Basics of Power System Protection
Basics of Power System Protection
Aims:
Continued supply for rest of system
Protect faulted part from damage
Protection Zones
1. Generator or Generator-Transformer Units
2. Transformers
3. Buses
4. Lines (transmission and distribution)
5. Utilization equipment (motors, static loads, etc.)
6. Capacitor or reactor (when separately protected)
Bus zone
Unit Generator-Tx zone
Bus zone
Line zone
Bus zone
Motor zone
Transformer zone
Transformer zone
~
Generato
r
XFMR
Bus
Line
XFMR
Bus
Bus
Motor
Zones of Protection
Zones are defined for:
Generators
Transformers
Buses
Transmission and distribution lines
Motors
Zones of Protection
For fault anyway within the zone, the
protection system responsible to
isolate everything within the zone
from the rest of the system.
Isolation done by CB
Must isolate only the faulty
equipment or section
Zones of Protection
Overlapped of Protection
No blind spot:
Neighboring zones are overlapped to
avoid the possibility of unprotected
areas
Overlapped of Protection
Overlap accomplish by having 2 sets of
instrument transformers and relays for each
CB.
Achieved by the arrangement of CT and CB.
Zone Overlap
1.
2.
Zone A
Relay Zone B
Relay Zone A
Zone B
Zone A
Relay Zone B
Zone B
remote sides
Selectivity
Selectivity
Clearly discriminate between normal and
abnormal system condition to avoid unnecessary,
false trips.
Sensitivity
Ability to distinguish the fault condition, although
the different between fault and normal condition
is small.
Economy
Provide maximum protection at minimum cost
Simplicity
Minimize protection equipment and circuitry