Hazardous Goods Hazardous Goods Storage Facilities Storage Facilities
Hazardous Goods Hazardous Goods Storage Facilities Storage Facilities
Hazardous Goods Hazardous Goods Storage Facilities Storage Facilities
A code of practice for the design and construction of static storage facilities, including static tanks, pipelines and pumping systems for facilities storing and transferring hazardous goods in bulk
Published by the: Explosives and Dangerous Goods Division Occupational Safety and Health Service Department of Labour New Zealand August 1989
ISBN 0-477-03440-3
CONTENTS
1. GENERAL 1.1 Introduction 1.2 Definitions 1.3 Limits of this Code 1.4 Legislation 1.5 Approval of Installations 1.6 Welding of Tanks and Pipelines 1.7 Hazard and Operability Studies 1.8 Containment of Spillage, Bunding 1.9 Code and Standard Organisations 1.10 Engineers Certificates 1.11 Repairs to Tanks and Pipelines 1.12 Fire Protection 1.13 Depot Security, Maintenance and Equipment Protection 1.14 Electrical Bonding 1.15 Training of Operators 1.16 Lining of Tanks and Pipelines 1.17 Colour Coding and Labelling 2. STATIC STORAGE TANKS 2.1 General 2.2 Approval Requirements 2.3 Stainless Steel Tanks 2.4 GRP Tanks 2.5 Approved Design Specifications 2.6 Tank Heating 2.7 Testing 2.8 Corrosion Protection 2.9 Tent Venting 2.10 Other Fittings 2.11 Decommissioning Class 3 Tanks 2.12 Recommissioning Used Tanks 3. PIPELINES 3.1 General 3.2 Types of Pipelines 3.3 Design Codes 3.4 Wharf Pipelines 3.5 Testing 3.6 Operations and Maintenance 3.7 Emergency Repair Procedures 3.8 Leak Detection Systems 3.9 Corrosion Protection 3.10 Loading and Unloading Facilities 3.11 Supports
4. EQUIPMENT 4.1 Valves 4.2 Heaters 4.3 Flanges, Fittings and Pipe 4.4 Pumps 4.5 Miscellaneous 4.6 Class Ratings 5. PRESSURISED PIPEWORK AND TANKS 5.1 General 5.2 Tanks 5.3 Valves and Fittings 5.4 Pumps and Compressors 5.5 Pipework and Hoses 5.6 LPG Low Pressure Systems 5.7 Testing 5.8 Decommissioning LPG Tanks 6. HAZARDOUS AREAS AND ELECTRICAL EQUIPMENT 6.1 General 6.2 Sources of Ignition 6.3 Electrical Installations within Hazardous Areas 6.4 Hazardous Areas 6.5 Ventilation APPENDICES Appendix A Appendix B Appendix C Appendix D Appendix E Appendix F Appendix G Appendix H Pipeline Test Sheet Static Tank Design Sheet Engineers Certificate Approval of Installation Storage Otherwise than in bulk Recommended Gas Freeing Methods Fire Protection Principles International Flammibility Classifications
SECTION 1: GENERAL
1.1 Introduction
1.1.1 This code is intended to supplement the Dangerous Goods (Class 3 Flammable Liquids) Regulations 1985 and Dangerous Goods (Class 2Gases) Regulations 1980 and their subsequent amendments, extending their provisions clarifying areas of approval, approved specifications and approved materials. 1.1.2 This code also clarifies areas of regulatory responsibility between the Department of Labour, Ministry of Transport and Ministry of Energy with respect to the storage and transfer of dangerous goods. 1.1.3 This code applies to any static facility storing Class 2 or Class 3 dangerous goods in bulk constructed after the date of introduction of this code. 1.1.9 It is not the function of this Department to act as a design consultant, however, this Department is required to assure itself that the facilities are designed and constructed to sound principles including acceptable codes and standards. 1.1.5 In the event that this code or the applicable regulations do not fully cover the installation, tanks or pipework or any part of it, an applicable specification may be used with the approval of the Department of Labour.
1.2 Definitions
The following definitions of terms apply throughout this code. Where any term used is not defined below, the meaning of that term shall be that defined by the Dangerous Goods Act and Regulations. 1.2.1 Approved Means that the item referred to is approved by an Inspector of Dangerous Goods. 1.2.2 (a) Class 3(a) Flammable Liquids Liquids, mixtures of liquids, and liquids containing solids in solution and suspension, which in each case has a flash point lower than 230C. A few examples of some such liquids are petrol, acetone, methanol, and ethanol. (b) Class 3(b) Flammable Liquids As above with flash point no lower than 230C and 610C or lower. (c) Class 3(c) Fuel oil. 1.2.3 Class 2(d) LPG (liquified petroleum gas) a substance which is composed predominantly of mixtures of propane (C3H8). and butane (C4H10). HAZARDOUS GOODS STORAGE FACILITIES 5
1.2.4 Tank A vessel exceeding 250 litres water capacity used for storage of Class 2(d) (LPO) or Class 3 (flammable liquids) in bulk. Tanks may be of the following types: (a) Fixed Tank tank which is permanently mounted on supports. (b) Skid Tank A tank designed for temporary storage and suitable for transportation from one location to another. (c) Horizontal Tanks tanks where the centreline of the cylindrical section is horizontal: - generally has dished ends and is mounted on saddle supports; - generally small (thousands of litres) and may be under pressure; (d) Vertical Tanks tanks where the centreline of the cylindrical section is vertical. - has a coned bottom and fixed or floating roof; - generally large and at atmospheric pressure; (e) Underground Tanks varied with depth of cover related to location and traffic loadings. 1.2.5 Ullage The ullage of a container is the air space left when the container is nominally full so that any expansion of the liquid will not cause over flow or excessive hydraulic pressure. The ullage space is to be measured at 150C. 1.2.6 Maximum Capacities All capacities quoted are water capacity (tank full) at standard temperature and pressure. Capacity of installations, whether a single tank or multi-tanks define isolation distances, tank operation, etc. Refer relevant regulations.
