
wrapped
spirally
upwards,
downwar
ds, and
then
upwards
again in
three
layers
Tightly
Seal the
two ends
of the
waterproo
f
connector
when
finish
wrapping
NOTE: For every two insulation tape layers, the tape on the upper
layer overlaps about half the width of the tape on the lower layer
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Technical point Waterproof Bend
When make a waterproof bend, the radius of the curve
should be more 20 times than the diameter of the jumper .
The jumper should be wrap tightly on the pole with the
ties.
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Technical pointColor Ring cable
Both side of the cable need to have the cable, If the
customer no specified label, according to our standard.
Example for the color ring
The colors of from sector0 to sector5
Sector Fiber
1
2
3
Power
Cable
Jumper
Main
Diversity
Red
One ring Two ring One ring
color
Yellow
One ring Two ring One ring
color
Blue
One ring Two ring One ring
color
The main ANT connect to ANT port A with two
ring
The diversity ANT connect to ANT port B with
one ring
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Technical point - Color Ring cable
Make the feeder or jumper color rings for 3
sectors
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Technical point - Color Ring cable
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Power, CPRI Ground and Jumper Labels
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Power, CPRI Ground and Jumper Labels
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Power, CPRI Ground and Jumper Labels
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Power, CPRI Ground and Jumper Labels
1
me
tro
Sali
da
1
1
me me
tro SHEL
tro
TER
RA
CK
19
1
m
etr
o
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page51
1 MI
m NIetr SH
o ELT
ER
Leftover FO Cables
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page52
Escalerilla gabinete-ESA. Proteccin de
cables.
El ingreso de conduits o cualquier orificio debe quedar sellado con sikaflex 11,
descartar la espuma. Los conduit que ingresan al gabinete deben incluir un terminal
de conduit metalico.
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page53
Escalerilla gabinete-ESA. Proteccin de
cables.
Los cables DC y FO deben protegerse mediante conduit corrugado desde la
salida del Gabiente , gabinete de energa o Shelter existente hasta una altura de
3 mts sobre el nivel de la escalerilla en la llegada a la ESA. Debe instalarse 2
canalizaciones conduit de 2 cada una, una para FO y otra para energa DC.
La fijacin de los conduit debe ser con abrazadera metlica galvanizada o de
acero inoxidable, se permitir la utilizacin de amarra plstica solo en el caso
que la escalerilla sea con tapa y este quede correctamente instalada.
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page54
Escalerilla gabinete-ESA. Proteccin de
cables.
Copyright 2014 Huawei Technologies Co., Ltd. All rights reserved.
Page55
Thank you