Zelio Logic Relays

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

Zelio-Logic Relays

SR1

Catalog

File 8501

03

CONTENTS Description Page Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Overview of Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Wiring Diagrams and Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Zelio-Logic Relay
Overview
Overview

The Zelio-Logic relay is more than a typical relay. It will accept inputs, and has relay outputs like a programmable controller, but can not be connected to a network. Because it has timers, counters and clocks that can be programmed, this product is ideal for applications where a typical relay, timer or time clock isnt enough, but a PLC is not justified. The Zelio-Logic relay is designed for use in small automated systems. It can be used in industrial and commercial applications. Its small size and ease of programming provides a competitive alternative to traditional relays, timers and counters. Zelio-Logic relays with four outputs will accept a 60 line program. Zelio-Logic relays with eight outputs will accept a 80 line program. Programming in Zelio-Soft can be done in ladder logic, electrical symbols or Zelio symbols. The ease of programming, ensured by the universality of the contact language, meets all automation requirements and also the needs of the electrician. The versions without display or buttons provide not only a competitively priced solution, but also the confidentiality of the program (blind version). Programming can be carried out: - independently, using the buttons on some smart relays, - on a PC, using Zelio Soft software, - on a Pocket PC, using Zelio Soft Pocket PC software. Description
SR1A, SR1B

Main Zelio-Logic Screen

1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11.

12. 13.

Retractable mounting feet Power supply terminals LCD display (4 lines, 12 characters) Screw terminal input connection Input terminals (0-10 V analog or 24 Vdc discrete) Delete or Cancellation button Insert a new line button Navigational keys or Input keys in RUN mode Selection or validation button Escape button Slot for memory back-up EEPROM cartridge or cable connection for down loading or uploading of programs. Screw terminal relay output connections Marking area

1. 2. 3.

4. 6 7 8 9 10 11 13 12 1

Status of inputs RUN or STOP mode indication Indication of a parameter (day and time is default for relays with a clock) Status of outputs

123456 STOP MO 0 8 :2 9 1234

1 2 3 4

SR1D, SR1E

1. 2. 3. 4.

5.

6.

7. 8.

Retractable mounting feet Power supply terminals Screw terminal input connections Input terminals (0-10 V analog or 010 V discrete) only applicable to SR1-E U/RUN: operating LED Steady : power on, Stop mode, Flashing : Run mode Fast flashing : relay fault Slot for memory back-up EEPROM cartridge or cable connection for down loading or uploading of programs Screw terminal relay output connections Marking area

1 2

I1

I2

I3

I4

I5

I6

IB

IC

U/Run

6 7 1

Back-up memory Allows a program to be copied into another smart relay (examples: for building identical equipment, remote transmission of updates). The memory also allows a back-up copy of the program to be saved prior to exchanging the product. When used with a smart relay without display or buttons, the copy of the program contained in the cartridge is automatically transferred into the smart relay at power-up.

The dc relays have a fast input function FILT. This function allows faster detection of changes in state of the inputs. This mode should only be used when necessary as it makes the relay inputs more sensitive to interference and contact bounce. A Fast or Slow choice is available.

10/03

2001-2003 Schneider Electric All Rights Reserved

Zelio-Logic Relay
Overview

Function

Electrical Scheme

Ladder Language

Zelio Relay Symbol Notes

N.O. SPSTNO

Ix

Contact

14

I corresponds to the real image of the contact connected to the input of the module.

13

N.C. SPSTNC

ix

22

i corresponds to the reversed image of the contact connected to the input of the module.

21

Standard Coil
A2

Qx

The coil is energized when the contacts to which it is connected are closed.

A1

Latch Coil (Set)


A2

SQ

The coil is energized when the contacts to which it is connected are closed. It remains energized when the contacts re-open.

A1

Unlatch Coil (Reset)

RQ

ix will work the inverse of Ix.

Example:
STOP START M

A2

The coil is de-energized when the contacts to which it is connected are closed. It remains inactive when the contacts re-open.

