Site Requirements Guide
Site Requirements Guide
Site Requirements Guide
NetApp, Inc. 495 East Java Drive Sunnyvale, CA 94089 U.S.A. Telephone: +1 (408) 822-6000 Fax: +1 (408) 822-4501 Support telephone: +1 (888) 4-NETAPP Documentation comments: [email protected] Information Web: http://www.netapp.com Part number 215-06458_A0 November 2011
ii
Table of Contents
Chapter 1 Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Required tools and equipment . . . . . . . . . . . . . . . . . . . . . . . . . . 2 System connectivity requirements . . . . . . . . . . . . . . . . . . . . . . . . 3 Circuit breaker, power outlet balancing, system cabinet power cord plugs, and console pinout requirements. . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter 2
Hardware Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Storage systems . . . . . . . . . . . . . . . . . . . . . . . FAS250 systems . . . . . . . . . . . . . . . . . . . FAS270 systems and GF270c gateways . . . . . . . FAS900 series systems and GF900 series gateways . 20xx series systems . . . . . . . . . . . . . . . . . 22xx series systems . . . . . . . . . . . . . . . . . 30xx series systems . . . . . . . . . . . . . . . . . 31xx series systems . . . . . . . . . . . . . . . . . 32xx series systems . . . . . . . . . . . . . . . . . 60xx series systems . . . . . . . . . . . . . . . . . 62xx series systems . . . . . . . . . . . . . . . . . SA systems . . . . . SA200 system SA300 system SA320 system SA600 system SA620 system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 21 23 25 27 45 54 58 66 71 74 77 78 84 86 88 90
NearStore systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 VTL appliances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Disk shelves. . . . . . . . . . . . DS14 series disk shelves . . DS2246 series disk shelves. DS4243 series disk shelves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96 . 97 .106 .108
Table of Contents
iii
Appendix A
Feature Update Record . . . . . . . . . . . . . . . . . . . . . . . . . . . .121 Copyright information . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125 Trademark information . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129
iv
Table of Contents
Site Preparation
About this chapter
This chapter describes the tools you need and the system connection, circuit breaker, and outlet requirements for your site.
Required tools and equipment on page 2 System connectivity requirements on page 3 Circuit breaker, power outlet balancing, system cabinet power cord plugs, and console pinout requirements on page 10
Prior to receiving your hardware, make sure that you have the appropriate tools and equipment assembled and ready to use:
Pallet jack, forklift, or hand truck, depending on what you receive #1 and #2 Phillips head screwdrivers and a flathead screwdriver for cable adapters ASCII terminal (also referred to as an ANSI terminal) or Serial console Null modem cable (optional)
Attention If the DB-9 to DB-9 straight-through serial cable for an ASCII terminal connection provided with your system is not compatible with your terminal connector, you need a null modem cable. WARNING Three people are required to install FAS20xx seriessystems, FAS900 series systems, GF900 series gateways, FAS6000 series systems, DS4243 disk shelves, and NearStore/VTL storage engines when both power supplies are installed. Two people are required to install all other storage systems and disk shelves safely into a rack or System Cabinet.
If you ordered a DC power version of your controller, you need the following items to fabricate the three-way cables required for DC power connections:
Wire-stripper Soldering tool and pliers (earlier version of the DC power supply) 12 AWG to 6 AWG x 3 copper wire (length determined by environment) 3/16'' flathead screwdriver
For details about your DC power supply, see the DC power supply documentation that came with your DC power supply. You can also find this documentation on the NetApp Support Site at support.netapp.com. Attention Do not mix different AC with DC power supplies in your controller.
Types of connectivity
Fibre ChannelConnects your controller to disk shelves, Fibre Channel switches, ATTO FireBridge 6500N, tape backup devices, and to other storage devices. They can connect through the following media:
Copper Fiber
SASConnects your appliance to SAS disk shelves and other SAS-based equipment. They can connect through the following media:
Copper Fiber
Your controller connects to disk shelves, Fibre Channel switches, ATTO FireBridge 6500N, tape backup devices, and other storage through onboard ports or adapter ports. The following illustration shows a typical LC connector used to connect Fibre Channel devices.
F TA CP RG E
PO
LC connector
RT
PO
RT
FI B CH RE AN N
EL
The following table lists maximum distances supported by 50 micron multimode fiber optic cables, with LC or SC connectors, connected to dual-port or quad-port Fibre Channel NICs, or ATTO FireBridge 6500N. Wavelength (Nanometers) 850 Core size (microns) 50 Modal Bandwidth (MHz/km) 500 Distance (Meters) 500 300 150 50 2000 860 500 270 150 Card (speed) 1 Gb 2 Gb 4 Gb 8 Gb 1 Gb 2 Gb 4 Gb 8 Gb
SAS connectivity
Your controller connects to SAS disk shelves and other SAS-based devices through SAS host bus adapters (HBAs) or onboard ports. The following illustrations show the dual-port SAS HBA with mini-SAS cables, and the quadport SAS HBA with copper cables with QSPFP connector.
1 3 4
1 2 3 4
Port A Port B QSFP-to-Mini-SAS copper cableMini-SAS connector (to X2062A card) QSFP-to-Mini-SAS copper cableQSFP connector (to disk shelf)
5 1 2
3 4
1 2 3 4 5
Ethernet connectivity
Your controller connects to a GbE network through either onboard ports or GbE network interface cards (NICs) which support either copper or fiber cabling. Copper GbE cabling and NICs: The cabling and network requirements are for GbE and 10GbE networks using copper cabling.
10Base-T/100Base-TX/1000Base-TX NICs
AC
T/L
NK
PO
RT
AC PO
T/L
NK
A AC
RT
T/L
RJ-45 connector
PO RT C
NK
AC T/L NK B 10 = 10 OFF 0= 10 GR 00 N =O RG
10 = 10 OFF 0= 10 GR 00 N =O RG
Dual-port Single-port
Types: Single-port, dual-port, quad-port Connector type: RJ-45 for all Cable type: Category 5, Category 5E or Category 6 unshielded four-pair cable for 10/100-T/100BASE-TX/1000BASE-TX Note Category 5 cables that do not have four-pair wires do not work properly with 10/100-T/100BASE-TX/1000BASE-TX speed networks. Use Category 6 cables for these networks. Maximum distance: 100m
Fiber GbE cabling and NICs: The following cabling and network requirements are for GbE networks using optical cabling.
1000Base-SX NICs
AC T
/LN
LC connector
KA
AC T/L N
AC T/L N
KB
Dual-port Single-port
The following table lists maximum distances supported by 50 or 62.5 micron multimode fiber optic cables, with LC or LC duplex connectors for the 1000BASE-SX NICs and 10GbE NICs, connected to single-port or dual-port Fibre Channel GbE NICs. Wavelength (Nanometers) MM laser 850 Core size (microns) 50 62.5 62.5 62.5 50 50 Modal Bandwidth (MHz/km) 500 160 200 200 2,000 4,700 Distance (Meters) 550 220 275 33 300 550 10GbE
Do not use less than the recommended 2,000 Mhz/km bandwidth for 10GBASESR cards. The following table lists maximum distances supported by some more common cable bandwidths. Modal Bandwidth (MHz/km) 2,000 500 400 62.5 200 160
Circuit breaker, power outlet balancing, system cabinet power cord plugs, and console pinout requirements
NEMA: If your equipment is mounted in a rack, the total number of circuit breakers required for your equipment is based on the current draw. You should not load a circuit beyond 80% of the rated limit for the circuit. For example, if you have a 20A circuit, you should load it to no more than 16A of draw. IEC: If your equipment is mounted in a rack, the total number of circuit breakers required for your equipment is based on the current draw. For example, if you have a 16A circuit, you should load it to no more than 16A of draw. Attention Overloading circuit breakers can lead to tripped breakers or power brownouts that can cause system errors.
A best practice is to plan how to distribute the total load across the PDU banks prior to plugging your system components into them. You should make each bank load as equal as possible. Keep the following considerations in mind when planning to balance the load:
Balancing the load depends on the number of components being connected and the location of the component power supply units (PSUs), as shown in the following illustrations. You should connect the components to different PDUs on opposite sides of the system cabinet, using the illustrations for reference. You should plug each component into the PDU outlet directly across from the component, using the illustrations for reference.
Examples of balancing the load with a single component: The following illustrations show three examples of connecting the PSUs of a single component, such as a controller in a single chassis, to the system cabinet PDUs.
10
Circuit breaker, power outlet balancing, system cabinet power cord plugs, and console pinout requirements
2 1
PSUs on the same side of the component
4 3
2 1 3
1 2 4
3
1 2 3 4 PSU 1 Left PDU outlet PSU 2 Right PDU outlet
11
Examples of balancing the load with two components: The following illustrations show three examples of connecting the PSUs of two components, such as a component with two controller modules in a single chassis or two components close together, to the system cabinet PDUs. PSUs on opposite sides of the component
13
6 10
8 12
14
11
13
6 10
8 12
11
14
1 6 10
13
3 8 12
11
14
12
Circuit breaker, power outlet balancing, system cabinet power cord plugs, and console pinout requirements
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Left PDU, bank A Left PDU, bank B Right PDU, bank A Right PDU, bank B PSU 1, component 1 Left PDU, bank A outlet PSU 2, component 1 Right PDU, bank A outlet PSU 1, component 2 Left PDU, bank B outlet PSU 2, component 2 Right PDU, bank B outlet Component 1 Component 2
13
Power cord NEMA L6-30 North America NEMA L6-20 North America
Plug
Socket view
Note NEMA L6-20 is slightly smaller in dimension than the NEMA L6-30. NEMA L15-30 North America
14
Circuit breaker, power outlet balancing, system cabinet power cord plugs, and console pinout requirements
Power cord IEC 60309, 32A, blue, P+N+E International IEC 60309, 16A, blue, P+N+E International
Plug
Socket view
Note The 16A plug is slightly smaller than the 32A plug. IEC 60309, 32A, red, 3P+N+E
AS/NZS3123-20 Australia
The length of a system cabinet power cord is 10 feet (3.05m) or 15 feet (4.57m).
15
The following table lists the pinout configuration for the RJ-45 to DB-9 adapter shipped with the systems. RJ-45 1 [not connected] 2 [not connected] 3 (connected to pin 3 on DB-9) TXD 3 (connected to pin 3 on RJ-45) Signal DB-9 (Male connector)
4 (connected to pin 5 on DB-9) 5 [not connected] 6 (connected to pin 2 on DB-9) 7 [not connected] 8 [not connected]
GND
RXD
2 (connected to pin 6 on RJ-45) [not connected] 1 [not connected] 4 [not connected] 6 through 9
The following table lists the RJ-45 connection pinout for the ASCII terminal console wiring. Pin number 1 2 3 4 5 6 7 8 Signal Connected to pin 8 Not connected TXD (from system) GND GND RXD (to system) Not connected Connected to Pin 1
16
Circuit breaker, power outlet balancing, system cabinet power cord plugs, and console pinout requirements
Hardware Characteristics
About this chapter This chapter tabulates hardware characteristics for the following types of hardware:
Storage systems on page 18 SA systems on page 77 Disk shelves on page 96 System cabinets on page 111 Third-party switches on page 119
17
Storage systems
This section lists tabulated descriptions of the hardware characteristics, clearance, environmental, and electrical requirements for different systems. Note Data for the FAS and V-series platforms are identified by the platform ID without using the FAS or V-series platform prefix. The prefixes are used only when the data is unique to that platform type.
These published system measurements are conservative. The following assumptions, conditions, and observations apply to these measurements:
Line voltage is either 100V AC, 200V AC, or -48V DC. Current and power are steady state rms values. Heat dissipation in BTU/hour is based on Watts multiplied by 3.4129 Measurements are taken at room ambient. Data is collected for each individual controller, controller module, or disk shelf, not for clustered systems or other combinations. Except for platforms that have two controllers in one chassis. Each disk shelf is fully populated with a particular drive type and speed and exercised with multiple threads of a disk stress test program. Controllers or controller modules with PCI slots are fully populated and are exercised with test program. To account for customer work loads that exceed these conditions, the total system workload is calculated using random read disk_qual to obtain electrical current, power, and heat dissipation values. If the system configuration causes fan speed to increase or decrease, the data is collected in that mode. Because fan speed can vary for a given set of conditions, the worst case set of numbers is presented. Electrical requirements for systems containing performance accelerator and Flash Cache modules are measured with the maximum number of these modules installed in the system.
18
Storage systems
The headings for the electrical requirements tables are defined as follows:
Worst-casePower consumption with system running on one PSU, high fan speed, and power distributed over one power cord. DS4xxx disk shelves are an exception, in that they require two PSUs. Per PSUTypical power needs, per PSU, for a system operating under normal conditions. SystemTypical total power needs for two PSUs in a system operating under normal condition and power distributed over two power cords, or four power cords for DS4243 disk shelves.
