M 208 Content
M 208 Content
M 208 Content
Air - CIeaning
The third AQ control strategy is to clean the air. Air cleaning is usually most effective when
used in conjunction with either source control or ventilation; however, it may be the only
approach when the source of pollution is outside of the building. Efficient air filtration prevents
fouling of the system and is of special importance in urban areas, where damage is likely to be
caused to decorations and fittings by discoloration owing to airborne dust particles. n order to
obtain maximum filtration efficiency with the minimum capital and maintenance expenditure, the
utmost care should be given to the location of the air intake in relation to the prevailing wind,
the position of chimneys and the relative atmospheric dust concentration in the environs of the
building.
Airborne dust and dirt can be generated within the building from the personnel and their
movements as well as by machines, such as those used for card sorting. The degree of
filtration necessary will depend on the use of the building or the conditioned space. The choice
of filtration systems will depend on the degree of contamination of the air and on the cleanliness
required. A combination of filter types may well give the best service and minimum operation
costs. There are four technologies that remove contaminants from the air:
1) Particulate filtration
2) Electrostatic precipitation
3) Negative ion generation
4) Gas sorption
The first three approaches are designed to remove particulates, while the fourth is designed to
remove gases.
!articulate filtration:
Particulate Filtration removes suspended liquid or solid materials whose size, shape and mass
allow them to remain airborne for the air velocity conditions present. Filters are available in a
range of efficiencies, with higher efficiency indicating removal of a greater proportion of
particles and of smaller particles. Moving to medium efficiency pleated filters is advisable to
improve AQ and increase protection for equipment. However, the higher the efficiency of the
filter, the more it will increase the pressure drop within the air distribution system and reduce
total airflow (unless other adjustments are made to compensate). t is important to select an
appropriate filter for the specific application and to make sure that the HVAC system will
continue to perform as designed. Filters are rated by different standards (e.g., arrestance and
dust spot) which measure different aspects of performance. The HEPA (high efficiency
particulate air) filters are recommended for maintaining absolutely clean environments.
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 20 oI 52
"lectrostatic Precipitation:
Electrostatic Precipitation is another type of particulate control. t uses the attraction of charged
particles to oppositely charged surfaces to collect airborne particulates. n this process, the
particles are charged by ionizing the air with an electric field. The charged particles are then
collected by a strong electric field generated between oppositely-charged electrodes. This
provides relatively high efficiency filtration of small respirable particles at low air pressure
losses.
Electrostatic precipitators may be installed in air distribution equipment or in specific usage
areas. As with other filters, they must be serviced regularly. Note, however, that electrostatic
precipitators produce some ozone. Because ozone is harmful at elevated levels, EPA has set
standards for ozone concentrations in outdoor air, and NOSH and OSHA have established
guidelines and standards, respectively, for ozone in indoor air. The amount of ozone emitted
from electrostatic precipitators varies from model to model.
#egative ion generators:
Negative ion generators use static charges to remove particles from the indoor air. When the
particles become charged, they are attracted to surfaces such as walls, floors, table tops,
draperies, and occupants.
Some designs include collectors to attract the charged particles back to the unit.
Negative ion generators are not available for installation in ductwork, but are sold as portable or
ceiling-mounted units. As with electrostatic precipitators, negative ion generators may produce
ozone, either intentionally or as a by-product of use.
$as sorption:
Fumes and smells can be removed from air by chemical processes such as "gas sorption
which control compounds that behave as gases rather than as particles (e.g., gaseous
contaminants such as formaldehyde, sulfur dioxide, ozone, and oxides of nitrogen). These may
be essential when the ambient air is heavily polluted, although it may be possible to limit
operating costs by minimizing the thermal loads caused by the introduction of large quantities of
fresh air. The decision to use odour removing equipment will normally be made on economic
grounds, but the arguments in its favor will be increased by the currently rising cost of energy.
Once this equipment is installed, it should be regularly serviced to ensure satisfactory
performance.
Gas sorption involves one or more of the following processes with the sorption material (e.g.,
activated carbon, chemically treated active clays):
1) A chemical reaction between the pollutant and the sorbent,
2) A binding of the pollutant and the sorbent, or
3) Diffusion of the contaminant from areas of higher concentration to areas of lower
concentration
Gas sorption units are installed as part of the air distribution system. Each type of sorption
material performs differently with different gases. Gas sorption is not effective for removing
carbon monoxide. There are no standards for rating the performance of gaseous air cleaners,
making the design and evaluation of such systems problematic.
Operating expenses of these units can be quite high, and the units may not be effective if there
is a strong source nearby.
Use carbon dioxide sensors for demand controI ventiIation:
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 21 oI 52
Carbon dioxide-based demand- controlled ventilation systems vary the ventilation rate based
on carbon dioxide (CO
2
) levels in the building. For spaces with extreme variations in
occupancy, such as banquet halls or meeting rooms, carbon dioxide sensors located in each
zone adjacent to the room thermostat or in the common return air automatically control the
amount of outside air. The controls are set such that the CO
2
level do not exceed ASHRAE
permissible levels of 1000ppm.
The equation for calculating outdoor quantities using carbon dioxide measurements is:
Where:
Cs= ppm of carbon dioxide in the mixed air (if measured at an air handler) or in supply air (if
measured in a room)
Cr= ppm of carbon dioxide in the return air
Co= ppm of carbon dioxide in the outdoor air
The auto-controller ensures that the increased ventilation is supplied only when required or
needed for higher occupancies. This benefit in the energy cost savings because of reduced
cooling and heating of outdoor air during reduced occupancy rates.
BuiIding Pressurization
A common cause of AQ problems in hot and humid climates is negative building pressure.
Negative building pressure can occur through the improper design and operation of the exhaust
systems in a building. Operating exhaust fans without the outside air being compensated
through the air-handling system will result in negative pressure in the building. Negative
pressure in a building allows uncontrolled infiltration through doors and the exterior envelope of
the building. This will typically make the building feel drafty and difficult to heat in cold climates
and muggy or musty in hot and humid climates since unconditioned outside air is being
constantly introduced into the building through uncontrolled infiltration.
The basic principle of air movement from areas of relatively higher pressure to areas of
relatively lower pressure can produce many patterns of contaminant distribution, including:
1. Local circulation in the room containing the pollutant source
2. Air movement into adjacent spaces that are under lower pressure (Note: even if two rooms
are both under positive pressure compared to the outdoors, one room is usually at a lower
pressure than the other)
3. Recirculation of air within the zone containing the pollutant source or in adjacent zones
where return systems overlap
4. Movement from lower to upper levels of the building
5. Air movement into the building through either infiltration of outdoor air or re-entry of exhaust
air
The HVAC system is generally the predominant pathway and driving force for air movement
and distribution of contaminants. The large buildings are divided into multiple zones each
having independent HVAC system or control. But still the contaminants can flow from one zone
to another because of building obstructions and people movement. For example, as air moves
from supply registers or diffusers to return air grilles, it is diverted or obstructed by partitions,
walls, and furnishings, and redirected by openings that provide pathways for air movement. On
a localized basis, the movement of people has a major impact on the movement of pollutants.
Some of the pathways change as doors and windows open and close. t is useful to think of the
entire building the rooms and the connections (e.g., chases, corridors, stairways, elevator
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 22 oI 52
shafts) between them as part of the air distribution system. Air moves from areas of higher
pressure to areas of lower pressure through any available openings. A small crack or hole can
admit significant amounts of air if the pressure differentials are high enough (which may be very
difficult to assess). Theoretically, one-inch water gauge pressure is equivalent to wind velocity
of 4005 feet per minute (~45 miles/hr). The amount of expected leakage can be calculated from
the following:
Leakage in CFM = x 4005
Assuming 0.05 wg,
Leakage = 0.223 x 4005
= 895 feet per minute
With a total of square feet opening size
Leakage = x 895 = ~450 CFM
With higher pressurization the leakage velocity, leakage rates and the processing costs shall
also increase. The room pressure should be limited to 0.03 to 0.05 (~0.75 to 1.25mm) as
pressure above this not only entails high capital costs but also increases the operating costs.
Positive pressurization can be maintained only if the sealing integrity of the building is
maintained. The building should be air tight for low air leakage performance. There are areas
with in the facility that require negative exhausts such as toilets, pantry, laboratory or battery
room but these are controlled ventilation areas having fixed amount of exhaust. Uncontrolled
leakages areas in the building are door undercuts; pass through, walls, ceilings and duct joints
etc; that should be restricted as far as possible. Remember a slogan;
"BuiId tight -ventiIate right"
The building shall be optimally pressurized to achieve low capital costs, overall energy
conservation and treatment costs on filtration.
