Transformer Protection 20
Transformer Protection 20
Transformer Protection 20
Target Audiance
Electrical Engineers
Protection Engineers
Test & Commissioning Engineers
Power System Engineers
Utility Engineers
Electrical Technicians
TRANSFORMER PROTECTION
Introduction
Transformers are a
critical and expensive
component of the
power system. Due to
long lead time for
repair and replacement
of transformers, a
major goal of
transformer protection
is limiting the damage
to a faulted
transformer. The
comprehensive
transformer protection
provided by multiple
function protective
relays is appropriate for
critical transformers of
all applications.
TRANSFORMER PROTECTION
TRANSFORMER PROTECTION
Any extended
operation of the
transformer under
abnormal condition
such as faults or
overloads
compromises the life
of the transformer,
which means
adequate protection
should be provided
for quicker isolation
of the transformer
under such condition.
TYPES OF FAULTS
10
OVERHEATING
WINDING FAULTS
The winding faults are called internal faults. The overheating or
mechanical shocks deteriorates the winding insulation. If the
winding insulation-is weak, there is a possibility of
Phase to phase faults
Earth faults
Inter turn faults
Persistent fault would have a possibility of oil-fire.
PROTECTION
Differential protection
Over current protection is also used as a backup protection
For earth fault protection, the restricted earth fault protection
system, neutral current relays or leakage to frame protection
system is used.
12
OPEN CIRCUIT
13
THROUGH FAULTS
Through faults are the external faults which occur outside the
protected zone.
These are not detected by the differential protection.
If faults persists the transformer gets subjected to thermal and
mechanical stresses which can damage the transformer.
PROTECTION
The overcurrent relays with undervoltage blocking, zero
sequence protection and negative sequence protection are
used to give protection
The setting of the overcurrent protection not only protects
transformer but also covers the station busbar and portion of a
transmission line.
14
OVERFLUXING
The flux density in the transformer core is proportional to the
ratio of the voltage to frequency i.e. V/f
Transformers are designed to work with certain value of flux
density in the core. In the generator transformer unit, if full
excitation is applied before generator reaches its synchronous
speed then due to high V/f the overfluxing of core may occur.
PROTECTION
V/f relay called volts/hertz relay is provided to give the
protection against overfluxing operation.
15
Other faults
Tap changer faults
High voltage surges due to lightning
Switching surges
Incipient faults
16
Importance of Protection
Detect and isolate fault
Maintain system stability
To limit the damage in adjacent equipment
Minimize fire risk
Minimize risk to personnel
17
Transformer Connections
18
Transformer Connections
a a2
A
C1
A2
C2
C B1
A
B
C
19
A2
B2
C2
A1
B1
C1
a1
b1
c1
c1
A1
B2 B
a2
b2
c2
a1
b1
b2
c2
c
a
b
Phase displacement
Yy0
Dd0
Zd0
Phase displacement
Yy6
Dd6
Dz6
Yd1
Dy1
Yz1
Yd11
Dy11
Yz11
Group 1
0
Group 2
180
Group 3
30
Group 4
30
20
Transformer Connections
A2
B2
C2
Low
Voltage
Windings
a1
a2
B1
b1
b2
C1
c1
c2
A1
21
Overcurrent Protection
22
Requirements
Fast operation for primary short circuits
Discrimination with downstream protections
Operation within transformer withstand
Non-operation for short or long term overloads
Non-operation for magnetising inrush
23
HV
LV
50
51
50 set to 1.2 - 1.3 x through fault level
24
Transient Overreach
Concerns relay response to offset waveforms (DC
transient)
Definition
I1 - I2
x 100
I2
I2
I1
25
D.
C
.
> Transformer Protection
I1 = Steady state
rms
pick up
current
I2 = Fully offset
rms
pickup
current
5
1
LV
5
1
HV
1
5
1
HV
2
HV1
Tim
e
HV2
LV
IF(LV)
IF(HV)
1.2IF(LV)
26
Curren
t
Current Distribution
I3
I3
0.866
I3
I3
27
HV relay
0.4 sec
LV relay
0.866 I3 I3
28
29
30
31
32
Parallel Transformers
Directional Relays (1)
51
Grid supply
67
Feeders
51
67
51
33
51
Parallel Transformers
Directional Relays (2)
51
Grid supply
51
Bus
Section
Feeders
51
51
34
51
35
36
IP
PR
Protective
Relay
ResistorlimitsE/Fcurrentto fullloadvalues
IF
Thus,primarycurrent, P
. F.L.