Use the following formula to calculate VA from watts: VA = Watts/PF PF = 0.95 Watts = Watts listed in the individual tables
NetApp systems have variable speed cooling fans. At higher ambient temperatures, the fans will spin faster and consume more power. This may counteract some energy savings anticipated by rasing the ambient temperature. You should operate your system within the NetApp-defined ambient temperature range of 10-40 C. As the temperature increases, the reliability and life expectancy of electronics and hard disk drives decreases.
For details about specific models of systems, see the following topics:
FAS250 systems on page 21 FAS270 systems and GF270c gateways on page 23 FAS900 series systems and GF900 series gateways on page 25 20xx series systems on page 27 22xx series systems on page 45 30xx series systems on page 54 31xx series systems on page 58 32xx series systems on page 66 60xx series systems on page 71 62xx series systems on page 74
19
SA200 system on page 78 SA300 system on page 84 SA320 system on page 86 SA600 system on page 88
20
Storage systems
Storage systems
FAS250 systems
FAS250 characteristics
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weight With disk drives Empty Rack units Height Rack-mount Tower Width Rack-mount Tower Depth Rack-mount Tower Clearance dimensions: Frontcooling Rearcooling All versions Tower Two-post rack Four-post rack Frontmaintenance Tower Two-post rack Four-post rack Rearmaintenance Tower Two-post rack Four-post rack 6 in. (15.3 cm) 12 in. (30.5 cm) 19 in. (48.3 cm) 12 in. (30.5 cm) 25 in. (63.5 cm) 25 in. (63.5 cm) 25 in. (63.5 cm) 12 in. (30.5 cm) 12 in. (30.5 cm) 12 in. (30.5 cm) 77 lbs (35 kg) 50.6 lbs (23 kg) 3 5.25 in. (13.3 cm) 20.3 in. (51.6 cm) 17.6 in. (44.7 cm) 10.4 in. (26.4 cm) 20 in. (50.8 cm) 20 in. (50.8 cm)
21
Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic level Input power frequency, Hz (AC) Input power voltage, V RMS (AC) (auto-ranging) Electrical requirements: Input voltage 100 to 120V Typical Worstcase, single PSU 2.84 3.27 283 326 964 1,110 System, two PSUs 1.71 3.99 345 397 1,178 1,354 Worstcase, single PSU 1.36 1.65 270 326 919 1,110 200 to 240V Typical System, two PSUs 1.71 2.01 330 392 1,125 1,335 41 F to 104 F (5 C to 40 C) -40 F to 140 F (-40 C to 60 C) 20 to 80% noncondensing 58 dBA@ 23 C 50 to 60 100-120V or 200-240V
Drives Input current measured, A 10K 15K Input power measured, W 10K 15K Thermal dissipation, BTU/hr 10K 15K
22
Storage systems
Storage systems
The following table lists the characteristics and requirements for your hardware. Physical characteristic: Weight With disk drives Empty Rack units Height Width Depth Clearance dimensions Frontcooling Rearcooling Frontmaintenance Rearmaintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic level Input power frequency, Hz (AC) Input power voltage, V RMS (AC) (auto-ranging 41 F to 104 F (5 C to 40 C) -40 F to 149 F (-40 C to 60 C) 20 to 80% noncondensing 58 dBA@ 23 C 50 to 60 100-120V or 200-240V All versionstwopost rack and four-post rack 6 in. (15.3 cm) 12 in. (30.5cm) 25 in. (63.5 cm) 12 in. (30.5 cm) 77 lbs (35 kg) 50.6 lbs (23 kg) 3 5.25 in. (13.3 cm) 17.6 in. (44.8 cm) 20 in. (50.9 cm)
23
FAS270 electrical requirements: Input voltage 100 to 120V Typical Worstcase, single PSU 3.12 3.83 311 382 1,062 1,302 System, two PSUs 3.76 4.30 375 429 1,279 1,463 Worstcase, single PSU 1.52 1.83 299 361 1,020 1,230 200 to 240V Typical System, two PSUs 1.83 2.07 355 405 1,212 1,380
Drives Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 10K 15K 10K 15K 10K 15K
GF270 electrical requirements: Input voltage 100 to 120V Typical Worstcase, single PSU Input power measured, W Thermal dissipation, BTU/hr 218 743 System, two PSUs 246 840 Worstcase, single PSU 210 716 200 to 240V Typical System, two PSUs 238 810
24
Storage systems
Storage systems
The following table lists the characteristics and requirements for your hardware. Physical characteristics Weight Rack units Height Width Depth Clearance dimensions Frontcooling Rearcooling Frontmaintenance Rearmaintenance All versions two-post rack and four-post rack 6 in. (15.2 cm) 12 in. (30.5 cm) 25 in. (63.5 cm) 40 in. (101.6 cm) 108 lbs (48.1 kg) 6 10.3 in. (26.2 cm) 17 in. (43.2 cm) 21.3 in. (54.1 cm)
25
Environmental requirements Operating temperature range Operating temperature recommended range Non-operating temperature range Relative humidity Acoustic level 50 F to 104 F (10 C to 40 C) 68 F to 77 F (20 C to 25 C) -40 F to 158 F (-40 C to 70 C) 20 to 80% noncondensing 49.5 dBA @ 23 C 6.4 bels @ 23 C Electrical requirements Input voltage, V Input current actual, A Input power actual, W Thermal dissipation, BTU/hr Input power frequency, Hz Input power voltage, V RMS (AC) (autoranging) 100 to 240 3.8 to 1.95 330 1,126 50 to 60 100-120V or 200-240V
26
Storage systems
Storage systems
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weighttwo controller modules and power supplies Rack units Height Width Depth Clearance dimensions: Frontcooling Rearcooling Front of chassismaintenance Rear of chassismaintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic levelNormal operating conditions at 23 C at sea level Input power frequency, Hz (AC) 50 F to 104 F (10 C to 40 C) -40 F to 140 F (-40 C to 60 C) 20 to 80% noncondensing All versions Two-post rack and four-post rack 6 in. (15.2 cm) 12 in. (30.5 cm) 30 in. (76.2 cm) 36 in. (91.4 cm) Full (chassis with all disk drives) Empty (no internal disks) 66 lbs (29.9kg) 57 lbs (25.9kg) 2 3.5 in. (8.9 cm) 17.6 in. (44.7 cm) 22.5 in. (57.2 cm)
27
100-120V or 200-240V
Electrical requirementsone controller module: Input voltage 100 to 120V Typical Worstcase, single PSU 3.83 4.44 4.44 3.75 3.07 3.22 3.37 3.37 3.36 System, two PSUs 3.39 3.89 3.89 3.68 2.94 3.09 3.22 3.22 3.29 Worstcase, single PSU 1.94 2.23 2.23 1.90 1.60 1.68 1.69 1.69 1.69 200 to 240V Typical System, two PSUs 1.87 2.16 2.16 1.87 1.57 1.61 1.66 1.66 1.68
Drives (in GB) Input current measured, A 144 SAS 300 SAS 450 SAS 600 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA 2-TB SATA
Per PSU 1.7 1.95 1.95 1.84 1.47 1.55 1.61 1.61 1.65
Per PSU 0.94 1.08 1.08 0.94 0.79 0.81 0.83 0.83 0.84
28
Storage systems
144 SAS 300 SAS 450 SAS 600 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA 2-TB SATA
377 439 439 375 300 319 332 332 334 1,287 1,497 1,497 1,279 1,024 1,088 1,133 1,133 1,139
165 191 191 182 144 151 158 158 162 563 649 649 621 490 514 539 539 553
330 381 381 364 287 301 316 316 324 1,125 1,298 1,298 1,242 979 1,028 1,077 1,077 1.105
371 431 431 360 304 322 327 327 326 1,264 1,470 1,470 1,228 1,035 1,099 1,114 1,114 1.112
174 204 204 178 145 147 152.5 152.5 160 593 669 669 606 494 501 520 520 546
348 407 407 355 289 294 305 305 320 1,185 1,338 1,338 1,211 987 1,002 1,039 1,039 1.092
144 SAS 300 SAS 450 SAS 600 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA 2-TB SATA
29
Electrical requirementstwo controller modules: Input voltage 100 to 120V Typical Worstcase, single PSU 4.69 4.94 4.94 4.73 3.82 3.94 4.13 4.13 4.22 464 488 488 458 377 389 409 409 415 System, two PSUs 4.09 4.75 4.75 4.57 3.72 3.80 3.89 3.89 4.12 400 465 465 458 365 372 382 382 401 Worstcase, single PSU 2.34 2.45 2.45 2.32 1.91 1.97 2.09 2.09 2.11 452 476 476 448 367 381 404 404 405 200 to 240V Typical System, two PSUs 2.22 2.37 2.37 2.29 1.86 1.93 1.98 1.98 2.08 419 448 448 432 345 360 372 372 390
Drives (in GB) Input current measured, A 144 SAS 300 SAS 450 SAS 600 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA 2-TB SATA Input power measured, W 144 SAS 300 SAS 450 SAS 600 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA 2-TB SATA
Per PSU 2.05 2.38 2.38 2.29 1.86 1.90 1.95 1.95 2.06 200 233 233 229 183 186 191 191 201
Per PSU 1.11 1.19 1.19 1.15 0.93 0.97 0.99 0.99 1.04 210 224 224 216 173 180 186 186 195
30
Storage systems
144 SAS 300 SAS 450 SAS 600 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA 2-TB SATA
31
Electrical requirementsone controller module, no disks: Input voltage 100 to 120V Typical Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 1.67 165 563 System, two PSUs 1.60 153 521 Worstcase, single PSU 0.9 160 544 200 to 240V Typical System, two PSUs 0.89 149 506
Electrical requirementstwo controller modules, no disks: Input voltage 100 to 120V Typical Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 2.63 254 866 System, two PSUs 2.23 215 731 Worstcase, single PSU 1.34 240 818 200 to 240V Typical System, two PSUs 1.18 208 709
32
Storage systems
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weighttwo controller modules and power supplies Rack units Height Width Depth Clearance dimensions: Frontcooling Rearcooling Front of chassismaintenance Rear of chassismaintenance Environmental requirement: Operating temperature range Non-operating temperature range Relative humidity Acoustic levelNormal operating conditions at 23 C at sea level Input power frequency, Hz (AC) Input power voltage, V RMS (AC) (auto-ranging) 50 F to 104 F (10 C to 40 C) -40 F to 140 F (-40 C to 60 C) 20 to 80% noncondensing All versions Two-post rack and four-post rack 6 in. (15.2 cm) 12 in. (30.5 cm) 30 in. (76.2 cm) 36 in. (91.4 cm) Full (chassis with all disk drives) Empty (no internal disks) 66 lbs (29.9kg) 57 lbs (25.9kg) 2 3.5 in. (8.9 cm) 17.6 in. (44.7 cm) 22.5 in. (57.2 cm)
33
Electrical requirementsone controller module: Input voltage 100 to 120V Typical Worstcase, single PSU 4.08 3.96 3.87 3.25 3.38 3.62 3.34 404 391 387 319 333 357 329 System, two PSUs 3.96 3.84 3.83 3.17 3.27 3.53 3.22 387 375 376 310 322 345 315 Worstcase, single PSU 2.3 1.97 1.91 1.62 1.69 1.81 1.66 392 379 368 310 324 347 319 200 to 240V Typical System, two PSUs 2 1.94 1.91 1.62 1.68 1.8 1.67 378 367 361 301 314 337 312
Drives (in GB) Input current measured, A 300 SAS 450 SAS 600 SAS 500 SATA 750 SATA 1-TB SATA 2-TB SATA Input power measured, W 300 SAS 450 SAS 600 SAS 500 SATA 750 SATA 1-TB SATA 2-TB SATA
Per PSU 1.98 1.92 1.92 1.59 1.64 1.77 1.61 194 188 188 155 161 173 158
Per PSU 1 0.97 0.96 0.81 0.84 0.90 0.84 189 184 181 151 157 169 156
34
Storage systems
300 SAS 450 SAS 600 SAS 500 SATA 750 SATA 1-TB SATA 2-TB SATA
35
Electrical requirementstwo controller modules: Input voltage 100 to 120V Typical Worstcase, single PSU 4.85 4.70 4.44 3.95 4.10 4.36 3.92 480 464 440 390 405 4.29 387 System, two PSUs 4.66 4.53 4.32 3.84 3.98 4.23 3.88 457 445 424 376 389 414 378 Worstcase, single PSU 2.39 2.32 2.18 1.97 2.04 2.16 1.97 464 451 425 379 393 416 382 200 to 240V Typical System, two PSUs 2.35 2.28 2.18 1.95 2.01 2.12 1.96 447 432 415 367 381 403 371
Drives (in GB) Input current measured, A 300 SAS 450 SAS 600 SAS 500 SATA 750 SATA 1-TB SATA 2-TB SATA Input power measured, W 300 SAS 450 SAS 600 SAS 500 SATA 750 SATA 1-TB SATA 2-TB SATA
Per PSU 2.33 2.27 2.16 1.92 1.99 2.12 1.94 229 223 212 188 195 207 189
Per PSU 1.18 1.14 1.09 0.98 1.01 1.06 0.98 224 216 208 184 191 202 186
36
Storage systems
300 SAS 450 SAS 600 SAS 500 SATA 750 SATA 1-TB SATA 2-TB SATA
37
Electrical requirementsone controller module, no disks: Input voltage 100 to 120V Typical Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 1.4 137 467 System, two PSUs 1.4 133 454 Worstcase, single PSU 0.77 134 457 200 to 240V Typical System, two PSUs 0.78 130 443
Electrical requirementstwo controller modules, no disks: Input voltage 100 to 120V Typical Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 1.96 192 655 System, two PSUs 1.95 187 638 Worstcase, single PSU 1.02 188 641 200 to 240V Typical System, two PSUs 1.04 182 621
38
Storage systems
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weighttwo controller modules and power supplies Rack units Height Width Depth Clearance dimensions: Frontcooling Rearcooling Front of chassis maintenance Rear of chassis maintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic levelNormal operating conditions at 23 C at sea level Input power frequency, Hz (AC) Input power voltage, V RMS (AC) (auto-ranging) 50 F to 104 F (10 C to 40 C) -40 F to 140 F (-40 C to 60 C) 20 to 80% noncondensing All versionsTwopost rack and four-post rack 6 in. (15.2 cm) 12 in. (30.5 cm) 30 in. (76.2 cm) 36 in. (91.4 cm) Full (chassis with all disk drives) Empty (no internal disks) 110 lbs (49.9 kg) 91 lbs (41.3 kg) 4 6.9 in. (17.5 cm) 17.6 in. (44.7 cm) 22.5 in. (57.2 cm)