1.4 Legislation
1.4.1 Ministry of Energy Under the Petroleum Act of 1937 as amended 1982 the Ministry of Energy has jurisdiction over pipelines, conveying natural gas (above 200 kPa), oil, minerals, or dangerous goods not including: (a) any bulk storage installation; (b) any pipeline wholly within the plant boundary, generally including all pipework on the plant side of the pig receiver.
Where a leak detection system is installed as part of the pipeline, the associated pipework and equipment is covered by the Petroleum Act. (The appropriate jursidiction is decided on a case-by-case basis by the Ministry of Energy and Department of Labour); (c) any pipeline between a bulk installation and a transfer system (other than another pipeline) unless the product is LPG. (Note the Ministry of Energy and Department of Labour can modify this requirement.) Under the Gas Act 1982, as amended 1987, the Ministry has jurisdiction over low pressure distribution of CNG and LPG (for vapour LPG, low pressure is defined as not more than 7 kPa and up to 200 kPa with dual jurisdiction with the Department of Labour). 1.4.2 Ministry of Transport (Marine Division) This Ministry of Transport is responsible for the pressure containment under the Boilers Lifts and Cranes Act. In the normal commercial and industrial environment the Marine Division is responsible for all safety containment functions which include design, materials. manufacture. workmanship, erection or installation. inspection, testing, commissioning, control. operation, maintenance and repair of: (a) all steam raising and steam generating equipment and their associated piping containing steam or feedwater; (b) all steam filled pressure vessels and their associated piping; (c) all pressure vessels and their associated pumps, compressors. relief and/or control valves, plus all associated piping which contain: air; liquified gases; hydrocarbon, gas and vapours; hydrocarbon liquids containing gases and vapours: cryogenic substances: and any mixtures of these; where pressure relief is designed to occur above 206 kPa. The term associated piping, as used above refers to piping which forms part of the boiler or pressure vessel and does not refer in any way to pipelines as defined in the Petroleum Act 1937. 1.4.3 Department of Health Under the Toxic Substances Act 1979 and subsequent regulation, the Department of Health has jurisdiction over installation, storage and transferring Class 6 (Toxic Substances) and Class 8 (Corrosives). 1.4.4 Department of Labour Under the Dangerous Goods Act 1974 and the subsequent regulations the Department of Labour has jurisdiction over installations and pipelines storing and transferring dangerous goods of Class 2, 3, 4 and 5 including pipelines as follows: (a) within designated tank farm areas; (b) for the reception of raw materials; (c) for the distribution of processed product; HAZARDOUS GOODS STORAGE FACILITIES 7
(d) for the supply of water for fire services. 1.4.5 In cases where jurisdiction overlaps, it is normal for the departments to agree on the extent of jurisdiction and for one Department to look after the interests of the other. In all cases, the higher requirements (e.g. in pressure testing) govern and are to be adhered to.
ASME IX API 1104 Other acceptable welding specifications are: BS 2971: Specification for Class II arc welding of carbon steel pipework. BS 2640 Specification for Class II oxy-acetylene welding of carbon steel pipework. 1.6.3 All welding of aluminium components shall comply with AS 1665: (SAA Aluminium Welding Code) with procedures qualified under BS 4870: Pt 2 Approval testing of welding procedures and approval of welders under BS 4871: Pt 2 Approval testing of welders working to approved welding procedures. 1.6.4 Inspection of the welding shall be carried out in accordance with the welding specification, and to be generally as follows: (a) verification of material; (b) verification of filler material; (c) qualification of welding procedures; (d) qualification of welders to the above procedures; (e) inspection of production welds. Visual testing may be carried out to to BS 5289: 1983 Code of practice for visual inspection of fusion welded joints. 1.6.5 Inspection is to be carried out by properly qualified personnel. In particular, testing laboratory registration under the TELARC system is required with personnel qualified under the CBIP scheme (Certification Board for Inspection Personnel). 1.6.6 As part of the approval of each unit, certification that this testing has been carried out and passed is to be sent to the Department of Labour. The documents from the above inspections are to be available for inspection at any time. The Department reserves the right to utlise an independent inspector or inspection agency at the cost of the owner to check the welding or construction if it considers that some aspect does not conform to the requirements of the specification or as specified in this code.
(including local authority and Department of Labour) and a representative of the Fire Service. ALSO refer to Administrative Guidelines for the Appraisal and Control of Major Accident Hazards in New Zealand issued by the Department of Labour.
NZS 4503:1974 Code of practice for the distribution, installation and maintenance of hand-operated fire fighting equipment for use in buildings. NZS 4504:19B1 Fire hose reels. NZS 4541P:1972 Rules for automatic fire sprinkler installations. BS 5306 Code of practice for fire extinguishing installations and equipment on premises (Part 1, 2, 3, 4, 5) NFPA National Fire Codes, including: - NFPA 11 Foam Extinguishing Systems - NFPA 12B Halon 1211 (BCF) Fire extinguishing systems. - NFPA 15:1985 Water spray systems for fire protection. - API 2001 Fire Protection in Refineries (5th Edition 1974). Also refer Dangerous Goods (Class 3 - Flammable Liquids) Regulations 1985, Regulation 72 and 171-191 (inclusive). 1.12.3 The Petroleum Industry Emergency Action Committee operates a scheme for the fire protection of bulk installations involving consultation and collaboration between the Oil Companies, the Fire Service and the Chief Inspector of Dangerous Goods. Generally, the oil companies provide the equipment and material, as agreed, for use by the fire brigade at each centre where there are oil company installations. The brigade is responsible for the supply of water although each company may install hydrants or other equpment within their installation (depending on requirements and/or company policy) for the convenience of the brigade. The standard of protection involves a minimum of mechanical air-foam and hand-operated generating nozzles (the foam is to be compatible and suitable for use with either salt or fresh water). The minimum rate of foam application is 7.4 litres of foam compound solution (before aeration) per minute for each square metre of horizontal surface of the largest diameter Class 3A tank for 30 minutes application. For further information on equipment and maintenance refer PIEAC Manual. 1.12.4 It is recommended that a fixed foam system should be permanently installed on fuel storage tanks. Alternatively, mobile foam monitors may be used but are not favoured because of: (a) time taken to set up equipment; (b) difficulties in approaching the fire; (c) foam would be less effective because of high impact. There are two main types of fixed foam systems for tanks: (a) base injection near bottom of tank foam floats through liquid and layers on the surface; (b) top pourer from above the liquid.
