Power System Protection
Power System Protection
Generation-typically at 420kV
Typical
Bulk
Power
System
Transmission-typically at 230-765kV
protection?
Protection
Protection Zones
Zones
1. Generator or Generator-Transformer Units
2. Transformers
3. Buses
4. Lines (transmission and distribution)
5. Utilization equipment (motors, static loads, etc.)
6. Capacitor or reactor (when separately protected)
Bus zone
Unit Generator-Tx zone
Bus zone
Line zone
Bus zone
Motor zone
Transformer zone
Transformer zone
~
Generato
r
XFMR
Bus
Line
4
GE Consumer & Industrial
Multilin
Bus
XFMR
Bus
Motor
Application Principles
Protection zones
Generat
or
Xfmr
Bus
Bus
Line
Application Principles
Protection zones determined by CT
location
Generat
or
Xfmr
Bus
Bus
Line
Application Principles
Protection zones determined by CT
location
Generat
or
Xfmr
Line
Transformer
Zone
Bus
Bus
Application Principles
Protection zones determined by CT
location
Generat
or
Xfmr
Transformer
zone
Unit generator-transformer
zone
Bus
Bus
Line
Application Principles
Protection zones determined by CT
location
Generat
or
Bus zone
Xfmr
Transformer
zone
Unit generator-transformer
zone
Bus
Bus
Line
Application Principles
Protection zones determined by CT
location
Generat
or
Bus zone
Xfmr
Transformer
zone
Unit generator-transformer
zone
10
Bus
Bus
Line
Line zone
Application Principles
Protection zones determined by CT
location
Generat
or
Bus zone
Bus zone
Bus
Bus
Xfmr
Transformer
zone
Unit generator-transformer
zone
11
Line
Line zone
Application Principles
Protection zones determined by CT
location
Generat
or
Bus zone
Bus zone
Bus
Bus
Xfmr
Transformer
zone
Unit generator-transformer
zone
12
Line
Line zone
Line zone
Application Principles
Protection zones determined by CT
location
Generat
or
Bus zone
Bus zone
Bus
Bus
Xfmr
Transformer
zone
Unit generator-transformer
zone
Line
Line zone
Line zone
Application Principles
Protection zones
Bus
Line
14
Xfmr
Bus
Motor
Application Principles
Protection zones determined by CT
location
Bus
Line
15
Xfmr
Bus
Motor
Application Principles
Protection zones determined by CT
location
Bus
Line
Line zone
16
Xfmr
Bus
Motor
Application Principles
Protection zones determined by CT
location
Bus zone
Bus
Line
Line zone
17
Xfmr
Bus
Motor
Application Principles
Protection zones determined by CT
location
Bus zone
Bus
Xfmr
Line
Line zone
Xfmr zone
18
Bus
Motor
Application Principles
Protection zones determined by CT
location
Bus zone
Bus
Bus zone
Xfmr
Line
Line zone
Xfmr zone
19
Bus
Motor
Application Principles
Protection zones determined by CT
location
Bus zone
Bus
Bus zone
Xfmr
Bus
Motor
Line
Line zone
Xfmr zone
20
Motor
zone
Application Principles
Protection zones determined by CT
location
Bus zone
Bus
Bus zone
Xfmr
Bus
Motor
Line
Line zone
Xfmr zone
Again, note the overlap
Also note:
A fault on a major element is covered by how many zones?
A fault within a circuit breaker is covered by how many zones?
21
Motor
zone
Zone
Zone Overlap
Overlap
1. Overlap is accomplished by the locations of CTs, the
key source for protective relays.
2. In some cases a fault might involve a CT or a circuit
breaker itself, which means it can not be cleared
until adjacent breakers (local or remote) are
opened.
Relay Zone A
Zone A
Relay Zone B
Relay Zone A
Zone B
Zone A
Relay Zone B
Zone B
remote sides
Art
Art & Science
Science of
of Protection
Protection
Selection of protective relays requires compromises:
Art
Art & Science
Science of
of Protection
Protection
Cost of protective relays should be balanced
against risks involved if protection is not
sufficient and not enough redundancy.
Primary objectives is to have faulted zones
primary protection operate first, but if there
are protective relays failures, some form of
backup protection is provided.
Backup protection is local (if local primary
protection fails to clear fault) and remote (if
remote protection fails to operate to clear
25
fault)
GE Consumer & Industrial
Multilin
Primary
Primary Equipment
Equipment &
&
Components
Components
Transformers - to step up or step down voltage level
Breakers - to energize equipment and interrupt fault
current to isolate faulted equipment
Insulators - to insulate equipment from ground and
other phases
Isolators (switches) - to create a visible and
permanent isolation of primary equipment for
maintenance purposes and route power flow over
certain buses.
Bus - to allow multiple connections (feeders) to the
26
Consumer
& Industrial
same sourceGEof
power
(transformer).
Multilin
values.
Convert from per cent to per unit values by
dividing 100.
representation
4. Impedances of machines are specified by the
manufacturer in terms of per unit values.
5. The per unit impedance referred to either side of
a single-phase transformer is the same.
6. The per unit impedance referred to either side of
a three -phase transformer is the same regardless
of the connection whether they are -, Y-Y or Y.
7. The computation effort in power system is very
much reduced with the use of per unit quantities.
8. Usually, the per unit quantities being of the
order of unity or less can easily be handled with a
digital computer. Manual calculation are also
simplified.
all variables.
This normalization is known as per unit
analysis.
30
actual quantity
quantity in per unit
base value of quantity
32
ZB
VB2, LL
S B3
( 3 VB , LN ) 2
3S 1B
VB2, LN
S 1B
S B3
3 S 1B
S 1B
1
IB
3 VB , LL
3 3 VB , LN VB , LN
Example 1
A 5 KVA 400/200 V, 50Hz, single phase
Xpu= (Xactual/Zbase)
Zb1= (V2b1/Sb)=4002/5000=32 ohm
Xpu= (Xactual/Zbase)= 12.5/32 = 0.390625
pu..1
X1pu = X1/Zb1
X2pu = X2/Zb2
Zb2 = (V2b2/Sb)= 2002/5000=8 ohm
X2pu = X2/Zb2 = 2.5/8 = 0.3125
X1pu = X1/Zb1 = 3.5/32 = 0.078125
Xpu= X1pu + X2pu = 0.390625..2
Both 1 and 2 matches which confirm that pu
Symmetrical Components
Symmetrical components
sudden test
A 7 KVA 1000/250 V, 50Hz, single phase
transformer has the primary and secondary
leakage reactance each of 5 ohm. Determine
the total reactance in per unit.
50
phasors
Advantages of Phasors
Current Transformers
Current transformers are used to step primary system
currents to values usable by relays, meters, SCADA,
transducers, etc.
CT ratios are expressed as primary to secondary; 2000:5,
1200:5, 600:5, 300:5
A 2000:5 CT has a CTR of 400
52
GE Consumer & Industrial
Multilin
IS
Relay
or Meter
IR
Forward Power
IP
IS
Relay
53
or Meter
GE Consumer & Industrial
Multilin
IR
Voltage Transformers
Voltage (potential) transformers are used to isolate and
step down and accurately reproduce the scaled voltage for
the protective device or relay
VT ratios are typically expressed as primary to secondary;
14400:120, 7200:120
A 4160:120 VT has a VTR of 34.66
VP
VS
Relay
54
GE Consumer & Industrial
Multilin
55
Courtesy
of Blackburn,
Protective Relay: Principles and
GE Consumer
& Industrial
Applications
Multilin
Secondary Circuit
point of use
56
GE Consumer & Industrial
Multilin