Guide Specifications
ZTS Series
Automatic Transfer Switches
An automatic closed transition transfer switch shall be furnished as specified herein.

ISO 9001

I
1

General

1.1 The transfer switch shall be rated for the voltage and ampacity as shown on the plans and shall have 600 volt insulation on all parts in accordance with NEMA standards. 1.2

1.7 Transfer switches shall comply with the applicable standards of UL, CSA, ANSI, NFPA, IEEE, NEMA and IEC. 1.8

The transfer switches shall be supplied with a microprocessor based control panel as detailed further in these specifications.

The current rating shall be a continuous rating when the switch is installed in an unventilated enclosure, and shall conform to NEMA temperature rise standards.

Sequence of Operation

1.3 The unit shall be rated based on all classes of loads, i.e., resistive, tungsten, ballast and inductive loads. Switches rated 400 amperes or less shall be UL listed for 100% tungsten lamp load. 1.4 As a precondition for approval, all transfer switches complete with accessories shall be listed by Underwriters Laboratories, under Standard UL 1008 (automatic transfer switches) and approved for use on emergency systems. 1.5 The withstand current capacity of the main contacts shall not be less than 20 times the continuous duty rating when coordinated with any molded case circuit breaker established by certified test data. Refer to required withstand and close ratings as detailed in this specification. 1.6 Temperature rise tests in accordance with UL 1008 shall have been conducted after the overload and endurance tests to confirm the ability of the units to carry their rated currents within the allowable temperature limits.

2.1 The ATS shall incorporate adjustable three phase under and over-voltage and three phase under and over-frequency sensing on the normal source. 2.2 When the voltage of any phase of the normal source is reduced to 80% or exceeds 110% nominal voltage, or frequency is displaced 2 Hz from nominal, for a period of 0-10 seconds (programmable) a pilot contact shall close to initiate starting of the engine generator. 2.3 The ATS shall incorporate adjustable three phase under and over-voltage and three phase under and over-frequency sensing on the emergency source. 2.4 When the emergency source has reached a voltage value within +/- 10% of nominal and achieved frequency within +/- 5% of the rated value, the load shall be transferred to the emergency source after a programmable time delay. 2.5 When the normal source has been restored to not less than 90% of rated voltage on all phases, the load shall be retransferred to the

830 West 40 th Street Chicago, IL 60609 USA Phone: 630 850-6880 Fax: 630 850-6899

GS-1101B (6/98)

E-Mail: [email protected] www.zenithcontrols.com

normal source after a time delay of 0 to 30 minutes (programmable). The generator shall run unloaded for 5 minutes (programmable) and then automatically shut down. The generator shall be ready for automatic operation upon the next failure of the normal source.
2.6

d. Touch pad test switch with Fast Test/Load/No Load positions to simulate a normal source failure. e. Time delay to override momentary normal source failure prior to engine start. Field programmable 0-10 seconds (adjustable by increments of 0.1 second) factory set at 3 seconds. Time delay on retransfer to normal source, programmable 0-60 minutes (adjustable by increments of 0.1 minute) factory set at 30 minutes. If the emergency source fails during the retransfer time delay, the transfer switch controls shall automatically bypass the time delay and immediately retransfer to the normal position.

If the engine generator should fail while carrying the load, retransfer to the normal source shall be made instantaneously upon restoration of proper voltage (90%) on the normal source.

f.

2.7 Inspection and operational tests shall be conducted by the contractor in the presence of the engineer, to indicate that the switch satisfies the specifications. 2.8 The transfer switch shall be equipped with a microprocessor based control panel. The control panel shall perform the operational and display functions of the transfer switch. The display functions of the control panel shall include ATS position and source availability. 2.9

g. Time delay on transfer to emergency, programmable 0-5 minutes, factory set at 1 second. h. Terminals for remote test/peak shave operation and transfer inhibit to the emergency source. i. An in-phase monitor shall be provided. The monitor shall compare the phase angle difference between the normal and emergency sources and be programmed to anticipate the zero crossing point to minimize switching transients. Auxiliary contacts (1 N.O.) shall be provided to indicate normal and emergency source availability.