____________________________________________________________________________
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 23 oI 52
Section# 4 ESTIMATING VENTILATION RATES
To satisfy the ventilation requirement a mechanical ventilation system should be capable of
delivering the design ventilation rate. The ventilation rate can be estimated using various
techniques:
Air QuaIity Method
ASHRAE Standard 62-1999: "Ventilation for Acceptable ndoor Air Quality is a nationally
accepted standard that provides acceptable ventilation rates per person and is related to the
occupational density and activity within the space. The table below provide snapshot of the
outside air recommendations and the procedure is as follows:
1) Determine the number of people occupying the respective building spaces; People =
Occupancy/1000 x Floor Area (ft
2
)
2) Find the Ventilation Rates for Acceptable ndoor Air Quality; Q = (cfm outdoor air person) *
(number of people)
Q is the desired flow rate. The "cfm outdoor air person is ASHRAE's recommended design
outdoor airflow rates. (Refer table below)
Alternatively ventilation rate can be estimated directly based on the sq-ft area;
Q = (cfm/sq ft floor area) * (sq ft floor area)
The "cfm/sq-ft floor area is ASHRAE's recommended design values.
VentiIation Recommendations
Application Occupancy
(people/1000ft
2
)
Cfm/person Cfm/ft
2
Food and
Beverage
Service
Dining rooms
Cafeteria, fast food
Bars, cocktail lounges
Kitchen (cooking)
70
100
100
20
20
20
30
15
Offices Office space
Reception areas
Conference rooms
7
60
50
20
15
20
Public Spaces Smoking lounge
Elevators
70 60
1.00
Retail stores,
Showrooms
Basement & Street
Upper floors
Malls and arcades
Smoking lounges
Beauty shops
Hardware stores
30
20
20
70
25
8
60
25
15
0.30
0.20
0.20
Sports and
Amusements
Spectator areas
Games rooms
150
70
15
25
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 24 oI 52
Application Occupancy
(people/1000ft
2
)
Cfm/person Cfm/ft
2
Playing rooms
Ballrooms and discos
30
100
20
25
Theaters Lobbies
Auditorium
150
150
20
15
Education Classroom
Music rooms
Libraries
Auditoriums
50
50
20
150
15
15
15
15
Hotels, Motels
Resorts,
Dormitories
Bedrooms
Living rooms
Lobbies
Conference rooms
Assembly rooms
Dry cleaning, laundry
Gambling casinos
30
50
120
30
120
15
20
15
30
30
30cfm/room
30cfm/room
Health Care
Facilities
Hospital operating rooms
Hospital patient rooms
Laboratories
Medical procedure rooms
Pharmacies
Physical therapy
20
10
30
20
20
20
30
25
20
15
15
15
Source: ASHRAE Standard 62-1989 "Ventilation for acceptable indoor air quality
The ventilation rates specified by ASHRAE effectively dilutes the carbon dioxide and other
contaminants created by respiration and other activities; it supplies adequate oxygen to the
occupants; and it removes contaminants from the space. The ventilation rates greater than by
ASHARE criteria are sometime required controlling odours and where cooling is not provided to
offset heat gains.
___________________________________________________________________________
Air Change Method
The most common method used to calculate ventilation air requirements is based on complete
changes of air in a structure or room in a given time period. To determine the airflow required to
adequately ventilate an area,
1) Calculate the Room Volume to be ventilated Width x Length x Height = ft
3
(cubic feet).
2) Calculate the Air Volume requirement by multiplying the Room Volume by the Air Change
Rate per hour = ft
3
/h.
The equation below is used in calculating cubic feet per minute of ventilation air.
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 25 oI 52
n this equation,
Q is the volume flow rate of air being calculated, and ACH is the number of air changes per
hour expected, based on the type of construction (tight, medium, or loose) under the given
conditions.
Alternatively divide the room volume (in cubic ft.) by the appropriate "Minutes per Air Change"
as shown in the chart below. *Note that Air Changes per Hour = 60/ minutes per air change
Additional considerations when determining the number of air changes are:
1) Local code requirements on air changes
2) Specific use of the space
3) The type of climate in the area
n the most severe conditions select the lower number (in the series shown) to change the air
more frequently. For moderate conditions, select the mid range. For less severe conditions in
cool climates, the higher number will provide adequate ventilation.
Suggested Air Changes for Good VentiIation
Type of Space
Minutes per
Air Change
Type of Space
Minutes per
Air Change
Assembly Halls 3 - 10 Heat Treat Rooms 1 - 2
Attic 2 - 4 Hospital 4 - 6
Auditoriums 4 - 15 Kitchens 2 - 4
Bakeries 1 - 3 Laboratory 2 - 5
Banks 3 - 10 Laundries 2 - 5
Banquet Halls 3 - 4 Locker Rooms 2 - 5
Bar/Lounge 2 - 5 Lodge Rooms 3 - 5
Barns 10 - 15 Machine Shops 3 - 5
Beauty Parlors 2 - 5 Meeting Rooms 4 - 6
Boiler Rooms 2 - 5 Mill (General) 3 - 8
Bowling Alleys 2 - 8 Mills (Paper) 2 - 3
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 26 oI 52
Type of Space
Minutes per
Air Change
Type of Space
Minutes per
Air Change
Cafeteria 3 - 5 Mills (Textile) 5 - 15
Church 4 - 10 Office 2 - 8
Schools/Classroom 4 - 6 Packing Houses 2 - 5
Club Room 3 - 7 Plating Rooms 1 - 5
Corridors/Halls 6 - 20 Printing Plants 3 - 8
Dairies, Creameries 2 - 5 Projection Room 1 - 2
Dance Hall 3 - 7 Recreation Rooms 2 - 8
Dining Rooms 3 - 6 Residences 3 - 6
Dormitories 5 - 8
Restaurants/Dining
Rooms
3 - 7
Dry Cleaners 2 - 5 Restrooms 3 - 6
Engine Rooms 1 - 2 Retail Stores 3 - 8
Factories (Light) 5 - 10 Ship Holds 8 - 10
Factories (Heavy) 2 - 6 Shops (General) 3 - 10
Forge Shops 1 - 3 Theaters 3 - 8
Foundries 1 - 4 Transfer Room 1 - 5
Garages 2 - 10 Transformer Rooms 1 - 5
Generator Room 2 - 5 Tunnels 6 - 10
Glass Plants 1 - 2 Turbine Rooms 2 - 6
Gymnasiums 3 - 8 Warehouses 3 - 10
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 27 oI 52
____________________________________________________________________________
Heat RemovaI Method
When the temperature of a space is higher than the ambient outdoor temperature, general
ventilation may be utilized to provide "free cooling. n air-conditioned buildings, winter heat loss
(and summer heat gain in closed, cooled buildings) occurs when fresh outdoor air enters a
building to replace stale indoor air. This heat exchange must be calculated when sizing heating
or cooling equipment or when estimating energy use per season. Air exchange increases a
building's thermal load in three ways.
1) First, the incoming air must be heated or cooled from the outdoor air temperature to the
indoor air temperature.
2) Second, air exchange increases a building's moisture content, which means humid outdoor
air must be dehumidified.
3) Third, air exchange can increase a building's thermal load by decreasing the performance
of the envelope insulation system.
The calculation of the heat lost (or gained) by the introduction of outdoor air into spaces is:
q = 1.08 * V * At
Where:
q = sensible heat exchange due to ventilation (Btu/h)
V = volume flow rate, in cubic feet per minute (cfm) of outdoor air introduced
AT = temperature difference between outdoor and indoor air F
1.08 = A constant derived from the density of air at 0.075 lb/cu ft under average conditions,
multiplied by the specific heat of air (heat required to raise 1 lb of air 1F), which is 0.24
Btu/lbF, and by 60 min/h. The units of this constant are Btu min/cu ft F h.
For example, if the total heat gain is say 82500 BTU/Hr, the outside shade temperature 70 F
and the maximum inside temperature required 85F then the volume of air required is:
82500/ [1.1 x (85 70)] = 5000 CFM
Note that a small reduction in the temperature difference makes a considerable increase in the
volume of air required. For instance, if in the example above the temperature difference is
reduced by say 5F, i.e., required inside temperature 80F, then the volume of air required
would be increased to:
82500/ [1.1 x (80 70)] = 7500 CFM
!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!!
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 28 oI 52
"#$%&'()*+* * * INDUSTRIAL VENTILATION
ndustrial ventilation is a method of controlling worker exposure to airborne toxic chemicals or
flammable vapors by exhausting contaminated air away from the work area and replacing it
with clean air. t is one alternative to control employee exposure to air contaminants in the
workplace. Other alternatives include process changes, work practice changes, substitution
with less toxic chemicals, or elimination of the use of toxic chemicals. ndustrial ventilation is
typically used to remove welding fumes, solvent vapors, oil mists or dusts from a work location
and exhaust these contaminants outdoors. The requirement for ventilation in industrial
situations is normally connected with the process requirements.