A1

L1

M1 L1

L2

L2

I1

I2 Q1

Q1

i1

I2 Q1

Q1

OR

4 2001-2003 Schneider Electric All Rights Reserved


10/03

Zelio-Logic Relay
Overview of Functions
Overview of Functions

Ten Timers (provided as standard in all relays)


Each timer function can be programmed to function in one of the following eight modes:

TT 1 RT . t T . O t = 0 0 . 0 0 S

A
On-Delay

TT 1 RT . t T . O t = 0 0 . 0 0 S

a
On-Delay (with momentary input)

TT 1 RT . T . t O t = 0 0 . 0 0 S

C
Off-Delay

TT 1 RT . T . t O t = 0 0 . 0 0 S

B
One Shot

TT 1 RT . T . t O t = 0 0 . 0 0 S

W
One Shot (when input is removed)

TT 1 RT . T . t O t = 0 0 . 0 0 S

D
Repeat Cycle (with maintained input)

TT 1 RT . T . t O t = 0 0 . 0 0 S

d
Repeat Cycle (with momentary input)

TT 1 2 1 RT . T . O t = 0 0 . 0 0 S

T
Totalizing Timer with Reset

Each timer function has a preset time in one of four timing ranges: 00.00 s (1/100 of a second) 000.0 s (1/10 of a second) 00:00 M:S (Minutes: Seconds) 00:00 H:M (Hours: Minutes) Maximum of 99.99 seconds Maximum of 999.9 seconds (16.665 minutes) Maximum of 99:59 Maximum of 99:59

The time setting on each timer can be locked. A password is required to unlock the timer.

Ten Counters (provided as standard in all relays)


Count up and/or count down. Each counter function can have a preset value of 0000 to 9999. The counter setting on each counter can be locked. A password is required to unlock the counter.

For more information on these timers and counters, refer to the Users Manual #SR1MAN01EN.

10/03

2001-2003 Schneider Electric All Rights Reserved

Zelio-Logic Relay
Overview of Functions

Some Versions Come With Four 24 Hour - 7 Day Clocks:


1 ABCD TU

ON OFF

2 M 0 1

2 0 9 : 3 :

4 S 0 0

9 A 0 0

On each clock you can set: Start Day End Day Start Time Each Day End Time Each Day

Example: (Sunday or Monday) (Friday or Saturday) (08:30 or 9:15) (4:57 or 5:30)

The clock settings on each clock can be locked. A password is required to unlock the clock. Fifteen Internal Relay Functions (provided as standard in all relays) Each internal relay can have multiple contacts that can be used elsewhere in the program. Each relay can be either a standard relay, a latching relay, or an unlatching relay. The internal relays do not have connection points that could be used to control external loads. These relays give much more freedom in programming. Arrow Keys (4) on the Front of the Relay can be used as Inputs They can be used as push buttons in the program. Some of the 12 Vdc or 24 Vdc Versions have Analog Inputs Analog inputs are only available on some 24 Vdc devices.
Can be Used as Inputs

They can accept input values 0 through 10 V. The following seven functions can be performed on the analog inputs:
Type of Function
I B Ref

Description

A1 A n a l o g 1 R e f = 4.9 V O

Contact A1 is closed when the value of analog input IB does not exceed the reference voltage entered in the reference field, 4.9 V in this example.

I B

Ref

A1 A n a l o g 2 R e f = 4.9 V O

Contact A1 is closed when the value of analog input IB equals or exceeds the reference voltage entered in the reference field, 4.9 V in this example.

I C

Ref

A1 A n a l o g 3 R e f = 4.9 V O

Contact A1 is closed when the value of analog input IC does not exceed the reference voltage entered in the reference field, 4.9 V in this example.

I C

Ref

A1 A n a l o g 4 R e f = 4.9 V O

Contact A1 is closed when the value of analog input IC equals or exceeds the reference voltage entered in the reference field, 4.9 V in this example.

I B A1 O

I C

A n a l o g 5

Contact A1 is closed when the value of analog input IB does not exceed the value of analog input IC.

I B A1 O

I C

A n a l o g 6

Contact A1 is closed when the value of analog input IB equals or exceeds the value of analog input IC.

I C - H I B I C + H A1 O A n a l o g 7 H = 4.9V

Contact A1 is closed when the value of analog input IB is between IC-H and IC+H. H (the hysteresis) is entered in the H field, 4.9 V in this example.

Text messages can be entered using the Zelio-Soft software and then displayed on the relay.

