Transmission Line Protection
Transmission Line Protection
Classification of line length depends on: Source-to-line Impedance Ratio (SIR), and Nominal voltage Length considerations: Short Lines: SIR > 4 Medium Lines: 0.5 < SIR < 4 Long Lines: SIR < 0.5
1/ GE / August-3-13
Current differential Phase comparison Permissive Overreach Transfer Trip (POTT) Directional Comparison Blocking (DCB)
2/ GE / August-3-13
Phase comparison Directional Comparison Blocking (DCB) Permissive Underreach Transfer Trip (PUTT) Permissive Overreach Transfer Trip (POTT) Unblocking Step Distance Step or coordinated overcurrent Inverse time overcurrent Current Differential
3/ GE / August-3-13
Phase comparison Directional Comparison Blocking (DCB) Permissive Underreach Transfer Trip (PUTT) Permissive Overreach Transfer Trip (POTT) Unblocking Step Distance Step or coordinated overcurrent Current Differential
4/ GE / August-3-13
RELAY (V,I)
For internal faults: > IZ V and V approximately in phase (mho) > IZ V and IZ approximately in phase (reactance)
5/ GE / August-3-13
Z I*Z - V
I*Z V=I*ZF
RELAY (V,I)
For external faults: > IZ V and V approximately out of phase (mho) > IZ V and IZ approximately out of phase (reactance)
6/ GE / August-3-13
RELAY
7/ GE / August-3-13
Z1 XL
End Zone
R XC
9/ GE / August-3-13
Blinders
Blinders limit the operation of distance relays (quad or mho) to a narrow region that parallels and encompasses the protected line Applied to long transmission lines, where mho settings are large enough to pick up on maximum load or minor system swings
10 / GE / August-3-13
Quadrilateral Characteristics
11 / GE / August-3-13
Quadrilateral Characteristics
Ground Resistance (Conductor falls on ground) R Resultant impedance outside of the mho operating region
12 / GE / August-3-13
Quadrilatera l
R
Standard for phase elements Used for phase elements with long heavily loaded lines heavily loaded Better coverage for ground faults due to resistance added to return path
13 / GE / August-3-13
DUTT Scheme
Zone 1
Bus Line
Bus
Zone 1
17 / GE / August-3-13
18 / GE / August-3-13
PUTT Scheme
Zone 2
Zone 1
Bus
Zone 1
Zone 2
& OR
Local Trip
POTT Scheme
Zone 2
Zone 1
Bus Line
Bus
Zone 1
Zone 2
(Z1)
Tx
(Z1)
Rx AND
OR
Zone 2
t o
21 / GE / August-3-13
Hybrid POTT
Intended for three-terminal lines and weak infeed conditions Echo feature adds security during weak infeed conditions Reverse-looking distance and oc elements used to identify external faults
22 / GE / August-3-13
Hybrid POTT
Zone 2
Zone 1
Zone 4
Zone 2
23 / GE / August-3-13
DCB Scheme
Zone 2
Zone 1
Zone 2
25 / GE / August-3-13
DCUB Scheme
Forward
Bus Line
Bus
Forward
(Un-Block)
Tx1
(Block)
Tx2
Forward
(Block)
AND
(Un-Block)
Rx1
Lockout
27 / GE / August-3-13
Redundancy Considerations
Redundant protection systems increase dependability of the
system: Multiple sets of protection using same protection principle and multiple pilot channels overcome individual element failure, or Multiple sets of protection using different protection principles and multiple channels protects against failure of one of the protection methods. Security can be improved using voting schemes (i.e., 2-outof-3), potentially at expense of dependability. Redundancy of instrument transformers, battery systems, trip coil circuits, etc. also need to be considered.
28 / GE / August-3-13
Single-pole Tripping
Distance relay must correctly identify a SLG fault and trip only the circuit breaker pole for the faulted phase. Autoreclosing and breaker failure functions must be initiated correctly on the fault event Security must be maintained on the healthy phases during the open pole condition and any reclosing attempt.
29 / GE / August-3-13
Out-of-Step Relaying
Out-of-step blocking relays Operate in conjunction with mho tripping relays to prevent a terminal from tripping during severe system swings & out-of-step conditions. Prevent system from separating in an indiscriminate manner. Out-of-step tripping relays Operate independently of other devices to detect out-of-step condition during the first pole slip. Initiate tripping of breakers that separate system in order to balance load with available generation on any isolated part of the system.
30 / GE / August-3-13
31 / GE / August-3-13