100% found this document useful (1 vote)
217 views

Generator Protection System

This document discusses generator protection systems. It covers topics like basics of electrical protection systems, synchronous machines, different protections used for generators including differential, interturn, negative sequence, loss of excitation protections. It discusses instrument transformers and provides a flow diagram of tripping process. It describes protection classes and specifications of a sample generator. It provides details on protections like differential, interturn, loss of excitation, overvoltage, frequency, overload protections. It discusses a microprocessor based relay and its features. It also includes case studies and synchronization procedure.

Uploaded by

dk010784
Copyright
© © All Rights Reserved
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
217 views

Generator Protection System

This document discusses generator protection systems. It covers topics like basics of electrical protection systems, synchronous machines, different protections used for generators including differential, interturn, negative sequence, loss of excitation protections. It discusses instrument transformers and provides a flow diagram of tripping process. It describes protection classes and specifications of a sample generator. It provides details on protections like differential, interturn, loss of excitation, overvoltage, frequency, overload protections. It discusses a microprocessor based relay and its features. It also includes case studies and synchronization procedure.

Uploaded by

dk010784
Copyright
© © All Rights Reserved
Available Formats
Download as PPT, PDF, TXT or read online on Scribd
You are on page 1/ 30

Generator Protection System

Davinder kumar Assistant Engineer (EMC)

Topics for Discussion

Basics of Electrical Protection system Synchronous machine Concept of reactive power and real power sharing Different Protections used for generator Advanced Protection Relays(Microprocessor based) Case studies (analysis of electrical faults) Synchronization

Different Protections used for Generator


Generator Differential Protection. Generator Inter Turn Protection. Generator Negative Sequence Protection. Generator Loss of Excitation Protection. Generator Over Voltage Protection. Frequency Protection Generator Over Load/ Over Current Protection Generator Rotor Earth Fault Protection Generator Back Up Impedance protection Generator Low Forward power Interlock Generator reverse power protection. 95% stator Earth Fault Protection

Instrument Transformers

Current Transformers Turns ratio is inversely proportional to the ratio specified Secondary current is according to primary current only Should not be left open circuited

Potential Transformers Turns ratio is directly proportional to the ratio specified Secondary current is according to burden connected Should not be short circuited

Flow Diagram of Tripping Process

Protection Classes
Class A Protection This master trip will operate when the fault needs to isolate the generator immediately This gives command to open the generator breaker and field breaker. Class B Protection This master trip will operate when the fault is not serious in view of generator or it is not directly harmful to generator This gives the command to trip turine Prime Mover Tripped This indicates (gives feed back)prime mover is tripped.

Basics of Electrical Protection system


The Protection System Protection Classes Inputs to the protection system. Instrument Transformers Contact Input Elements of protection system.

Generator Differential Protection

CTR 10000/5 Relay Setting 5% Stabilizing Resistance High impedance Relay Sensitivity to the type of fault

Elements of protection system

Current relays Voltage relays Power relays Impedance relays Frequency relays Special function relays Auxiliary Relays Timers

Protection System

Cause of Operation of Protection is the the Fault. It Is Basically Designed, To detect the fault at its earliest possible stage. To give protection to the equipment against secondary damage. To avoid the equipment to run out side the capability specified.

Specifications of Generator

Make: BHEL MVA: 247 Connection: Three Phase Double Star Connected. Voltage: 15750 Volts Current: 9050 Amp Frequency: 50 Hz Speed: 3000 RPM No. of Poles: 2

Synchronous Impedance: 222% Sub Transient Impedance: 30.5% Transient Impedance: 21.4% Cooling: water/ Hydrogen Cooled Neutral Grounding: High Impedance (Through NGT)

Generator Inter Turn Protection


Difference of sharing between split phases Reasons of diff. In currents If there is any inter-turn short with in the winging If gen is supplying through fault and small circulating currents gets proportionately increased Tripping provided at 5% of rated current

Generator Negative Sequence Protection.


Balanced and unbalanced systems Sequence components Positive sequence component I1 = 1/3 (IR +a2 *IY + a * IB) Negative sequence component I2 = 1/3 (IR +a *IY + a2 * IB) Zero sequence component I0 = 1/3 (IR +IY + IB) Effect of negative sequence component on synchronous machine. Generator Capability for I2 Continuous I2 capability 5% of Im I2 2 * t = 8

Balanced Phasers

Generator Loss of Excitation Protection.

Study of Generator capability curve


Setting criteria Xa1 = 0.5*Xd*CTR/PTR Xd = 30.5% = 0.305 pu subtransient reactance of generator Xd in ohms = Xd (pu)*kv2/MVA = 0.305*15.752/247 =0.306311993 Xa1 = 2.139 ohm Xb1 = Xd * CTR/PTR Xd (ohmic) = Xd(pu)*kv2/MVA Xb1 = 2.22(15.752/247)(10000/5)(110/15750) = 31.14 ohm

Generator capability curve

Generator Over Voltage Protection.

