Power System Protection New
Power System Protection New
Power System Protection New
What is Protection
System ?
Def: A COMPLETE ARRANGEMENT OF PROTECTION
EQUIPMENT AND OTHER DEVICES REQUIRED TO
ACHIEVE A SPECIFIED FUNCTION BASED ON A
PROTECTION PRINCIPLE.
Need: WHEN EQUIPMENT FAILS, THE ENERGY IS
RELEASED AND EVERY COMPONENT IN THE SYSTEM
IS AT RISK. THE PROTECTIVE RELAYING SYSTEM
MONITORS THE SYSTEM AND INITIATE ACTION
ACCORDINGLY.
2
Purpose of Protection
System:
The protective relaying system senses the abnormal condition
of power system and gives an alarm or isolates the
defective system from the healthy system.
A fault in an electrical system is defined as a defect in its
electrical circuit due to which the current is diverted from
the intended path. Faults are generally caused by breaking
of conductors or failure of insulation. Some other causes of
fault conditions include:
Mechanical failure
Environment disturbances
Excessive internal & external stresses
Operating error
Equipment malfunctions
The fault impedance being low, the fault current are relatively
very high and flows towards the fault.
3
Requirements of Protection
system:
Selectivity - ability to select the faulty part of in
system & disconnect the faulty part without
disturbing rest of the healthy system.
Speed of Operation The faulty section should be
isolated as fast as possible to minimize the
damage to equipments and increase the
stability of operation of healthy system.
Sensitivity - ability to operate with low value of
actuating quantities.
Reliability - ability to operate under the faulty
conditions only.
4
Types of Protective
equipment
FUSES
MINIATURE CIRCUIT BREAKERS
(MCB)
PROTECTIVE RELAYS
5
FUSES
A Fuse is a short piece of metal,
inserted in the circuit, which melts
when excessive current flows
through the circuit and thus breaks
the faulty circuit.
The fuse element is generally made of material
having low of low melting point, high
conductivity and least deterioration due to
oxidation, e.g. silver, copper etc. it is inserted in
series in the circuit to be protected.
6
Classification of Fuses:
i.
Low-voltage fuses
Semi-enclosed rewirable fuse
High rupturing capacity (HRC) cartridge fuse
HRC fuse with tripping device
ii.
High-voltage fuses
Cartridge type
Liquid type
Metal clad fuses
7
Protection Relay
A protection relay is a device that detects the fault
and initiates the operation of the circuit breaker
to isolate the defective system from the rest of
the healthy system.
The relay detects the abnormal condition by
constantly measuring the electrical quantities
e.g. voltage, current, frequency, phase angle,
status of circuit breakers , etc.
In changes of one or more quantities, the relay
senses the faults, its type and location of the
fault.
9
10
Essential Requirements of
Protective System:1. Current Transformers or CT :CT,s are required to scale down the
primery current to suitable level so
that relay can use it. CT,s can be
single core or multi core. Each core
can be single ratio or multi-ratio.
Separate cores are needed for
metering or protection purposes.
Normally secondary current is 1A or
5A as per requirement.
11
13
4. Circuit Breakers:
Circuit breakers or CB,s are very much needed
to operate the electrical circuits in all the
operating conditions i.e. on no-Load, on Fullload.
CB are also required to isolate the faulty
system from healthy system on receipt of
command from the protective system in the
shortest possible time.
CB status is also available to the protective
system to properly take the decision of the
fault.
14
1)
i.
ii.
iii.
Electromagnetic Induction
Relay
18
STATIC RELAY
In Static Relays, the measurement is performed by
electronic/magnetic/optical or other components
without mechanical motion. Static relays have
versatile characteristics, offer low burden and
incorporate several protective/control/monitoring
functions in one compact unit.
19
MICROPROCESSOR
based
Numerical
Relays:
In 1980s, programmable static relays incorporating
Microprocessor have been introduced.
A programmable protection & control system has a
Microprocessor or Microcomputer in its circuit.
With the help of the logic and the Microprocessor,
the integrated system can perform several
functions of Data acquisition, Data processing,
Data transmission, protection & control.
Earlier for each of these functions, separate
Electromagnetic or Static units were used along
with complex inter module wiring.
20
CB
CT
VT
Input Unit
Input Unit
A/D
Convert
er
Setting
Data
Request &
Display
Trip
coil
MICROPROCESS
OR
Data Logger
21
22
23
24
25
27
Generator Protection
Generator Transformer Protection
Bus-bar Protection
Bus Coupler protection
Transmission Line Protection
Shunt Reactor protection
28
Generator/ Unit
Main-I (GRP-1) Protection comprising :
Protections
i. Generator Differential
Relay : Model-REG216, Make-ABB
ii.
iii.
iv.
v.
vi.
vii.
viii.
ix.
x.