39
Electrical requirementsone controller module: Input voltage 100 to 120V Typical Worstcase, single PSU 5.64 6.62 6.62 4.40 4.64 5.07 5.07 560 658 658 435 459 504 504 System, two PSUs 4.76 5.92 5.92 4.04 4.36 4.51 4.51 465 583 583 393 425 439 439 Worstcase, single PSU 2.82 3.27 3.27 2.30 2.33 2.46 2.46 547 636 636 439 447 474 474 200 to 240V Typical System, two PSUs 2.65 2.76 2.76 2.07 2.17 2.40 2.40 502 523 523 386 408 447 447
Drives (in GB) Input current measured, A 144 SAS 300 SAS 450 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA Input power measured, W 144 SAS 300 SAS 450 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA
Per PSU 2.38 2.96 2.96 2.02 2.18 2.26 2.26 233 292 292 197 213 220 220
Per PSU 1.33 1.38 1.38 1.04 1.09 1.20 1.20 251 266 266 193 204 224 224
40
Storage systems
144 SAS 300 SAS 450 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA
41
Electrical requirementstwo controller modules: Input voltage 100 to 120V Typical Worstcase, single PSU 6.31 7.51 7.51 5.54 5.74 5.91 5.91 628 747 747 549 567 585 585 System, two PSUs 5.68 6.68 6.68 4.98 5.67 5.47 5.47 558 659 659 487 554 536 536 Worstcase, single PSU 3.09 3.73 3.73 2.7 2.89 2.97 2.97 600 728 728 518 561 575 575 200 to 240V Typical System, two PSUs 2.89 3.41 3.41 2.52 2.65 2.77 2.77 550 655 655 474 503 524 524
Drives (in GB) Input current measured, A 144 SAS 300 SAS 450 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA Input power measured, W 144 SAS 300 SAS 450 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA
Per PSU 2.84 3.34 3.34 2.49 2.84 2.74 2.74 279 330 330 244 277 268 268
Per PSU 1.45 1.71 1.71 1.26 1.33 1.39 1.39 275 328 328 237 252 262 262
42
Storage systems
144 SAS 300 SAS 450 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA
43
Electrical requirementsone controller module, no disks: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 2.10 205 698 Typical Per PSU 0.90 86.5 295 System, two PSUs 1.80 173 589 200 to 240V Worstcase, single PSU 1.10 198 675 Typical Per PSU 0.50 84 287 System, two PSUs 0.99 168 574
Electrical requirementstwo controller modules, no disks: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 2.62 256 874 Typical Per PSU 1.19 114 387 System, two PSUs 2.37 227 773 200 to 240V Worstcase, single PSU 1.35 250 851 Typical Per PSU 0.62 111 379 System, two PSUs 1.24 222 758
44
Storage systems
Storage systems
2240-2 characteristics
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weight 1 controller module 2 controller modules Rack units Height Width Depth with cable management arm installed Clearance dimensions: Frontcooling Rearcooling and maintenance Frontmaintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humiditynoncondensing Acoustic levelNormal operating conditions at 23 C at sea level Altitude 50 F to 104 F (10 C to 40 C) -40 F to 158 F (-40 C to 70 C) 20 to 80% operating 5 to 95% nonoperating 51.0 dBA sound pressure (LpA) 6.9 Bel sound power (LwAd) 10,000 ft. operating 40,000 ft. nonoperating All versions two-post rack and four-post rack 6 in. (15.3 cm) 12 in. (30.5 cm) 25 in. (55.9 cm) 50.7 lbs (23 kg) 56 lbs (25.4 kg) 2 3.3 in. (8.4 cm) 17.6 in. (44.7 cm) 23.1 in. (58.7)
45
Input power frequency, Hz (AC) Input power voltage, V RMS (AC) (auto-ranging)
50 to 60 100-120V or 200-240V
2240-2 electrical requirementswith one controller module with a FC mezzanine card and either 450-GB or 600-GB disks: Input voltage 100V Typical Worst -case, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 4.11 409 1,396 System, two PSUs 2.72 270 922 Worstcase, single PSU 2.01 397 1,355 200V Typical System, two PSUs 1.41 263 898 Worstcase, single PSU 1.87 397 1,355 215V Typical System, two PSUs 1.35 263 898
46
Storage systems
2240-2 electrical requirementswith one controller module with a 10 GbE mezzanine card and either 450-GB or 600-GB disks: Input voltage 100V Typical Worst -case, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 4.11 409 1,396 System, two PSUs 2.72 270 922 Worstcase, single PSU 2.01 397 1,355 200V Typical System, two PSUs 1.41 263 898 Worstcase, single PSU 1.87 397 1,355 215V Typical System, two PSUs 1.35 263 898
2240-2 electrical requirementswith one controller module, no mezzanine card and either 450-GB or 600-GB disks: Input voltage 100V Typical Worst -case, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 3.92 390 1,332 System, two PSUs 2.70 269 919 Worstcase, single PSU 1.92 3.79 1,294 200V Typical System, two PSUs 1.40 262 895 Worstcase, single PSU 1.79 378 1,291 215V Typical System, two PSUs 1.33 261 891
47
2240-2 electrical requirementswith two controller modules with a FC mezzanine card and either 450-GB or 600-GB disks: Input voltage 100V Typical Worst -case, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 5.07 509 1,738 System, two PSUs 3.61 357 1,219 Worstcase, single PSU 2.47 487 1,663 200V Typical System, two PSUs 1.78 340 1,161 Worstcase, single PSU 2.29 487 1,663 215V Typical System, two PSUs 1.66 338 1,154
2240-2 electrical requirementswith two controller modules with a 10GbE mezzanine card and either 450-GB or 600-GB disks: Input voltage 100V Typical Worst -case, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 5.07 509 1,738 System, two PSUs 3.61 357 1,219 Worstcase, single PSU 2.47 487 1,663 200V Typical System, two PSUs 1.78 340 1,161 Worstcase, single PSU 2.29 487 1,663 215V Typical System, two PSUs 1.66 338 1,154
48
Storage systems
2240-2 electrical requirementswith two controller modules, no mezzanine card and either 450-GB 600-GB disks Input voltage 100V Typical Worst -case, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 4.76 474 1,618 System, two PSUs 3.60 356 1,215 Worstcase, single PSU 2.31 456 1,557 200V Typical System, two PSUs 1.76 339 1,157 Worstcase, single PSU 2.15 456 1,557 215V Typical System, two PSUs 1.64 336 1,147
49
2240-4 characteristics
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weight 1 controller module 2 controller modules Rack units Height Width Depth Clearance dimensions: Frontcooling Rearcooling and maintenance Frontmaintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic levelNormal operating conditions at 23 C at sea level Input power frequency, Hz (AC) Input power voltage, V RMS (AC) (auto-ranging) 50 F to 104 F (10 C to 40 C) -40 F to 158 F (-40 C to 70 C) 20 to 80% noncondensing 49.6 dBA sound pressure (LpA) 6.9 Bel sound power (LwAd) 50 to 60 100-120V or 200-240V All versions two-post rack and four-post rack 6 in. (15.3 cm) 12 in. (30.5 cm) 25 in. (55.9 cm) 102.3 lbs (46.4 kg) 107.8 lbs (48.9 kg) 4
50
Storage systems
2240-4 electrical requirementswith one controller module with a FC mezzanine card and either 1-TB, 2-TB, or 3-TB disks: Input voltage 100V Typical Worst -case, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 5.39 537 1,833 System, two PSUs 4.93 489 1,669 Worstcase, single PSU 2.71 524 1,789 200V Typical System, two PSUs 2.53 477 1,628 Worstcase, single PSU 2.56 521 1,779 215V Typical System, two PSUs 2.41 475 1,622
2240-4 electrical requirementswith one controller module with a 10GbE mezzanine card and either 1-TB, 2-TB, or 3-TB disks: Input voltage 100V Typical Worst -case, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 5.39 537 1,833 System, two PSUs 4.93 489 1,669 Worstcase, single PSU 2.71 524 1,789 200V Typical System, two PSUs 2.53 477 1,628 Worstcase, single PSU 2.56 521 1,779 215V Typical System, two PSUs 2.41 475 1,622
51
2240-4 electrical requirementswith one controller module, no mezzanine card and either 1-TB, 2-TB, or 3-TB disks: Input voltage 100V Typical Worst -case, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 5.34 533 1,820 System, two PSUs 4.85 482 1,646 Worstcase, single PSU 2.68 517 1,765 200V Typical System, two PSUs 2.5 468 1,598 Worstcase, single PSU 2.53 515 1,758 215V Typical System, two PSUs 2.37 466 1,591
2240-4 electrical requirementswith two controller modules with a FC mezzanine card and either 1-TB, 2-TB, or 3-TB disks Input voltage 100V Typical Worst -case, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 6.0 597 2,038 System, two PSUs 5.65 562 1,919 Worstcase, single PSU 3.02 584 1,994 200V Typical System, two PSUs 2.94 560 1.912 Worstcase, single PSU 2.82 578 1,973 215V Typical System, two PSUs 2.8 561 1,915
52
Storage systems
2240-4 electrical requirementswith two controller modules with a 10GbE mezzanine card and either 1-TB, 2-TB, or 3-TB disks: Input voltage 100V Typical Worst -case, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 6.0 597 2,038 System, two PSUs 5.65 562 1,919 Worstcase, single PSU 3.02 584 1,994 200V Typical System, two PSUs 2.94 560 1.912 Worstcase, single PSU 2.82 578 1,973 215V Typical System, two PSUs 2.8 561 1,915
2240-4 electrical requirementswith two controller modules, no mezzanine card and either 1-TB, 2-TB, or 3-TB disks: Input voltage 100V Typical Worst -case, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 5.87 582 1,987 System, two PSUs 5.52 545 1,861 Worstcase, single PSU 2.94 568 1,939 200V Typical System, two PSUs 2.79 531 1,813 Worstcase, single PSU 2.76 565 1,929 215V Typical System, two PSUs 2.66 529 1,806
53
Storage systems
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weight Rack units Height Width Depth Clearance dimensions: Frontcooling Rearcooling Frontmaintenance Rearmaintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic levelNormal operating conditions at 23 C at sea level Input power frequency, Hz (AC) Input power voltage, V RMS (AC) (auto-ranging) 50 F to 104 F (10 C to 40 C) -40 F to 149 F (-40 C to 65 C) 20 to 80% noncondensing 49 dBA sound pressure (LpA) 50 to 60 100-120V or 200-240V All versions two-post rack and four-post rack 6 in. (15.2 cm) 12 in. (30.5 cm) 30 in. (76.2 cm) 36 in. (91.4 cm) 68 lbs (30.84 kg) 3 5.13 in. (13 cm) 17.73 in. (45.0 cm) 24 in. (60.7 cm)
54
Storage systems
3020 electrical requirements: Input voltage 100 to 120V Typical Worst -case, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 3.39 336 1,144 System, two PSUs 2.4 236 805 Worstcase, single PSU 1.77 329 1,122 200 to 240V Typical System, two PSUs 1.40 229 783 Worstcase, single PSU 8.2 328 1,118 -40 to -60V Typical System, two PSUs 5.7 226 771
3040 electrical requirements: Input voltage 100 to 120V Typical Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 3.66 363 1,238 System, two PSUs 3.4 338 1,152 Worstcase, single PSU 1.9 358 1,221 200 to 240V Typical System, two PSUs 1.9 330 1,127 Worstcase, single PSU 7.94 318 1,084 -40 to -60V Typical System, two PSUs 7.4 296 1,011
55
3040 electrical requirements with one Performance Acceleration module or Flash Cache modulel: Input voltage 100 to 120V Typical Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 4.21 418 1,425 System, two PSUs 3.63 355 1,212 Worstcase, single PSU 2.21 417 1,422 200 to 240V Typical System, two PSUs 2.07 350 1,193 Worstcase, single PSU 9.74 389 1,328 -40 to -60V Typical System, two PSUs 8.21 328 1,119
3050 electrical requirements: Input voltage 100 to 120V Typical Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 3.88 386 1,317 System, two PSUs 3.4 328 1,119 Worstcase, single PSU 2.04 384 1,309 200 to 240V Typical System, two PSUs 1.9 327 1,116 Worstcase, single PSU 9.49 380 1,295 -40 to -60V Typical System, two PSUs 8.0 319 1,089
56
Storage systems
3070 electrical requirements: Input voltage 100 to 120V Typical Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 4.03 400 1,365 System, two PSUs 3.7 362 1,233 Worstcase, single PSU 2.06 387 1,320 200 to 240V Typical System, two PSUs 2.1 355 1,212 Worstcase, single PSU 10.57 423 1,442 -40 to -60V Typical System, two PSUs 9.4 376 1,283
3070 electrical requirements with two Performance Acceleration modules or Flash Cache modules: Input voltage 100 to 120V Typical Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 4.51 449 1,530 System, two PSUs 4.08 402 1,369 Worstcase, single PSU 2.29 438 1,493 200 to 240V Typical System, two PSUs 2.43 415 1,414 Worstcase, single PSU 10.67 427 1,455 -40 to -60V Typical System, two PSUs 9.26 370 1,263
57
Storage systems