3
2
circuit
3
37
x .F.L.
3
IF
0.8
Star
Side
0.7
0.6
51
0.5
Overcurrent
Relay
0.4
Delta
Side
0.3
0.2
0.1
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
p.u..
IF
Star
Side
7
6
51
Overcurrent
Relay
4
3
2
Delta
Side
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
p.u..
39
IF
9
8
7
6
IP
IN
IP
5
4
3
2
IN
40
p.u..
I=
2
3
Differential
Relay
Setting = IS
41
20%
41%
30%
28%
40%
17%
50%
7%
51
N
5
1
42
5
1
5
1
51
N
51
N
5
1
5
1
5
1
Protected
Zone
RE
F
A B C N
LV restricted E/F
protection trips
both HV and LV breaker
Recommended setting : 10%
rated
45
A B C N
46
Source
Protected zone
REF
RCT
RCT
RL
IF
IS
VS
RL
RL
RS
RT
RL
VS = IF (RCT + 2RL)
VS
RR
Metrosil Characteristic
V = CI
1MVA
(5%)
11000V
415V
1600/1
RCT =
4.9
Calculate :
1) Setting voltage (VS)
80MV
A
2) Value of stabilising
resistor required
3) Effective setting
1600/1
RCT =
4.8
51
RS
MCAG14
IS = 0.1
Amp
2 Core 7/0.67mm
(7.41/km)
100m Long
4) Peak voltage
developed by CTs
for internal fault
Solution (1)
Earth fault calculation :Using 80MVA base
Source impedance = 1 p.u.
Transformer impedance = 0.05 x 80 = 4 p.u.
1
p.u.
1 P.U.
Total impedance = 14
1
4
I1 = 1 = 0.0714 p.u.
14
I1
= 111296 Amps
I2
IF
4
I0
Sequence Diagram
52
= 3 x 0.0714 x 111296
= 23840 Amps (primary)
= 14.9 Amps (secondary)
Solution (2)
53
Solution
(4)
54
200/5
51 5
0
10MVA
33/11KV
600/5
51
N
64
600/5
5/5A
55
87
Differential Protection
56
Differential Protection
Overall differential protection may be justified for
larger transformers (generally > 5MVA).
Provides fast operation on any winding
Measuring principle :
Based on the same circulating current principle as the
restricted earth fault protection
However, it employs the biasing technique, to maintain
stability for heavy through fault current
Differential
Current
I1
BIAS
OPERATE
BIAS I
2
I1 I2
OPERATE
I1 I2
RESTRAIN
I1 +
I2
2
58
Mean Through
Current
Differential Protection
HV
PROTECTED
ZONE
LV
P1
P2
A2
A1
60
a1
a2
P2
P1
Use of Interposing CT
P1
S1
P2
A2
A1 a1
P1
S2
S1 P1
Interposing CT provides :
Vector correction
Ratio correction
Zero sequence compensation
> Transformer Protection
P2
S2
S2
61
a2
P2
S1
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
Differential Protection
150/5
P2
P1
S1
15MVA
66kV / 11kV
A2
A1 a1
a2
800/5
P2
P1
S2
S2
S1
Dy1
Differential Protection
800/5
150/5
P1
S1
P2
A2
A1 a1
a2
P2
P1
S2
S2
4.37A
4.92A
S1
S2 P1
(2.56)
S1
P2
(5)
R
R
= 62.7 kV
= 138 Amp
Secondary current
= 4.6 Amp
83
A2
a2
P1
P2
S1
P1
P2
S1
S2
REF
S2
P2
P1
S1
S2
To differential relay
84
300/5
25MV
A
11KV
1600/5
50MV
A
33KV
1000/5
4.59
5.51
10.33
2.88
2.88
Yd11(+30)
R
R
Interposing CT provides :
Vector correction
Ratio correction
Zero sequence compensation
86
Numeric
Relay
Ratio
correction
Vectorial
correction
Virtual interposing CT
87
Differential
element
Virtual interposing CT
Transformer Magnetising
Characteristic
Twice
Normal
Flux
Normal
Flux
Normal
No Load
Current
No Load Current
at Twice Normal
Flux
88
+ m
V
Im
- m
89
Im
2m
90
91
92
93
A
B
C
94
95
Inter-Turn Fault
CT
E
Load
Shorted
