National Building Code Presentation
National Building Code Presentation
National Building Code Presentation
Buildings proposed for construction shall comply with all the regulations and specifications herein set forth governing quality, characteristics and properties of materials, methods of design and construction, type of occupancy and classification.
All other matters relative to the structural design of all buildings and other structures not provided for in this Chapter shall conform with provisions of the Engineering pursuant to Republic Act Number 544, as amended, otherwise knows as the Civil Engineering Law.
(a) Subject to the provisions of Articles 684 to 686 of the Civil Code of the Philippines on lateral and subjacent support, the design and quality of materials used structurally in excavation, footings, and in foundations shall conform to accepted engineering practice.
SECTION 9. - Lateral and Subjacent Support (n) Sec. 684. No proprietor shall make such excavations upon his land as to deprive any adjacent land or building of sufficient lateral or subjacent support. Art. 685. Any stipulation or testamentary provision allowing excavations that cause danger to an adjacent land or building shall be void. Art. 686. The legal easement of lateral and subjacent support is not only for buildings standing at the time the excavations are made but also for constructions that may be erected. Art. 687. Any proprietor intending to make any excavation contemplated in the three preceding articles shall notify all owners of adjacent lands.
(1) Excavation or fills for buildings or structures shall be so constructed or protected that they do not endanger life or property.
(2) Whenever the depth of excavation for any construction is such that the thereon would beaffected in a manner that the stability or safety of the same is endangered, the personundertaking or causing the excavation to be undertaken shall be responsible for the expense of underpinning or extending the foundation or footings of the aforementioned property or structure. (3) Excavation and other similar disturbance made on public property shall, unless otherwise excluded by the Building Official, be restored immediately to its former condition within 48 hours from the start of such excavation and disturbances by whosoever caused such excavation of disturbance.
(c) Footings, Foundations, and Retaining Walls (1) Footings and foundations shall be of the appropriate type, of adequate size, and capacity in order to safely sustain the superimposed loads under seismic or any condition of external forces that may affect the safety or stability of the structure. It shall be the responsibility of the architect and/or engineer to adopt the type and design of the same in accordance with the standards set forth by the Secretary. (2) Whenever or wherever there exist in the site of the construction an abrupt change in the ground levels or level of the foundation such that instability of the soil could result, retaining walls shall be provided and such shall be of adequate design and type of construction as prescribed by the Secretary.
(b) Design Requirements. The design of all veneer shall comply with the following:
(1) Veneer shall support no load other than its own weight and vertical dead load of veneer immediately above. (2) vertical and Surfaces to which veneer is attached shall be designed to support the additional lateral loads imposed by the veneer.
(3) Consideration shall be given to differential movements of the supports including those caused by temperature changes, shrinkage, creep, and deflection
(4) Adhered veneer and its backing shall be designed to have a bond to the supporting elements sufficient to withstand shearing stresses due to their weights including seismic effects on the total assemblage.
(5) Anchored veneer and its backing shall designed t o have a bond to the supporting Elements sufficient to withstand shearing stresses due to their weights including seismic effects on the total assemblage. (6) Anchors supports and ties shall be non-combustible and corrosion-resistant.
(a) General. Vertical openings shall be enclosed depending upon the fireresistive requirements of a particular type of construction as set forth in this Code. (b) Elevator Enclosures. Walls and partitions enclosing elevators and escalators shall be of not less than the fire-resistive construction required under the types of Construction. Enclosing walls of elevator shafts may consist of wire glass set in metal frames on the entrance side only. Elevator shafts extending through more than two storeys shall be equipped with and approved means of adequate ventilation to and through the main roof of the building: Provided, that in those buildings housing Groups F and G Occupancies equipped with automatic fire-extinguishing systems throughout, enclosures shall not be required for escalators: Provided, further that the top of the escalato opening at each storey shall be provided with a draft curtain. Such draft curtain shall enclose the perimeter of the unenclosed opening and shall extend from the ceiling downward at least 300 millimeters on all sides. Automatic sprinklers shall be provided around the perimeter of the opening and within a 600 millimeters of the draft curtain. The distance between the sprinkles shall not exceed 1.80 meters center-tocenter.
(c) Other Vertical Openings. All shafts ducts, chutes, and other vertical openings not covered in paragraph (b) above shall have enclosing walls conforming to the requirements specified under the type of construction of the building in which they are located. In other than Group A Occupancies rubbish and linen chutes shall terminate in rooms separated from the remainder of the building by a One-Hour FireResistive Occupancy Separation. Openings in to the chutes shall not be located in required exit, corridors or stairways. (d) Air Ducts. Air ducts passing through a floor shall be enclosed in a shaft. The shaft shall be as required in this Code for vertical openings. Dampers shall be installed where ducts pierce the shaft enclosure walls. Air ducts in Group A Occupancies need not be enclosed in a shaft it conforming to the mechanical provisions of this Code.
(a) Floors shall be of such materials and construction as specified under Chapter 5 Fire Zones and Fire-Resistive Standards and under Chapter 6 - Types of Construction. (b) All floors shall be so framed and secured into the framework and supporting walls to form an integral part of the whole building. (c) The types of floor construction used shall provide means to keep the beam and girders from lateral buckling.