Datasheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

Allen Bradley NEMA Motor Starters

and Ferraz Shawmut Fuses

Type 2 Protection

Achieving Type 2 No Damage Motor Start Protection


Type 2 No Damage Protection - What Is It and Which Fuses Are Best?
Type 2 protection, also referred to as no damage protection, simply means that if a short circuit occurs, the short circuit protective device
will operate fast enough to prevent fault current damage to healthy equipment in the system. Tests show that current-limiting fuses are the best
choice for the protection of the motor controllers if damage-free performance is required. To ensure that correct fuse choices are made, short
circuit tests must be made on every possible combination of motor control and fuse. This sheet summarizes a major manufacturers motor
starter and the Ferraz Shawmut time-delay fuses which give Type 2 no damage protection. All combinations are UL witnessed and certified.

200 Volt, Three-Phase Motors

230 Volt, Three-Phase Motors

STARTER
HEATER
HP (FLC)
CAT. #
CLASS J CLASS RK1
SIZE
# ELEMENT
SCCR (kA)

STARTER
HEATER
HP (FLC)
CAT. #
CLASS J CLASS RK1
SIZE
# ELEMENT

SCCR
(kA)

1 1/2

509-A

W48

AJT15

A6D15R

100

509-A

W48

AJT15

A6D15R

100

509-A

W50

AJT15

A6D15R

100

509-A

W52

AJT20

A6D20R

100

509-A

W53

AJT20

A6D20R

100

509-B

W57

AJT30

A6D30R

100

509-B

W59

AJT30

A6D30R

100

7 1/2

509-C

W61

AJT45

A6D45R

100

7 1/2

509-C

W63

AJT50

A6D50R

100

10

509-C

W64

AJT60

A6D60R

100

10

509-D

W65

AJT60

A6D60R

100

15

509-D

W66

AJT90

A6D90R

100

15

509-D

W68

AJT100

A6D100R

100

20

509-D

W69

AJT100

A6D100R

100

20

509-D

W71

AJT100

A6D100R

100

25

509-D

W73

25

509-D

W75

AJT150

A6D150R

100

30

509-D

W75

AJT150

A6D150R

30

509-E

W77

AJT175

A6D175R

100

40

509-E

W79

AJT175

A6D175R

100

40

509-E

W81

AJT200

A6D200R

100

50

509-E

W83

AJT200

A6D200R

100

AJT100 A6D100R

100

50

509-F

W37

AJT200 A6D200R

100

60

509-F

W37

60

509-F

W39

AJT250 A6D250R

100

75

509-F

W40

AJT300

A6D300R

100

75

509-F

W41

100

100

509-F

W43

AJT400

A6D400R

100

AJT350

A6D350R

460 Volt, Three-Phase Motors

AJT200 A6D200R

100

100

575 Volt, Three-Phase Motors

STARTER
HEATER
CAT. #
CLASS J CLASS RK1
HP (FLC)
SIZE
# ELEMENT
SCCR (kA)

STARTER
HEATER
CLASS J CLASS RK1
HP (FLC)
CAT. #
# ELEMENT
SIZE

SCCR
(kA)

509-A

W49

AJT15

A6D15R

100

509-A

W47

AJT12

A6D12R

100

7 1/2

509-B

W53

AJT20

A6D20R

100

7 1/2

509-B

W51

AJT20

A6D20R

100

10

509-B

W56

AJT30

A6D30R

100

10

509-B

W53

AJT20

A6D20R

100

15

509-C

W61

AJT45

A6D45R

100

15

509-C

W58

AJT35

A6D35R

100

20

509-C

W63

AJT60

A6D60R

100

25

509-C

W63

AJT60

A6D60R

100

25

509-D

W66

AJT60

A6D60R

100

30

509-D

W64

AJT70

A6D70R

100

30

509-D

W66

AJT90

A6D90R

100

40

509-D

W66

AJT90

A6D90R

100

40

509-D

W69

AJT100

A6D100R

100

50

509-D

W69

AJT100

A6D100R

100

50

509-D

W72

AJT100

A6D100R

100

60

509-E

W71

AJT100

A6D100R

100

60

509-E

W74

AJT125

A6D125R

100

75

509-E

W74

AJT125

A6D125R

100

75

509-E

W77

AJT175

A6D175R

100

100

509-E

W78

AJT175

A6D175R

100

100

509-E

W82

AJT200

A6D200R

100

125

509-F

W35

AJT200

A6D200R

100

125

509-F

W37

AJT200 A6D200R

100

150

509-F

W36

150

509-F

W39

AJT250 A6D250R

100

200

509-F

W40

200

509-F

W42

AJT400

A6D400R

AJT200 A6D200R
AJT300

A6D300R

100
100

100

Catalog number is not complete. Refer to Bulletin 509 Section of A-B Industrial Control Catalog to
specify complete catalog starter number.
May be too small to allow some motors to start.