6 2001-2003 Schneider Electric All Rights Reserved


10/03

Zelio-Logic Relay
Overview of Functions
ZELIO-SOFT: SOFTWARE
Zelio-Soft software enables: the entering of control wiring diagrams the monitoring of applications, using its test feature the programming of messages for display on the Zelio-Logic simplification of setting-up Input Modes for Control Wiring Diagrams The Zelio input mode enables the user to program the Zelio Relay via software using the same key strokes as used on the face of the Zelio Relay. The free input mode, which is more intuitive, is very user friendly and incorporates several additional features. Using Zelio-Soft in free mode enables the user to select their preferred symbol language from the following 3 alternatives: Zelio symbols Ladder symbols Electrical symbols The free input mode also enables the creation of notes associated to each line of the program. Instant switching between one input mode and another is obtained by clicking the mouse. Basic Programming Error Check and Applicable Language The basic programming error check feature of Zelio-Soft monitors the applications and an input error will turn the tool bar eye red. A mouse click on the eye will locate the problem. At any time, Zelio-Soft can be switched between 6 applicable languages (English, French, German, Italian, Portuguese and Spanish) including the editing of the application file. It also enables selection of the representation mode (Zelio, Ladder or electrical) for editing the file. Inputting Messages for Display on Zelio-Logic Zelio-Soft allows 4 Text function blocks to be configured, corresponding to 4 screens of 4 lines x 12 characters, which can be displayed on all the relays. These screens are activated in the same manner as a coil in the control scheme. It is then possible to display messages as text only or to associate them with 1 or 2 variables, the latter being current values, and/or setting of function blocks used in the program. Set-Up Simulation The Zelio-Soft simulator enables testing of all the programs, i.e.: activating the discrete inputs and their N.O. or N.C. contact modes (momentary or maintained) indicating the output states varying the voltage of the analog inputs IB and IC activating the pushbuttons simulating the application program in real time and accelerated time dynamically indicating in red the various active elements of the program

10/03

2001-2003 Schneider Electric All Rights Reserved

Zelio-Logic Relay
Overview of Functions
Zelio Soft Software for Pocket PC

L N

I1 I2 I3 I4 I5 I6

Del.

Ins.line

z1 z4 z2 z3

Esc.

Sel./OK

O1

O2

O3

O4

I1 I2 I3 I4 I5 I6 IB IC

O1

O2

O3

O4

L N

I1 I2 I3 I4

I5 I6 I7 I8

I9 IA IB IC

Del.

Ins.line

z1 z4 z2 z3

Esc.

Sel./OK

O1

O2

O3

O4

O5

O6

O7

O8

The Pocket PC allows: - full entry of control schemes, including the messages to be displayed on the smart relay screen (text blocks) - transfer of programs created with Zelio Soft on a PC to the Pocket PC and vice versa - transfer of programs created on a PC or on a Pocket PC to any smart module in the range and vice versa, as well as debugging of programs while connected or not connected to the smart relay The Pocket PC therefore avoids having to move the PC or smart relays for transfer and debugging of applications. It is particularly useful for setting up smart relays which do not have a display or buttons. Recommenced Pocket PCs (1): - Hewlett Packard Jornada 525 or 545, available under Telemecanique reference VW3-A8103pp - Hewlett Packard Jornada 545 and 548, to be ordered directly from an HP dealer - Compaq Ipaq 3630, to be ordered directly from a Compaq dealer - Casio Casiopeia EM 505, to be ordered directly from a Casio dealer Zelio Soft for Pocket PC Includes virtually all the functions of Zelio Soft software for PC: - inputting of control schemes in free input mode in a choice of 3 languages - Zelio, Ladder or electrical symbols - with associated comments - program coherence test - inputting of text function blocks (text only or text + variables) - supervision of programs (2) with: - on line display of the program and current values of function blocks - forcing of inputs, outputs, control relays and function block values - adjustment of parameters, date and time - switching from Stop to Run mode Program Test with Smart Relay Connected Supervision Mode The software can be quickly installed in the Pocket PC, via a PC, using a special installation CD (ref: SR1-SFT02). Exchange of files between the Pocket PC and PC is achieved by means of the Active Sync software (version V3.1 or greater) supplied with the Pocket PC. After the software has been installed, the Pocket PC can be used independently, as the only programming and adjustment tool for Zelio Logic smart. (1) Likely to change as Pocket PC manufacturers develop their ranges. Please consult your usual supplier. (2) Only with module versions greater than or equal to V1.7.