Base or sub-surface injection is preferred in a fixed or cone roof tank (and for cone roof tanks with internal covers) for the following reasons: (a) foam flow through the liquid carries cold liquid to the top layers reducing vapour production; (b) equipment unlikely to be damaged during an explosion or fire; (c) base injection can be installed cheaper and is more likely to be better maintained. Base injection of foam shall only use foam acceptable and proven in these conditions with the specific product. Top pourers are preferred for fuel with either a low flashpoint (less than 40C) and a low boiling point or with high viscosity at storage temperatures (generally greater than heavy fuel oil). Also top pourers are essential on tanks containing polar solvents because the foam cannot pass through a polar liquid and still function effectively. With a floating roof tank, where fire would initially occur in the rim seal area, foam systems are designed to pour foam into the annular space between the tank wall and a dam on the floating roof. Fluoroprotein foams are normally used here because of minimal contamination by fuel and good burn-back resistance. Horizontal tanks generally do not require foam protection, only water for cooling. Portable foam monitors may be used for cone roof tanks less than 15m diameter or under 9 m high. Ground level monitors are not recommended for use against floating roof rim fires because of the excessive amount of foam required, the difficulty of accurate placement and the considerable weight of foam on the roof. Monitors on trucks are preferable in this case. Portable monitors are also effective in fighting spill fires.
a depot area. Use of tools or equipment that constitute a source of ignition (where required for equipment maintenance or erection) are allowed within such an area if the work is carried out in accordance with approved procedures. 1.13.4 Precautions are to be taken where equipment damage from vehicular traffic is a possibility, e.g. by crash barriers or bollards. Note also that underground vessels are to be similarly protected, e.g. by barriers or a concrete slab cover.
(a) the material of the tank or pipeline is substantially immune to attack by the materials to be storage therein; or (b) the material of the tanks or pipeline is thin enough to withstand at least 10 years normal service without being reduced at any point to a thickness less than the minimum thickness specified under the design specification; (c) The chemical reaction between the material of the tank or pipeline and the commodity to be transported therein is such as to allow proper passivation or neutralisation if it is not frequently cleaned and not used for other commodities.
2.1.5 Filling ratios and ullages for fixed roof tanks and vessels (a) For flammable liquids and low concentration acids and alkalis: 97% degree of filling = 1 + a(Tr - tf) (b) For high concentration toxic liquids and high concentration acids and alkalis: 95% degree of filling = 1 + a(Tr - tf) where a = mean coefficient of cubical expansion of the liquid between the mean temperature of the liquid during filling (tf) and the maxima mean bulk temperature (Tr) and is calculated as follows: a = d15 - d50 35 x d50 in which dl5 and d50 are the densities of the liquid at 150C and 500C respectively. (c) If the tank contents are heated above 500C, the above does not apply. In this case, the degree of filling shall be such that the tank is not filled to more than 95% of its capacity at any time. (d) Ullage is calculated as (100% deg of filling). (e) Under no circumstances shall the ullage be less than 2% or the degree of filling greater than that calculated as above.
Also refer Seismic Design of Storage Tanks, published by the NZ National Society of Earthquake Engineering. 2.2.5 In lieu of full design check to an approved specification, a letter of compliance including calculations and drawings shall be supplied, via District Offices to Head Office signed by a Registered Engineer, stating that design is in accordance with the approved specification (see Appendix C). 2.2.6 All tanks to be permanently fitted with a corrosion resistant nameplate in accordance with the design specification, showing a minimum of: manufacturers name basic vessel data including: tank material and thickness design specification design pressure and temperature nominal capacity product and specific gravity
tank number (specific to each tank) LAB number (approval number where applicable).
2.2.7 Inspection of tank and installation, including sighting of certification, is required before approval will be given for operation.
storage. Specific approval is required full supporting details of design and materials are required for each application; (c) for structural strength use at least 40% glass; (d) concrete supports of adequate design are required; (e) hold-down straps of minimum width 400 mm are to be used.
Part 2 - Austenitic Stainless Steel. - operation up to 4000C. covers external pressure, jacketed vessels and tube plates. not applicable where wall thickness less than 2.5 mm. minimum pressure limit based on diameter. static liquid head only. Sizes in multiples of 1.2m sq bolted sections. Temperature not be exceed l00OF. maximum working pressure 40 kPa; maximum internal vacuum 10 kPa; temperature range 10C to 150C. above ground with saddle supports and underground tanks, dished ends. BS 2654 Vertical Steel Welded Storage Tanks. specifically for the petroleum industry. carbon steels, generally Gr 43 and above.
design temperature -10C minimum. minimum plate thickness 5mm (for diameter smaller than 15m). three types: atmospheric pressure - maximum pressure 7.5 kPa, maximum low pressure - maximum pressure 20 kPa, maximum vacuum 6 kPa. high pressure - maximum pressure 56 kPa, maximum vacuum 6 kPa. vacuum 2.5 kPa.
BS 4741 Vertical Cylindrical Welded Steel Storage Tanks for low-temperature Service. Temperature to -50C. pressure not to exceed 14 kPa, and vacuum no lower than 6 mbar; notch ductility and impact requirements; generally low carbon steels (similar to BS 2654). temperature between 0OC and 100C; maximum pressure 500kPa.
BS 5387 Vertical Cylindrical Welded Storage Tanks for Low-temperature Service: Double-wall tanks for temperatures down to -196C. (cryogenic) pressure not to exceed 14 kPa. Aluminium and steel alloys. (supersedes BS 1500 and BS 1515); not for vessels for transport or atmospheric storage; steel and aluminium.
AS 1692 Steel Tanks for the Storage of Flammable and Combustible Liquids. six categories of tank. Up to 150 m 3 and above using alternative codes. Includes stainless steel, covers design, construction and testing. generally for pressures above 100 kPa.
* AS 1210 Unfired Pressured Vessels AS 1727 Tank Containers (International size). NZS 1841 Fusion Welded Tanks (for water supply, generally steel). * NZS 2213 Fusion Welded Pressure Vessels for General Purpose (BS 1500). (Since withdrawn and superseded by BS 5500). NZS 5418: 1983 - Part 1 Transportation Containers for Hazardous Substances.
from IMDG Code for Type 1 and Type 2 tanks (IMO) for 10 ft and 20 ft 150 module base sizes; see Note 2.