IEC on Reverse

Phone: 978-462-6662 Fax: 978-462-0181 us.ferrazshawmut.com

Allen Bradley IEC Motor Starters


and Ferraz Shawmut Fuses

Type 2 Protection

200 Volt, Three-Phase Motors

230 Volt, Three-Phase Motors

CONTACTOR OVERLOAD RELAY


HP (FLC) BASIC CAT. #
BASIC CAT. #
CLASS J CLASS CC
(a)
(b)
SCCR (kA)

HP (FLC)

CONTACTOR
BASIC CAT. #
(a)

OVERLOAD RELAY
BASIC CAT. #
CLASS J CLASS CC
(b)

SCCR
(kA)

1/2

100-C09

193-E**EB

AJT6

ATDR6

100

1/2

100-C09

193-E**DB

AJT6

ATDR6

100

3/4

100-C09

193-E**EB

AJT10

ATDR10

100

3/4

100-C09

193-E**EB

AJT10

ATDR10

100

100-C09

193-E**FB

AJT15

ATDR15

100

100-C09

193-E**FB

AJT15

ATDR15

100

1 1/2

100-C09

193-E**FB

AJT15

ATDR15

100

1 1/2

100-C09

193-E**FB

AJT15

ATDR15

100

100-C09

193-E**FB

AJT15

ATDR15

100

100-C09

193-E**FB

AJT15

ATDR15

100

AJT20

ATDR20

100

100-C12

193-E**FB

AJT20

ATDR20

100

100-C12

193-E**FB

100-C23

193-E**GB

AJT30

ATDR30

100

100-C16

193-E**GB

AJT20 ATDR20

7 1/2

100-C30

193-E**HC

AJT40

100

7 1/2

100-C23

193-E**GB

AJT30 ATDR30

100

10

100-C37

193-E**HC

AJT50

100

10

100-C30

193-E**HC

AJT40

100

15

100-C60

193-E**KE

AJT80

100

15

100-C43

193-E**JD

AJT50

100

20

100-C72

193-E**KE

AJT100

100

20

100-C60

193-E**KE

AJT80

100

25

100-C85

193-E**KE

AJT100

100

25

100-C72

193-E**KE

AJT100

100

30

100-C85

193-E**KE

AJT100

100

HP (FLC)

CONTACTOR
BASIC CAT. #
(a)

460 Volt, Three-Phase Motors

100

575 Volt, Three-Phase Motors

CONTACTOR OVERLOAD RELAY


HP (FLC) BASIC CAT. #
BASIC CAT. #
CLASS J CLASS CC
(a)
(b)
SCCR (kA)

OVERLOAD RELAY
BASIC CAT. #
CLASS J CLASS CC
(b)

SCCR
(kA)