____________________________________________________________________________
ReguIatory Information
Various regulations require that, as far as practicable, employers must reduce the risks from
hazardous substances. The regulation also requires that control measures such as ventilation
be used in preference to personal protective equipment. There are various regulations and
standards pertaining to adequacy of ventilation. Foremost are those recommended by the Air
Movement and Control Association (AMCA), the American Society of Heating, Refrigerating,
and Air-Conditioning Engineers (ASHRAE), the American National Standards nstitute (ANS),
the Sheet Metal and Air Conditioning Contractors National Association (SMACNA), the National
Fire Protection Association (NFPA), and the American Conference of Governmental ndustrial
Hygienists (ACGH). AMCA is a trade association that has developed standards and testing
procedures for fans.
1) ASHRAE is a society of heating and air conditioning engineers that has produced, through
consensus, a number of standards related to indoor air quality, filter performance and
testing, and HVAC systems.
2) ANS has produced several important standards on ventilation, including ventilation for
paint spray booths, grinding exhaust hoods, and open-surface tank exhausts. Four ANS
standards were adopted by OSHA in 1971 and are codified in 29 CFR 1910.94; these
standards continue to be important as guides to design. ANS has recently published a new
standard for laboratory ventilation (ANS Z9.5).
3) SMACNA is an association representing sheet metal contractors and suppliers. t sets
standards for ducts and duct installation.
4) NFPA has produced a number of recommendations (which become requirements when
adopted by local fire agencies), e.g., NFPA 45 lists a number of ventilation requirements for
laboratory fume hood use.
5) The ACGH has published widely used guidelines for industrial ventilation.
6) OSHA REGULATONS Ventilation criteria or standards are included in OSHA regulatory
codes for job- or task-specific worker protection. n addition, many OSHA health standards
include ventilation requirements. The four standards in 29 CFR 1910.94 deal with local
exhaust systems, and OSHA's construction standards (29 CFR 1926) contain ventilation
standards for welding. OSHA's compliance policy regarding violation of ventilation
standards is set forth in the Field nspection Reference Manual.
The ventilation system should comply with the requirements laid down in the current statutory
legislation or any revisions currently in force, and consideration should also be given to any
relevant insurance company requirements.
_____________________________________________________________________
Exhaust VentiIation System
Exhaust ventilation systems are used to remove airborne contaminants consisting of dusts,
fumes, mists, fibers, vapors, and gases that can create an unsafe, unhealthy, or undesirable
atmosphere. Replacement air, which is usually filtered and/or conditioned, provides air to the
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 29 oI 52
work space, which replaces exhausted air. A complete industrial ventilation program includes
replacement air systems that provide a total volumetric flow rate equal to the total exhaust rate.
f insufficient replacement air is provided, the pressure of the building will be negative relative to
local atmospheric pressure. Negative pressure allows air to infiltrate through open doors,
window cracks, and combustion equipment vents.
There are two types of exhaust systems:
1) General Exhaust or Dilution system in which an entire work space is exhausted without
considering specific operations.
2) Local Exhaust, in which the contaminant is controlled at its source.
_____________________________________________________________________
GeneraI Exhaust (or DiIution) VentiIation System
The terms "general exhaust and "dilution ventilation are often used interchangeably.
This type of exhaust refers to dilution of contaminated air in a general area, room, or building
and is usually accomplished with the use of large exhaust fans in the walls or roof of a building
or room. Opening doors or windows can be used as dilution ventilation, but this is not always a
reliable method since air movement is not controlled. Cooling fans (floor fans) are also
sometimes used as a method of ventilation, but these fans usually just blow the contaminant
around the work area without effectively controlling it. n general, dilution ventilation is not as
satisfactory for health hazard control as is local exhaust. n some cases, dilution ventilation
must be used because the operation or process prohibits local exhaust. Circumstances may be
found in which dilution ventilation provides an adequate amount of control more economically
than a local exhaust system. Economical considerations should not be based entirely upon the
first cost of the system because dilution ventilation frequently exhausts large volumes of heat
from a building and can easily be a troublesome factor.
General exhaust ventilation (dilution ventilation) is appropriate when:
1) Emission sources contain materials of relatively low hazard. (The degree of hazard is
related to toxicity, dose rate, and individual susceptibility);
2) Emission sources are primarily vapors or gases, or small, respirable-size aerosols (those
not likely to settle);
3) Emissions occur uniformly;
4) Emissions are widely dispersed;
5) Moderate climatic conditions prevail;
6) Heat is to be removed from the space by flushing it with outside air;
7) Concentrations of vapors are to be reduced in an enclosure; and
8) Portable or mobile emission sources are to be controlled.
9) Local exhaust ventilating is appropriate when:
10) Emission sources contain materials of relatively high hazard;
11) Emitted materials are primarily larger-diameter particulates (likely to settle);
12) Emissions vary over time;
13) Emission sources consist of point sources;
14) Employees work in the immediate vicinity of the emission source;
15) The plant is located in a severe climate; and
16) Minimizing air turnover is necessary.
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 30 oI 52
Dilution ventilation is most often used to advantage to control the vapors from organic liquids
such as the less toxic solvents. To successfully apply the principles of dilution to such a
problem, factual data are needed on the rate of vapor generation or on the rate of liquid
evaporation. To determine the correct volume flow rate for dilution (Q
d
), it is necessary to
estimate the evaporation rate of the contaminant (q
d
) according to the following equation:
Where
q
d
= Evaporation rate in ACFM
387 = Volume in cubic feet formed by the evaporation of one lb-mole of a substance, e.g. a
solvent
MW = Molecular weight of the emitted material
lbs = Pounds of evaporated material
Min = time of evaporation in minutes
d = density correction factor
The appropriate dilution volume flow rate for toxics is:
Where
Q
d
= Volume flow rate of air, in ACFM
q
d
= Evaporation rate in ACFM
Km = Mixing factor to account for poor or random mixing (note Km= 2 to 5; Km = 2 is optimum)
Ca = Accessible airborne concentration of the material (typically half of the PEL)
____________________________________________________________________________
DiIution VentiIation - Limiting Factors
The use of dilution ventilation has four limiting factors:
1) The quantity of contaminant generated must not be too great or the air volume necessary
for dilution will be impractical.
2) Workers must be far enough away from contaminant evolution, or evolution of contaminant
must be in sufficiently low concentrations so workers will not have an exposure in excess of
the established Threshold Limit Values (TLVs).
3) The toxicity of the contaminant must be low.
4) The evolution of contaminants must be reasonably uniform.
Dilution ventilation is seldom applied to fumes and dusts because the high toxicities often
encountered require too great a quantity of dilution air, velocity and rate of evolution are usually
very high, and data on the amount of fumes and dust production are very difficult, if not
impossible, to obtain.
____________________________________________________________________________
Effectiveness of DiIution VentiIation
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 31 oI 52
Dilution ventilation can be more effective if the exhaust fan is located close to exposed workers
and the makeup air is located behind the worker so that contaminated air is drawn away from
the worker's breathing zone. n cases where the source of contamination is widely scattered or
is from a mobile source, like carbon monoxide from a forklift, large wall or roof exhaust fans can
be effective. Makeup air to replace the air exhausted is necessary for the best control. Simple
openings in walls or doors can be sources of makeup air, or a second fan can draw makeup air
into the building or room. However, makeup air may require heating in the winter resulting in
increased heating bills. n practice, replacement depends on mixing efficiency. Some basic
principles to be applied to a dilution ventilation system are as follows:
1) From factual data, select the amount of air required for satisfactory dilution of the
contaminant.
2) Locate the exhaust openings near the sources of contaminant if possible, in order to obtain
the benefit of spot ventilation.
3) For dilution methods to be effective, the exhaust outlet and air supply must be located so
that all the air used in the ventilation passes through the zone of contamination.
4) Replace exhausted air by a make-up air system. Make-up air should be heated during cold
weather. Dilution ventilation systems usually handle large quantities of air by means of
propeller fans. Make-up air usually must be provided if the ventilation is to be adequate and
the system is to operate satisfactorily.
5) The general air movements in the room caused by suction at the exhaust opening should
keep the contaminated air between the operator and the exhaust opening, and not draw
contaminants across the operator.
6) A combined supply and exhaust system is preferred with a slight excess of exhaust if there
are adjoining occupied spaces, and a slight excess of supply if there are no such spaces.