Input of a Control Screen

Configuration of a Time Delay Function Block

8 2001-2003 Schneider Electric All Rights Reserved


10/03

Zelio-Logic Relay
Application Data
Application Data

Environmental Characteristics
File E164866 File E164866 CCN NRAQ CNN NRAQ7 Guide 2252 01 C-Tick, GL

Product Certifications Degree of Protection Temperature Maximum Relative Humidity Altitude Mechanical Resistance Resistance to Electrostatic Discharges Resistance to HF Interference
Immunity to vibration Immunity to mechanical shock Immunity to electrostatic discharges Immunity to electromagnetic radiated fields Immunity to rapid, pulsed, transients Immunity to surges Immunity to damped oscillatory waves Operation Storage CSA File LR203359 CE IP 20

32 F to 131F (0 C to 55 C) conforming to IEC 60068-2-1 and 60068-2-2 -13 F to 158 F (-25 C to 70 C) conforming to IEC 61131-2 95% without condensation or dripping water 0 to 6500 ft (0 to 2000 m) Conforming to standard IEC 60068-2-6, test Fc Conforming to standard IEC 60068-2-27, test Ea Conforming to standard IEC 61000-4-2, level 3 Conforming to standard IEC 61000-4-3, level 3 Conforming to standard IEC 61000-4-4, level 3 Conforming to standard IEC 61000-4-5 Conforming to standard IEC 61000-4-12

Supply Characteristics Vdc


Smart Relay Type
Primary Voltage limits Nominal input current Heat dissipation Hold up time (loss of power) Protection

SR1Nominal voltage Including ripple V V mA W

B121JD

A101BD B121BD

A201BD B201BD

B122BD

Acceptable duration

12 24 10.4...14.4 19.230 105 83 1.3 1.6 1 ms, repeated 20 times Against polarity inversion

130 2.9

45 1.1

Supply Characteristics Vac


Smart Relay Type
Primary Voltage limits Nominal frequency Nominal input current Heat dissipation Hold up time (loss of power) Isolation Acceptable duration Primary / ground

SR1Nominal voltage Including ripple V V Hz mA W V

B101B
24 20.426.4 50-60 (4763) 80

B201B

A101FU B101FU
100...240 85...264

A201FU B201FU

130

3 5 10 ms, repeated 20 times 2000 (50-60 Hz)

100 Vac 50 240 Vac 27 3

100 Vac 80 240 Vac 40 5.3

Discrete 24 Vdc Input Characteristics


Smart Relay Type
Connection Nominal value of inputs State 1 State 0 Voltage Current Voltage Current Voltage Current State 0 to 1 State 1 to 0 3-wire 2-wire Between supply and inputs Between inputs Hz V mA V mA V mA k ms ms

SR1-ppppBD SR1-ppppJD
Input I1 to IA Screw terminals 24 12 3 3 15 6.5 > 1.8 > 1.6 <5 < 6.2 < 0.5 < 1.5 8 4 0.3 (fast)3 (slow) 0.5 (fast)5 (slow) Yes, Type 1 Yes PNP (only) No Resistive None None 60

SR1-pppBD

SR1-pppJD

Input switching limit values

Input impedance at state 1 Configurable response time Conformity to IEC 1131-2 Sensor compatibility Type of input Isolation Maximum counting frequency Minimum level under test conditions defined by the standards.