1/2

100-C09

193-E**DB

AJT3

ATDR3

100

1/2

100-C09

193-E**DB

AJT3

ATDR3

100

3/4

100-C09

193-E**DB

AJT6

ATDR6

100

3/4

100-C09

193-E**DB

AJT3

ATDR3

100

100-C09

193-E**DB

AJT6

ATDR6

100

100-C09

193-E**DB

AJT6

ATDR6

100

1 1/2

100-C09

193-E**EB

AJT10

ATDR10

100

1 1/2

100-C09

193-E**DB

AJT6

ATDR6

100

100-C09

193-E**EB

AJT10

ATDR10

100

100-C09

193-E**EB

AJT10

ATDR10

100

100-C09

193-E**FB

AJT15

ATDR15

100

100-C09

193-E**FB

AJT10

ATDR10

100

100-C09

193-E**FB

AJT15

ATDR15

100

100-C09

193-E**FB

AJT15

ATDR15

100

7 1/2

100-C12

193-E**FB

AJT20

ATDR20

100

100-C09

193-E**FB

AJT15

ATDR15

100

10

100-C16

193-E**GB

AJT20 ATDR20

100

7 1/2

100-C09

193-E**FB

AJT15

ATDR15

100

15

100-C23

193-E**GB

AJT30 ATDR30

100

10

100-C12

193-E**FB

AJT20

ATDR20

100

20

100-C30

193-E**HC

100

15

100-C23

193-E**GB

AJT30

ATDR30

100

25

100-C37

193-E**HC

AJT50

100

20

100-C30

193-E**HC

AJT40

100

30

100-C43

193-E**JD

AJT50

100

25

100-C37

193-E**HC

AJT50

100

AJT40

40

100-C60

193-E**KE

AJT80

100

30

100-C37

193-E**HC

AJT50

100

50

100-C72

193-E**KE

AJT100

100

40

100-C60

193-E**KE

AJT80

100

60

100-C85

193-E**KE

AJT100

100

50

100-C72

193-E**KE

AJT100

100

100-C85

193-E**KE

AJT100

100

(a) Catalog number is not complete, add coil voltage code and auxiliary contact description.
(b) Catalog number is not complete, replace ** with trip class and reset mode.
May be too small to allow some motors to start.
Sized larger than code max for single motor
http://literature.rockwellautomation.com/idc/groups/literature/documents/br/193-br001_-en-p.pdf

Disclaimer: Regarding information available in this document, Ferraz Shawmut, Inc. does not warrant or assume any legal liability or responsibility for the accuracy or usefulness of
any information disclosed. The content in this guide is for informational purposes only. All information has been gathered from the individual websites of the product manufacturers
listed in this document.

NEMA on Reverse

Phone: 978-462-6662 Fax: 978-462-0181 us.ferrazshawmut.com

General Electric Motor Starters &


Ferraz Shawmut Fuses

Type 2 Protection

Achieving Type 2 No Damage Motor Start Protection


Type 2 No Damage Protection - What Is It and Which Fuses Are Best?
Type 2 protection, also referred to as no damage protection, simply means that if a short circuit occurs, the short circuit protective device
will operate fast enough to prevent fault current damage to healthy equipment in the system. Tests show that current-limiting fuses are the best
choice for the protection of the motor controllers if damage-free performance is required. To ensure that correct fuse choices are made, short
circuit tests must be made on every possible combination of motor control and fuse. This sheet summarizes a major manufacturers motor
starter and the Ferraz Shawmut time-delay fuses which give Type 2 no damage protection. All combinations are UL witnessed and certified.
200 Volt, Three-Phase Motors
HP

CONTACTOR

OLR

230 Volt, Three-Phase Motors


CLASS J SCCR (kA)

HP

CONTACTOR

OLR CLASS J SCCR (kA)