7) Avoid re-entrance of the exhausted air by discharging the exhaust high above the roof line,
or by assuring that no window, outside air intakes, or other such openings are near the
exhaust discharge.
_____________________________________________________________________
LocaI Exhaust VentiIation Systems
Local exhaust ventilation captures air contaminants at their source.
Local exhaust ventilation unlike dilution ventilation is designed to capture an emitted
contaminant at or near its source, before the contaminant has a chance to disperse into the
workplace air. Local exhaust ventilation operates on the principle that air moves from an area of
high pressure to an area of low pressure and the difference in pressure is created by a fan that
draws or sucks air through the ventilation system. A local exhaust system operates in the same
manner as a household vacuum cleaner.
Local exhaust ventilation is needed when employees are exposed to high toxicity chemicals,
when large amounts of dusts or welding fumes are generated, or when increased heating costs
from ventilation in cold weather are a concern. t is necessary when:
1) the contaminant is toxic or corrosive (such as lead fumes, acid mist, solvent vapor)
2) contaminant levels are high
3) contaminants must be filtered out before release into the air
4) The process gives off heat.
t is most effective because:
1) t minimizes employee exposure to contaminants
2) The volume of exhaust air is much less than for general ventilation
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 32 oI 52
3) The contaminant can be collected for disposal or recovery
4) Equipment in the workplace is protected from heat and corrosive substances
5) Employees may not have to wear respiratory protection.
____________________________________________________________________________
System Configuration
A typical local exhaust ventilation system is composed of five parts:
1) A fan that moves the air through the system and discharges (blows) it outdoors,
2) A "hood" or opening that captures the contaminant at the source,
3) Ducts that transport the airborne chemicals through the system,
4) An air cleaning device (not always required) that removes the contaminant from the moving
air in the system,
5) An exhaust stack through which the contaminated air is discharged.
The figure below illustrates the basic components of local exhaust system.
As with dilution ventilation, makeup air must be provided to replace the air exhausted in order
for the system to operate properly.
_____________________________________________________________________
Fan
The fan is the heart of the system, creating movement of air to shift the contaminants. These
must provide enough air pressure difference ("suction") to capture contaminants at the source,
draw them through the hood, carry them through the ducting and exhaust them outdoors.
To choose the proper fan for a ventilation system, the following information must be known:
1) Air volume to be moved;
2) Fan static pressure;
3) Type and concentration of contaminants in the air (because this affects the fan type and
materials of construction); and
4) The importance of noise as a limiting factor.
Once this information is available, the type of fan best suited for the system can be chosen.
Many different fans are available, although they all fall into one of two classes: axial flow fans
and centrifugal fans. Axial or propeller fans are most commonly used for dilution ventilation or
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 33 oI 52
for cooling. They can move large amounts of air if there is little resistance, but are not suited for
local exhaust ventilation because they do not provide enough suction to draw air through the
system.
Centrifugal fans can operate at against a high resistance and are typically used in local exhaust
ventilation systems. There are several types of centrifugal fans. The rugged radial blade
centrifugal fans are the best type for exhausting heavy amounts of dust because they are less
likely to become clogged or abraded by the dust.
Fans carrying corrosive materials must be lined with or constructed of corrosive-resistant
materials. Fans carrying combustible materials must be explosion proof and have wheels and
housings constructed of nonferrous or non-sparking materials. Motors mounted in the air
stream must also be explosion proof. When flammable, combustible, or other harmful materials
or substances are conveyed, fans must be placed outside of buildings.
_____________________________________________________________________
Hoods
The hood captures, contains, or receives contaminants generated at an emission source.
Hoods come in a variety of designs. The one you choose should enclose or be located as close
as possible to the contaminant source and be matched to the particular process. The hood
should be designed so it captures contaminants as they are given off. Examples of different
types of hoods are illustrated in figure below.
1) Enclosure - contains contaminants released inside the hood.
2) Receiving hood - catches contaminants that rise or are thrown into it.
3) Capturing hood - reaches out to draw in contaminants
4) Downdraft hood
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 34 oI 52
The hoods are made of various materials, such as epoxy-coated steel, stainless steel,
fiberglass, epoxy resin, polypropylene, and PVC. The front of the hood is called the face and is
usually equipped with a movable, transparent sash. Enclosing hoods provide the best control
but they are often not feasible because they would interfere with the work being done by the
employee. n those cases, a capture exhaust hood can only be located near the source of the
contaminant. These types of hoods "reach out" to capture the contaminant much like a vacuum
cleaner sucking dirt off a floor.
____________________________________________________________________________
Hoods: Basic Design PrincipIes
The basic goal of industrial hood design is to enclose the industrial process as completely as
possible, allowing only enough access for the user and for maintenance. When complete
enclosure is not practical, the hood should be designed to accommodate the work process
while remaining as closed as possible. The hood should be located close to the work process to
minimize air volume. The access openings of well-designed and built hoods minimum are
located away from the natural path of contaminant travel to eliminate or minimize air motion
around the work process. The hood should also be positioned so contaminants are removed
away from the user.
VeIocity
Proper hood design includes components to provide necessary air velocity. Velocity is the
speed of the air through the various exhaust components, given in feet per minute (fpm).
Capture velocity is the air velocity at any point in front of the hood or at the hood opening
necessary to overcome opposing air currents and to capture contaminated air at that point by
causing it to flow into the hood.
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 35 oI 52
The air velocity at the hood opening and inside the hood must be sufficient to capture and carry
the air contaminants. The hood should enclose the source of contaminant as much as possible
or be placed as close to the source as possible.
The conventional hood has a movable, vertical or combination horizontal and vertical sash. n
the full open vertical position of the sash, the free area of the hood face is generally about 10 to
13 square feet. The volume of air exhausted is calculated using: Q = A x V, where Q is air
volume in cfm; A is face area in square feet; and V is face velocity in fpm. Therefore, a Class B
laboratory fume hood with a minimum average face velocity of 100 fpm would exhaust 1,000 to
1,300 cfm of air through the hood.
____________________________________________________________________________
VeIocity Range
Lower velocities are acceptable when minimal room air currents are present. Lower velocities
are also acceptable when there are other conditions that are favorable to capture contaminants
or when the contaminants are of low toxicity. Additionally, lower velocities are used when the
work process is intermittent or there is a low production of contaminants and the hood is large
with a large air volume.
Higher velocity ranges are needed for high velocity room air currents or for other conditions that
are unfavorable to the capture of contaminants. Higher velocities are required when
contaminants have a high toxicity or when the work process has a high production of
contaminants or the hood is small.
The exhaust system design must also account for duct velocity, face velocity, slot velocity, and
plenum velocity. Duct velocity is the air velocity through the duct. Minimum duct velocity is the
minimum air velocity required to move particles or contaminants through the duct. Face velocity
is the air velocity at the hood opening. Slot velocity is the air velocity through the openings in a
slotted hood, and plenum velocity is the air velocity in the plenum.
____________________________________________________________________________
VoIume
Air volume through the fume hood and exhaust system is measured in cubic feet per minute
(cfm). The volume of exhaust air necessary to safely remove contaminants from the work
process must be adequate but should not be excessive. A high volume of air may increase
velocities to an extent that the effectiveness and safety of the hood is compromised. ncreased
air volume increases horsepower requirements by as much as the cube of the volume.
Therefore, the hood should be as close to the work as possible, as the volume of the exhaust
air varies with the square of the distance from the process. For example, a work process
requiring 1,000 cfm of exhaust air would actually need 4,000 cfm of exhaust air if the process
were twice the distance from the hood.
____________________________________________________________________________
System Pressure
The pressure inside a local exhaust system is slightly negative compared to the pressure
outside the system and is measured in units called "inches of water". This negative pressure
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 36 oI 52
varies through the system and is usually measured to determine how well the system is
functioning.
The hood converts duct static pressure to velocity pressure the hood's ability to convert static
pressure to velocity pressure is given by the coefficient of entry (C
e
), as follows:
C
e
= (VP/SP
h
)
0.5
= [1/ (1+K)]
0.5
Where
K = Loss factor
VP = Velocity pressure in duct
SP
h
= Absolute static pressure about 5 duct diameters down the duct from the hood
____________________________________________________________________________
Design Points to Note
1) The hood should be designed to achieve good air distribution into the hood openings so
that all the air drawn into the hood helps to control contaminants.
2) High capture velocity with low air volume is desirable. To minimize air-flow requirements,
the operation should be enclosed as much as possible, either with a ventilated enclosure,
side baffles, or curtains. This helps both to contain the material and to minimize the effect
of room air currents.
3) Reducing the amount of contaminants generated or released from the process reduces
ventilation requirements.
4) The purpose of most ventilation systems is to prevent worker inhalation of contaminants.