Under Impedance
Negative Phase Sequence
Gen. Over Current (Inst. & IDMT type)
100% Stator Earth Fault
Reverse Power
Over Voltage
Loss of Excitation
Balance Voltage
Gen. Thermal Protection
29
31
32
33
34
35
36
37
38
Protection
LED
No.
Function
Curve/Setting
Time Delay
06
Alarm
1.15 Un
2.00 sec
23
07
ESD
Alarm
1.25 Un
0.70 Un
Inst.
2.00 sec
05
Alarm
0.20 Un
0.04 sec
28
PSD
0.20 Un
1.00 sec
21
ESD
1.60 Un
0.50 sec
22
ESD
PSD
1.30 In
5.00 In
2.00 sec
0.02 sec
PSD
IDMT
8
9
31
30
10
04
PSD
I2 =0.05 In
5.00 sec
11
26
25
PSD
PSD
IB =0.78 In
12
IDMT
3 sec
13
32
ESD
XA = -1.11 Un/In
XB = -0.18 Un/In
0.2 sec
14
29
ESD
As per curve
15
24
ESD
IB =0.10 In
T/f ratio-50
REs-0.91k
16
18
ESD
0.176 Un/ In
3 sec
17
17
ESD
g setting = 0.10 In
v setting = 0.25
Inst.
-0.05 PN
1 sec
39
Protection
LED
No.
Function
Curve/Setting
Time Delay
03
Alarm
1.15 Un
2.00 sec
17
ESD
1.25 Un
0.00 sec
04
Alarm
0.85 Un
10.0 sec
20
ESD
0.80 Un
3.20 sec
07
Alarm
52.0 Hz
1.00 sec
23
PSD
52.5 Hz
1.00 sec
06
Alarm
48.5 Hz
1.00 sec
22
PSD
47.0 Hz
2.00 sec
05
Alarm
1.15 Un/fn
2.00 sec
10
21
PSD
1.1 UB/fn
0.05 min
11
26
PSD
As per curve
12
27
ESD
1.3 In
3.00 sec
13
18
PSD
IB =0.30 In
As per curve
14
24
ESD
0.05 sec
15
25
ESD
0.05 Un
g setting = 0.20 In
v setting = 0.5
Inst.
40
Generator Transformer
Protection :
i.
ii.
iii.
iv.
v.
vi.
vii.
viii.
Differential Protection
Back-up Over Current
Neutral Over Current
Restricted Earth Fault
Winding Temperature High
Oil Temperature High
Buchholz Gas Relay
Pressure Relief Valve
41
43
44
45
Bus-Coupler Protection
Relay : Model-SPAJ140C, Make-ABB
Provided to trip the buscoupler
CB in case of over-loading of
bus-coupler or fault on any of
the bus-bar
i . Over Current Protection,
ii. Earth Fault Protection
46
47
48
49
50
51
52
53
Differential Protection
Restricted Earth Fault
Back-up Impedance Protection,
Winding Temperature High
Oil Temperature High
Buchholz Gas Relay protection
Pressure Relief Valve
54
56
57
5. Carrier Inter-tripping
Schemes
:- of Principal Line Section
Normally 80%
is covered by Zone-1 of the Line
protection, the rest of the 20% is
covered by Zone-2 protection with a
minimum delay of 0.4 sec.
To cover end 20% line fault in Zone-1
time also, Various carrier based carrier
inter-tripping schemes are used:-
58
59
Testing of Protective
Relays schemes
&
Associated
Equipments.
60
62
64
66
Secondary Injection Of
PT,s:
- Injection of Potential circuit is carried
out with the help of Secondary
Injection Test Kits or with the help of
Single phase variac, Rheostat etc.
The voltage is measured in all voltage
circuits of all the phases one by one
to ensure that during actual operation
voltage will flow in the correct phase
only and not otherwise,
67
Checking of DC Schemes:
-The wiring of complete scheme is checked and corrected
according to scheme.
- Auxiliary DC supply is given to the panel and DC supply
is checked at various points in the scheme/ Relays
- The operation of DC relays checked as per schematics.
68
Testing Of Relays:
-All the relays are tested for operation on various settings
with the help of Secondary Relay Testing Kit Like as
Doble, Omricon, TURH, ZFB etc.
-The operating time of the relays is also measured to
ensure the operation of relays within permissible limits.
69
70
71
72
74
76
Testing Of Transformers
Testing Of Reactors:
Following Tests are performed to
Check the healthiness of Reactors:1. Insulation Resistance- HV-E by
5KV/ 10KV Megger.
2. Open circuit Test from HV,
3. Magnetic Balance Test from HV
78
79
THANK YOU