NZS 7521 Underground steel storage tanks for the petroleum industry (non-pressurised, horizontal, cylindrical flat-ended). Capacities between 5.000L and 50, 000L * ASME Unfired Pressure Vessels, Section VIII. for pressures over 100 kPa. ID, width, height or cross-section over 150mm.
API 620 Recommended Rules for Design and Construction of Large, Welded Low-Pressure Storage Tanks. steel only, temp not to exceed 100C, pressure 0.5 psi to 15 psi. temp not to exceed 100C, pressure not to exceed 17 kPa. (0.5 psi) steel only. API 650 Welded Steel Tanks for Oil Storage.
API 12B Bolted Product tanks (12th Edition 1977) (see Note 1). API 12D Field Welded Tanks for Storage of Production Liquids (9th Edition 1982) API 12F Shop Welded Tanks for Storage of Production Liquids (8th Edition 1982) ASTM D4021-81 Glass Fibre Reinforced Polyester Underground Petroleum Storage Tanks. NS 1545 (Norwegian Standard under NVS) Horizontal, cylindrical glass fibre reinforced polyester (GRP) petroleum storage tanks 1.2 to 50 m 3. NOTE: 1. API 12B is not approved for Class 3A products due to nature of product. Some situations however may require use of this type of tank full details of proposal to be submitted to Chief Inspector for approval. NOTE 2. Containers to NZS 5418 (multi-modal) are approved for storage under the following additional conditions: (a) container to be approved by Marine Division, Ministry of Transport; (b) containers manufactured to approved specifications are approved by an acceptable approving authority. 2.5.3 General principles of tank design are as follows: (a) Floating roof tanks there are recommended for the storage of Class 3A liquids and for 3B and 3C liquids stored at temperatures at or above their flash points (roof pontoons shall be maintained free from leaks and be properly bonded in accordance with accepted practice to prevent rim fires). Crude oils may also be stored in these tanks.
(b) Covered floating roof tanks these may be used as above with a diameter no greater than 46m (due to floating roof binding on columns). Tanks are to be vented to API 650 where necessary. Rim fires are much less frequent with this design. (c) Cone roof tanks are preferable for Class 3B and 3C liquid, but not to be used if the vapour space is explosive at storage temperature unless it is inert gas blanketed. Tank vents to API 2000 shall be fitted. (d) Cone roof tanks with internal floating covers if the cover is made of combustible material it is to be treated as a cone roof tank. For the storage of volatile liquids the tanks are to have venting in accordance with API 650 installed.
2.6.3 For heating liquids above their flashpoints the following additional requirements shall be met: (a) Inert blanket to be used over liquid this may be a flammable vapour of the liquid, provided no oxygen is present. (b) The inert blanket shall be vented to a flare unless vapour recovery is used. (c) Procedure for tank cleaning and maintenance to be drawn up ensuring no hazardous situations arise. (d) Shall have interlock between tank heater and level control, such that heater can never be operated without liquid cover. (e) Tank heater shall be to good oil field practice. Refer API 12K Specification for Indirect-Type Oil Field Heaters.
2.7 Testing
2.7.1 Above-Ground Tanks Before entering service all above-ground tanks shall be tested for liquid tightness as follows: (a) vertical tanks to be tested, also to prove their foundations, by filling them to their maximum liquid capacity with water; (b) all other tanks shall be tested either with air at 35 kPa or water such that every part of the tank is subjected to the maximum static head. The test pressure shall be held for a sufficient period such that the tank is thoroughly inspected for tightness and unacceptable deformation. Recommended minimum period is 30 minutes. All tanks designed and constructed to an approved specification shall be tested in accordance with that specification or as above (whichever is the strictest requirement). Tanks containing products with specific gravities above 1.0 may be required to be tested differently (see design specification). 2.7.2 Underground Tanks Before entering service and while the tank is in the pit and before backfilling, the tanks are to be tested as follows: (a) with air or water to a pressure of 35 kPa (measured at the level of the bottom of the tank); (b) a certificate to be supplied to the licensing authority stating that the tank is free from leaks; (c) an Inspector may be required to witness the test; (d) if product head is higher than 4 m, the Inspector may require a higher hydraulic test pressure.
(b) Approved venting facilities design may include provision for inbreathing (vacuum relief) and outbreathing (pressure relief) under normal and emergency conditions. 2.9.3 Under normal conditions, including filling and discharge, excess pressure shall be relieved by a vent. These shall be screened with brass gauge of 500 microns nominal aperature size. The vent shall be no smaller than the filling or discharge connection and shall be sized on the maximum anticipated simultaneous flow. Generally internal pressures not to exceed design pressure of 17 kPa for atmospheric tanks. Vent outlets shall be arranged such that the discharge does not impinge on any part of the tank. 2.9.4 Venting shall be designed to an approved specification (e.g. API 2000 Venting Atmospheric and Low Pressure Storage Tanks, 3rd Edition 1982). 2.9.5 Flame arrestors may be required to be fitted.
SECTION 3: PIPELINES
3.1 General
3.1.1 The design, fabrication, assembly, test and inspection of piping systems containing liquids shall be suitable for the expected working pressures, temperatures and structural stresses. The materials used shall be compatible with the products. Above-ground pipelines shall be protected from mechanical damage. Pipelines outside bulk oil premises shall preferably be placed underground. 3.1.2 Low melting point materials (metals and non-metals) may be used underground for all liquids but above ground and outdoors only under the following conditions: (a) they are protected against fire exposure; (b) any leak, fire, etc will not unduly expose people or property; (c) they are located such that any leakage can be readily isolated. Non-metallic pipework shall not be used unless specifically approved by the Chief Inspector. Proof of manufacture to acceptable standards is required. Pipework to be designed and installed to the manufacturers specification including: (a) temperature range; (b) pressure rating, including vacuum where applicable; (c) assembly, installation and support recommendations. 3.1.3 All pipe joints shall be liquid tight. All joints shall be readily accessible for inspection and repair. 3.1.4 All flexible hoses connecting pipelines to vessels shall be of approved quality with a safe working pressure at least 50% higher than the actual working pressure. 3.1.5 All pipelines with heating facilities shall comply with AS 1940, Section 7.6 or equivalent. 3.1.6 Threading of pipeline may be carried out in accordance with generally acceptable standards including: BS 21:1973 Pipe threads for pressure tight joints. API 5B: Specification for Threading, Logging and Thread Inspection of Casing, Tabing and Line Pipe Threads. AS 1722 Pipe threads of Whitworth form (Pt 1 and Pt 2).