IB and IC Screw terminals 24 12 0.62 0.21 9.9 9.9 0.16 0.16 <5 <5 0.08 0.08 38 57 3 (not configurable) 5 (not configurable) No Yes No

10/03

2001-2003 Schneider Electric All Rights Reserved

Zelio-Logic Relay
Application Data
AC Input Characteristics
Smart Relay Type
Connection Voltage Nominal value of inputs Current Frequency At state 1 Input switching limit values At state 0 State 0 to 1 Response time State 1 to 0 Isolation Maximum counting frequency 50/60 Hz ms Between supply and inputs Between inputs Hz Voltage Current Voltage Current 50/60 Hz V mA Hz V mA V mA ms

SR1-pp01FU
Screw terminals 100240 0.65 (U = 115 V) 1.3 (U = 240 V) 4763 79 0.4 (U = 240 V) < 40 < 0.3 4550 (U = 110 V), 8590 (U = 240 V) 4550 (U = 110 V), 1822 (U = 240 V) None None 10

SR1-pp01B
Screw terminals 24 3 (U = 24 V) 4763 12 1.5 <5 < 0.6 1822 2325 None None 10

Integral Analog Input Characteristics


Smart Relay Type
Analog inputs Number of channels Voltage range of input Input impedance Maximum non destructive voltage Resolution Conversion time Precision Repeat accuracy Between analog channel & supply V k V

SR1-BpppBD

SR1-B121JD

Conversion

Isolation Wiring distance

@ 25 C @ 60 C @ 55 C V m

2 0-10 62.5 at 10 V 30 15 8 bits Relay cycle time 1.6% of the full range 2.9% of the full range < 0.1% of the full range None 10 m maximum with shielded cable (sensor not isolated)

Relay Output Characteristics (Screw Terminal Connections) (1)


Smart Relay Type Number of Outputs Operating Limit Values Contact Type Thermal Current Without common potential SR1-B121JD, SR1-p1p1BD, SR1-p201BD, SR1-p201FU, SR1-p101FU, SR1-p101B SR1-p201B 4 8 5-150 Vdc, 24-250 Vac N.O. 8A 24 Vdc 1.5 A 24 Vdc L/R = 10 ms 0.6 A 230 Vac 1.5 A 230 Vac 0.9 A 10 mA 17 V - 5 mA Failure rate for 100 million operating cycles: 1 10 Hz 0.5 Hz 10 2.5 kV 10 ms 5 ms None None 1 conductor: 0.141.5, cable: AWG26AWG16 2 conductors: 0.140.75, cable: AWG26AWG18 1 conductor: 0.142.5, cable: AWG26AWG14 1 conductor: 0.142.5, cable: AWG26AWG14 2 conductors: 0.141.5, cable: AWG26AWG16 0.6

DC-12 DC-13 Utilization category AC-12 AC-15 Minimum Switching Capacity Low Power Switching Reliability of Contact Maximum Operating Rate Mechanical Life Rated Impulse Withstand Voltage Response Time Incorporated Protection At 5 V minimum voltage

Electrical Durability for 500,000 Operating Cycles

No-load At le In millions of operating cycles Conforming to IEC 60947-1 Trip Reset Against short-circuit Against overvoltage and overload Flex cable with cable end mm2 mm2 mm2 Nm

Connection to screw terminals (Tightened using 3.5 screwdriver)

Semi-rigid cable Rigid cable Tightening torque

10 2001-2003 Schneider Electric All Rights Reserved


10/03

Zelio-Logic Relay
Application Data
Transistor Output Characteristics (screw terminal connections)
Smart Relay Type Number of outputs Operating limit values Loads Drop out voltage Response time Built-in protection With positive polarity common potential V Nominal voltage V Nominal current A Maximum current A At state 1 V Trip ms Reset ms SR1-B122BD 4 (PNP) 19.230 24 Vdc 0.5 0.625 at 30 V 2 for I = 0.5 A 1 1 Against overload and short-circuits Against overvoltage (2) Against inversions of power supply

(1) Characteristics at 55 C for 60 % loading of inputs/outputs or at 45 C for 100 % loading of inputs/outputs. (2) If there is no volt-free contact between the relay output and the load.

Processing Characteristics
Smart Relay Type SR1 Number of control scheme lines Maximum cycle time Response time (2) A1pppp, B1pppp 60 ms ms Day/time h Program and adjustments Current values and states (3) s A2pppp, B2pppp 80

Back-up time in case of power failure Program memory checking Clock drift Time delay block accuracy

6 8 12 to 24 14 to 26 (SR1-p201BD) (SR1-B121JD and p1ppBD) 22 to 42 20 to 40 (SR1-p201FU and p201B) (SR1-p101FU and p101B) 150 at 40 C only applicable to SR1-B and SR1-E (4) For life, internal EEPROM For life, internal EEPROM on smart relays SR1B/SR1E only (4) At each power-up y 6 per month 12 ms 0.5 % of the time displayed

(1) Minimum level under test conditions defined by the standards. (2) Time between change of state of an input and change of state of an output directly linked by the program in the same cycle (3) The values and states to be saved must be configured in the remanence menu (retains last known value of timers, counters, latching relays, and internal logic relays). (4) As from product version V1.7.

