Lecture 08 - Symmetrical Faults
Lecture 08 - Symmetrical Faults
Spring 2012
Preliminaries
A fault in a circuit is any failure that interferes with the normal flow of current to the load. In most faults, a current path forms between two or more phases, or between one or more phases and the neutral (ground). Since the impedance of a new path is usually low, an excessive current may flow. High-voltage transmission lines have strings of insulators supporting each phase. The insulators must be large enough to prevent flashover a condition when the voltage difference between the line and the ground is large enough to ionize the air around insulators and thus provide a current path between a phase and a tower.
Fundamentals of Power Systems
Spring 2012
Preliminaries
If flashover occurs on a single phase of the line, an arc will be produced. Such faults are called single line-to-ground faults. Since the short-circuit path has a low impedance, very high currents flow through the faulted line into the ground and back into the power system. Faults involving ionized current paths are also called transient faults. They usually clear if power is removed from the line for a short time and then restored. Single line-to-ground faults can also occur if one phase of the line breaks and comes into contact with the ground or if insulators break This fault is called a permanent fault since it will remain after a quick power removing. Approximately 75% of all faults in power systems are either transient or permanent single line-to-ground faults.
Fundamentals of Power Systems
Spring 2012
Preliminaries
Sometimes, all three phases of a transmission line are shorted together symmetrical three-phase faults. Two phases of a line may touch, or flashover may occur between two phases a line-to-line fault. When two lines touch each other and also touch the ground, the fault is called a double line-to-ground fault. Lighting strokes cause most faults on high-voltage transmission lines producing a very high transient that greatly exceeds the rated voltage of the line. This voltage usually causes flashover between the phase and the ground of the line creating an arc. Once the current starts flowing through the arc, it remains even after the lighting disappears.
Spring 2012
Preliminaries
High currents due to a fault must be detected by protective circuitry and the circuit breakers on the affected transmission line should automatically open for a brief period (about 1/3 second). This will allow ionized air to deionize. If the fault was transient, normal operation should be restored after reclosing the breaker. Therefore, many transient faults are cleared automatically. Otherwise, the circuit breaker should open again isolating the transmission line. Selecting an appropriate circuit breaker (type, size, etc.) is important
Fundamentals of Power Systems
Spring 2012
Spring 2012
Spring 2012
Spring 2012
Spring 2012
10
Spring 2012
11
=
The rms magnitude of the AC fault current in a synchronous generator varies over time as
(12.11.1)
(12.11.2)
Spring 2012
12
Similarly, the transient reactance is the ratio of the fundamental component of the internal generated voltage to the transient component of current at the beginning of the fault. This value of current is found by extrapolating the transient region back to time zero
(12.12.1)
Fundamentals of Power Systems
(12.12.2)
Spring 2012
13
(12.13.1)
(12.13.2)
Spring 2012
14
Spring 2012
15
Since currents in a damper winding are of little importance during the transient and steady-state periods of faults, induction motors may be ignored in fault current analysis after the subtransient period.
Spring 2012
16
= 1.00,
and the time constants are
= 0.25,
= 0.12
= 1.10 ,
= 0.04
The initial DC component in this machine averages 50 percent of the initial AC component. a) What is the AC component of current in this generator the instant after the fault? b) What is the total current (AC + DC) in the generator right after the fault occurs? c) What will the AC component of the current be after 2 cycles? After 5 s?
Fundamentals of Power Systems
Spring 2012
17
, =
3 ,
100,000,000 3 13,800
= 4,184
The subtransient, transient, and steady-state currents are (per-unit and Amps)
Spring 2012
18
= 1.5 = 52,350
c) The AC component of current as a function of time is
/ "
which has the largest contribution from the transient current component transient period. At 5 s, the current reduces to
Spring 2012
19
Spring 2012
20
=
Therefore:
The reactance of the transformer is already given on the system base, it will not change
= 0.08
Spring 2012
21
Since there is no load on the system, the voltage at the terminals of each generator, and the internal generated voltage of each generator must also be 1.044 pu. The per-phase per-unit equivalent circuit of the system is
We observe that the phases of internal generated voltages are arbitrarily chosen as 00. The phase angles of both voltages must be the same since the generators were working in parallel.
Fundamentals of Power Systems
Spring 2012
22
Spring 2012
23
1 2.5 + 1 j2.5 + 1 12.5 = 2.61 90o +2.61 90o 5.2290o 1 = = 0.2980o 17.5
Therefore, the subtransient current in the fault is
3, = 100 3 115
= 502
Spring 2012
24
= + +
(12.24.1)
= +
(12.24.2)
Therefore, the internal generated voltage within a synchronous generator will change with load on the machine. A similar equation exists relating the internal generated voltage and terminal voltage of a synchronous generator under subtransient conditions.