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weightone controller module Weighttwo controller modules Rack units Height Width Depth Clearance dimensions: Frontcooling Rearcooling Frontmaintenance Rearmaintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic levelNormal operating conditions at 22 C at sea level Input power frequency, Hz (AC) 50 F to 104 F (10 C to 40 C) -40 F to 149 F (-40 C to 65 C) 20 to 80% noncondensing All versions two-post rack and four-post rack 6 in. (15.2 cm) 12 in. (30.5 cm) 30 in. (76.2 cm) 36 in. (91.4 cm) 102 lbs (46.27 kg) 121 lbs (54.89 kg) 6 10.75 in. (27.3 cm) 17.73 in. (45.0 cm) 24 in. (60.7 cm)
58
Storage systems
100-120V or 200-240V
3140 electrical requirementsone controller module: Input voltage 100 to 120V Typical Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 3.98 396 1,350 System, two PSUs 3.77 373 1,272 Worstcase, single PSU 1.97 385 1,313 200 to 240V Typical System, two PSUs 1.93 366 1,249 Worstcase, single PSU 8.38 336 1,146 -40 to -60V Typical System, two PSUs 9.75 389 1,327
100 to 120V Typical Worstcase, single PSU System, two PSUs 5.97 594
200 to 240V Typical Worstcase, single PSU 3.60 712 System, two PSUs 2.98 581
-40 to -60V Typical Worstcase, single PSU 15.27 612 System, two PSUs 15.23 607
7.38 736
59
2,509
1,013
2,026
2,427
991
1,981
2,088
1,036
2,071
3140 electrical requirements with two Performance Acceleration modules or Flash Cache modulesone controller module: Input voltage 100 to 120V Typical Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 4.06 402 1,372 System, two PSUs 3.86 383 1,307 Worst -case, single PSU 2.01 396 1,352 200 to 240V Typical System, two PSUs 1.98 379 1,293 Worstcase, single PSU 8.55 343 1,170 -40 to -60V Typical System, two PSUs 10.05 401 1,368
60
Storage systems
3140 electrical requirements with four Performance Acceleration modules or Flash Cache modulestwo controller modules: Input voltage
100 to 120V Typical Worstcase, single PSU System, two PSUs 6.58 655 2,234
200 to 240V Typical Worstcase, single PSU 3.75 745 2,543 System, two PSUs 3.15 630 2,150
-40 to -60V Typical Worstcase, single PSU 15.91 638 2,177 System, two PSUs 16.03 639 2,180
100 to 120V Typical Worstcase, single PSU System, two PSUs 4.50 440 1,502
200 to 240V Typical Worstcase, single PSU 2.38 460 1,570 System, two PSUs 2.32 450 1,535
-40 to -60V Typical Worstcase, single PSU 10.07 404 1,378 System, two PSUs 11.79 470 1,604
61
100 to 120V Typical Worstcase, single PSU System, two PSUs 7.76 760 2,594
200 to 240V Typical Worstcase, single PSU 4.40 860 2,935 System, two PSUs 3.80 755 2,577
-40 to -60V Typical Worstcase, single PSU 18.78 752 2,566 System, two PSUs 16.15 646 2,204
3160 electrical requirements with two Performance Acceleration modules or Flash Cache modulesone controller module: Input voltage
100 to 120V Typical Worstcase, single PSU System, two PSUs 4.62 453 1,546
200 to 240V Typical Worstcase, single PSU 2.44 478 1,631 System, two PSUs 2.38 460 1,570
-40 to -60V Typical Worstcase, single PSU 10.33 414 1,412 System, two PSUs 12.09 482 1,645
62
Storage systems
3160 electrical requirements with four Performance Acceleration modules or Flash Cache modulestwo controller modules: Input voltage
100 to 120V Typical Worstcase, single PSU System, two PSUs 8.17 809 2,761
200 to 240V Typical Worstcase, single PSU 4.51 890 3,037 System, two PSUs 3.90 775 2,645
-40 to -60V Typical Worstcase, single PSU 19.24 770 2,627 System, two PSUs 18.78 751 2,563
100 to 120V Typical Worstcase, single PSU System, two PSUs 4.74 470 1,602
200 to 240V Typical Worstcase, single PSU 2.52 493 1,680 System, two PSUs 2.38 459 1,564
-40 to -60V Typical Worstcase, single PSU 10.75 430 1,467 System, two PSUs 12.18 486 1,658
63
100 to 120V Typical Worstcase, single PSU System , two PSUs 8.14 810 2,761
200 to 240V Typical Worstcase, single PSU 4.69 930 3,170 System, two PSUs 4.03 788 2,686
-40 to -60V Typical Worstcase, single PSU 20.00 800 2,730 System, two PSUs 20.68 827 2,822
3170 electrical requirements with four Performance Acceleration modules or Flash Cache modulesone controller module: Input voltage
100 to 120V Typical Worstcase, single PSU System, two PSUs 4.98 494 1,685
200 to 240V Typical Worstcase, single PSU 2.62 513 1,749 System, two PSUs 2.5 482 1,644
-40 to -60V Typical Worstcase, single PSU 20.00 800 2,730 System, two PSUs 20.68 827 2,822
64
Storage systems
3170 electrical requirements with eight Performance Acceleration modules or Flash Cache modulestwo controller modules: Input voltage
100 to 120V Typical Worstcase, single PSU System, two PSUs 8.98 894 3,049
200 to 240V Typical Worstcase, single PSU 5.08 1,006 3,430 System, two PSUs 4.44 868 2,960
-40 to -60V Typical Worstcase, single PSU 21.67 867 2,958 System, two PSUs 22.77 911 3,109
65
Storage systems
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weightone controller module Weighttwo controller modules Weightcontroller and I/O expansion module Rack units Height Width Depth Clearance dimensions: Frontcooling Rearcooling Frontmaintenance Rearmaintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic levelNormal operating conditions at 23 C at sea level 50 F to 104 F (10 C to 40 C) -40 F to 158 F (-40 C to 70 C) 20 to 80% noncondensing 55.4 dBA sound pressure (LpA) 7.1 B sound power (LWAd) All versions two-post rack and four-post rack 10 in. (25.4 cm) 12 in. (30.5 cm) 30 in. (76.2 cm) 30 in. (76.2 cm) 67.3 lbs (30.5 kg) 79.5 lbs (36.1 kg) 74.5 lbs (33.8 kg) 3 5.12 in. (13.0 cm) 17.61 in. (44.7 cm) 24 in. (60.7 cm)
66
Storage systems
Input power frequency, Hz (AC) Input power voltage, V RMS (AC) (auto-ranging)
50 to 60 100-120V or 200-240V
3210 electrical requirements with one 256-GB Flash Cache module one controller module: Input voltage
100 to 120V Typical Worstcase, single PSU System, two PSUs 3.03 299 1,021
200 to 240V Typical Worstcase, single PSU 2.11 411 1,403 System, two PSUs 1.66 293 1,000
-40 to -60V Typical Worstcase, single PSU 10.45 418 1,427 System, two PSUs 7.30 292 997
67
3210 electrical requirements with one 256-GB Flash Cache module per controller moduletwo controller modules: Input voltage
100 to 120V Typical Worstcase, single PSU System, two PSUs 4.64 462 1,577
200 to 240V Typical Worstcase, single PSU 3.11 612 2,089 System, two PSUs 2.38 450 1,536
-40 to -60V Typical Worstcase, single PSU 15.8 632 2,157 System, two PSUs 11.6 464 1,584
3240 electrical requirements with one 256-GB, one 512-GB, or one 1TB Flash Cache module per controller moduletwo controller modules: Input voltage
100 to 120V Typical Worstcase, single PSU System, two PSUs 4.70 466 1,591
200 to 240V Typical Worstcase, single PSU 3.15 620 2,116 System, two PSUs 2.41 456 1,557
-40 to -60V Typical Worstcase, single PSU 15.9 636 1,611 System, two PSUs 11.8 472 2,171
Storage systems
3240 electrical requirements with one 256-GB, one 512-GB, or one 1TB Flash Cache module and one I/O expansion module: Input voltage
100 to 120V Typical Worstcase, single PSU System, two PSUs 3.71 368 1,256
200 to 240V Typical Worstcase, single PSU 2.50 478 1,632 System, two PSUs 1.96 360 1,229
-40 to -60V Typical Worstcase, single PSU 12.55 502 1,714 System, two PSUs 9.2 368 1,256
3270 electrical requirements with one 256-GB, one 512-GB, or one 1TB Flash Cache module per controller moduletwo controller modules: Input voltage
100 to 120V Typical Worstcase, single PSU System, two PSUs 5.56 552 1,884
200 to 240V Typical Worstcase, single PSU 3.58 707 2,413 System, two PSUs 2.83 541 1,847
-40 to -60V Typical Worstcase, single PSU 18.2 728 2,485 System, two PSUs 13.9 556 1,898
69
3270 electrical requirements with one 256-GB, one 512-GB, or one 1TB Flash Cache module and one I/O expansion module: Input voltage
100 to 120V Typical Worstcase, single PSU System, two PSUs 4.14 408 1,393
200 to 240V Typical Worstcase, single PSU 2.73 533 1,820 System, two PSUs 2.13 398 1,359
-40 to -60V Typical Worstcase, single PSU 13.55 542 1,850 System, two PSUs 10.1 404 1,379
70
Storage systems
Storage systems
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weight Rack units Height Width Depth (including cable management tray) Clearance dimensions: Frontcooling Rearcooling Front of chassismaintenance Rear of chassismaintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic levelNormal operating conditions at 22 C at sea level Input power frequency, Hz (AC) Input power voltage, V RMS (AC) (auto-ranging) 50 F to 104 F (10 C to 40 C) -40 F to 158 F (-40 C to 70 C) 20 to 80% noncondensing 56.5 dBA sound pressure (LpA) 50 to 60 100-120V or 200-240V All versions two-post rack and four-post rack 6 in. (15.2 cm) 12 in. (30.5 cm) 25 in. (63.5 cm) 40 in. (102 cm) 122 lbs (55.34 kg) 6 10.32 in. (26.21 cm) 17.53 in. (44.52 cm) 29 in. (73.66 cm)
71
6030/FAS6040 electrical requirements: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 9.75 968 3,301 Typical Per PSU 2.87 279 949 System, two PSUs 5.74 557 1,898 200 to 240V Worstcase, single PSU 4.87 934 3,185 Typical Per PSU 1.57 217 923 System, two PSUs 3.14 541 1,845
6030/FAS6040 electrical requirements with four Performance Acceleration modules or Flash Cache modules: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 10.15 1,009 3,440 Typical Per PSU 3.03 293 998 System, two PSUs 6.05 585 1,996 200 to 240V Worstcase, single PSU 5.06 969 3,305 Typical Per PSU 1.65 289 985 System, two PSUs 3.29 578 1,969
72
Storage systems
6070/FAS6080 electrical requirements: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 11.68 1,162 3,961 Typical Per PSU 3.63 352 1,201 System, two PSUs 7.25 704 2,401 200 to 240V Worstcase, single PSU 5.76 1,115 3,804 Typical Per PSU 1.96 231 1,182 System, two PSUs 3.91 693 2,363
6070/FAS6080 electrical requirements with five Performance Acceleration modules or Flash Cache modules: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 12.11 1,203 4,104 Typical Per PSU 3.85 376 1,283 System, two PSUs 7.70 752 2,566 200 to 240V Worstcase, single PSU 5.97 1,158 3,950 Typical Per PSU 2.07 368 1,255 System, two PSUs 4.14 736 2,509
73
Storage systems
62xxseries characteristics
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weight Single controller module Controller and I/O expansion module Two controller modules Rack units Height Width Depth (including cable management tray) Clearance dimensions: Frontcooling Rearcooling Front of chassismaintenance Rear of chassismaintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic levelNormal operating conditions at 23 C at sea level 50 F to 104 F (10 C to 40 C) -40 F to 158 F (-40 C to 70 C) 20 to 80% noncondensing 61.3 dBA sound pressure (LpA) 7.5 B sound power (LWAd) All versions two-post rack and four-post rack 6 in. (15.2 cm) 12 in. (30.5 cm) 30 in. (76.2 cm) 36 in. (91.4 cm) 99.2 lbs (45 kg) 125.7 lbs (57 kg) 130.1 lbs (59 kg) 6 10.2 in. (25.86 cm) 17.6 in. (44.68 cm) 29 in. (73.66 cm)
74
Storage systems
Input power frequency, Hz (AC) Input power voltage, V RMS (AC) (auto-ranging)
50 to 60 100-120V or 200-240V
6210 single-controller module electrical requirements: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 5 490 1,673 Typical Per PSU 2.25 215 734 System, two PSUs 4.5 430 1,468 200 to 240V Worstcase, single PSU 2.5 480 1,639 Typical Per PSU 1.15 208 709 System, two PSUs 2.3 415 1,417
6210 two controller modules electrical requirements: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr Typical Per PSU System, two PSUs N/A N/A N/A 200 to 240V Worstcase, single PSU 4.8 930 3,174 Typical Per PSU 2.05 380 1,297 System, two PSUs 4.1 760 2,594
75
6240 controller module and I/O expansion module electrical requirements: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 9.3 920 3,140 Typical Per PSU 3.3 312.5 1,067 System, two PSUs 6.6 625 2,134 200 to 240V Worstcase, single PSU 4.5 875 2,987 Typical Per PSU 1.65 308 1,050 System, two PSUs 3.3 615 2,099
6280 controller module and I/O expansion module electrical requirements: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 9.6 950 3,243 Typical Per PSU 3.5 332.5 1,135 System, two PSUs 6.9 665 2,270 200 to 240V Worstcase, single PSU 4.7 910 3,106 Typical Per PSU 1.75 323 1,101 System, two PSUs 3.5 645 2,202
76
Storage systems
SA systems
This section lists tabulated descriptions of the hardware characteristics, clearance requirements, environmental requirements, and electrical requirements for SA systems.