Zelio Soft Software for the PC


SR1Version 1.2 Version 1.3 Version 1.4 Version 1.5 Apppp Yes Yes Yes Yes Bp01B No No No Yes Bpp1BD Yes (3) Yes (5) Yes (5) Yes Bp01FU Yes (3) Yes (5) Yes (5) Yes B122BD No Yes (5) Yes (5) Yes B121JD No No No Yes Dpppp No No Yes Yes Epppp No No Yes (5) Yes

Zelio Soft

(3) Only for earlier version smart relays V1.1 and V1.2. (5) Only for smart relay versions V1.1, V1.2, V1.5 and V1.6.

10/03

2001-2003 Schneider Electric All Rights Reserved

11

Zelio-Logic Relay
Application Data

OPERATING CURVES
Electrical Durability (in millions of operating cycles) (conforming to IEC 60947-5-1)
DC Loads
DC-12 (1)
3.0
1.4

DC-13 (2)

Millions of Operating Cycles

2.5 2.0 1.5 1.0 0.5 0.0 0 0.5 1 Current (A) 1.5 2 48 V 24 V

Millions of Operating Cycles

L/R = 10 ms 48 V 1.2 L/R = 10 ms 24 V 1.0 0.8 0.6 0.4 0.2 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 L/R = 60 ms 48 V L/R = 60 ms 24 V

Current (A)

AC Loads
AC-13 (3)
3.0 Millions of Operating Cycles 2.5 24 V 2.0 48 V 1.5 Millions of Operating Cycles

AC-14 (4)
2.5 2.0 110 V 1.5 230 V 1.0 0.5 0.0 48 V 24 V

SR1101FU 1.0
0.5 0.0 0 0.5 1.0 1.5

110 V 230 V

2.0 2.5 Current (A)

3.0

3.5

4.0

4.5

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

Current (A)

AC-15 (5)
1.0

Millions of Operating Cycles

0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0.0 0.5 0.7 0.9 1.1 1.3 1.5 1.7 1.9 110 V 230 V 48 V

Current (A)

(1) DC-12: switching resistive loads and photo-coupler isolated solid state loads, L/R 1 ms. (2) DC-13: switching electromagnets, L/R 2 x (Ue x Ie) in ms, Ue: rated operational voltage, Ie: rated operational current (with protection diode on load, use the DC-12 curves and apply a coefficient of 0.9 to the million of operating cycles value). (3) AC-12: switching resistive loads and photo-coupler isolated solid state loads, cos 0.9. (4) AC-14: switching electromagnetic loads whose power drawn with the electromagnet closed is 72 VA, making: cos = 0.3, breaking: cos = 0.3. (5) AC-15: switching electromagnetic loads whose power drawn with the electromagnet closed is > 72 VA, making: cos = 0.7, breaking: cos = 0.4. The product life expressed above is based on average usage and normal operating conditions. Actual operating life will vary with conditions. The above statements are not intended to, nor shall they create any expressed or implied warranties as to product operation or life. For information on the listed warranty offered on this product, refer to the Square D terms and conditions of sale found in the Square D Digest.