Fundamentals of Power Systems
Spring 2012
25
" = + "
(12.25.1)
Spring 2012
26
= +
(12.26.1)
Therefore, the internal voltage EA under transient conditions can be calculated if the load current and the terminal voltage are known just before the fault. The voltage determined by (12.25.1) is the voltage driving the transient fault current flow from the generator and is called sometimes the voltage behind transient reactance. Since this voltage varies as a function of the load on the generator before the fault occurs, the transient current flow in a fault will depend on the prefault load conditions of the power system. This variation is also typically less than 10 % for different load conditions. The voltage behind transient reactance can be approximated as the prefault phase voltage of the generator.
Fundamentals of Power Systems
Spring 2012
27
Since synchronous motors are the same machines as synchronous generators, they have the same types of subtransient and transient reactances. When the motor is short-circuited, it does not receive power from the line but its field circuit is still energized and still spinning (due to inertia in the machine and in its load). Therefore, the motor acts as a generator, supplying power to the fault. The equivalent circuit of a synchronous motor is the same as the one of the synchronous generator except that the direction of the current flow is reversed. Therefore, the equations for the internal generated voltage, voltage behind the subtransient reactance, and voltage behind transient reactance become
= + " = + " = +
These voltages can be used in subtransient and transient fault current analyses similarly to the analysis of synchronous generators.
Fundamentals of Power Systems
Spring 2012
28
Spring 2012
29
3, 3 115,000
100 3 13.8
= 4,184
a) Before the fault, the generator was working at rated conditions and the per-unit current was:
= 1.0 25.84o
The voltage behind subtransient reactance is
Spring 2012
30
= 0.00o
The voltage behind subtransient reactance is
The difference in the fault current when the voltage behind subtransient reactance is considered and when it is ignored is small and usually systems are assumed unloaded.
Fundamentals of Power Systems
Spring 2012
31
2) Add a short circuit between one node of the equivalent circuit and the neutral and calculate the current flow through that short by standard analysis.
This approach always works but can get complex while dealing with complex systems. Therefore, a nodal analysis technique will be used. We introduce a new voltage source in the system to represent the effects of a fault at a bus. By solving for the currents introduced by this additional voltage source, we will find fault currents automatically.
Fundamentals of Power Systems
Spring 2012
32
Spring 2012
33
Spring 2012
34
Spring 2012
35
Spring 2012
36
=
Fundamentals of Power Systems
(12.36.1)
Spring 2012
37
11 21 31 41
12 22 32 42
13 23 33 43
14 1 0 " 24 34 = 0 3 44 0 4
(12.37.1)
where 1 , 3 , and 4 are the changes in the voltages at those busses due to the current If injected at bus 2 by the fault. The solution to (12.37.1) is found as
= 1 =
Fundamentals of Power Systems
(12.37.2)
Spring 2012
38
1 3 4
11 21 = 31 41
12 22 32 42
13 23 33 43
14 24 34 44
0 " 0 0
(12.38.1)
where = 1 . Since only bus 2 has current injected at it, the system (12.38.1) reduces to
" 1 = 12 " = 22 " 3 = 32 " 4 = 42
Fundamentals of Power Systems
(12.38.2)
Spring 2012
39
= 22
(12.39.1)
The voltage differences at each of the nodes due to the fault current can be calculated by substituting (12.39.1) into (12.38.2):
12 1 = = 22 2 = = 32 " 3 = 32 = 22 42 " 4 = 42 = 22
" 12
Fundamentals of Power Systems
(12.39.2)
Spring 2012
40
Therefore, we can calculate the voltage at every bus in the power system during the fault from a knowledge of the pre-fault voltage at the faulted bus and the bus impedance matrix!
Fundamentals of Power Systems
12 1 22 22 1 1 0 2 2 = + = + 32 = 1 32 3 3 22 22 4 4 42 42 1 22 22
(12.40.1)
Spring 2012
41
2. Calculate the bus admittance matrix Ybus. Include the admittances of all transmission lines, transformers, etc. between busses including the admittances of the loads or generators themselves at each bus. 3. Calculate the bus impedance matrix Zbus as inverse of the bus admittance matrix. 4. Assume that the power system is at no load and determine the voltage at every bus, which will be the same for every bus and the same as the internal voltage of the generators in the system. This is the pre-fault voltage .
Fundamentals of Power Systems
Spring 2012
42
(12.42.1)
6. Calculate the voltages at each bus during the fault. The voltage at bus j during a symmetrical 3 phase fault at the bus i is found as
= 1
(12.42.2)
7. Calculate the currents in any desired transmission line during the fault. The current through a line between bus i and bus j is found as
=
Fundamentals of Power Systems
(12.42.3)
Spring 2012
43
b) Calculate the per-unit voltage at every bus in the system during the subtransient period. c) Calculate the per-unit current 1 flowing in line 1 during the subtransient period of the fault. Following the 7 steps discussed before, we write: 1. The per-phase per-unit equivalent circuit is shown in slide 33.
Spring 2012
44
= 1.000o
5. The current at the faulted bus is computed as
" ,2
45
2 = 0.00o
Thats it!
Fundamentals of Power Systems
Spring 2012