For this reason, the hood should be located so that contaminants are not drawn through the
worker's breathing zone. This is especially important where workers lean over an operation
such as an open-surface tank or welding bench.
5) Hoods must meet the design criteria in the ACGH Industrial Ventilation Manual or
applicable OSHA standards. Most hood design recommendations account for cross-drafts
that interfere with hood operation. Strong cross-drafts can easily reduce a hood's
effectiveness by 75%. Standard hood designs may not be adequate to contain highly toxic
materials.
____________________________________________________________________________
RuIes of Thumb for Hoods AppIication
1) Distance between Source and the Hood
The distance between the face of the hood and source must be short to effectively capture
the contaminant. A hood moved from two inches away from a source to four inches away
from a source will require four times the amount of air volume through the system to
provide the same degree of capture. Adding a flange to the edges of the capturing hood
provides more efficient capture of contaminants. Place hood as close to the source of the
contaminant as possible. The required air volume varies with the square of the distance to
the source.
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 37 oI 52
2) ReIationship of Capture VeIocity (V
c
) to Duct VeIocity (V
d
)
Hood placement must be close to the emission source to be effective. Maximum distance from
the emission source should not exceed 1.5 duct diameters.
The approximate relationship of capture velocity (V
c
) to duct velocity (V
d
) for a simple plain or
narrow flanged hood is illustrated in figure below. For example, if an emission source is one duct
diameter in front of the hood and the duct velocity (V
d
) = 3,000 feet per minute (fpm), then the
expected capture velocity (V
c
) is 300 fpm. At two duct diameters from the hood opening,
capture velocity decreases by a factor of 10 to 30 fpm.
3) Maximum Capture distance shouId not be more than 1.5 times the duct diameter.
Figure below shows a rule of thumb that can be used with simple capture hoods. f the duct
diameter (D) is 6 inches, then the maximum distance of the emission source from the hood
should not exceed 9 in. Similarly, the minimum capture velocity should not be less than 50 fpm.
4) Figure below provides guidance for determining an effective fIange width (W).
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 38 oI 52
Ductwork
Ducts carry the contaminants from their source to an outlet point. To do this effectively, the
types of effluents or waste materials that will be in the hood and exhaust ducts and discharged
into the atmosphere must be known when designing ductwork. Note the key design features as
below:
1) Air velocity in the ducting must be high enough to prevent contaminants settling in the
system, but not so high that it causes vibration and noise problems. Air flows turbulently
through ducts at between 2,000-6,000 feet per minute (fpm).
2) Smooth, round ducts are recommended for local exhaust systems. Dust can get trapped in
the corners of square ducts, and air turbulence is higher inside them, reducing air velocity.
3) There should be as little resistance in the form of turbulence or friction as possible. Friction
losses vary according to ductwork type, length of duct, velocity of air, duct area, density of
air, and duct diameter. Sharp bends or tees should be avoided in ducts as well as abrupt
changes in diameter. Also, smaller diameter duct will have greater friction than larger
diameter ductwork.
4) Ducting should be straight at least two duct diameters before entering the fan to maintain
smooth airflow into the fan. Duct connections must also be as tight as possible to prevent a
reduction in air velocity at the hood because of leaks at joints.
5) The ambient temperature of the space in which the ductwork is installed is also important
because temperature affects the condensation of the vapors in the exhaust system, and
condensation can cause corrosion of ductwork metals. Consideration must also be given to
the length and arrangement of duct runs. The longer the duct the longer shall be the
exposure to effluents and, therefore, more condensation. When condensation is likely,
sloped ductwork and condensate drains should be provided. Condensate drains that may
accumulate hazardous materials must be given special consideration.
6) Exhaust ductwork should be of adequate strength and construction to accommodate the
type of waste material flowing through the duct and the air pressures generated by the fan
system.
7) Ducts can be made of galvanized metal, fiberglass, plastic, and concrete. Proper design
does not use flexible duct connectors in hidden spaces or with corrosive materials.
____________________________________________________________________________
System Effect Loss
System effect loss, which occurs at the fan, can be avoided if the necessary ductwork is in
place. Use of the six-and-three rule ensures better design by providing for a minimum loss at
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 39 oI 52
six diameters of straight duct at the fan inlet and a minimum loss at three diameters of straight
duct at the fan outlet (refer figure below).
An iIIustration of the "Six and Three RuIe"
System effect loss is significant if any elbows are connected to the fan at inlet or outlet. For
each 2 diameters of straight duct between the fan inlet and any elbow, CFM loss will be 20%.
____________________________________________________________________________
Air CIeaners
Air cleaning devices on ventilation systems are sometimes necessary to capture large amounts
of dust. n some instances, they may be required by air pollution regulations. The type of air
cleaner depends on the type of contaminant being removed, its concentration in the air, the
amount of contaminant that must be removed, and other factors.
The types of air cleaning equipment is common use are settling chambers, cyclones, filter
panels of various types, electrostatic precipitators, carbon filters, gas scrubbers and air
sterilizers (for bacteria). Dust filters are the most common type of air cleaners found in industry.
The selection of equipment suitable for a particular job depends on the degree of fineness of
the dust (particle size), the required efficiency of collection (the percentage of the finer particles
to be removed), and the amount of dust to be collected. Local air pollution regulations dictate
the type of air cleaner required. The cost and extra resistance that these air cleaners add to an
exhaust ventilation system must be considered in the design. Regular maintenance of air
cleaners increases their efficiency and minimizes worker exposure.
____________________________________________________________________________
Exhaust Stacks
Stacks disperse exhaust air into the ambient environment. t must be high enough to avoid gas
re-entering the workplace and make sure contaminant levels on the ground are within clean air
standards. The amount of re-entrainment depends on exhaust volume, wind speed and
direction, temperature, location of intakes and exhausts, etc. Exhaust stacks also need to be
designed and located properly for the most efficient operation of a local exhaust system. A
common mistake is to locate them too close to building fresh air intakes. When installing stacks:
1) Locate stacks on the highest roof of the building so that exhausts are discharged above the
building envelope and not on the side of the building. Provide ample stack height (a
minimum of 10 ft above adjacent rooflines or air intakes);
2) Place stack downwind of air intakes;
3) Provide a stack velocity of a minimum of 1.4 times the wind velocity;
4) Air velocity out of the stack should be at least 3000 feet per minute to overcome the effects
of downdrafts from wind blowing over the building.
5) Place the stack as far from the intake as possible to prevent re-circulation of contaminants
(50 ft is recommended);
6) Stacks work best when they are tall, usually at least 10 feet above the roof line; and
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 40 oI 52
7) Rain caps should not be used on exhaust stacks, as they tend to deflect air downward,
increasing the chances that contaminated air would lay on the roof and circulate into the
building. Additionally, rain caps have high friction losses and may actually provide less rain
protection than a properly designed stack head.
____________________________________________________________________________
Type of LocaI Exhaust System
Local exhaust systems can be classified as: (1) Constant Air Volume or (2) Variable Air
Volume, based on the method of system operation and control. Each of these classifications
can be further broken down into individual or central systems based on the arrangement of the
major system components such as the fans, plenums, or duct mains and branches.
Constant Air VoIume Systems
This type of system exhausts a fixed quantity of air from each safety cabinet, fume hood, or
room module. Constant air volume systems will handle the same exhaust air quantity for any
condition. For this reason, the capacities of the exhaust air and supply air systems will limit the
total number of fume hoods and room modules to be installed. This type of system is flexible
with respect to location of hoods but may incur high ownership and operating costs because of
the large air volumes handled. These high costs may impose a limitation on the total number of
hoods or modules that can be installed in the building.
Constant air volume systems are highly stable in operation and simple to balance.
n most installations, there is no need for continuous adjustment of air balance during normal
operation.
____________________________________________________________________________
VariabIe Air VoIume Systems
Variable air volume systems can shut down inactive fume hoods and room modules.
This capability results in an economic system that reduces the air flow during periods when
some of the hoods and room modules are not in use, and the exhaust air system is operated at
less than full capacity. More freedom in the installation of the hoods and room modules is
possible since the total number of units that may be connected does not entirely depend on the
capacity of the exhaust system.
Variable air volume systems are not as stable in operation as constant air volume systems are.
They are also more difficult to balance and control. Sensitive instrumentation and controls are
required, which result in high initial and maintenance costs. Reliability in a corrosive
atmosphere is highly questionable.
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 41 oI 52
For some applications, the use of balancing dampers in exhaust air ducts is prohibited by
codes. One problem associated with the variable air volume system is the regulation of the total
simultaneous operating usage to match design usage factors. f the collective area of operating
hood openings at any one time exceeds design opening diversity values, the proper face
velocity requirements will not be achieved and personnel could be endangered. Visual and
audible alarms should be equipped on hoods to warn workers of unsafe air flows.