3.1.7 Miscellaneous BS 729 Hot dip galvanised coating on iron and steel articles. AS 1650 Galvanised coatings. 3.1.8 Pipelines shall be located such that in the event of a leak or emergency, unimpeded access is available. In particular underground pipelines shall
ANSI B 31:8 Gas Transmission and Distribution Piping Systems. BS 3351:1971 Piping Systems for Petroleum Refineries and Petrochemical Plants. similar to B31:3, also includes materials for low temperature service.
NZS 5223 Code of practice for high pressure gas and petroleum liquids pipelines. DOT Departmental of Transportation (USA) Code of Federal Regulations.
API 1102 Recommended Practice for Liquid Petroleum Pipelines Crossing Railroads and Highways (5th Edition1981)
3.5 Testing
3.5.1 All pipelines, except as below, shall be tested after construction and prior to commissioning as follows: (a) In accordance with the design specification; (b) In accordance with the Dangerous Goods (Class 3 Flammable Liquid) Regulations 1985. Where it is impractical to test the line as above, alternative arrangements may be used as approved by the Chief Inspector. Also refer API RP 110 Recommended Practice on Pipeline Hydrostatic Testing. 3.5.2 In the event where the design specification does not fully cover the testing procedure, Regulation 89 of the Dangerous Goods (Class 3 Flammable Liquid) Regulations 1985 is to be complied with, as follows: (a) Test pressure 1.5 times maximum working pressure or 750 kPa minimum with water as test medium;
(b) Pipeline to remain above test pressure for 24 hours minimum; (c) Constant reading to be taken of pressure and temperature of test medium. The test will be considered successful if there are no leaks and any pressure variation can be related to temperature variation. 3.5.3 In addition to the above, all oil pipelines (excluding those solely used for operations within licensed premises) shall be maintained as follows: (a) Shall be examined by the owner or representative at least once every five years; (b) Shall be hydraulically tested (as 3.5.1) at six-monthly intervals or two-monthly intervals, if kept full of water. Test pressure 1.5 times maximum working pressure and may be carried out full of product. Test pressure to be held without loss for either 8 hours minimum (buried lines) or 4 hours minimum (uncovered lines). Results of tests to be kept by line owner or representative for inspection. (c) A greater frequency of testing may be required by the Chief Inspector, if circumstances dictate. It is recommended that pipelines within licensed premises are maintained to a similar standard. 3.5.4 All flexible hoses used for connecting pipelines to vessels shall be regularly inspected both internally and externally. Hoses shall be tested at intervals of six months maximum or 1000 pumping hours (whichever comes sooner). Results to be kept for inspection.
3.11 Supports
3.11.1 Pipe supports shall be designed to withstand all foreseeable loads, including temperature variation, seismic forces and wind forces. They shall also offer the piping system protection from physical damage and excessive stresses from settlement, vibration, explansion and
contraction. The installation of non-metallic piping shall be in accordance with the manufacturers instructions. 3.11.2 Supports shall be constructed to general sound engineering principles including: (a) Concrete to NZ 3104 steel reinforcement to NZ 3402P concrete pipes to NZ 3107.
(b) Structural steelwork to generally acceptable NZS, BSS or AS specifications: bolts, nuts and washers to AS 1110 and A1112 galvanising to BS 729 blast cleaning to BS CP 2008:1966 or 515 testing of welds to BS 709
SECTION 4: EQUIPMENT
4.1 Valves
4.1.1 General Piping systems shall contain sufficient valves to properly operate the system and protect the plant. To include as follows: (a) All equipment to be capable of being isolated for removal or repair; (b) Check valves to be installed where backflow is undesireable. 4.1.2 Valve Standards BS 1414 Flanged and butt welding end steel outside Screw-and-yoke wedge gate valves for the petroleum industry. BS 1868 Flanged steel check valves for the petroleum industry. BS 1873 Flanged steel globe valve for the petroleum industry. BS 2080 Steel valves for the petroleum, petrochemical and allied industries. Summary of face-to-face dimensions of flanged ferrous valves for the petroleum industry. BS 3952 Cast iron butterfly valves (withdrawn). BS 5146 Steel valves for the petroleum, petrochemical and allied industries: Inspection and test Part 1 and 2. BS 5150 Cast iron wedge and double disc gate valves for general purposes. BS 5325 Steel wedge gate, globe and check valves, 50 mm and smaller for the petroleum, petrochemical and allied industries. BS 5351 Steel Ball valves for the petroleum, petrochemical and allied industries. BS 5353 Plug Valves. API 600 Steel gate valves flanged and buttwelding ends. API 602 Compact design carbon steel gate valves for refinery use. ANSI B16.34 Valves flanged and buttwelding end, additional requirements may be specified, e.g.: API RP 6F Recommended practice for fire test for valves API 607 Fire test for soft-seated ball valves. FM 6033 (Factory Mutual) fire safe valves.
4.2 Heaters
4.2.1 Indirect heaters shall be designed and constructed to:
API 12K Indirect type oil-field heaters design specification, including heat calculations, generally for water bath heaters.
ANSI B16.10 Steel Pipes. ANSI B36.19 Stainless steel pipes (note Schedule 5S and 10S do not permit threading in accordance with ANSI B2.1). BS 3601 Steel pipes and tubes for pressure purposes. BS 1387 Steel pipes and tubulars suitable for screwing to BS 21 pipe threads. AS 1074 Process piping (identical to BS 1387). AS 1836 Refrigerant piping (was ammonia piping). AS 1450 Circular steel tubes for mechanical and general engineering purposes (structural tubing).
4.4 Pumps
4.4.1 Pumps pumping Class 3 products shall be approved and shall be installed in an approved location. 4.4.2 Pumps installed in hazardous areas shall comply with the requirements for the area.