1/2

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1J

AJT4

100

1/2

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1J

AJT4

100

1/2

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1K

AJT8

100

3/4

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1K

AJT8

100

3/4

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1K

AJT8

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1L

AJT10

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1L

AJT10

100

1 1/2

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1L

AJT10

100

1 1/2

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1M

AJT12

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1M

AJT12

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1N

AJT20

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1N

AJT20

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1P

AJT20

100

CL02, CL03, CL04, CL25, CL45

RT*1S AJT35

100

CL02, CL03, CL04, CL25, CL45

RT*1S

AJT35

100

CL06, CL07, CL08, CL09, CL10

RT*2B AJT35

100

CL06, CL07, CL08, CL09, CL10

RT*2B

AJT35

100

7 1/2

CL03, CL04, CL45

RT*1T

AJT45

100

CL03, CL04, CL45

RT*1T

AJT45

100

7 1/2

CL06, CL07, CL08, CL09, CL10

RT*2C

AJT45

100

7 1/2

CL04, CL05

RT*1U

AJT45

100

7 1/2

CL03, CL04, CL45

RT*1U

AJT45

100

7 1/2

CL06, CL07, CL08, CL09, CL10

RT*2D

AJT60

100

10

CL04

RT*1V

AJT60

100

7 1/2

CL04, CL45

RT*1V

AJT60

100

10

CL45

RT*1V

AJT60

100
100

10

CL45

RT*1W

AJT70

100

10

CL06, CL07, CL08, CL09, CL10

RT*2D

AJT60

10

CL06, CL07, CL08, CL09, CL10

RT*2E

AJT70

100

15

CL06, CL07, CL08, CL09, CL10

RT*2F

AJT90

100

15

CL07, CL08, CL09, CL10

RT*2G

AJT100

100

20

CL07, CL08, CL09, CL10

RT*2G AJT100

100
100

20

CL08, CL09, CL10

RT*2H

AJT125

100

20

CL07, CL08, CL09, CL10

RT*2H AJT125

20

CK08, CK09, CK95

RT*3B

AJT125

100

25

CK08, CK09, CK95

RT*3B AJT125

100

25

CK08, CK09

RT*3C

AJT150

100

25

CL08, CL09, CL10

RT*2J AJT125

100

30

CK08, CK09, CK95

RT*3B AJT125

100

25

CK08, CK09

RT*3C AJT150

100

* Replace * with A or M
May be too small to allow some motors to start.
Sized larger than code max for single motor.
www.geindustrial.com

460V & 565V on Reverse

Phone: 978-462-6662 Fax: 978-462-0181 us.ferrazshawmut.com

General Electric Motor Starters &


Ferraz Shawmut Fuses

Type 2 Protection

460 Volt, Three-Phase Motors


HP

CONTACTOR

OLR

575 Volt, Three-Phase Motors


CLASS J SCCR (kA)

HP

CONTACTOR

OLR CLASS J SCCR (kA)

1/2

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1F AJT1-1/2

100

1/2

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1F AJT1-1/2

100

1/2

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1G

AJT2

100

3/4

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1G

AJT2

100

3/4

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1H

AJT4

100

3/4

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1H

AJT4

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1J

AJT4

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1H

AJT4

100

1 1/2

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1K

AJT8

100

1 1/2

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1J

AJT4

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1K

AJT8

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1J

AJT4

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1L

AJT10

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1K

AJT8

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1N

AJT20

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1K

AJT8

100

7 1/2

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1P

10

CL02, CL03, CL04, CL25, CL45

RT*1R

AJT20

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1L

AJT10

100

AJT25

100

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1M

AJT12

100

10

CL06, CL07, CL08, CL09, CL10

RT*2A

AJT30

100

7 1/2

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1N

AJT20

100

15

CL03, CL04, CL45

RT*1T

AJT45

100

10

CL00, CL01, CL02, CL03, CL04, CL25, CL45 RT*1P

AJT20

100

15

CL06, CL07, CL08, CL09, CL10

RT*2C

AJT45

100

15

CL02, CL03, CL04, CL25, CL45

RT*1S

AJT35

100

20

CL04, CL45

RT*1V

AJT60

100

15

CL06, CL07, CL08, CL09, CL10

RT*2B

AJT35

100

20

CL06, CL07, CL08, CL09, CL10

RT*2D

AJT60

100

20

CL03, CL04, CL45

RT*1T

AJT45

100

25

CL45

RT*1W

AJT70

100

20

CL06, CL07, CL08, CL09, CL10

RT*2C

AJT45

100

25

CL06, CL07, CL08, CL09, CL10

RT*2E

AJT70

100

20

CL03, CL04, CL45

RT*1U

AJT45

100

30

CL06, CL07, CL08, CL09, CL10

RT*2E

AJT70

100

25

CL04, CL45

RT*1V

AJT60

100

30

CL06, CL07, CL08, CL09, CL10

RT*2F

AJT90

100

25

CL06, CL07, CL08, CL09, CL10

RT*2D

AJT60

100

40

CL07, CL08, CL09, CL10

RT*2G

AJT100

100

30

CL04, CL45

RT*1V

AJT60

100

50

CL08, CL09, CL10

RT*2H

AJT125

100

30

CL06, CL07, CL08, CL09, CL10

RT*2D

AJT60

100

50

CL08, CL09, CL10

RT*3B

AJT125

100

30

CL45

RT*1W

AJT70

100

50

CL08, CL09, CL10

RT*2J

AJT125

100

30

CL06, CL07, CL08, CL09, CL10

RT*2E

AJT70

100

60

CL09, CL10

RT*3B

AJT125

100

40

CL06, CL07, CL08, CL09, CL10

RT*2E

AJT70

100

60

CL09, CL10

RT*2K

AJT150

100

40

CL06, CL07, CL08, CL09, CL10

RT*2F

AJT90

100

50

CL07, CL08, CL09, CL10

RT*2G AJT100

100

60

CL07, CL08, CL09, CL10

RT*2H AJT125

100

60

CK08, CK09, CK95

RT*3B AJT125

100

75

CK08, CK09, CK95

RT*3B AJT125

100

75

CK08, CK09

RT*3C AJT150

100

* Replace * with A or M
May be too small to allow some motors to start.
Sized larger than code max for single motor.
www.geindustrial.com

Disclaimer: Regarding information available in this document, Ferraz Shawmut, Inc. does not warrant or assume any legal liability or responsibility for the accuracy or usefulness of
any information disclosed. The content in this guide is for informational purposes only. All information has been gathered from the individual websites of the product manufacturers
listed in this document.