The digital display shall be accessible without opening the enclosure door and shall be provided with a 4 line by 20 character LCD display screen with touch pad function and display menus. The programming functions shall be pass code protected.

2.10 The control panel shall be provided with menu driven display screens for transfer switch monitoring, control and field changeable functions and settings. 2.11 The control panel shall be optoisolated from electrical noise and provided with the following inherent control functions and capabilities:

j.

a.

Multipurpose display for continuous monitoring and control of the ATS functions and settings. All field changeable functions shall be pass code protected and accessible through the keypad.

k. A load/no load clock exerciser shall be incorporated within the microprocessor and shall be programmable to start the engine generator set and transfer the load (when selected) for exercise purposes on a weekly basis. The exerciser shall contain a lithium battery for memory retention during an outage. l. A timed auxiliary contact (1 N.C.) adjustable 0-60 seconds shall be provided to allow motor loads to be disconnected prior to transfer in either direction.

b. Built-in diagnostic display that includes the capturing of historical data, such as number of transfers and time on emergency power source, for ease of troubleshooting. c. Capability for external communication and network interface through an RS 485 serial port.

m. Provide a momentary pushbutton to bypass the time delays on transfer and retransfer and programmable commit/no commit control logic.

Zenith Controls, Inc. GS-1101B

2.12 Note to Specifier: Please see attached list of additional accessories available (found under specifier notes #3) and insert in this section as required.

Any Molded Case Breaker *


Size (Amps) Amps RMS Symmetrical

Up to 150

10,000 30,000 35,000 50,000 100,000

Construction and Performance

151 - 1260 261 - 1400 401 - 1200 1201 - 4000

3.1 The automatic transfer switch shall be of double throw construction operated by a reliable electrical mechanism momentarily energized. There shall be a direct mechanical coupling to facilitate transfer in 6 cycles or less. 3.2

Specific Coordinated Molded Case Breaker

The normal and emergency contacts shall be mechanically interlocked such that failure of any coil or disarrangement of any part shall not permit a neutral position.

Size (Amps)

Amps RMS Symmetrical

Up to 150 151 - 1260 261 - 1400 401 - 1600 601 - 1200 1201 - 4000

30,000 42,000 50,000 65,000 85,000 100,000

3.3 For switches installed in systems having ground fault protective devices, and/or wired so as to be designated a separately derived system by the NEC, a 4th pole shall be provided. This additional pole shall isolate the normal and emergency neutrals. The neutral pole shall have the same withstand and operational ratings as the other poles and shall be arranged to break last and make first to minimize neutral switching transients. Add-on or accessory poles that are not of identical construction and withstand capability are not acceptable. 3.4

All values 480 volt, RMS symmetrical, less than 20% power factor.

3.6 A dielectric test at the conclusion of the withstand and closing tests shall be performed. 3.7 The automatic transfer switch manufacturer shall certify sufficient arc interrupting capabilities for 50 cycles of operation between a normal and emergency source that are 120 degrees out of phase at 480 volts, 600% of rated current at .50 power factor. This certification is to ensure that there will be no current flow between the two isolated sources during switching. 3.8

The contact structure shall consist of a main current carrying contact which is a silver alloy with a minimum of 50% silver content. The current carrying contacts shall be protected by silver tungsten arcing contacts on all sizes above 400 Amps.

3.5 The transfer switch manufacturer shall submit test data for each size switch, showing it can withstand fault currents of the magnitude and the duration necessary to maintain the system integrity. Minimum UL listed withstand and close into fault ratings shall be as follows: Current Limiting Fuse
Size (Amps) Amps RMS Symmetrical

All relays shall be continuous duty industrial type with wiping contacts. Customer interface contacts shall be rated 10 amperes minimum. Coils, relays, timers and accessories shall be readily front accessible. The control panel and power section shall be interconnected with a harness and keyed disconnect plugs for maintenance. Main and arcing contacts shall be visible without major disassembly to facilitate inspection and maintenance.