turn
- 11,000 / 240
- 11,000 / 1
- 1 / 11,000
96
10
Fault current in short
circuited turns
80
Fault current
(multiples of
rated current)
60
6
Primary input current
40
20
10
15
20
25
97
Primary current
(multiples of
rated current)
Non-electrical Protection
Buchholz Protection
Pressure Relief Protection
Sudden Pressure Protection
Winding Temperature Protection
Oil Temperature Protection
Oil Level Abnormal Protection
98
Buchholz Protection
99
100
101
102
103
3 x internal pipe
diameter (minimum)
Conservator
5 x internal pipe
diameter (minimum)
Oil conservator
3 minimum
Transformer
104
Buchholz Relay
Petcock
Alarm bucket
Counter balance
weight
Mercury switch
Oil level
To oil
conservator
From transformer
Trip bucket
Aperture adjuster
Drain plug
105
Deflector plate
Overfluxing Protection
106
Transformer protection
Overfluxing
Generator transformers
Grid transformers
Usually only a problem during run-up or shut down, but can be
caused by loss of load / load shedding etc.
Flux V
f
Effects of overfluxing :
108
V = kf
2m
CAUSES
Low frequency
High voltage
Geomagnetic disturbances
EFFECTS
109
Ie
V K
f
Trip and alarm outputs for clearing prolonged overfluxing
Alarm : Definite time characteristic to initiate corrective action
Trip : IDMT or DT characteristic to clear overfluxing condition
Settings
Pick-up 1.5 to 3.0 i.e.
110
V/Hz Characteristics
Enables co-ordination with plant withstand characteristics
t = 0.8 + 0.18 x K
(M - 1)2
1000
K = 63
K = 40
K = 20
K=5
K=1
100
Operating
time (s)
10
1
1.1
1.2
1.3
1.4
M = V Hz
Setting
111
1.5
1.6
112
Over temperature
Generally regarded as overload protection also deals
with failure of or interference with pumps and fans or
shutting of valves to pumps
Winding hot spot temperature is the main issue, but both
oil and winding temperature are usually measured and
used to:
initiate an alarm
trip circuit breakers
control fans and pumps
113
Over temperature
Two temperatures must be monitored:
Winding temperature (WTI) -(short
thermal ) this can rise rapidly, without
much of an increase in oil temperature
Oil temperature (OTI) -(long thermal )
this can rise slowly to a critical point
without an unacceptable winding
temperature increase
114
Overheating Protection
I load
Alarm
TD
setting
Top oil of
power
transformer
Trip
I load
On
Fan
control
Off
On
Pump
control
Off
Heater
Temp. indication
Local
Thermal
replica
116
Temperature
sensing resistor
Remote
117
Protection of Parallel
Transformer Feeders
Higher voltage
busbar
Z
OC
OC
FTS
FTS
REF
REF
DP
DP
Bh
WT
WT
Bh
REF
DOC
REF
SBEF
2 stage
SBEF
2 stage
OC
OC
Load
Load
118
Lower voltage
busbar
DOC
Transformer Feeders
FEEDE
R
PW
PILOT
S
P
W
P1
S1
P2
S2
23
24
25
26
27
28
II
ii
III
iii
MCTH
MBCI
27
28
MFAC
14
19
17
17
PILOTS
18
19
18 17
19
1
+ MVTW
02
13
14
120
S1
A
B
C
17
19
P1
S2
MCTH 23
17
23
24
25
26
27
28
P2
MBCI
18
24
25
26
27
28
23
24
25
26
27
28
Protection
of Transformer Feeders
Power transformer
P540
Scheme
Ratio
correction
Vectorial
correction
Virtual interposing CT
121
Virtual interposing CT