4 5 Miscellaneous
4.5.1 Small piping for instrumentation purposes shall be austenitic stainless steel to ASTM A312-806 or ASTM A403 806 or equivalent. Also acceptable are ASTM A213, A249 and A269. Joints using compression type fittings shall have a maximum pipe size of 12.5 mm nominal bore and a minimum bursting pressure of four times the maximum operating pressure. Copper pipe shall comply with BS 2017:1983 (withdrawn) or BS 2871 Part 1 1971. Also refer to AS 1432 Seamless copper tubes (Types A, B. C and D) intended for use in water, gas and sanitary plumbing installations. The manufacturers recommendations are to be followed in the design and construction of instrument tubing. See information by Crawford Filling Company for Swagelok tube fittings, etc. 4.5.2 Gaskets shall be to B5 2815 Grade A for compressed asbestos fibre (or equivalent) or ASTM requirements for spiral wound. 4.5.3 Bolting shall be carbon steel to B5 4882 (UNC thread) or ASTM A193 and A194 or equivalent. 4.5.4 For inspection of equipment also refer to API Guides for Inspection of Refinery Equipment (Chapter I-XX and Appendix).
This is based on carbon steel (e.g. ASTM A105 material) at a service temperature of -20 to 100C. Note that different materials and temperatures will have different ratings.
5.2 Tanks
5.2.1 The materials of construction shall be steel alloy or other as approved by Marine Division, Ministry of Transport. Refer section 2.5 for list of acceptable specifications. noting that approval by Marine Division, MOT is required. 5.2.2 For the purposes of the regulations and this code 0.5 kg of LPG is regarded as equivalent to one litre.
The maximum filling ratio of LPG shall be such that: (a) The container does not become liquid full at a temperature of less than: for tanks 5,0001 and below 47.5 C for tanks exceeding 5,0001 45C
(b) The liquid will not exceed 97% of total liquid capacity under normal conditions of storage. The maximum filling ratios as given below will comply with the above requirement:
For tanks 5,000L and below n - butane iso - butane propane 0.533 0.512 0.449 For tanks exceeding 5,000L 0.535 0.515 0.454
For mixtures, use filling ratio to comply with (a) above. 5.2.3 The maximum pressure attained by LPG at a temperature of 40C (for containers over 5,000L but not exceeding 26,000L) or 40C (for containers exceeding 26,000L) shall be used for the minimum allowable working pressure of the vessel. 5.2.4 For other gases contained under pressure refer Dangerous Goods (Class 2 - Gases) Regulations 1980.
Also refer API RP 520 - Recommended Practice for the Design and Installation of Pressure - Relieving Systems in Refineries, Parts 1 and 2. 5.3.2 For LPG service the following shall also apply: (a) All liquid pipelines and vapour lines should be seamless and conform to BS 3601 or equivalent. (b) Vapour lines operating below 480 kPa (70 psi) may conform to BS 1387 (medium or heavy gauge) or equivalent. (c) Copper tubing should be seamless conforming to BS 2017 or equivalent. For vapour service above 480 kPa copper tubing should not exceed 12.5 mm nominal bore. (d) Flanges and fittings for liquid and vapour lines shall be to BS 1560 or equivalent. Flanges on vapour lines operating below 480 kPa may conform to BS 10 or BS 4505. Bolting shall be to BS 4882 or equivalent. 5.3.3 All pipelines shall be supported with adequate flexibility allowing for thermal and other stresses.
required duty. Design shall be to an approved code (BS 3351 is acceptable for above-ground and underground piping). Piping, valves and fittings shall be located, protected and secured to provide protection from damage. Screwed joints shall only be used on 50 mm diameter pipe and smaller. Pipework shall be maintained free from leaks. 5.5.2 Flexible hose shall be of an approved type and shall be marked with the design working pressure (together with LP GAS or LPG for LPG hose) or the number of the specification to which it was manufactured. Hoses which may be subjected to container pressure shall be tested to the design working pressure without leaking. Also refer to BS 3212:1975 Flexible Tubing or Hose for Use in Butane/Propose Gas Installations. 5.5.3 For liquefiable gases, a relief valve shall be installed between two shut-off valves in any pipe and shall discharge to a safe location. 5.5.4 The following requirements are to be followed for pressurised pipework (in particular LPG) installed underground: (a) Pipework to be underground only where necessary and to be installed separately from other services and in any case not in general service ducts. Pipework maybe installed in ducts that are filled with sand or equivalent. (b) Pipe shall be protected from corrosion by coating, and cathodic protection or earthing. Care to be taken to protect the coating during backfilling (backfill to consist of clean soft sand approximately 150mm in depth). (c) Pipes to be well identified on entry and exit from ground with warning notices if necessary.
5.7 Testing
The pipework shall be tested in accordance with the design specification and Marine Division, MOT, requirements at least once every 5 years. This includes a hydrostatic test and a leak test (e.g. soap bubble). Where possible during construction, underground lines should be tested before backfilling. HAZARDOUS GOODS STORAGE FACILITIES 39
Flexible hoses shall be tested as follows: (a) Visually once every month. (b) Hydrostatically at a pressure not less than the design pressure once a year. A written record of every test shall be kept by the operator.
In addition, the following relate to specific equipment, some of which is in a hazardous area: NZS 5425:1980 Part 1 Code of practice for CNG compressor and refuelling stations. AS 1593 Electrical equipment for explosive atmospheres. AS 1939 Classification of degrees of protection by enclosures. AS 2229:1979 Part 1 and 2. Electrical equipment for explosive atmospheres (dispensary systems). (Also see AS 1829, 1482, 1826) AS 2380 Electrical equipment for explosive gas atmospheres. BS 4533 Part 2, Section 2 Light fittings for Division 2 areas. 6.3.3 Electrical apparatus for potentially explosive atmospheres is divided by BS 5501:1977 Part (European Standard EN 50 014) into: Group I: electrical apparatus for mines susceptible to firedamp. Group II: electrical apparatus for places with a potentially explosive atmosphere. For certain types of protection Group II is subdivided according to the nature of the potentially explosive atmosphere for which it is intended. In these cases subdivisions A, B and C are prescribed based on the maximum experimental safe gap (MESG) for flameproof enclosures or on the minimum ignition current (MIC) for intrinsically safe electrical apparatus. 6.3.4 Electrical apparatus shall be tested and certified and marked for a particular explosive atmosphere by an acceptable testing organisation, e.g. BASEEFA (British Approvals Service for Electrical Equipment in Flammable Atmospheres), UL (Underwriters Laboratories) and FM (Factory Mutual). See also BASEEFAs List of Certified Electrical Equipment.
