Generator Protection System
Generator Protection System
Basics of Electrical Protection system Synchronous machine Concept of reactive power and real power sharing Different Protections used for generator Advanced Protection Relays(Microprocessor based) Case studies (analysis of electrical faults) Synchronization
Generator Differential Protection. Generator Inter Turn Protection. Generator Negative Sequence Protection. Generator Loss of Excitation Protection. Generator Over Voltage Protection. Frequency Protection Generator Over Load/ Over Current Protection Generator Rotor Earth Fault Protection Generator Back Up Impedance protection Generator Low Forward power Interlock Generator reverse power protection. 95% stator Earth Fault Protection
Instrument Transformers
Current Transformers Turns ratio is inversely proportional to the ratio specified Secondary current is according to primary current only Should not be left open circuited
Potential Transformers Turns ratio is directly proportional to the ratio specified Secondary current is according to burden connected Should not be short circuited
Protection Classes
Class A Protection This master trip will operate when the fault needs to isolate the generator immediately This gives command to open the generator breaker and field breaker. Class B Protection This master trip will operate when the fault is not serious in view of generator or it is not directly harmful to generator This gives the command to trip turine Prime Mover Tripped This indicates (gives feed back)prime mover is tripped.
The Protection System Protection Classes Inputs to the protection system. Instrument Transformers Contact Input Elements of protection system.
CTR 10000/5 Relay Setting 5% Stabilizing Resistance High impedance Relay Sensitivity to the type of fault
Current relays Voltage relays Power relays Impedance relays Frequency relays Special function relays Auxiliary Relays Timers
Protection System
Cause of Operation of Protection is the the Fault. It Is Basically Designed, To detect the fault at its earliest possible stage. To give protection to the equipment against secondary damage. To avoid the equipment to run out side the capability specified.
Specifications of Generator
Make: BHEL MVA: 247 Connection: Three Phase Double Star Connected. Voltage: 15750 Volts Current: 9050 Amp Frequency: 50 Hz Speed: 3000 RPM No. of Poles: 2
Synchronous Impedance: 222% Sub Transient Impedance: 30.5% Transient Impedance: 21.4% Cooling: water/ Hydrogen Cooled Neutral Grounding: High Impedance (Through NGT)
Difference of sharing between split phases Reasons of diff. In currents If there is any inter-turn short with in the winging If gen is supplying through fault and small circulating currents gets proportionately increased Tripping provided at 5% of rated current
Balanced and unbalanced systems Sequence components Positive sequence component I1 = 1/3 (IR +a2 *IY + a * IB) Negative sequence component I2 = 1/3 (IR +a *IY + a2 * IB) Zero sequence component I0 = 1/3 (IR +IY + IB) Effect of negative sequence component on synchronous machine. Generator Capability for I2 Continuous I2 capability 5% of Im I2 2 * t = 8
Balanced Phasers
Generator high voltage is harm full to the insulation of generator, generator transformer, excitation transformer, UAT, etc Generator Over Voltage Capability 10% Setting Adopted Stage 1 = 10%, 5 Sec delay Stage 2 = 15%, 500msec delay
Frequency Protection
Over frequency protection It indicates excess generation than demand hence tripping should graded among the units Under frequency protection Under frequency is harmful to turbine Adopted settings
CAPACITY
TRIP
52.5 HZ, 1 SEC DELAY 52.0 HZ, 2 SEC DELAY 52.0 HZ, 2.0 SEC DELAY
time in Sec.
Rotor E/F
1.
Generator Differential Protection: - High Impedance / Biased Differential 2. Phase fault over current protection: 3.Neutral voltage displacement protection: 4.100% Stator earth fault protection: 5.Under/over voltage protection: - Two stage under and Over voltage protection. 6.Under/over frequency protection: - Four stage under frequency and two stage over frequency protection. 7.Reverse power: - Protection against loss of prime mover. 8.Low forward power: - Provides an interlock for non-urgent tripping. 9.Field failure: - Two stage element for protection against loss of excitation. 1 Negative phase sequence protection: - Provides protection against unbalanced loading, which can cause overheating of the generator rotor. 1Over fluxing: - Provides protection for the generator/transformer against unusual voltage or frequency conditions. 1 Unintentional energization at standstill (dead machine) protection: Protection against inadvertent closing of the generator circuit breaker when machine is not running.
2.
3. 4. 5. 6.
P343
Tripping of unit on Loss of excitation protection. Tripping of unit No 4 on over voltage protection during external disturbance. Local AC failure due to theft attempt in switch yard Unit 4 tripped on stator earth fault. Tripping of unit on Negative sequence protection Tripping of units while supplying external faults
Synchronization Procedure
Keep Excitation on Manual Channel. Make the FF Supply ON. Close the field Breaker and observe FF and FB both breakers ON Voltage start building up At @ 70% of rated voltage FF breaker gets OFF Voltage stops rising at @ 14 KV Raise the voltage to @15.75KV with the help of Manual Control. Match the Null meter with the help of Auto Pot. Put the excitation on AUTO Proceed for Synchronization.
Thank You