For details about specific models of systems, see the following topics:
SA200 system on page 78 SA300 system on page 84 SA320 system on page 86 SA600 system on page 88 SA620 system on page 90
77
SA systems
SA200 system
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weight Full (chassis with all disk drives) Empty (chassis-only) Rack units Height Width Depth Clearance dimensions: Frontcooling Rearcooling Front of chassismaintenance Rear of chassismaintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic levelNormal operating conditions at 23 C at sea level Input power frequency, Hz (AC) 50 F to 104 F (10 C to 40 C) -40 F to 140 F (-40 C to 60 C) 20 to 80% noncondensing All versions Two-post rack and four-post rack 6 in. (15.2 cm) 12 in. (30.5 cm) 30 in. (76.2 cm) 36 in. (91.4 cm) 110 lbs (49.9 kg) 91 lbs (41.3 kg) 4 6.9 in. (17.5 cm) 17.6 in. (44.7 cm) 22.5 in. (57.2 cm)
78
SA systems
100-120V or 200-240V
Electrical requirementsone controller module: Input voltage 100 to 120V Typical Worstcase, single PSU 5.64 6.62 6.62 4.40 4.64 5.07 5.07 560 658 658 435 459 504 504 System, two PSUs 4.76 5.92 5.92 4.04 4.36 4.51 4.51 465 583 583 393 425 439 439 Worstcase, single PSU 2.82 3.27 3.27 2.30 2.33 2.46 2.46 547 636 636 439 447 474 474 200 to 240V Typical System, two PSUs 2.65 2.76 2.76 2.07 2.17 2.40 2.40 502 523 523 386 408 447 447
Drives (in GB) Input current measured, A 144 SAS 300 SAS 450 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA Input power measured, W 144 SAS 300 SAS 450 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA
Per PSU 2.38 2.96 2.96 2.02 2.18 2.26 2.26 233 292 292 197 213 220 220
Per PSU 1.33 1.38 1.38 1.04 1.09 1.20 1.20 251 266 266 193 204 224 224
79
144 SAS 300 SAS 450 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA
80
SA systems
Electrical requirementstwo controller modules: Input voltage 100 to 120V Typical Worstcase, single PSU 6.31 7.51 7.51 5.54 5.74 5.91 5.91 628 747 747 549 567 585 585 System, two PSUs 5.68 6.68 6.68 4.98 5.67 5.47 5.47 558 659 659 487 554 536 536 Worstcase, single PSU 3.09 3.73 3.73 2.7 2.89 2.97 2.97 600 728 728 518 561 575 575 200 to 240V Typical System, two PSUs 2.89 3.41 3.41 2.52 2.65 2.77 2.77 550 655 655 474 503 524 524
Drives (in GB) Input current measured, A 144 SAS 300 SAS 450 SAS 250 SATA 500 SATA 750 SATA 1 TB SATA Input power measured, W 144 SAS 300 SAS 450 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA
Per PSU 2.84 3.34 3.34 2.49 2.84 2.74 2.74 279 330 330 244 277 268 268
Per PSU 1.45 1.71 1.71 1.26 1.33 1.39 1.39 275 328 328 237 252 262 262
81
144 SAS 300 SAS 450 SAS 250 SATA 500 SATA 750 SATA 1-TB SATA
82
SA systems
Electrical requirementsone controller module, no disks: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 2.10 205 698 Typical Per PSU 0.90 86.5 295 System, two PSUs 1.80 173 589 200 to 240V Worstcase, single PSU 1.10 198 675 Typical Per PSU 0.50 84 287 System, two PSUs 0.99 168 574
Electrical requirementstwo controller modules, no disks: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 2.62 256 874 Typical Per PSU 1.19 114 387 System, two PSUs 2.37 227 773 200 to 240V Worstcase, single PSU 1.35 250 851 Typical Per PSU 0.62 111 379 System, two PSUs 1.24 222 758
83
SA systems
SA300 system
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weight Rack units Height Width Depth Clearance dimensions: Frontcooling Rearcooling Frontmaintenance Rearmaintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic levelNormal operating conditions at 23 C at sea level Input power frequency, Hz (AC) Input power voltage, V RMS (AC) (auto-ranging) 50 F to 104 F (10 C to 40 C) -40 F to 149 F (-40 C to 65 C) 20 to 80% noncondensing 49 dBA sound pressure (LpA) 50 to 60 100-120V or 200-240V All versions two-post rack and four-post rack 6 in. (15.2 cm) 12 in. (30.5 cm) 30 in. (76.2 cm) 36 in. (91.4 cm) 68 lbs (30.84 kg) 3 5.13 in. (13 cm) 17.73 in. (45.0 cm) 24 in. (60.7 cm)
84
SA systems
SA300 electrical requirements: Input voltage 100 to 120V Typical Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 4.03 400 1,365 System, two PSUs 3.7 362 1,233 Worstcase, single PSU 2.06 387 1,320 200 to 240V Typical System, two PSUs 2.1 355 1,212 Worstcase, single PSU 10.57 423 1,442 -40 to -60V Typical System, two PSUs 9.4 376 1,283
SA300 electrical requirements with two Performance Acceleration modules or Flash Cache modules: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 4.51 449 1,530 Typical Per PSU 2.04 201 685 System, two PSUs 4.08 402 1,369 200 to 240V Worstcase, single PSU 2.29 438 1,493 Typical Per PSU 1.22 208 707 System, two PSUs 2.43 415 1,414
85
SA systems
SA320 system
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weightone controller module Weighttwo controller modules Weightcontroller and I/O expansion module Rack units Height Width Depth Clearance dimensions: Frontcooling Rearcooling Frontmaintenance Rearmaintenance All versions two-post rack and four-post rack 10 in. (25.4 cm) 12 in. (30.5 cm) 30 in. (76.2 cm) 30 in. (76.2 cm) 67.3 lbs (30.5 kg) 79.5 lbs (36.1 kg) 74.5 lbs (33.8 kg) 3 5.12 in. (13.0 cm) 17.61 in. (44.7 cm) 24 in. (60.7 cm)
86
SA systems
Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic levelNormal operating conditions at 23 C at sea level Input power frequency, Hz (AC) Input power voltage, V RMS (AC) (auto-ranging) 50 F to 104 F (10 C to 40 C) -40 F to 158 F (-40 C to 70 C) 20 to 80% noncondensing 55.4 dBA sound pressure (LpA) 7.1 B sound power (LWAd) 50 to 60 100-120V or 200-240V
SA320 electrical requirements with one 256-GB, one 512-GB, or one 1-TB Flash Cache module and one I/O expansion module: Input voltage Input current measured, A Input power measured, W Thermal dissipation, BTU/hr Input current measured, A Input power measured, W
100 to 120V 5.47 547 1,867 2.07 204 697 4.14 408 1,393
200 to 240V 2.73 533 1,820 1.07 199 680 2.13 398 1,359
-40 to -60V 13.55 542 1,850 5.05 202 690 10.1 404 1,379
5.47 547
2.07 204
4.14 408
2.73 533
1.07 199
2.13 398
13.55 542
5.05 202
10.1 404
87
SA systems
SA600 system
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weight Rack units Height Width Depth (including cable management tray) Clearance dimensions: Frontcooling Rearcooling Front of chassismaintenance Rear of chassismaintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic levelNormal operating conditions at 22 C at sea level Input power frequency, Hz (AC) 50 F to 104 F (10 C to 40 C) -40 F to 158 F (-40 C to 70 C) 20 to 80% noncondensing 56.5 dBA sound pressure (LpA) 50 to 60 All versions two-post rack and four-post rack 6 in. (15.2 cm) 12 in. (30.5 cm) 25 in. (63.5 cm) 40 in. (102 cm) 122 lbs (55.34 kg) 6 10.32 in. (26.21 cm) 17.53 in. (44.52 cm) 29 in. (73.66 cm)
88
SA systems
SA600 electrical requirements: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 9.72 966 3,293 Typical Per PSU 2.8 274 935 System, two PSUs 5.6 548 1,870 200 to 240V Worstcase, single PSU 4.84 928 3,166 Typical Per PSU 1.45 266 908 System, two PSUs 2.9 532 1,816
SA600 electrical requirements with five Performance Acceleration modules or Flash Cache modules: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 12.11 1,203 4,104 Typical Per PSU 3.85 376 1,283 System, two PSUs 7.70 752 2,566 200 to 240V Worstcase, single PSU 5.97 1,158 3,950 Typical Per PSU 2.07 368 1,255 System, two PSUs 4.14 736 2,509
89
SA systems
SA620 system
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weight Single controller module Controller and I/O expansion module Two controller modules Rack units Height Width Depth (including cable management tray) Clearance dimensions: Frontcooling Rearcooling Front of chassismaintenance Rear of chassismaintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic levelNormal operating conditions at 23 C at sea level 50 F to 104 F (10 C to 40 C) -40 F to 158 F (-40 C to 70 C) 20 to 80% noncondensing 61.3 dBA sound pressure (LpA) 7.5 B sound power (LWAd) All versions two-post rack and four-post rack 6 in. (15.2 cm) 12 in. (30.5 cm) 25 in. (63.5 cm) 40 in. (102 cm) 99.2 lbs (45 kg) 125.7 lbs (57 kg) 130.1 lbs (59 kg) 6 10.32 in. (26.21 cm) 17.53 in. (44.52 cm) 29 in. (73.66 cm)
90
SA systems
Input power frequency, Hz (AC) Input power voltage, V RMS (AC) (auto-ranging)
50 to 60 100-120V or 200-240V
SA620 controller module and I/O expansion module electrical requirements: Input voltage 100 to 120V Worstcase, single PSU Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 9.6 950 3,243 Typical Per PSU 3.5 332.5 1,135 System, two PSUs 6.9 665 2,270 200 to 240V Worstcase, single PSU 4.7 910 3,106 Typical Per PSU 1.75 323 1,101 System, two PSUs 3.5 645 2,202
91
NearStore systems
This section lists tabulated descriptions of the hardware characteristics, clearance requirements, environmental requirements, and electrical requirements for NearStore systems.
For details about specific models of NearStore systems, see VTL appliances on page 93.