Zone 2 (BS 5345) or Class 1 Zone 2 (MP 6105). explosive mixtures not likely to occur under normal operation or, if so, only for short time.
Under MP 6105 there are two classes of hazardous areas: Class I - Hazardous Gases and Vapours Class II - Hazardous dusts, fibres or flyings (with Division I and Division II) NOTE: Some standards divide Class II into Class II (combustible gases) and Class III (Ignitable fibres or flyings) see National Electrical Code (USA). 6.4.3 The following codes and standards are approved for use in delineating hazardous areas: NZ 6101:1972 P (Provisional) Classification of hazardous locations. IP Model Code of Safe Practice Area Classification. AS 2430 Classification of hazardous areas. Part 1: Explosive gas atmospheres. Part 3: Specific occupancies. API RP 500C Classification of Locations for Electrical Installations of Pipeline Transportation Facilities. 6.4.4 Several factors affect the classification of areas where flammable liquids or vapours are present: (a) legislation regulations; (b) flash point of substance; (c) flammable limits of substance; (d) auto-ignition temperature. MP6105 classifies electrical equipment in terms of its maximum surface temperature.
CLASS T1 T2 T3 T4 T5 T6 MAX SURFACE TEMP 0C 450 300 200 135 100 85
(e) rate of vapour release; (f) ventilation of area; (g) probability of vapour release; (h) specific location and features.
6.5 Ventilation
Ventilation, either natural or forced, should be employed to discharge vapours clear of unapproved electrical equipment ducts shall discharge into open air and vent openings must not be situated close to an opening in a building. Systems shall ensure that under normal working conditions the vapour concentration will not exceed 25% of the lower flammable limit of the vapour.
APPENDIX A:
PLANT: OWNER OF PLANT: PRODUCT: LPG/3A/3B/3C/OTHER: DATE OF TEST: DESCRIPTION OF PIPEWORK: SIZES: LENGTH: PLANT DESIGN CODE: DESIGN PRESSURE: TEST PROCEDURE: TEST MEDIUM: LOCATION OF TEST GAUGE: CALIBRATION: TIME START 1HR 2HR 3HR 4HR COMMENTS: PRESSURE TEMPERATURE SIGN COMMENTS AIR/HYDRAULIC ADDITIVES: TEST PRESSURE: IN GROUND: EXPOSED:
I HEREBY CERTIFY THAT THE PIPEWORK DESCRIBED AND TESTED AS ABOVE HAS BEEN TESTED AND ACCEPTED FOR OPERATION IN ACCORDANCE WITH THE DESIGN CODE REQUIREMENTS AS REQUIRED UNDER THE DANGEROUS GOODS ACT 1974. SIGNED: WITNESSED: DATE: NOTES: 1. Attach any information or drawings showing relevant pipework 2. Test Procedure to be approved by Inspector of Explosives 3. Refer: (a) Dangerous Goods (Class 3 - Flammable Liquids) Regulations 1985 (b) Dangerous Goods (Class 2 - Gases) Regulations 1980
APPENDIX B:
1. OWNER: SERVICE: 2. TANK: MANUFACTURER: DESIGN CODE: DESIGN TERM: DIMENSIONS: CAPACITY: MATERIAL: SHELL THICKNESS: END DESIGN: Base Roof HOLDING DOWN: SEISMIC DESIGN: WIND DESIGN: 3. NOZZLES: INLET: OUTLET: MANWAY: OTHER: FLANGES: 4. EQUIPMENT: END THICKNESS: Base Roof DESIGN PRESSURE:
5. DRAWINGS:
6. COMMENTS:
APPENDIX C:
current Annual Practising Certificate certify that I have inspected the design/construction (delete as required) of
(description of plant/equipment) and made such detailed examinations and checks as I considered necessary and it is my opinion that: the design is in accordance with (state codes or specifications) the construction is in accordance with good and widely accepted engineering practice and the design as shown on the drawing list attached. The inspection has been carried out in accordance with the requirements of the design code. I have witnessed and/or verified non-destructive testing/hydrotesting. This tank/installation is subject to further conditions as follows:
Therefore, I recommend that this tank/installation be approved under the Dangerous Goods (Class 3 - Flammable Liquids) Regulations 1985/Dangerous Goods (Class 2 - Gases) Regulations 1980.
Signed:
APPENDIX D:
APPROVAL OF INSTALLATIONS
1. Underground Tanks
Before the installation of any underground tank intended for the storage of dangerous goods of Class 3 the installer shall, not less than one week prior to the installation of the tank, notify the licensing authority of the proposed installation giving the following details of the proposal. This information is required by the Dangerous Goods Inspector when approval is requested and a form of application for licence to store Dangerous Goods is to be completed. (a) General details including name of owner and address. (b) Function of installation, i.e. whether bulk installation, etc. (c) Mode of delivery to installation. (d) Site plans showing layout of all equipment. (e) Details of tanks including specification, foundation, fittings and corrosion protection. (f) Certificate of test to be supplied after installation. (g) Details of tank tagging.
2. Bulk Installation
Inspection of bulk installations will generally be carried out to the following checklist: (a) Details of installation including owner, tanks (number and capacities). (b) Initial approval of installation plans subsequent modifications conditions of approval, etc. (c) Bonding whether effective, especially in view of modification. (d) Drainage and flame traps. (e) Bonding and earthing, including, cathodic protection systems of tanks and pipelines. (f) Tank operation including vents, level devices, stop valves operation and condition. (g) Electrical equipment - correct type for hazardous area (including forklift trucks). (h) General tidiness, notices, fencing. (i) Operator training on hazards and emergency procedures. (j) Tankwagon parking. (k) Tankwagon/rail tanks car filling/discharging facilities.