200V & 230V on Reverse

Phone: 978-462-6662 Fax: 978-462-0181 us.ferrazshawmut.com

Cutler Hammer Freedom Series NEMA


Interchangeable Heater Starters &
Ferraz Shawmut Fuses

Type 2 Protection

Achieving Type 2 No Damage Motor Start Protection


Type 2 No Damage Protection - What Is It and Which Fuses Are Best?
Type 2 protection, also referred to as no damage protection, simply means that if a short circuit occurs, the short circuit protective device
will operate fast enough to prevent fault current damage to healthy equipment in the system. Tests show that current-limiting fuses are the best
choice for the protection of the motor controllers if damage-free performance is required. To ensure that correct fuse choices are made, short
circuit tests must be made on every possible combination of motor control and fuse. This sheet summarizes a major manufacturers motor
starter and the Ferraz Shawmut time-delay fuses which give Type 2 no damage protection. All combinations are UL witnessed and certified.

200 Volt, Three-Phase Motors


HP

SIZE

STARTER
NUMBER

230 Volt, Three-Phase Motors

HEATER
NUMBER CLASS RK1 SCCR (kA)

HP

SIZE

STARTER
NUMBER

HEATER
NUMBER

CLASS
RK1

SCCR
(kA)

1/2

00

AN16ANO_C H2006B-3

A6D5R

100

1/2

00 AN16ANO_C H2006B-3

A6D5R

100

3/4

00

AN16ANO_C H2007B-3

A6D6R

100

3/4

00 AN16ANO_C H2007B-3

A6D6R

100

00

AN16ANO_C H2008B-3

A6D8R

100

00 AN16ANO_C H2008B-3

A6D8R

100

1 1/2

AN16NDO_C H2009B-3

A6D12R

100

1 1/2

00 AN16ANO_C H2009B-3

A6D12R

100

AN16BNO_C H2010B-3 A6D17-1/2R

100

AN16BNO_C H2009B-3

A6D12R

100

AN16BNO_C H2011B-3

A6D25R

100

AN16BNO_C H2011B-3

A6D25R

100

7 1/2

AN16DNO_B H2013B-3

A6D45R

100

AN16DNO_B H2012B-3

A6D40R

100

AN16GNO_B H2015B-3

10

15

AN16KNO_

H2021-3

A6D70R

100

7 1/2

AN16DNO_B H2013B-3

A6D45R

100

A6D110R

100

7 1/2

AN16GNO_B H2013B-3

A6D45R

100

20

AN16KNO_

25

AN16KNO_

H2021-3

A6D110R

100

10

AN16GNO_B H2014B-3

A6D60R

100

H2022-3

A6D175R

100

15

AN16GNO_B H2015B-3

A6D70R

100

30

40

AN16NNO_

H2023-3

A6D200R

100

20

AN16KNO_

H2021-3

A6D110R

100

AN16NNO_

H2024-3

A6D200R

100

25

AN16KNO_

H2022-3

A6D175R

100

50
60

AN16SNO_B H2007B-3 A6D400R

100

30

AN16KNO_

H2022-3

A6D175R

100

AN16SNO_B H2007B-3 A6D400R

100

40

AN16NNO_

H2023-3

A6D200R

100

75

AN16SNO_B H2008B-3 A6D400R

100

50

AN16NNO_

H2024-3

A6D200R

100

60

AN16SNO_B H2007B-3 A6D400R

100

75

AN16SNO_B H2007B-3 A6D400R

100

100

AN16SNO_B H2008B-3 A6D400R

100

_ Empty space designates where coil suffix must be added.



http://www.eaton.com/EatonCom/Markets/Electrical/Products/MotorControl/NEMAStartersContactors/
FreedomNEMA/index.htm?ssSourceNodeId=3483&ssSourceSiteId=EatonCom