____________________________________________________________________________
IndividuaI Exhaust Systems
ndividual exhaust air systems use a separate exhaust air fan, exhaust connection, and
discharge duct for each hood or module. These are used in selective applications requiring
special exhaust filtration, special duct or fan construction for corrosive elements, or to exhaust
fumes that have very hazardous elements.
Each fume hood has its own exhaust connection, duct, and fan, which does not directly affect
the operation of any other area of the building, which permits selective operation of individual
hoods and modules by starting or stopping the fan motor. Normally, the exhaust fan is always
on and is interlocked electrically with the supply fan so that when the exhaust goes off the
supply fan does too.
Although more fans are used than for central systems, the overall space requirements are
usually less for individual systems because of the small, direct duct connection. ndividual fume
hood exhaust systems are inexpensive for small systems having only a few fans. However, if
the system is large, the initial investment and the operating costs are high because of the
greater number of fans, roof penetrations, and controls, and the more extensive ductwork and
wiring that must be installed and maintained. The maintenance costs are also high but since
each hood has its own ductwork, exhausted air from fume hoods does not mix and shutdowns
for repairs or maintenance are localized.
The shutdown of individual exhaust air systems will upset the proper directional air flow and
may cause potentially hazardous contaminants and odours to flow into the corridor and
adjacent rooms. f this type of system is used, precautions to reverse air flow (such as air locks)
should be provided.
____________________________________________________________________________
CentraI Exhaust Systems
Facilities that use many fume hoods usually have a central exhaust system. Central exhaust air
systems consist of a common suction plenum, a primary fan, a standby fan and branch
connections to multiple exhaust terminals. Grouping exhaust devices by type, proximity, fire
pressurization, or contamination zones minimizes cost.
Compared to an individual system of equivalent size, a central exhaust system requires a
smaller initial investment and has a lower operating cost. The air is more diluted before being
exhausted into the atmosphere. The central system has a standby fan for safety and provides
greater flexibility for future expansion.
Central systems are more difficult to balance and require frequent periodic re-balancing to
ensure proper airflow. Air balancing of central systems is more difficult when there are various
types of exhaust devices installed on common duct runs.
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 42 oI 52
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 43 oI 52
Section# 6 GeneraI System Design Considerations
1) Aim for full cross-ventilation of the space. The cross-ventilation is based on the natural
tendency of the air to move from high to low pressures. The warm air moves naturally,
producing air displacement through the building (natural ventilation).
2) Air replacement should be provided at the minimum rate of 1 sq-ft of free area per 600
CFM of air moved. Air replacement grilles usually have a free area of approximately
60%.For example - a 12 square grille will have a face area of 12 x 12 = 1 sq-ft, therefore
60% of 1 sq-ft = 0.6 sq-ft free area. This means that this grille will provide air replacement
for the rate of 0.6 x 600 = 360 CFM. Use sufficient correctly sized grilles to keep supply and
extract air velocities between 300 feet per minute and 600 feet per minute, if possible.
3) Locate units at high level, and inlet grilles usually just above head level to avoid
uncomfortable draughts to the occupants. The natural upward convection currents and the
secondary entrained air movements caused by the "jet of air, more or less horizontal, from
the inlet grilles will give sufficient gentle air turbulence around breathing level to maintain a
feeling of freshness.
4) Locate intake and exhaust fans to make use of prevailing winds. Locate fans and intake
ventilators for maximum sweeping effect over the working area. f filters are used on gravity
intake, size intake ventilator to keep intake losses below 1/8 in-wg.
5) n larger industrial buildings, temperature differences encourage the upward flow of air. f
the building contains the hot processes, dusts and fumes are carried rapidly up to be
discharged through roof ventilators or fans. Always extract from as high as possible to
prevent the collection of heated air under the roof or ceiling from extending downwards to
near breathing level. Fans at or near the ridge in such cases are ideal, with air replacement
from side windows above the head level. This method assists the natural tendency for
warmer air to rise and the quicker this 'fug' is removed from high level the better will be the
conditions at breathing level.
6) When considering air replacement, the location of suitable air intake points is as important
as the location of the extract units. Note that with ventilation alone, the temperature inside a
room cannot be reduced to the outside shade temperature - it will always be a few degrees
above. However, it is worth considering pulling the replacement air from the "cold" side of
the building - the north facing (north of the equator).
7) Air movement from inlets is directional, maintaining high velocities for a considerable
distance, whereas air movement into extract openings is not directional, so air velocities
close to extract openings are generally low. The fast moving airstream from the inlet
therefore has more influence on air movement in the room or workplace, entraining air and
causing turbulence over a wide area. This principle sometimes permit inlet and extract
ports to be positioned close to each other over a limited area.
8) Supply and extract points external to the building should be a minimum of 6 feet apart.
Figure below indicates the required separations and clearances for intake and exhaust vent
openings. Vents should be at least 1meter (40 inches) from any corner of the building to
minimize wind effects. ntakes should be at least 450 mm (18 inches) and exhaust vents at
least 200 mm (8 inches) above the ground to avoid snow blockage and contamination by
ground care products such as herbicides. ntakes and exhaust vents should be separated
vertically or horizontally by at least 1800 mm (6 feet) to minimize the potential for cross
contamination.
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 44 oI 52
9) These vents should be located where they are shielded from the direct impact of the wind,
and away from sources of potential contamination, such as vehicle parking, loading bays,
and fuel or chemical storage. n addition, intake vents can conduct noise and so should be
located away from sound sources, such as mechanical equipment, fans, air-conditioning
condensing units and cooling towers.
10) Avoid fans blowing opposite each other, when necessary; separate by at least 6 fan
diameters.
11) Exhaust ducts should be installed with backdraft dampers to prevent them from functioning
as intakes when they are not powered. All intake and exhaust openings should be provided
with hoods and non-corroding screens to protect them from weather and entry by insects
and small animals.
12) Proper air distribution and circulation is very important. n spite of an adequate supply of
ventilation air, there may be inadequate supply for some rooms because of poor
distribution. Continuous positive air movement is highly desirable since it equalizes
temperature, carbon dioxide, and humidity levels within the building. Though the optimum
air velocity has never been thoroughly investigated, it is suggested that a minimum velocity
of 40 FPM should be provided. Below this level, air flow is unpredictable, and mixing
throughout will not be achieved.
13) The level of air motion at the worker is important. At fixed work positions with light activity,
the velocity should not exceed 200 fpm for continuous exposure. With high work levels and
intermittent exposures, velocities of 400 to 800 fpm may be used. When high-velocity air is
used, it is important to avoid the undesirable effects of hot air convection and disturbance
of local exhaust ventilation systems. Table below lists some acceptable air motion rates.
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 45 oI 52
14) Use Class B insulated motors where ambient temperatures are expected to be high for air-
over motor conditions.
15) f air moving over motors contains hazardous chemicals or particles, use explosion-proof
motors mounted in or out of the airstream, depending on job requirements. For hazardous
atmosphere applications use fans of non-sparking construction.
16) f the room is very wide, say over 80 ft it may be necessary to extract centrally and bring in
replacement air along each side.
17) Design System for Zero Temperature Stratification- Temperature stratification in simple
word means vertical temperature difference between feet and head. t is a common
problem caused by convection, the tendency of light- warm air to rise and heavier-cooler air
to sink. f air is not properly mixed by the ventilation system, the temperature near the
ceiling can be several degrees warmer than at floor level.
18) Absence of Drafts: Large vertical surfaces can also produce a significant flow of naturally-
convecting air, producing complaints of draftiness. As a rule of thumb, horizontal
temperature differences should not exceed 10C and vertical temperature differences
should not exceed 5C. To avoid draft, ASHRAE suggests that air speeds should be below
40 FPM with ventilation systems that create 30-60% turbulence intensity. Use ceiling
diffusers with 45 or 90 angles over 10 angles because 10 angles can cause draught at
the head; Circulated air should be no more than 2F different from the ambient space
temperature.
19) To provide effective general ventilation for heat relief by either natural or mechanical
supply, the air must be delivered in the work zones (no more than 10 ft above the floor) with
an appreciable air velocity. A sufficient exhaust volume is necessary to remove the heat
liberated in the space. Local relief systems may require supplementary supply air for heat
removal.
20) Modifications to a room or workplace, particularly the installation of internal partitions, may
affect the circulation of air and reduce the effectiveness of ventilation. Where part of a
workplace is blocked or partitioned off, for example, to create internal offices, it is important
to ensure that the ventilation system extends to all areas and that suitably sized air grilles
are incorporated in the partition walls or doors if necessary. n some cases, supplementary
fans may be required to promote air movement and prevent localized stagnation.