92
NearStore systems
NearStore systems
VTL appliances
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weight Storage engine DS14mk2 AT Fully loaded in system cabinet Rack units Storage engine DS14mk2 AT Height Storage engine DS14mk2 AT Width Storage engine DS14mk2 AT Depth Storage engine DS14mk2 AT Clearance dimensions: Front Rearcooling Bezel Rearmaintenance Vertical rack space Vertical rack space between storage engine and disk shelf Storage engine and DS14mk2 AT 25 in. (63.5 cm) 12 in. (30.5 cm) 1.5 in. (3.8 cm) 40 in. (101.6 cm) 10.5 in. (26.7 cm) 1.5 in. (3.8 cm) 75 lbs (34.019 kg) 77 lbs (35 kg) 999 lbs (453.14 kg) 3 3 5.13 in. (13 cm) 5.25 in. (13.3 cm) 17.68 in. (44.9 cm) 17.6 in. (44.8 cm) 24.33 in. (61.8 cm) 21.75 in. (55.2 cm)
93
Environmental requirements: Operating temperature maximum range Storage engine DS14mk2 AT Storage engine and DS14mk2 AT Storage engine and DS14mk2 AT Storage engine DS14mk2 AT Acoustic level Storage engine DS14mk2 AT Input power frequency, Hz (AC) Input power voltage, V RMS (AC) (autoranging) VTL300/700/1400 electrical requirements: Input voltage 100 to 120V Typical Worstcase, single PSU Input current measured, A Input power measured, W 4.03 400 System, two PSUs 3.7 362 Worstcase, single PSU 2.06 387 200 to 240V Typical System, two PSUs 2.1 355 Worstcase, single PSU 10.57 423 -40 to -60V Typical System, two PSUs 9.4 376 54 dBA @ 23 C 58 dBA at 23 C 50 to 60 100-120V or 200-240V 50 F to 104 F (10 C to 40 C) 41 F to 104 F (5 C to 40 C) 68 F to 77 F (20 C to 25 C) -40 F to 140 F (-40 C to 60 C) 20 to 80% noncondensing
94
NearStore systems
1,365
617
1,233
1,320
606
1,212
1,442
642
1,283
95
Disk shelves
This section lists tabulated descriptions of the hardware characteristics, clearance requirements, environmental requirements, and electrical requirements for disk shelves. Note NearStore VTL system disk shelf information is listed in the section Storage systems on page 18.
For details about specific models of disk shelves, see the following topics:
DS14 series disk shelves on page 97 DS2246 series disk shelves on page 106 DS4243 series disk shelves on page 108
96
Disk shelves
Disk shelves
The following table lists the characteristics and requirements for your hardware. Note The DS14 series includes the DS14, DS14mk2 FC, DS14mk4 FC with an ESH, ESH2, or ESH4 (ESH refers to ESH 2 and ESH4), and DS14mk2 AT. Physical characteristics: Weight With disk drivesDS14mk2 FC, DS14mk4 With disk drivesDS14mk2 AT Empty Rack units Height Width Depth DS14mk2 FC/DS14mk4 FC DS14mk2 AT Clearance dimensions: Frontcooling Rearcooling and maintenance Frontmaintenance All versionstwopost rack and four-post rack 6 in. (15.3 cm) 12 in. (30.5 cm) 25 in. (55.9 cm) 77 lbs (35 kg) 68 lbs (30.8 kg) 50.06 lbs (23 kg) 3 5.25 in. (13.3 cm) 17.6 in. (44.7 cm) 20 in. (50.8 cm) 22 in. (55.2 cm)
97
Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Acoustic levelNormal operating conditions at 23 C at sea level Input power frequency, Hz (AC) Input power voltage, V RMS (AC) (auto-ranging) 41 F to 104 F(5 C to 40 C) -40 F to 140 F(-40 C to 60 C) 20 to 80% noncondensing 58 dB sound pressure (LpA)
50 to 60 100-120V or 200-240V
98
Disk shelves
DS14mk2 AT 7.2K speed, HE PSU electrical requirements: Input voltage 100 to 120V Typical Worst -case, single PSU 2.72 2.51 2.50 271 250 249 924 853 849 System, two PSUs 2.48 2.38 2.34 247 237 230 842 808 784 Worst -case, single PSU 1.28 1.22 1.28 254 243 246 866 829 839 200 to 240V Typical System, two PSUs 1.21 1.17 1.21 240 233 214 819 795 730 682 268 200 79 8.0 3.15 Worst -case, single PSU -40 to -60V Typical System, two PSUs N/A N/A 6.3 N/A N/A 157 N/A N/A 535
Size GB Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 750 1-TB 2-TB 750 1-TB 2-TB 750 1-TB 2-TB
Per PSU 1.24 1.19 1.17 124 119 115 421 404 392
Per PSU 0.61 0.59 0.61 120 117 107 410 398 365
Per PSU
99
DS14mk2 AT 7.2K speed electrical requirements: Input voltage 100 to 120V Typical Worst -case, single PSU 2.79 2.85 2.94 3.42 3.15 279 284 293 341 315 953 968 998 1,163 1,073 System, two PSUs 2.72 3.12 2.9 3.22 3.10 271 310 288 321 308 923 1,058 983 1,095 1,050 Worst -case, single PSU 1.38 1.43 1.43 1.63 1.55 271 283 286 323 309 923 964 975 1,103 1,054 200 to 240V Typical System, two PSUs 1.39 1.56 1.47 1.60 1.56 264 304 283 309 300 900 1,035 964 1,054 1,024 Worst -case, single PSU 7.38 7.4 8.04 8.42 8.33 295 296 322 337 333 1,007 1,009 1,097 1,148 1,136 -40 to -60V Typical System, two PSUs 5.67 5.64 6.22 7.25 6.48 227 226 249 290 259 773 769 848 989 884
Size GB Input current measured, A 250 320 500 750 1-TB Input power measured, W 250 320 500 750 1-TB Thermal dissipation, BTU/hr 250 320 500 750 1-TB
Per PSU 1.36 1.56 1.45 1.61 1.55 136 155 144 161 154 462 529 492 548 525
Per PSU 0.70 0.78 0.74 0.53 0.78 132 152 142 155 150 450 518 482 527 512
Per PSU 2.84 2.82 3.11 6.63 3.24 114 113 125 145 130 387 385 424 495 442
100
Disk shelves
DS14mk2 FC 10K speed electrical requirements: Input voltage 100 to 120V Typical Worst -case, single PSU 3.31 3.56 4.0 330 356 399 1,125 1,215 1,362 System, two PSUs 3.43 3.43 3.89 342 342 387 1,167 1,167 1,320 Worst -case, single PSU 1.61 1.75 1.96 318 348 420 1,084 1,185 1,433 200 to 240V Typical System, two PSUs 1.67 1.73 1.9 323 334 374 1,103 1,140 1,275 Worst -case, single PSU 7.61 9.23 10.54 305 369 422 1,039 1,259 1,437 -40 to -60V Typical System, two PSUs 6.04 7.26 7.45 242 290 298 825 990 1,016
Size GB Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 72 144 288 72 144 288 72 144 288
Per PSU 1.72 1.72 1.95 171 171 194 584 584 660
Per PSU 0.84 0.87 0.95 162 167 187 552 570 638
Per PSU 3.02 3.63 3.73 121 145 149 413 495 508
101
DS14mk2 FC 15K speed electrical requirements: Input voltage 100 to 120V Typical Worst -case, single PSU 3.41 3.96 4.43 4.43 340 395 443 443 1,159 1,347 1,512 1,512 System, two PSUs 3.63 3.75 4.32 4.32 362 373 431 431 1,234 1,272 1,470 1,470 Worst -case, single PSU 1.67 1.93 2.23 2.23 331 383 443 443 1,129 1,245 1,512 1,512 200 to 240V Typical System, two PSUs 1.78 1.88 2.13 2.13 345 365 415 415 1,178 1,305 1,414 1,414 1,370 1,418 1,634 543 563 595 402 416 479 159 165 175 Worst -case, single PSU 10.04 10.40 11.98 -40 to -60V Typical System, two PSUs 7.95 8.25 8.72 N/A 318 330 349 N/A 1,085 1,125 1,190 N/A
Size GB Input current measured, A 72 144 288 450 Input power measured, W 72 144 288 450 Thermal dissipation, BTU/hr 72 144 288 450
Per PSU 1.82 1.88 2.16 2.16 181 187 216 216 617 636 735 735
Per PSU 0.89 0.94 1.07 1.07 173 183 208 208 589 653 707 707
102
Disk shelves
DS14mk4 FC 10K speed electrical requirements: Input voltage 100 to 120V Typical Worst -case, single PSU 2.81 3.44 3.89 279 344 388 953 1,174 1,324 System, two PSUs 3.01 3.36 3.78 299 334 377 1,020 1,140 1,287 Worst -case, single PSU 1.38 1.68 1.90 272 333 376 926 1,137 1,283 200 to 240V Typical System, two PSUs 1.51 1.66 1.87 290 321 364 990 1,095 1,242 Worst -case, single PSU 7.57 9.11 10.24 303 364 410 1,032 1,242 1,397 -40 to -60V Typical System, two PSUs 5.87 7.23 8.07 235 289 323 801 986 1,101
Size GB Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 72 144 288 72 144 288 72 144 288
Per PSU 1.51 1.68 1.89 150 167 189 510 570 644
Per PSU 0.76 0.83 0.94 145 161 182 495 548 621
Per PSU 2.94 3.62 4.04 118 145 162 401 493 551
103
DS14mk4 FC 15K speed electrical requirements: Input voltage 100 to 120V Typical Worst -case, single PSU 3.42 3.54 4.52 4.52 342 354 451 451 1,167 1,208 1,538 1,538 System, two PSUs 3.65 3.45 4.27 4.27 363 344 426 426 1,238 1,174 1,452 1,452 Worst -case, single PSU 1.66 1.73 2.23 2.23 329 343 443 443 1,122 1,170 1,512 1,512 200 to 240V Typical System, two PSUs 1.82 1.73 2.12 2.12 353 334 414 414 1,204 1,140 1,410 1,410 1,394 1,295 1,599 559 514 656 409 380 469 164 151 193 Worst -case, single PSU 10.22 9.49 11.73 -40 to -60V Typical System, two PSUs 8.2 7.54 9.61 N/A 328 301 385 N/A 1,118 1,028 1,311 N/A
Size GB Input current measured, A 72 144 288 450 Input power measured, W 72 144 288 450 Thermal dissipation, BTU/hr 72 144 288 450
Per PSU 1.83 1.73 2.14 2.14 182 172 213 213 619 587 726 726
Per PSU 0.91 0.87 1.06 1.06 177 167 207 207 602 570 705 705
104
Disk shelves
DS14mk4 FC 15K speed, HE PSU electrical requirements: Input voltage 100 to 120V Typical Worst -case, single PSU 2.82 3.39 3.59 3.44 281 358 358 342 959 1,221 1,221 1,166 System, two PSUs 2.66 3.29 3.29 3.24 265 328 328 321 904 1,119 1,119 1,094 Worst -case, single PSU 1.36 1.75 1.75 1.70 270 349 349 332 921 1,191 1,191 1,132 200 to 240V Typical System, two PSUs 1.30 1.61 1.61 1.68 259 321 321 316 883 1,095 1,095 1,077 971 396 285 116 11.4 4.65 Worst -case, single PSU -40 to -60V Typical System, two PSUs N/A N/A N/A 9.3 N/A N/A N/A 232 N/A N/A N/A 791
Size GB Input current measured, A 144 288 450 600 Input power measured, W 144 288 450 600 Thermal dissipation, BTU/hr 144 288 450 600
Per PSU 1.33 1.65 1.65 1.62 133 164 164 161 452 560 560 547
Per PSU 0.65 0.81 0.81 0.84 130 161 161 158 442 548 548 539
Per PSU
105
Disk shelves
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weight With disk drives Without disk drives 49 lbs (22.2 kg) 34 34.6 lbs (15.7 kg) Empty Rack units Height Width Depth Clearance dimensions: Frontcooling Rearcooling and maintenance Frontmaintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Altitude operating non-operating operating non-operating Input power frequency, Hz (AC) 50 F to 104 F (10 C to 40 C) -40 F to 158 F (-40 C to 70 C) 20 to 80% noncondensing 10 to 95% noncondensing 0 to 10,000 ft (0 to 3,045 m) -1,000 to 40,000 ft (-305 to 12,192 m) 50 to 60 All versionstwopost rack and four-post rack 6 in. (15.3 cm) 12 in. (30.5 cm) 25 in. (55.9 cm) 17.4 lbs (7.9 kg) 2 3.4 in. (8.5 cm) 19 in. (48.0 cm) 19.1 in. (48.4 cm)
106
Disk shelves
Acoustic
SAS drives
Electrical requirementsSAS drives: 200 to 240V (200V actual) Typical Per PSU 1.38 1.39 137 134 468 456 System, two PSUs 2.76 2.77 274 267 936 912 Worstcase, single PSU 2.29 2.29 420 418 1,434 1,427 Typical Per PSU 0.79 0.82 135 133 461 454 System, two PSUs 1.58 1.64 270 266 922 908
Input voltage
100 to 120V Worstcase, single PSU 4.28 4.22 428 422 1,461 1,441
Size (GB) Input current measured, A Input power measured, W Thermal dissipation, BTU/hr 450 600 450 600 450 600
107
Disk shelves
The following table lists the characteristics and requirements for your hardware. Physical characteristics: Weight With disk drives Without disk drives Empty Rack units Height Width Depth Clearance dimensions: Frontcooling Rearcooling and maintenance Frontmaintenance Environmental requirements: Operating temperature range Non-operating temperature range Relative humidity Altitude operating non-operating operating non-operating Input power frequency, Hz (AC) 50 F to 104 F (10 C to 40 C) -40 F to 158 F (-40 C to 70 C) 20 to 80% noncondensing 10 to 95% noncondensing 0 to 10,000 ft (0 to 3,045 m) -1,000 to 40,000 ft (-305 to 12,192 m) 50 to 60 All versionstwopost rack and four-post rack 6 in. (15.3 cm) 12 in. (30.5 cm) 25 in. (55.9 cm) 110 lbs (49.9 kg) 53.7 lbs (24.4kg) 21.1 lbs (9.6 kg) 4 7 in. (17.8 cm) 19 in. (48.3 cm) 24 in. (61 cm)
108
Disk shelves
Acoustic
Electrical requirementsSAS drives: 200 to 240V (200V actual) Typical Worstcase, two PSUs 5.5 6.00 5.98 550 600 595 1,877 2,047 2,028 Per PSU pair 3.0 3.15 2.86 300 315 284 1,024 1,075 917 Sys., four PSUs 6.0 6.30 5.71 600 630 567 2,048 2,150 1,833 Worstcase, two PSUs 2.8 3.00 2.99 560 600 584 1,911 2,047 1,991 Typical Per PSU pair 1.5 1.60 1.44 300 320 274 1,024 1,092 933 Sys., four PSUs 3.0 3.20 2.87 600 640 547 2,048 2,184 1,865 1,908 2,054 1,027 1,101 559 602 301 323 Worstcase, two PSUs 2.6 2.80 200 to 240V (215V actual) Typical Per PSU pair 1.4 1.50 Sys., four PSUs 2.8 3.00 N/A 602 645 N/A 2,055 2,201 N/A
Input voltage
100 to 120V
Size (GB) Total input current measured, A Total input power measured, W Total thermal dissipation, BTU/hr 300 450 600 300 450 600 300 450 600
109
Electrical requirementsSATA drives: 200 to 240V (200V actual) Typical Worstcase, single PSU 4.30 4.41 4.72 4.95 1.96 430 439 469 495 196 1,467 1,499 1,599 1,688 669 Sys., two PSUs 4.40 4.42 4.62 4.60 1.63 440 438 458 456 163 1,501 1,495 1,561 1,555 557 Worstcase, single PSU 2.10 2.21 2.42 2.43 1.0 420 429 470 476 200 1,433 1,465 1,602 1,624 683 Typical Sys., two PSUs 2.20 2.27 2.42 2.38 0.9 440 424 456 448 180 1,501 1,448 1,554 1,528 615 700 308 615 205 1,395 1,395 90 771 771 180 1,542 1,542 N/A 0.95 409 409 0.42 226 226 0.84 452 452 N/A Worstcase, single PSU 1.90 1.90 200 to 240V (215V actual) Typical Sys., two PSUs 2.10 2.10 N/A
Input voltage
100 to 120V
Size (GB) Input current measured, A 500 1-TB 2-TB 3-TB 100 (SSD) Input power measured, W 500 1-TB 2-TB 3-TB 100 (SSD) Thermal dissipation, BTU/hr 500 1-TB 2-TB 3-TB 100 (SSD)
Per PSU 2.20 2.21 2.31 2.30 0.82 220 219 229 228 82 751 748 781 518 279
Per PSU 1.10 1.14 1.21 1.19 0.45 220 212 228 224 90 751 724 777 764 308
110
Disk shelves
System cabinets
This section lists tabulated descriptions of the hardware characteristics, clearance requirements, environmental requirements, and electrical requirements for NetApp System Cabinets.