460V & 575V on Reverse

Phone: 978-462-6662 Fax: 978-462-0181 us.ferrazshawmut.com

Cutler Hammer Freedom Series NEMA


Interchangeable Heater Starters &
Ferraz Shawmut Fuses

Type 2 Protection

460 Volt, Three-Phase Motors


HP

SIZE

1/2

00

STARTER
NUMBER

575 Volt, Three-Phase Motors

HEATER
NUMBER CLASS RK1 SCCR (kA)

AN16ANO_C H2004B-3 A6D2-1/4R

100

HP
3/4

SIZE

STARTER
NUMBER

HEATER
NUMBER

CLASS
RK1

00 AN16ANO_C H2004B-3 A6D2-1/4R

SCCR
(kA)
100

3/4

00

AN16ANO_C H2005B-3 A6D3-2/10R

100

00 AN16ANO_C H2005B-3

A6D32/10R

00

AN16ANO_C H2006B-3

A6D5R

100

1 1/2

00 AN16ANO_C H2006B-3

A6D5R

100

1 1/2

00

AN16ANO_C H2007B-3

A6D6R

100

00 AN16ANO_C H2007B-3

A6D6R

100

00

AN16ANO_C H2008B-3

A6D8R

100

AN16BNO_C H2008B-3

A6D8R

100

AN16BNO_C H2009B-3

A6D12R

100

AN16BNO_C H2009B-3

A6D12R

100

AN16BNO_C H2010B-3 A6D17-1/2R

100

7 1/2

AN16DNO_B H2010B-3 A6D17-1/2R

100

7 1/2

AN16DNO_B H2011B-3

A6D25R

100

10

AN16DNO_B H2011B-3

A6D25R

100

10

AN16DNO_B H2012B-3

A6D40R

100

15

AN16GNO_B H2012B-3

A6D40R

100

15

AN16GNO_B H2013B-3

A6D45R

100

20

AN16GNO_B H2013B-3

A6D45R

100

20

AN16GNO_B H2014B-3

A6D60R

100

25

AN16GNO_B H2014B-3

A6D60R

100

25

AN16GNO_B H2015B-3

A6D70R

100

30

AN16KNO_

H2019-3

A6D60R

100

30

AN16KNO_

H2020-3

A6D80R

100

40

AN16KNO_

H2020-3

A6D80R

100

40

AN16KNO_

H2021-3

A6D110R

100

50

AN16KNO_

H2021-3

A6D110R

100

50

AN16KNO_

H2022-3

A6D175R

100

60

AN16NNO_

H2021-3

A6D110R

100

60

AN16NNO_

H2022-3

A6D175R

100

75

AN16NNO_

H2022-3

A6D175R

100

75

AN16NNO_

H2023-3

A6D200R

100

100

AN16NNO_

H2023-3

A6D200R

100

AN16NNO_

H2024-3

100

100

A6D200R

100

125

AN16SNO_B H2006B-3 A6D400R

100

125

AN16SNO_B H2007B-3 A6D400R

100

150

AN16SNO_B H2007B-3 A6D400R

100

150

AN16SNO_B H2007B-3 A6D400R

100

200

AN16SNO_B H2007B-3 A6D400R

100

200

AN16SNO_B H2008B-3 A6D400R

100

_ Empty space designates where coil suffix must be added.


http://www.eaton.com/EatonCom/Markets/Electrical/Products/MotorControl/NEMAStartersContactors/FreedomNEMA/index.htm?ssSourceNodeId=3483&ssSourceSiteId=EatonCom

200V & 230V on Reverse

Phone: 978-462-6662 Fax: 978-462-0181 us.ferrazshawmut.com

Cutler Hammer Freedom Series IEC


Interchangeable Heater Starters &
Ferraz Shawmut Fuses

Type 2 Protection

Achieving Type 2 No Damage Motor Start Protection


Type 2 No Damage Protection - What Is It and Which Fuses Are Best?
Type 2 protection, also referred to as no damage protection, simply means that if a short circuit occurs, the short circuit protective device will operate fast enough to prevent fault current damage to healthy equipment in the system. Tests show that current-limiting fuses are the best choice for the
protection of the motor controllers if damage-free performance is required. To ensure that correct fuse choices are made, short circuit tests must be
made on every possible combination of motor control and fuse. This sheet summarizes a major manufacturers motor starter and the Ferraz Shawmut
time-delay fuses which give Type 2 no damage protection. All combinations are UL witnessed and certified.
200 Volt, Three-Phase Motors
HP (FLC)