Generator high voltage is harm full to the insulation of generator, generator transformer, excitation transformer, UAT, etc Generator Over Voltage Capability 10% Setting Adopted Stage 1 = 10%, 5 Sec delay Stage 2 = 15%, 500msec delay

Frequency Protection
Over frequency protection It indicates excess generation than demand hence tripping should graded among the units Under frequency protection Under frequency is harmful to turbine Adopted settings

Adopted Frequency settings


UNIT NO.
1 2 3 4 5

CAPACITY

UNDER FREQ. TRIP SETTING

OVER FREQUENCY SETTING

TRIP

30 MW 30 MW 210 MW 210 MW 210 MW

47 HZ, 0.5 54.5 HZ, 21.15 SEC DELAY SEC DELAY

52.5 HZ, 1 SEC DELAY 52.0 HZ, 2 SEC DELAY 52.0 HZ, 2.0 SEC DELAY

Generator Over Load/ Over Current Protection1


% O/C 1.1 1.15 1.2 1.25 1.3 1.35 1.4 1.5 Gen Capability 3600 900 360 300 240 180 120 60 652.8 362.4 252.6 192.6 155.4 129.3 90 Relay Char.

Generator Over Load/ Over Current Protection2


Generator Capability 950 900 850 800 750 700 650 600 550 500 450 400 350 300 250 200 150 100 50 0 1 1.05 1.1 1.15 1.2 1.25 1.3 1.35 1.4 1.45 1.5 1.55 1.6 % over current Relay characristic

time in Sec.

Rotor E/F

Generator Back Up Impedance protection


Impedance protection to be covered up to 220 KV bus bar that is Z = Z(G.T.) 12.5% Ohmic value of Z (G.T.) = Z(pu)*KV2/MVA = 0.125*15.752/250 = 0.124 ohm Z at C.T.,P.T. secondary level = Z*(CTR/PTR) = 0.124*(10000/5)*(110/15750)= 1.73 ohm For 3 phase impedance 1.73*sqrt(3) = 2.996 ohm Time setting = 2.5 sec (considering the line under Impedance time setting that is to allow the line protections to clear the fault before tripping of generator) Z<1 setting (for P343 main only) Setting criteria: for long faults and sustained overloading the setting of this stage should be kept to operate at 30% overloading i.e. it should be set at 70% impedance of the full load parameters of the generator. Zfull load at C.T., P.T. level = rated volts (phase to phase)/ Ifull load = 110/4.525 = 24.3 ohms Z 70% = Zfull load*0.7 = 24.3*0.7 = 17.01 ohms delay = 5 sec

95% stator Earth Fault Protection

Salient Features of the relay P343:

1.

Following Protections of generator are covered in the relay

Generator Differential Protection: - High Impedance / Biased Differential 2. Phase fault over current protection: 3.Neutral voltage displacement protection: 4.100% Stator earth fault protection: 5.Under/over voltage protection: - Two stage under and Over voltage protection. 6.Under/over frequency protection: - Four stage under frequency and two stage over frequency protection. 7.Reverse power: - Protection against loss of prime mover. 8.Low forward power: - Provides an interlock for non-urgent tripping. 9.Field failure: - Two stage element for protection against loss of excitation. 1 Negative phase sequence protection: - Provides protection against unbalanced loading, which can cause overheating of the generator rotor. 1Over fluxing: - Provides protection for the generator/transformer against unusual voltage or frequency conditions. 1 Unintentional energization at standstill (dead machine) protection: Protection against inadvertent closing of the generator circuit breaker when machine is not running.

Other non-protective features of the relay:


1. Voltage transformer supervision: - To prevent maloperation of voltage dependent protection elements upon loss of a VT input signal. Measurements: - Various measurement of value for display on the relay or accessed from the serial communications e.g. Currents, voltages, Power etc. Fault / event / disturbance records: - Available from the serial communication or on the relay display (fault and event records only on relay display. Four setting groups: - Independent setting groups to cater for alternative arrangements or user specific application. Continuous self monitoring: - Power on diagnostics and self checking routine to provide maximum relay reliability and availability. Circuit breaker state monitoring: - Provides indication of discrepancy between circuit breaker auxiliary contacts.

2.
3. 4. 5. 6.

P343

Case studies (analysis of electrical faults)

Tripping of unit on Loss of excitation protection. Tripping of unit No 4 on over voltage protection during external disturbance. Local AC failure due to theft attempt in switch yard Unit 4 tripped on stator earth fault. Tripping of unit on Negative sequence protection Tripping of units while supplying external faults

Synchronization Procedure

Keep Excitation on Manual Channel. Make the FF Supply ON. Close the field Breaker and observe FF and FB both breakers ON Voltage start building up At @ 70% of rated voltage FF breaker gets OFF Voltage stops rising at @ 14 KV Raise the voltage to @15.75KV with the help of Manual Control. Match the Null meter with the help of Auto Pot. Put the excitation on AUTO Proceed for Synchronization.

Thank You

You might also like