42U system cabinet characteristics on page 112. 42U system cabinet, deep characteristics on page 113
For details about the supported PDUs, see the following section.
111
System cabinets
42U cabinets
The following table lists the characteristics and requirements for the 42U system cabinet. Note The system cabinet uses passive air flow for cooling.
Physical characteristics: Weight Loaded Empty (no rails installed) PDU weight 20A PDU x 4 PDU per cabinet 30A PDUsingle-Phase x 2 PDU per cabinet 30A PDUsingle-Phase x 4 PDU per cabinet 3-Phase 30A PDU x 2 PDU per cabinet Height Cabinet Crate Width Cabinet Crate Depth Cabinet Crate Up to 1,500 lbs (Up to 680 kg) 287 lbs (130.2 kg) 7.8 lbs (3.54 kg) per PDU 13.4 lbs (6.08 kg) per PDU 7.8 lbs (3.54 kg) per PDU 17.0 lbs (7.7 kg) per PDU (IEC) 16.7 lbs (7.6 kg) per PDU (NEMA) 78.7 in. (200 cm) 85.8 in. (218 cm) 23.6 in. (60 cm) 29.8 in. (75.7 cm) 37.4 in. (95 cm) 48 in. (121.9 cm)
112
System cabinets
Clearance dimensions: Front Rear Top Environmental requirements: Operating temperature maximum range Operating temperature recommended range Non-operating temperature range Relative humidity 32 F to 104 F (0 C to 40 C) 68 F to 77 F (20 C to 25 C) -40 F to 149 F (-40 C to 65 C) 10 to 90% noncondensing 30 in. (76.3 cm) 30 in. (76.3 cm) 12 in. (30 cm)
The following table lists the characteristics and requirements for the 42U system cabinet, deep. Note The system cabinet uses passive air flow for cooling. Physical characteristics: Weight Loaded with system cabinetship weight Loaded with system cabinetstatic weight Empty Up to 1,807 lbs (820 kg) Up to 2,307 lbs (1,046 kg) 307 lbs (138 kg)
113
PDU weight
20A PDU x 4 PDU per cabinet 30A PDUsingle-Phase x 2 PDU per cabinet 30A PDUsingle-Phase x 4 PDU per cabinet 3-Phase 30A PDU x 2 PDU per cabinet
7.8 lbs (3.54 kg) per PDU 13.4 lbs (6.08 kg) per PDU 7.8 lbs (3.54 kg) per PDU 17.0 lbs (7.7 kg) per PDU (IEC) 16.7 lbs (7.6 kg) per PDU (NEMA) 78.7 in. (200 cm) 85.8 in. (218 cm) 23.6 in. (60 cm) 29.8 in. (75.7 cm) 44.3 in. (112.5 cm) 51 in. (129.5 cm)
Height
Cabinet Crate
Width
Cabinet Crate
Depth
Cabinet Crate
Clearance dimensions: Front Rearrecommended Note The rear door is split. Actual minimum rear clearance is approximately 1/2 the recommendation. Top Environmental requirements: Operating temperature maximum range Operating temperature recommended range
114
32 F to 104 F (0 C to 40 C) 68 F to 77 F (20 C to 25 C)
System cabinets
The following table lists the floor space needed to unpack the system cabinet from the shipping crate. Shipping crate ramp length Clearance beyond the ramp for cabinet mobility Rear clearance to remove the crate shell Shipping crate height Shipping crate width Shipping crate pallet depth Shipping pallet width Shipping pallet and crate height 80 in. (203.2 cm) 72 in. (182.9 cm) 51 in. (129.5 cm) 80 in. (203.2 cm) 30 in. (76.2 cm) 57 in. (144.8 cm) 42 in. (106.6 cm) 86 in. (218.4 cm)
The system cabinets can have one of the PDU configurations listed in the following table.
115
PDU desc. Singlephase 20A with NEMA power cords Singlephase 20A with IEC or Australia power cords Singlephase 30A NEMA
PDU current capacity in amps per side (redund ant power capacity 32
Approx. max. available power per cabinet (current limit x line voltage) 6.7 kW @ 208V
# of power cords 2 per side, detachable input cord; PDU limited to 16A
32
7.4 kW @ 230V
25,120
X8712R6
PDU, 1Phase, 16 Outlet, 30A, NEMA, R6 PDU, 1Phase, 8 Outlet, 30A, NEMA, R6
24
5.0 kW @ 208V
17,038
16
X8712BR6
48
10.0 kW @ 208V
34,075
16
116
System cabinets
Packing list desc. PDU, 1Phase, 12 Outlet, 30A, NEMA, R6 PDU, 1Phase, 16 Outlet, 30A, IEC, R6 PDU, 1Phase, 8 Outlet, 30A, IEC, R6 PDU, 1Phase, 12 Outlet, 30A, IEC, R6
PDU current capacity in amps per side (redund ant power capacity 48
Approx. max. available power per cabinet (current limit x line voltage) 10.0 kW @ 208V
X8713R6
30
6.9 kW @ 230V
23,550
16
1 per side; tethered; limited to 30A by 2x 15A breakers 2 per side; 4 plugs per cabinet; limited to 24A input/PDU 2 per side
X8713BR6
48
11.0 kW @ 230V
37,680
16
X8713CR6
64
14.7 kW @ 230V
50,239
24
117
Packing list desc. PDU, 3phase, 24Outlet, 30A, NEMA, 4-Pin, R6 PDU, 3phase, 24Outlet, 30A, NEMA, 5-Pin, R6 PDU, 3phase, 24Outlet, 32A, IEC, R6
PDU current capacity in amps per side (redund ant power capacity 41.5
Approx. max. available power per cabinet (current limit x line voltage) 8.6 kW @ 208V
X8720A -R6
X8718A -R6
96
22.1 kW @ 230V
75,359
24
1 per side
Note All PDUs have 200 to 240V input voltage and input frequency of 50/60 Hz. Note For complete power redundancy, each PDU must be connected to a dedicated circuit. See Balancing the load across PDUs on page 10 for PDU and PSU connection examples.
118
System cabinets
Third-party switches
See your switch documentation for height, dimensions, weight, clearance, environmental, and electrical requirements.
119
120
Third-party switches
A
Documentation revision for feature date April 2007
The following table lists and describes the history of changes made to this manual. When a change is implemented, it applies to the release in which it was implemented and all subsequent releases, unless otherwise specified.
Feature updates Added specifications for ESH4 and DS14mk4 FC disk shelves.
Feature first implemented in Data ONTAP 6.4.4 or higher and Data ONTAP 6.5.1 or higher Data ONTAP 7.2.1 or higher
Revised power figures for FAS250, FAS270, FAS3000 series systems, and FAS60xx series systems. Removed legacy equipment. Implementation of Feature Update Record (this chapter). Added FAS2020 and FAS2050 information Added diskless FAS2050 information. Added RJ-45 to DB-9 console port adapter and ASCII terminal pinout tables. Added FAS6040 and FAS6080 information. Added information to DS14 disk shelf section for different drive capacities. Added diskless FAS2050 single controller module power requirements. Modified PDU information for 42U System Cabinet.
December 2007
121
Feature updates Added SA systems information. Added power information for PDUs deployed in Europe. Added FAS31xx and V31xx series system information. Added Performance Acceleration Module I information Removed Inrush data from all platform and disk shelf tables Added FAS3160 information. Added DC power figures to FAS31xx series systems Add DS4243 information Add Performance Acceleration Module II (Flash Cache) information Modified DS4243 table heading for SAS drives Added PDU load balancing illustrations Updated 30A, 12-outlet PDU information Added HE PSU electrical information Corrected DS4243 environmental data Added DS2246, FAS32xx, and 42U System Cabinet, Deep information
Feature first implemented in Data ONTAP 7.2.5 or higher and Data ONTAP 7.3 or higher
June 2008
Data ONTAP 7.2.6 N/A Data ONTAP 7.3.2 Data ONTAP 8.0
October 2009
N/A
March 2010
September 2010
Added FAS2020 600 GB and 2-TB disk electrical information Added FAS62xx data Corrected FAS32xx power data. Removed FAS/V prefixes to all systems from 30xx onward.
November 2010
February 2011
122
Feature updates Updated DS2246 electical information Added 1TB FlashCache information
Added 3TB Disk information for DS4243 disk shelf Updated Acoustic information for FAS20xx, FAS30xx, FAS3100, FAS32xx, FAS60xx, FAS62xx, DS14, SA2246, abd DS4243 Added ATTO FireBridge 6500N information Added 2240-2 information Added 2240-4 information Added 450-GB and 650-GB drive information to 2240-x section Data ONTAP 8.1 Data ONTAP 8.1 Data ONTAP 8.1
July 2011
123
124
Copyright information
Copyright 1994-2011 NetApp, Inc. All rights reserved. Printed in the U.S.A. No part of this document covered by copyright may be reproduced in any form or by any meansgraphic, electronic, or mechanical, including photocopying, recording, taping, or storage in an electronic retrieval systemwithout prior written permission of the copyright owner. Software derived from copyrighted NetApp material is subject to the following license and disclaimer: THIS SOFTWARE IS PROVIDED BY NETAPP AS IS AND WITHOUT ANY EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, WHICH ARE HEREBY DISCLAIMED. IN NO EVENT SHALL NETAPP BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. NetApp reserves the right to change any products described herein at any time, and without notice. NetApp assumes no responsibility or liability arising from the use of products described herein, except as expressly agreed to in writing by NetApp. The use or purchase of this product does not convey a license under any patent rights, trademark rights, or any other intellectual property rights of NetApp. The product described in this manual may be protected by one or more U.S.A. patents, foreign patents, or pending applications. RESTRICTED RIGHTS LEGEND: Use, duplication, or disclosure by the government is subject to restrictions as set forth in subparagraph (c)(1)(ii) of the Rights in Technical Data and Computer Software clause at DFARS 252.277-7103 (October 1988) and FAR 52-227-19 (June 1987).