STARTER
NUMBER

1/2

AE16ANSO_C

230 Volt, Three-Phase Motors

HEATER
NUMBER CLASS J CLASS CC SCCR (kA)
H2106B-3

AJT6

ATDR6

HP (FLC)

STARTER
NUMBER

100

1/2

AE16ANSO_C

HEATER
NUMBER CLASS J CLASS CC
H2106B-3

AJT6

ATDR6

SCCR
(kA)
100

3/4

AE16ANSO_C

H2107B-3

AJT6

ATDR6

100

3/4

AE16ANSO-C

H2106B-3

AJT6

ATDR6

100

AE16ANSO_C

H2108B-3

AJT15

ATDR15

100

AE16ANSO-C

H2108B-3

AJT15

ATDR15

100

1 1/2

AE16ANSO_C

H2109B-3

AJT15

ATDR15

100

1 1/2

AE16ANSO-C

H2109B-3

AJT15

ATDR15

100

AE16BNSO_C

H2110B-3

AJT25

ATDR25

100

AE16BNSO_C

H2109B-3

AJT15

ATDR15

100

AE16CNSO_C

H2111B-3

AJT35

100

AE16BNSO_C

H2110B-3

AJT25

ATDR25

100

AE16DNSO_C

H2112B-3

AJT50

100

AE16DNSO_C

H2112B-3

AJT50

100

7 1/2

AE16ENSO_B

H2114B-3

AJT60

100

7 1/2

AE16ENSO_C

H2113B-3

AJT50

100

10

AE16HNSO_B

H2115B-3

AJT80

100

10

AE16FNSO_B

H2114B-3

AJT60

100

15

AE16JNSO_B

H2116B-3

AJT110

100

15

AE16HNSO_B

H2116B-3

AJT110

100

20

AE16KNSO_B

H2117B-3

AJT110

100

20

AE16JNSO_B

H2117B-3

AJT110

100

25

AE16LNSO_

H2022-3

AJT150

100

25

AE16KNSO_B

H2117B-3

AJT110

100

30

AE16MNSO_

H2023-3

AJT200

100

30

AE16LNSO_

H2022-3

AJT150

100

40

AE16NNSO_

H2024-3

AJT200

100

40

AE16MNSO_

H2023-3

AJT200

100

50

AE16NNSO_

H2024-3

AJT200

100

HP (FLC)

STARTER
NUMBER

3/4

AE16ANSO_C

H2104B-3

AJT3

ATDR3

100

460 Volt, Three-Phase Motors


HP (FLC)

STARTER
NUMBER

1/2

AE16ANSO_C

575 Volt, Three-Phase Motors

HEATER
NUMBER CLASS J CLASS CC SCCR (kA)
H2104B-3

AJT3

ATDR3

100

HEATER
NUMBER CLASS J CLASS CC

SCCR
(kA)