Up to 4000

200,000

3.9

Zenith Controls, Inc. GS-1101B

3.10 A manual handle shall be provided for maintenance purposes with the switch de-energized. An operator disconnect switch shall be provided to defeat automatic operation during maintenance, inspection or manual operation. 3.11 The switch shall be mounted in a NEMA 1 enclosure unless otherwise indicated on the plans. 3.12 Switches composed of molded case breakers, contactors or components thereof not specifically designed as an automatic transfer switch will not be acceptable. 3.13 The automatic transfer switch shall be protected by Zeniths 2/5/10 year warranty or the equivalent. 3.14 The automatic transfer switch shall be Zenith ZTS Series or approved equal.

NFPA 110: IEEE 241:

Standard for emergency and standby power systems I.E.E.E. recommended practice for electrical power systems in commercial buildings I.E.E.E. recommended practice for emergency and standby power systems

IEEE 446:

NEMA ICS 2-447: AC automatic transfer switches UL 50/508: ICS 6: ANSI C33.76: NEMA 250: IEEE 472: EN55022: Enclosures Enclosures Enclosures Enclosures (ANSI C37.90A): Ringing wave immunity (CISPR11): Conducted and radiated emissions (Exceeds Class B: EN55011 & MILSTD 461 Class 3) (Level 4): ESD immunity test (ENV50140): Radiated RF, electromagnetic field immunity test Electrical fast transient/burst immunity test IEEE C62.41: Surge immunity test (1.2 x 50Fs, 5 & 8 kV) (ENV50141): Conducted immunity test Voltage dips and interruption immunity

Specifier Notes:
1. Standard dropout voltage is 80%, pickup 90% of nominal. Settings are adjustable. Specify pickup/ dropout if other than factory standard is desired. ZTS switches are in conformance with the applicable portions of: UL 1008: Underwriters Laboratories standard for automatic transfer switches C22.2 No. 178 certified at 600 VAC 947-6-1 certified at 480 VAC National Electrical Code including use in emergency and standby systems in accordance with Articles 517, 700, 701, 702 Essential electrical systems for health care facilities Life safety code

EN61000-4-2: EN61000-4-3: EN61000-4-4: EN61000-4-5: EN61000-4-6: EN61000-4-11:

2.

CSA: IEC: NFPA 70:

3.

NFPA 99: NFPA 101:

Listed below are other frequently requested optional features which are available for ZTS transfer switches: B F Battery Chargers Fan Contact: Closed when engine runs (S.P.N.O.)

Zenith Controls, Inc. GS-1101B

Time Delay - Engine Start: Non-adjustable delay on starting engine after normal failure. Factory set at 3 seconds; includes Accessory E Heater and Thermostat Frequency Meter Meters: M1 M2 M3 M4 Ammeter: Single phase Ammeter: Three phase with phase selector switch Voltmeter: Single phase Voltmeter: Three phase with phase selector switch

S14

Retransfer to normal/test/auto (key operated)

HT K M

Test Switch: A pushbutton (momentary) test switch is standard on all ZTS Automatic Transfer Switches; MX200 microprocessor switches are standard with load/no load and fast test (with load) modes and are pass code protected; other selector switches, available at additional cost, include: 6A 6B 6C Maintained Auto Maintained Test Maintained Auto - Momentary Test (key operated) Maintained Auto - Maintained Test (key operated)

P2

Extended Time Delay Engine Start: Adjustable 0.5 to 300 seconds Inhibit Transfer to Normal: Input circuit to inhibit transfer to normal; 120 VAC or 24 VDC Load Shed Control (ZTS): Input to remote circuit for load shed from emergency to dead normal; 120 VAC or 24 VDC

Q7

Many additional accessories are available to meet your installation requirements. Consult your Zenith representative with your project needs.

R15

R15D Load Shed Control (ZTSD): Input to remote circuit for load shed from emergency to center-off position; 120 VAC or 24 VDC S Selector and Disconnect Switches: S1 S2 Three-position selector switch; Stop/Test/Automatic Disconnect switch in series with Accessory E to disconnect engine starting circuit Source selector switch circuit to select either source as primary Combination auto/manual retransfer selector switch Automatic/manual operation for ATS
Zenith Controls, Inc. GS-1101B

S3 S5 S12

830 West 40th Street Chicago, IL 60609 USA

Phone: 630 850-6880 Fax: 630 850-6899 www.zenithcontrols.com E-Mail: [email protected]

GS-1101B 1998 Zenith Controls, Inc.