126
Copyright information
Trademark information
NetApp, the NetApp logo, Network Appliance, the Network Appliance logo, Akorri, ApplianceWatch, ASUP, AutoSupport, BalancePoint, BalancePoint Predictor, Bycast, Campaign Express, ComplianceClock, Cryptainer, CryptoShred, Data ONTAP, DataFabric, DataFort, Decru, Decru DataFort, DenseStak, Engenio, Engenio logo, E-Stack, FAServer, FastStak, FilerView, FlexCache, FlexClone, FlexPod, FlexScale, FlexShare, FlexSuite, FlexVol, FPolicy, GetSuccessful, gFiler, Go further, faster, Imagine Virtually Anything, Lifetime Key Management, LockVault, Manage ONTAP, MetroCluster, MultiStore, NearStore, NetCache, NOW (NetApp on the Web), Onaro, OnCommand, ONTAPI, OpenKey, PerformanceStak, RAID-DP, ReplicatorX, SANscreen, SANshare, SANtricity, SecureAdmin, SecureShare, Select, Service Builder, Shadow Tape, Simplicity, Simulate ONTAP, SnapCopy, SnapDirector, SnapDrive, SnapFilter, SnapLock, SnapManager, SnapMigrator, SnapMirror, SnapMover, SnapProtect, SnapRestore, Snapshot, SnapSuite, SnapValidator, SnapVault, StorageGRID, StoreVault, the StoreVault logo, SyncMirror, Tech OnTap, The evolution of storage, Topio, vFiler, VFM, Virtual File Manager, VPolicy, WAFL, Web Filer, and XBB are trademarks or registered trademarks of NetApp, Inc. in the United States, other countries, or both. IBM, the IBM logo, and ibm.com are trademarks or registered trademarks of International Business Machines Corporation in the United States, other countries, or both. A complete and current list of other IBM trademarks is available on the Web at www.ibm.com/legal/copytrade.shtml. Apple is a registered trademark and QuickTime is a trademark of Apple, Inc. in the U.S.A. and/or other countries. Microsoft is a registered trademark and Windows Media is a trademark of Microsoft Corporation in the U.S.A. and/or other countries. RealAudio, RealNetworks, RealPlayer, RealSystem, RealText, and RealVideo are registered trademarks and RealMedia, RealProxy, and SureStream are trademarks of RealNetworks, Inc. in the U.S.A. and/or other countries. All other brands or products are trademarks or registered trademarks of their respective holders and should be treated as such. NetApp, Inc. is a licensee of the CompactFlash and CF Logo trademarks. NetApp, Inc. NetCache is certified RealSystem compatible.
128
Trademark information
Index
C
cable requirements 1000BASE-T TOE NIC 7 10G BASE-SR NIC 8 cabling to system cabinet PDUs 10, 12 calculating volt-amps 19 clearance dimensions 42U system cabinet deep 114 42-unit cabinet 113 DS14 series disk shelf 97 DS14mk2 AT disk shelf 93 DS2246 series disk shelf 106 DS4243 series disk shelf 108 FAS2020 series system 27 FAS2040 series system 33 FAS2050 series system 39 FAS2240-2 series system 45 FAS2240-4 series system 49 FAS250 system 21 FAS270 system 23 FAS30xx series system 54 FAS31xx series system 58 FAS32xx series system 66 FAS60xx series system 71 FAS62xx series system 74 FAS900 series system 25 GF270c gateway 23 GF900 series gateway 25 NearStore VTL appliance 93 SA200 system 78 SA300 system 84 SA320 system 86 SA600 system 88 SA620 system 90 V30xx series system 54 V31xx series system 58 V32xx series system 66 V60xx series system 71 V62xx series system 74 Console ASCII terminal pinout 16 RJ-45 to DB-9 adapter pinout 16
Index
D
disk shelves DS14 series 97 DS14mk4 FC 97 DS2246 series 106 DS4243 series 108 DS14 series disk shelf electrical requirements DS14mk2 AT 7.2 K speed 100 DS14mk2 AT 7.2 K speed, HE PSU 99 DS14mk2 FC 10 K speed 101 DS14mk2 FC 15 K speed 102 DS14mk4 FC 10 K speed 103 DS14mk4 FC 15 K speed 104 DS14mk4 FC 15 K speed, HE PSU 105 DS2246 series disk shelf electrical requirements DS2246 SAS drives 107 DS4243 series disk shelf electrical requirements DS4243 SAS drives 109 DS4243 SATA drives 110 DS4243 SATA SSD drives 110 DS4243 series disk shelves 110
E
electrical requirements 42-unit cabinet 115 calculating volt-amps (VA) 19 DS14mk2 AT 7.2 K speed 100 DS14mk2 AT 7.2 K speed, HE PSU 99 DS14mk2 AT disk shelf in a VTL appliance
94
DS14mk2 FC 10 K speed 101 DS14mk2 FC 15 K speed 102 DS14mk4 FC 10 K speed 103 DS14mk4 FC 15 K speed 104 DS14mk4 FC 15 K speed, HE PSU 105 DS2246 SAS drives 107 DS4243 SAS drives 109 DS4243 SATA drives 110 DS4243 SATA SSD drives 110 FA3270 system 69 FAS2020 series system 28, 30, 32
129
FAS2040 series system 34, 36, 38 FAS2050 series system 40, 42, 44 FAS2240-2 system with one controller module with a 10 GbE mezzanine card and either 450-GB or 600-GB disks 46 FAS2240-2 system with one controller module with a FC mezzanine card and either 450-GB or 600-GB disks 46 FAS2240-2 system with one controller module, no mezzanine card and either 450-GB or 600-GB disks 47 FAS2240-2 system with two controller modules with a 10GbE mezzanine card and either 450-GB or 600-GB disks 48 FAS2240-2 system with two controller modules with a FC mezzanine card and either 450-GB or 600-GB disks
FAS3040 system 55 FAS3050 system 56 FAS3070 system 57 FAS3070 system with one Performance Acceleration module or Flash Cache module 57 FAS3140 system 59 FAS3140 system with four Performance Acceleration modules or Flash Cache modules 61 FAS3140 system with two Performance Acceleration modules or Flash Cache modules 60 FAS3160 system with four Performance Acceleration modules or Flash Cache modules 63 FAS3160 system with one controller module
61
FAS3160 system with two controller modules
47
FAS2240-2 system with two controller modules, no mezzanine card and either 450-GB 600-GB disks 48 FAS2240-4 system with one controller module with a 10GbE mezzanine card and either 1-TB, 2-TB, or 3-TB disks 50 FAS2240-4 system with one controller module with a FC mezzanine card and either 1-TB, 2-TB, or 3-TB disks 50 FAS2240-4 system with one controller module, no mezzanine card and either 1-TB, 2-TB, or 3-TB disks 51 FAS2240-4 system with two controller modules with a 10GbE mezzanine card and either 1-TB, 2-TB, or 3-TB disks 52 FAS2240-4 system with two controller modules with a FC mezzanine card and either 1-TB, 2-TB, or 3-TB disks
62
FAS3160 system with two Performance Acceleration modules or Flash Cache modules 62 FAS3170 system 63 FAS3170 system with eight Performance Acceleration modules or Flash Cache modules 65 FAS3170 system with four Performance Acceleration modules or Flash Cache modules 64 FAS3170 system with two controller modules
64
FAS3210system 67, 68 FAS3270 system 70 FAS6030/FAS6040 system 68, 69, 72 FAS6030/FAS6040 system with four Performance Acceleration modules or Flash Cache modules 72, 75 FAS6070/FAS6080 system 73 FAS6070/FAS6080 system with five Performance Acceleration modules or Flash Cache modules 73 FAS6210/FAS6210 system with a single controller module 75
51
FAS2240-4 system with two controller modules, no mezzanine card and either 1-TB, 2-TB, or 3-TB disks 52 FAS250 system 22 FAS270 system 24 FAS3020 system 55
130
Index
FAS6240 system with a single controller module and single I/O expansion module 76 FAS6280 system with a single controller module and single I/O expansion module 76 FAS900 series system 26 GF270c gateway 24 GF900 series gateway 26 N6240 system 68 NearStore VTL appliance 94 SA200 system 79, 81, 83 SA300 system 85 SA320 system 87 SA600 system 89 SA620 system with a single controller module and single I/O expansion module 91 table heading definitions 19 V3020 system 55 V3040 system 55 V3050 system 56 V3070 system 57 V3070 system with one Performance Acceleration module or Flash Cache module 57 V3140 system 59 V3140 system with four Performance Acceleration modules or Flash Cache modules 61 V3140 system with ttwo Performance Acceleration modules or Flash Cache modules 60 V3160 system with four Performance Acceleration modules or Flash Cache modules 63 V3160 system with one controller module 61 V3160 system with two Performance Acceleration modules or Flash Cache modules 62 V3160 system with with two controller modules 62 V3170 system 63 V3170 system with eight Performance Acceleration modules or Flash Cache modules 65
131
V3170 system with four Performance Acceleration modules or Flash Cache modules 64 V3170 system with two controller modules 64 V3210 system 67, 68 V3270 system 69, 70 V6030 system 68, 69, 72 V6030 system with four Performance Acceleration modules or Flash Cache modules 72, 75 V6070 system 73 V6070 system with five Performance Acceleration modules or Flash Cache modules 73 V6210 system with a single controller module
75
V6240 gateway 68 V6240 system with a single controller module and single I/O expansion module 76 V6280 system with a single controller module and single I/O expansion module 76 environmental requirements DS14 series disk shelf 98 DS14mk2 AT disk shelf 94 DS2246 series disk shelf 106 DS4243 series disk shelf 108 FAS2020 series system 27 FAS2040 series system 33 FAS2050 series system 39 FAS2240-2 series system 45 FAS2240-4 series system 49 FAS250 system 22 FAS270 system 23 FAS30xx series system 54 FAS31xx series system 58 FAS32xx series system 66 FAS60xx series system 71 FAS62xx series system 74 FAS900 series system 26 GF270c gateway 23 GF900 series gateway 26 NearStore VTL appliance 94 SA200 system 78 SA300 system 84 SA600 system 88
Index
SA620 system 90 V30xx series system 54 V31xx series system 58 V32xx series system 66 V60xx series system 71 V62xx series system 74 environmental requirementsSA320 system 87
F
fan speed, ambient temperature impact on energy savings 19
G
gFiler gateways GF270c 23 GF900 series 25
H
HE PSU DS14mk2 AT 7.2 K speed electrical requirements 99 DS14mk4 FC 15 K speed electrical requirements 105
L
load balancing in system cabinets single component 10 two components 12
N
NearStore systems, NearStore VTL appliance 93
DS14 series disk shelf 97 DS14mk2 AT 93 DS2246 series disk shelf 106 DS4243 series disk shelf 108 FAS2020 system 27 FAS2040 system 33 FAS2050 series system 39 FAS2240-2 series system 45 FAS2240-4 series system 49 FAS250 system 21 FAS270 system 23 FAS30xx series system 54 FAS31xx series system 58 FAS32xx series system 66 FAS6000 series system 71 FAS62xx series system 74 FAS900 series system 25 GF270c gateway 23 GF900 series gateway 25 N7000 series system 71 NearStore VTL appliance 93 SA200 system 78 SA300 system 84 SA320 system 86 SA600 system 88 SA620 system 90 V30xx series system 54 V31xx series system 58 V32xx series system 66 V6000 series system 71 V62xx series system 74 V7000 series system 71 Pinout ASCII terminal pinout 16 RJ-45 to DB-9 console port adapter pinout 16
P
PDU 20A general specifications - IEC 116 general specifications - NEMA 116 physical characteristics 42U system cabinet deep 113 42-unit cabinet 112
132
S
SSD drives 110 storage system FAS2020 27 FAS2040 33 FAS2050 39 FAS2240-2 series 45 FAS2240-4 series 49
Index
FAS250 21 FAS270 23 FAS30xx series 54 FAS31xx series 58, 66 FAS900 series 25 SA200 78 SA300 84 SA320 system 86 SA600 system 88 system cabinet load balancing with a single component 10 load balancing with two components 12
T
temperature ambient range and electronics life 19 fan speed and energy savings relationship 19 tools and equipment required 2
U
unpacking space requirements 42U system cabinet deep 115
V
volt-amps, calculating 19 V-Series systems V31xx 58, 66, 86 V6000 27, 39, 58, 74
133
Index
134
Index