____________________________________________________________________________
Fire and Safety Considerations
The installation of mechanical installation system may affect the fire risk within the building,
both as regards structural protection and means of escape in case of fire and may influence
any necessary fire venting or fight fighting considerations.
The extent and detail of statutory control and other specialist interests may vary considerably
according to the design, use, occupation and location of the building, and the type of system of
mechanical ventilation proposed. t is particularly important that the appropriate authority be
fully consulted at an early stage.
The degree of control and the requirements imposed vary according the circumstance of the
case, depending on whether the control concerns means of escape (e.g. clearance for smoke
in the event of fire), structural fire precautions (e.g. maintenance of structural fire separations),
health of occupants, conservation of energy or any combination of these. Full details may have
to be approved by the local authority in such cases as:
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 46 oI 52
1) Buildings controlled from the point of view of the means of escape where recirculation of air
is involved and/or where pressurized staircases are contemplated as part of the smoke
control arrangements
2) Places of public gathering/entertainment
3) Flats and apartments where mechanical ventilation is necessary to lobby and corridors as
part of the smoke control arrangements
4) Large garages and car parks, hotels, parts of buildings used for trades or processes
involving a special risk, departmental stores and similar shop risks in large buildings
5) Certain areas of the building require separate and independent mechanical ventilation
systems. These include: lavatories, toilets, garages, kitchens and car parks, staircases for
control of smoke, boiler chambers, and areas containing oil immersed electric plant or
hazardous materials.
Locker Room, ToiIet, and Shower Space VentiIation
The ventilation of locker rooms, toilets, and shower spaces is important in removing odour and
in reducing humidity. Legal minimum requirements should be consulted when designing these
facilities. n toilets recommended rates of exhaust ventilation are 10 ACH or 2cfm /sq-ft
whichever is higher. Supply air may be introduced through door or wall grilles. Toilets must be
maintained at negative pressure.
When control of workroom contaminants is inadequate, the total exposure to employees can be
reduced by making sure that the level of contamination in the locker rooms, lunchrooms, and
break rooms is minimized by pressurizing these areas with excess supply air.
When mechanical ventilation is used, the supply system should have supply fixtures such as
wall grilles, ceiling diffusers, or supply plenums to distribute the air adequately throughout the
area. n locker rooms, the exhaust should be taken primarily from the toilet and shower spaces,
as needed, and the remainder from the lockers and the room ceiling. Table below provides a
guide for ventilation of these spaces.
VentiIation for Locker Rooms, ToiIets and Shower Spaces
Description VentiIation Rate
Lockers Room
1) Coat hanging or clean change room
for non-laboring employees with
clean work clothes
2) Change room for laboring
employees with wet or sweaty
clothes
3) Change room for heavy laborers or
workers assigned to working and
cleaning where clothes will be wet
or pick up odours.
1cfm /sq-ft
2cfm /sq-ft; 7cfm
exhausted from each
locker
3cfm /sq-ft; 10cfm
exhausted from each
locker
ToiIet Spaces 2cfm /sq-ft; at least 25cfm
per toilet facility; 200cfm
minimum
Shower Spaces 2cfm /sq-ft; at least 50cfm
per shower head; 200cfm
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 47 oI 52
per shower head; 200cfm
minimum
____________________________________________________________________________
Process VentiIation
1) Collect fumes and heat as near the source of generation as possible.
2) Make all runs of ducts as short and direct as possible.
3) Keep duct velocity as low as practical considering capture for fumes or particles being
collected.
4) When turns are required in the duct system use long radius elbows to keep the resistance
to a minimum (preferably 2 duct diameters).
5) After calculating duct resistance, select the fan having reserve capacity beyond the static
pressure determined.
6) Use same rationale regarding intake ventilators and motors as in General Ventilation
guidelines above.
7) nstall the exhaust fan at a location to eliminate any recirculation into other parts of the
plant.
8) When hoods are used, they should be sufficient to collect all contaminating fumes or
particles created by the process.
_____________________________________________________________________
Kitchen VentiIation
Extract systems from kitchen equipment should be separate from any other and the extracted
air should not be recirculated. The following design guidelines should be noted:
Hoods and Ducts
1) Duct velocity should be between 1500 and 4000 fpm
2) Hood velocities (not less than 50 fpm over face area between hood and cooking surface)
3) Extend hood beyond cook surface 0.4 x distance between hood and cooking surface
4) Canopy, ducting and lagging should be made from non-combustible material.
Filters
1) Select filter velocity between 100 - 400 fpm
2) Determine number of filters required from a manufacturer's data (usually 2 cfm exhaust for
each sq. in. of filter area maximum)
3) nstall at 45 - 60 to horizontal, never horizontal
4) Shield filters from direct radiant heat. Follow the following for the filter mounting height:
No exposed cooking flame1-1/2' minimum to filter
Charcoal and similar fires4' minimum to filter
Provide removable grease drip pan
Establish a schedule for cleaning drip pan and filters and follow it diligently
____________________________________________________________________________
CommerciaI Kitchens
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 48 oI 52
Efficient ventilation is an important factor in kitchen design. t must effectively remove cooking
fumes and odours and the products of combustion given off by gas cooking apparatus, and
ensure an adequate supply of comparatively fresh replacement air without creating
uncomfortable draughts.
The main points when preparing a scheme are:
1) Give an adequate air fIow- Use a minimum ventilation rate of 25 ACH for commercial
kitchens, increasing these figures as necessary to deal with higher than average loading
and cooking equipment. When calculating the amount of air necessary to give the selected
ACH it is usual to base the volume of the kitchen on a height of 3m. This will automatically
compensate for different ceiling or roof heights by increasing the ventilation rate for a low
ceiling, and reducing it for a high ceiling.
2) Specific VoIumes for Cooking Equipment- Current practice for commercial kitchen
ventilation extends the guidelines for sizing ventilation schemes. Whilst retaining the
minimum of 20-30 ACH, specific quantities of air to be provided for each piece of cooking
apparatus are now available. Therefore, when the details of the equipment are known, a
more accurate assessment of the air volume required can be made. These requirements
can result in substantially higher rates of extraction than the minimum rates, and will take
much of the uncertainty out of deciding by how much the minimum must be exceeded. The
volumes can be used for determining both general extraction and canopy extraction
requirements.
Kitchen Cooking Equipment VoIume Requirements
Apparatus m/h I/s ft/min (cfm)
Cookers per m 1080 300 640
Pastry ovens 1080 300 640
Fish fryers 1620 450 950
Grills 900-1080 250-300 530-640
Steak grills 1620 450 950
Salamanders 1620 450 950
Boiling pans (140-
180 liter)
1080 300 640
Steamers 1080 300 640
Sink (sterilizing) 900 250 530
Bain Marie 720 200 420
Tea sets 540-900 150-250 320-530
Alternatively, calculations can be based on the number of meals prepared per hour, multiplied
by 10-15, to give an extract volume in litres per second.
Locate extract units as high as possible and as near the source of the fumes as convenient. Hot
moist fumes from cooking operations rise fast to ceiling level, and unless they are removed
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 49 oI 52
quickly from that level they will spread over ceiling, walls and windows depositing the moisture
content and grease as it condenses on the cooler surfaces. Roof lights and lantern lights are
sometimes an ideal location for extract units in a commercial kitchen as they are usually over
some cooking equipment at or near the centre of the kitchen, and it is a simple matter to fit roof
fans in the glazing. f due to some obstruction it is not possible to site the unit at high level
directly above the cooker, then keep it at high level and move it a foot or two to one side. This is
better than putting the unit immediately above the cooker but only half way up the wall, as the
velocity of the steam and fumes would carry them past the unit to ceiling level where they would
spread horizontally and hang about for some time before cooling sufficiently to drop to the level
of the extract point. This is a common fault in domestic kitchens, the low siting of the unit
sometimes allowing cooking fumes to float through the top of a doorway before they can sink
low enough to be extracted by the fan.
3) Use canopies over 'heavy' cooking equipment, particularly in commercial kitchens, to
collect and 'hold' the fumes at source. The removal of fumes and steam from cooking and
industrial processes should be done as near to the source as possible. Warm fumes and
steam rises quickly and spread over a comparatively large area of the kitchen and must be
'picked up' and removed quickly. To deal with this sort of local problem by increasing the
general ventilation rate of the room is not always economical or convenient due to the large
volume of air extraction necessary to reduce the spread of the fumes. n such cases a
canopy, or hood, would be fitted directly above the equipment and overlapping it by up to
300 mm all round to collect the fumes. The canopies and fans should be of sufficiently large
capacity to 'hold' and carry away the fumes without undue spillage from the mouth of the
canopy. To achieve this, the velocity of the air through the open area between the canopy
and the equipment must be sufficiently high to draw in fumes near the edge of the
equipment against the eddying effects of local draughts which could be caused by the
movement of people around the equipment.