(1) Drum facilities filling, isolation, notices, etc. (m) Pipelines maintenance, valves, check of test records. (n) Fire fighting facilities maintenance and operation, communication with Fire Service. For pressurised systems and tanks (e.g. LPG installations) the following additional checks will be carried out: (a) Tank valves and other fittings to comply including pressure gauge, contents gauge, excess flow valves, external shut-off valves, drain valves; (b) Vapourisers; (c) Pipeworks, including flexible hoses, relief valves; (d) Medium pressure system (200kPa 7kPa) including valves, flexible connections, pressure relief, certification of installation by qualified gas fitter; (e) Underground pipework including corrosion protection, pipe coating.
APPENDIX E:
is total quantity if total quantity over 5,000 litres minimum compound capacity of one half total quantity or 5,000 litres. 6. Other construction requirements include: (a) no artificial light or fittings which could be a source of igniteshall be installed inside the depot; (b) depots shall be ventilated at high and low levels by openings direct to the open air above the compound level. Openings shall be covered with brass gauze of 500 microns nominal aperture size.
APPENDIX F:
APPENDIX G:
1 Halon Systems
The halon family of chemical fire extinguishing agents was developed for commercial use after World War II. Three fluorinated compounds are generally recognised: Halon 1301 (CF3Br) used extensively in fixed systems in North America. Halon 2402 (c2F4Br2) used predominantly in Eastern Europe. Halon 1211 (cF2clBr or BCF) used in portable fire extinguishers. These compounds do not corrode or damage equipment and will result in a minimum of decomposition products during use on a fire. Many halon 1301 systems are based on total flooding in a closed area. The level of 1301 required is less than that at which significant toxic effects have been reported but sufficient to suppress the fire regardless of the exact site of it. Halon 1301 is generally stored in liquid form within cylinders, pressurised to 2480 kPa (360 psi) with nitrogen which provides the pressure to discharge the halon within the time required (refer NFPA standards, etc.). The system is generally designed to rapidly mix halon and air to a specified concentration (generally 5% v/v).
2 Foam Systems
(a) Foam systems consist of a water supply, foam concentrate, a proportioner (mixes foam and water in the desired proportions usually 3 - 6%) an aspirator (mixes air with the foam solution) and an applicator (applies foam to the fire). The foam concentrate is required to meet acceptable requirements (e.g. UL). There are six basic types of foam concentrate: 1. protein foam (P) 2. fluoro protein foam (FP) 3. synthetic foam (S) 4. aqueous film forming foam (AFFF) 5. film forming fluoroprotein foam (FFFP) 6. alcohol resistant foam (AR). These are generally divided into three types with the following charactertistics: 1. Low expansion up to 20:1 (P. FP, AFFF, FFFP): These have good water retention and heat resistance with long term stability. Also they flow readily and can be thrown long distances but have limited volume and fill capacity.
2. Medium expansion from 21:1 to 200:1 (S. FP, AFFF, FFFP): These have medium properties of the low expansion type but cannot the thrown long distances as they are affected by the wind. 3. High expansion from 201:1 to 1000:1 (S): These are very voluminous and cannot be thrown as they are severely affected by the wind. Also they have limited water retention, heat resistance and stability. The foam is required to be stable for long-term storage. Some foams are corrosive and require special conditions of storage to prevent sludge formation. Foam shall be formulated specifically for use in conditions where ambient temperature is below 12C and it shall not be heated above 38C. (b) Chemical foam is produced by the reaction of an alkaline and an acid solution. These are two basic systems: 1. Stored solution (wet storage) requires large tanks, pumps and a fixed piping system. 2. Dry powder - uses trooper-type generators where water is mixed with the powder when the foam is required either a single or two (A and B) powder system is used. For large diameter tanks handling the amount of powder required is a problem therefore use of chemical foam is not recommended. Rates of application of foam are prescribed in various standards, e.g. NFPA 11. For open top floating roof tanks greater than 46 m diameter, fixed systems are recommended.
3 Water Supply
In addition to water for foam systems, water is required for tank cooling. In general, for large installations, the fire water mains shall be arranged as a loop or grid system. The design water flow is generally based on the largest tank requirement plus cooling for adjacent unshielded tanks. The system should also be designed to provide at least o90kPa residual hydra.- pressure when cooling streams are used. If fire trucks supply additional Taxiing water this may be reduced. Generally, ring mains are 200 mm diameter minimum and have a sufficient number of isolation valves such that fire protection is maintained if a pipe section is damaged or broken.
Halon 1301 Fire Extinguishing Systems 1985 Halon 1211 Fire Extinguishing Systems 1985 Installation of Sprinkler Systems 1987 Standpipe and Hose Systems for Fire Protection Deluge Foam-Water Sprinkler Systems and Foam-Water Spray Systems 1986 Dry Chemical Extinguishing Systems 1985 Wet Chemical Extinguishing Systems 1986 Wetting Agents 1986 Centrifugal Fire Pumps, Installation of 1987
APPENDIX H:
France:
Category A vapor pressure in excess of one atmosphere at 15C Category A.1 stored at less than 0C Category A.2stored under other conditions Category B flash point up to and including 55C Category C flash point above 550C up to and including 100C Category D flash point above 100C
Germany:
flash point below 21C flash point at and above 21C, to and including 55C flash point above 55C to 100C vapor pressure greater than one atmosphere at 37C flash point of 21C or less flash point above 21C up to and including 55C flash point above 55C up to and including 100C
Holland:
Italy:
Category A flash point below 21C Category B flash point from 21C up to and including 65C Category C flash point above 65C
Sweden:
flash point of 21c or less flash point above 21C up to and including 30C flash point above 30C up to and including 60C flash point above 60C flash point below 22.8C flash point from 22.8C up to and including 65.6C flash point above 65.6C flash point below 37.8C flash point below 22.8C and boiling below 37.8C (100F) flash point below 22.8C and boiling at or above 37.8C (100F) flash point at or above 22.8C and below 37.8C flash point at or above 37.8C and below 60C flash point at or above 60C flash point at or above 93.4C, flammable liquids are Class 1 and combustible liquids are Class II and IIIA
UK:
United States: Class I Class IA Class IS Class IC Class II Class IIIA Class IIIB