12 2001-2003 Schneider Electric All Rights Reserved


10/03

Zelio-Logic Relay
Ordering Information
Ordering Information

Relays
Supply Voltage 12 Vdc Inputs 8 - 12 Vdc 6 - 24 Vdc 6 - 24 Vdc 8 - 24 Vdc 8 - 24 Vdc 8 - 24 Vdc 12 - 24 Vdc 12 - 24 Vdc 6 - 24 Vac 12 - 24 Vac 6 - 100/240 Vac 6 - 100/240 Vac 6 - 100/240 Vac 6 - 100/240 Vac 12 - 100/240 Vac 12 - 100/240 Vac Outputs 4 Relay 4 Relay 4 Relay 4 Relay 4 Relay 4 Transistor 8 Relay 8 Relay 4 Relay 8 Relay 4 Relay 4 Relay 4 Relay 4 Relay 8 Relay 8 Relay Blind Version No No Yes No Yes No No No No No No No Yes Yes No No With Clock Yes No No Yes Yes Yes No Yes Yes Yes No Yes No Yes No Yes Catalog Number SRIB121JD SR1A101BD SR1D101BD SR1B121BD SR1E121BD SR1B122BD SR1A201BD SR1B201BD SRIB101B SRIB201B SR1A101FU SR1B101FU SR1D101FU SR1E101FU SR1A201FU SR1B201FU Weight lb (kg) 0.64 lb (0.290 kg) 0.64 lb (0.290 kg) 0.64 lb (0.290 kg) 0.64 lb (0.290 kg) 0.64 lb (0.290 kg) 0.64 lb (0.290 kg) 0.77 lb (0.350 kg) 0.77 lb (0.350 kg) 0.64 lb (0.290 kg) 0.64 lb (0.290 kg) 0.64 lb (0.290 kg) 0.64 lb (0.290 kg) 0.64 lb (0.290 kg) 0.64 lb (0.290 kg) 0.77 lb (0.350 kg) 0.77 lb (0.350 kg)

24 Vdc

SR1121BD

24 Vac

100 - 240 Vac

Separate Accessories
Description Relay to PC interconnecting cable - 1.8 m length EEPROM memory cartridge (1 k bytes) Zelio-Soft Software SR1101FU Catalog Number SR1CBL01 SR1MEM01 SR1SFT01 Weight lb (kg) 0.77 lb (0.350 kg) 0.002 lb (0.001 kg) 0.33 lb (0.150 kg)

Zelio Soft Software for Pocket PC


Description Catalog Number Connecting cable between Sub-D-9 connector on the Pocket PC and the smart relay SR1-CBL02 Programming software for Pocket PC (also contains Zelio Soft multi-language software) SR1-SFT02 Weight lb (kg) 0.77 lb (0.350 kg) 0.33 lb (0.150 kg)

Promotional Kits
Description CD-ROM, and cable SR1B121BD and SR1KIT01 SR1B101FU and SR1KIT01 Catalog Number SR1KIT01 SR1PACKBD SR1PACKFU Weight lb (kg) 1.1 lb (0.500 kg) 1.74 lb (0.790 kg) 1.74 lb (0.790 kg)

Documentation
Description Language English French German Italian Spanish Catalog Number SR1MAN01EN SR1MAN01FR SR1MAN01DE SR1MAN01IT SR1MAN01ES Weight lb (kg) 0.0022 lb (0.001kg) 0.0022 lb (0.001kg) 0.0022 lb (0.001kg) 0.0022 lb (0.001kg) 0.0022 lb (0.001kg)

Users guide

2 configurable analog inputs.

Power Supply (1)


Input Voltage 100240 V 4763 Hz Nominal Output Voltage 12 Vdc 24 Vdc Nominal Output Current 1.9 A 1.4 A Catalog Number ABL-7RM1202 ABL-7RM2401 Weight lb (kg) 0.39 (0.180 kg) 0.40 (0.182 kg)

ABL-7RM2401

10/03

2001-2003 Schneider Electric All Rights Reserved

13

Zelio-Logic Relay
Wiring Diagrams and Dimensions
Wiring Diagrams and Dimensions

DIMENSIONS

4.33

3.54 90

2.34 59.5

2.36 60 A

Catalog Number
SR1A101BD SR1B101B SR1B121BD SR1B121JD SR1D101BD SR1E121BD SR1A101FU SR1B101FU SR1D101FU SR1E101FU SR1B122BD SR1A201BD SR1B201B SR1B201BD SR1A201FU SR1B201FU

2.83 " (72 mm)

4.96 " (126 mm)

3.94 100

110

Dual Dimensions inches mm

WIRING DIAGRAMS
3-wire Sensor on:
SR1A101BD SR1B121BD SR1B122BD SR1D101BD SR1E121BD SR1A201BD SR1B201BD SR1B121JD

Analog Inputs on:


SR1B121BD SR1E121BD SR1B122BD SR1B121JD

Analog Inputs on:


SR1B201BD

24 Vdc

(1)
(1)

0-10 Vdc Analog


Ca / Ta 1 Ca / Ta 2

0-10 Vdc Analog


Ca / Ta 1 Ca / Ta 2

+
BL BK BN BL BK BN

+
24 Vdc

(1)

24 Vdc

+ -

I1 I2 I3 I4 I5 I6 IB IC

24 Vdc

+ -

I1 I2 I3 I4 I5 I6 IB 24 Vdc

IC

+ -

I1 I2 I3 I4

I5 I6 I7

I8

I9 IA IB IC

--

24 Vdc

1 Q1 2 1 Q2 2 1 Q3 2 1 Q4 2 1 Q5 2 1 Q6 2 1 Q7 2 1 Q8 2

1 Q1 2 1 Q2 2 1 Q3 2 1 Q4 2

1 Q1 2 1 Q2 2 1 Q3 2 1 Q4 2

(1)1 A ultra fast fuse or supplementary protector

14 2001-2003 Schneider Electric All Rights Reserved


10/03

Zelio-Logic Relay
Wiring Diagrams and Dimensions
WIRING DIAGRAMS, CONTINUED
SR1A101BD or SR1D101BD SR1B121BD or SR1E121BD SR1B121JD
(1)

SR1A201BD SR1B201BD

L/+ 24 Vdc N/-

(1)

L/+ 24 Vdc N/-

+ -

I1 I2 I3 I4 I5 I6 IB IC

+ -

I1 I2 I3 I4

I5 I6 I7 I8

I9 IA IB IC

--

24 Vdc

24 Vdc

1 Q1 2 1 Q2 2 1 Q3 2 1 Q4 2

1 Q1 2 1 Q2 2 1 Q3 2 1 Q4 2 1 Q5 2 1 Q6 2 1 Q7 2 1 Q8 2

L/+ 12-240 Vac 50 / 60 Hz or 12-125 Vdc N / -

(2)
U

(3)

12-240 Vac 50 / 60 Hz

L/+ 12-240 Vac 50 / 60 Hz or 12-125 Vdc N / -

(2)
U 12-240 Vac 50 / 60 Hz

(3)

U 12-125 Vdc

(4)
12-125 Vdc

(4)

Terminals IB and IC are not available on this device.

SR1A101FU or SR1B101FU SR1B122BD SR1D101FU or SR1E101FU

SR1A201FU or SR1B201FU SR1A201B, SR1B201B


L 100-240 Vac 50 / 60 Hz N L N
I1 I2 I3 I4 I5 I6 I7 I8 I9 IA IB IC

(1)

+
24 V

(1)

L 100-240 Vac 50 / 60 Hz N

(1)

L N

I1 I2 I3 I4 I5 I6

100-240 Vac

+
24 V

I1 I2 I3 I4 I5 I6 IB IC

100-240 Vac

+ +
24 V

Q1

Q2

Q3

Q4

1 Q1 2 1 Q2 2 1 Q3 2 1 Q4 2

1 Q1 2 1 Q2 2 1 Q3 2 1 Q4 2 1 Q5 2 1 Q6 2 1 Q7 2 1 Q8 2

(2)

L/+ 12-240 Vac 50 / 60 Hz or 12-125 Vdc N / -

(2)
U

L/+

(2)
U 12-240 Vac 50 / 60 Hz

(3)

12-240 Vac 50 / 60 Hz 12-125 Vdc N / -

(3)

12-240 Vac 50 / 60 Hz

(4)

U 12-125 Vdc

(4)

12-125 Vdc

(1) (2) (3) (4)

1 A ultra fast fuse or circuit protector. 16 A maximum fuse or supplementary protector. Resistive load. Inductive load.

10/03

2001-2003 Schneider Electric All Rights Reserved

15

Schneider Electric 8001 Highway 64 East Knightdale, NC 27545 1-888-SquareD (1-888-778-2733) www.SquareD.com

Schneider Canada Inc. 19 Waterman Avenue, M4B 1 Y2 Toronto, Ontario 1-800-565-6699 www.schneider-electric.ca

Catalog No. 8501CT0001R1/03 October 2003 20012003 Schneider Electric All Rights Reserved Replaces 8501CT0001 dated February 20001.