Estimating Air VoIume
Where the items of cooking equipment to be placed under a canopy are known, the total of
the volumes of air required for each piece of equipment will constitute the extract volume to
be provided by the canopy extract fan/s. Where the equipment is not known, the formula
shown below can be used. This formula uses the base area of the canopy, rather than the
open perimeter area used in earlier formulae, and more closely matches the volume of hot
air rising from the cooking equipment. The volumes obtained by this formula should be
regarded as minimums and no harm will result if they are increased by 50%.
Vol. m/s = L (m) W (m) K,
Where
K =
0.25 for domestic
0.30 for Light Commercial
0.40 for Commercial and Light ndustrial
0.50 for Heavy Commercial and ndustrial
(The factor K represents the face velocity (m/s) of the airflow at the canopy)
ExampIe
A canteen kitchen (equivalent to a light commercial kitchen having face velocity of 0.3 m/s) is to
have a canopy 3 m x 1.25 m and covering cooking equipment not yet specified. Find the air
volume required.
SoIution
Air req. m/s = 3 1.25 0.3 = 1.125 m/s (4050m/h)
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 50 oI 52
Other points to consider:
1) Minimum height from floor to underside of canopy 2m
2) Air replacement based on 75-85% of extracted air
3) Temperature of replacement air must not be below 10C when coming into contact with
cooked food
4) Maximum duct velocity 1200 feet per minute
5) Plastic flexible ducting should not be used to extract from kitchen canopies, as it is very
difficult to clear and would constitute a fire hazard. Steel ductwork should be used, with
adequate access panels for cleaning. n special cases, flexible metal ducting could be
used, but only where it is short enough to be easily dismantled for cleaning or replacement.
Canopy grease filters are necessary to remove the bulk of the oil and fat droplets from the
air before it passes along ducting and through extract fans.
6) Ensure ample air replacement openings well distributed to eliminate local draughts and to
spread the supply of fresh air. Some air replacement from adjoining rooms is not a
disadvantage as the flow of air through the doorways will reduce the possibility of fumes
from the kitchen passing through to these adjoining rooms. Extract units should be
switched on as soon as any cooking apparatus is in use to prevent a build-up of hot fumes,
and should be left running for 20 to 30 minutes after cooking is finished to clear away any
residual fumes and hot air convected from the cooker surfaces.
7) Where a fish fryer is used no fire dampers should be fitted in the ventilation extract duct
unless any statutory requirement exists otherwise but adequate cleaning facilities should be
provided.
8) Canopy, ducting and lagging should be made from non-combustible material. Where
ducting passes through other floors between the kitchen and the external weathering cowl,
it should be enclosed in fire-resisting construction at least equal to the standard of fire
resisting construction at least equal to the standard of fire resistance required in the floor.
____________________________________________________________________________
Laboratory VentiIation & ChemicaI Storage Areas
1) Provide a minimum of ten air exchanges per hour.
2) The ventilation system should shut down when the fire alarm is activated and be capable of
manual restarting.
3) Pressure differences should be maintained such that air flows from low to high hazard
spaces.
4) Dilution ventilation systems should have the capacity to increase air flow under emergency
conditions such as a spill.
5) All chemicals should be maintained in a properly designed chemical storage area. This
includes flammables, poisons and corrosives cabinets. The venting of flammables cabinets
is not recommended, unless local codes require it. The National Fire Protection Association
standards do not require venting but if the cabinet is vented it must not compromise the
cabinet. f you vent the cabinet be sure you consult with an engineer or industrial hygienist
to avoid compromising the cabinet or violating the code.
LocaI Exhaust VentiIation for Fume hoods:
1) The chemical fume hood is the primary engineering control for limiting exposure in
laboratories and often serves as the OSHA designated area
2) Locate the fume hood to avoid doorways, high traffic areas, windows or any other structure
which might create disruptions in air flow. Note: A hood having a face velocity of 100 fpm is
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 51 oI 52
equivalent to an air flow rate of 1 mile per hour. Opening or closing a door can create a 5
mph air flow and compromise the fume hood.
3) The hood should have a face velocity of 60-100 fpm of non turbulent air.
4) The hood should be equipped with an airfoil to reduce turbulence at the hood opening.
5) The top slot of the hood should be fixed at 0.5-0.75 inch open and the bottom slot should
be full open. Note: Consult the manufacturer's recommendations to achieve maximum
efficiency.
6) The fan should be located outside the building.
7) Exhausts should be located away from air intakes and should project above the roofline.
NFPA Standards require a minimum of 7 feet.
8) Fume hoods should be equipped with a velocity indicator. deally the hood should be
equipped with a velocity alarm.
9) Fume hoods should not be used to store chemicals or equipment.
10) The minimum amount of equipment and/or chemicals for the specific procedure should be
in the fume hood.
11) Locate equipment at least 6 inches behind the sash opening.
12) Never work in fume hood with the sash open more than the safe operating position. This
should be clearly marked on the side of the hood.
13) When conducting demonstrations involving the sudden release of energy, be sure the sash
is closed completely and that all cracks are covered.
14) Before using the fume hood, conduct a brief visual inspection to confirm that the slots are
not blocked, that the hood is providing the required face velocity, that the sash is not
cracked and that it slides freely and that no obvious defects are present.
15) The fume hood should be tested at least quarterly and an inspection sticker affixed to the
side of the hood. Do not use fume hoods without inspection stickers or hoods having
expired stickers.
16) Exhaust hoods and canopies should be designed to capture the unwanted fumes or dust
irrespective of other air currents in the vicinity.
17) Because of the normally large volumes of ventilation air required all means of heat recovery
should be considered.
____________________________________________________________________________
DiIution VentiIation V/s LocaI Exhaust Systems - A Comparison
n general a system employing the dilution method will usually be indicated where the
contaminant originates at scattered points dispersed generally throughout the area. A
combination of local exhaust and dilution methods is often economical since well designed
exhaust hoods or openings removing the bulk of the contamination will greatly reduce the air
volumes required for dilution purposes. There are advantages and disadvantages to the use of
either dilution ventilation or local exhaust ventilation in terms of costs and effectiveness. Table
below compares the two types.
DiIution VentiIation LocaI Exhaust VentiIation
Advantages Disadvantages Advantages Disadvantages
Usually lower Does not completely Captures Higher cost for
www.PDHcenter.com PDH Course M208 www.PDHonline.org
Page 52 oI 52
DiIution VentiIation LocaI Exhaust VentiIation
Advantages Disadvantages Advantages Disadvantages
equipment and
installation costs.
remove
contaminants.
contaminant at
source and removes
it from the workplace.
design, installation
and equipment.
Requires less
maintenance.
Cannot be used for
highly toxic
chemicals.
Only choice for highly
toxic airborne
chemicals.
Requires regular
cleaning, inspection
and maintenance.
Effective control for
small amounts of
low toxicity
chemicals.
neffective for dusts
or metal fumes or
large amounts of
gases or vapors.
Can handle all sorts
of contaminants
including dusts and
metal fumes.
Effective control for
flammable or
combustible gases
or vapors.
Requires large
amounts of heated or
cooled makeup air.
Requires smaller
amount of makeup air
since smaller
amounts of air are
being exhausted.
Best ventilation for
small dispersed
contaminant
sources or mobile
sources.
neffective for
handling surges of
gases or vapors or
irregular emissions.
Less energy costs
since less makeup air
to heat or cool.
___________________________________________________________________________
Assessment
Various techniques can be used in the assessment of building ventilation systems and their
effectiveness. These include:
1) Measurement of air velocities could be done either in the ductwork to enable air flows to be
calculated or in the room to detect air movement. Measurement in the room is often difficult
because velocities are low, typically less than 60 FPM.
2) The use of visualization techniques, for example, smokes generators, to show the pattern
of air movement.
3) The use of tracers gases such as sulphur hexafluoride or particles such as potassium
iodide to detect and trace air movement through a building. Tracer gases can also be used
to measure actual ventilation air change rates in the building. This is done by releasing the
tracer once and then measuring the rate of decay (i.e. fall in concentration) or by
continuously releasing tracer gases at a known rate and measuring the equilibrium
concentration.
4) Monitoring for airborne contaminants from a process or combustion equipment and
monitoring for carbon dioxide from building occupants.
Note that for tracers or for airborne contaminants is a specialized technique and should be
carried out be competent people with suitable equipment.
__________________________________________________________________________