3/4

AE16ANSO_C

H2105B-3

AJT3

ATDR3

100

AE16ANSO_C

H2105B-3

AJT3

ATDR3

100

AE16ANSO_C

H2105B-3

AJT3

ATDR3

100

1 1/2

AE16ANSO_C

H2106B-3

AJT6

ATDR6

100

1 1/2

AE16ANSO_C

H2106B-3

AJT6

ATDR6

100

AE16ANSO_C

H2107B-3

AJT6

ATDR6

100

AE16ANSO_C

H2108B-3

AJT15

ATDR15

100

AE16ANSO_C

H2108B-3

AJT15

ATDR15

100

AE16ANSO_C

H2108B-3

AJT15

ATDR15

100

AE16ANSO_C

H2109B-3

AJT15

ATDR15

100

AE16BNSO_C

H2110B-3

AJT25

ATDR25

100

7 1/2

AE16BNSO_C

H2110B-3

AJT25

ATDR25

100

7 1/2

AE16CNSO_C

H2111B-3

AJT35

100

10

AE16CNSO_C

H2111B-3

AJT35

100

10

AE16DNSO_C

H2111B-3

AJT35

100

15

AE16DNSO_C

H2112B-3

AJT50

100

15

AE16ENSO_C

H2113B-3

AJT50

100

20

AE16ENSO_C

H2113B-3

AJT50

100

20

AE16FNSO_B

H2114B-3

AJT60

100

25

AE16FNSO_B

H2114B-3

AJT60

100

25

AE16GNSO_B

H2115B-3

AJT80

100

30

AE16GNSO_B

H2115B-3

AJT80

100

30

AE16HNSO_B

H2116B-3

AJT110

100

40

AE16HNSO_B

H2116B-3

AJT110

100

40

AE16JNSO_B

H2116B-3

AJT110

100

50

AE16KNSO_B

H2116B-3

AJT110

100

50

AE16KNSO_B

H2117B-3

AJT110

100

60

AE16LNSO_

H2021-3

AJT110

100

60

AE16LNSO_

H2022-3

AJT150

100

75

AE16LNSO_

H2022-3

AJT150

100

75

AE16MNSO_

H2023-3

AJT200

100

100

AE16MNSO_

H2023-3

AJT200

100

100

AE16NNSO_

H2024-3

AJT200

100

125

AE16NNSO_

H2024-3

AJT200

100

_ Empty space designates where coil suffix must be added.


May be too small to allow some motors to start.
http://www.eaton.com/EatonCom/Markets/Electrical/Products/MotorControl/NEMAStartersContactors/FreedomNEMA/index.htm?s
sSourceNodeId=3483&ssSourceSiteId=EatonCom

IEC Fixed Heater Starters on Reverse

Phone: 978-462-6662 Fax: 978-462-0181 us.ferrazshawmut.com

Cutler Hammer Freedom Series IEC


Fixed Heater Starters &
Ferraz Shawmut Fuses

Type 2 Protection

200 Volt, Three-Phase Motors

230 Volt, Three-Phase Motors

STARTER
NUMBER
HP (FLC) (FIXED HEATERS) CLASS J CLASS CC SCCR (kA)

STARTER
NUMBER
HP (FLC) (FIXED HEATERS) CLASS J CLASS CC SCCR (kA)

1/2

AE17ANSO_FJ

AJT6

ATDR6

100

1/2

AE17ANSO_FH

AJT3

ATDR3

100

3/4

AE17ANSO_FK

AJT6

ATDR6

100

3/4

AE17ANSO_FK

AJT6

ATDR6

100

AE17ANSO_FL

AJT15

ATDR15

100

AE17ANSO_FK

AJT6

ATDR6

100

1 1/2

AE17ANSO_FM

AJT15

ATDR15

100

1 1/2

AE17ANSO_FM

AJT15

ATDR15

100

AE17BNSO_FP

AJT25

ATDR25

100

AE17BNSO_FN

AJT15

ATDR15

100

AE17CNSO_FQ

AJT35

100

AE17CNSO_FP

AJT25

ATDR25

100

AE17DNSO_FR

AJT35

100

AE17DNSO_FR

AJT35

100

7 1/2

AE17FNSO_FT

AJT60

100

7 1/2

AE17ENSO_FS

AJT50

100

10

AE17HNSO_KC

AJT80

100

10

AE17FNSO_FT

AJT60

100

15

AE17JNSO_KE

AJT110

100

15

AE17HNSO_KD

AJT110

100

20

AE17KNSO_KF

AJT110

100

20

AE17JNSO_KE

AJT110

100

25

AE17KNSO_KF

AJT110

100

460 Volt, Three-Phase Motors

575 Volt, Three-Phase Motors

STARTER
NUMBER
HP (FLC) (FIXED HEATERS) CLASS J CLASS CC SCCR (kA)

STARTER
NUMBER
HP (FLC) (FIXED HEATERS) CLASS J CLASS CC SCCR (kA)

1/2

AE17ANSO_FF

AJT2

ATDR2

100

3/4

AE17ANSO_FF

AJT2

ATDR2

3/4

AE17ANSO_FG

AJT3

ATDR3

100

AE17ANSO_FG

AJT3

ATDR3

100
100

AE17ANSO_FH

AJT3

ATDR3

100

1 1/2

AE17ANSO_FH

AJT3

ATDR3

100

1 1/2

AE17ANSO_FJ

AJT6

ATDR6

100

AE17ANSO_FJ

AJT6

ATDR6

100

AE17ANSO_FK

AJT6

ATDR6

100

AE17ANSO_FL

AJT15

ATDR15

100

AE17ANSO_FM

AJT15

ATDR15

100

AE17ANSO_FM

AJT15

ATDR15

100

AE17BNSO_FN

AJT15

ATDR15

100

7 1/2

AE17BNSO_FP

AJT25

ATDR25

100

7 1/2

AE17CNSO_FQ

AJT35

100

10

AE17CNSO_FQ

AJT35

100

10

AE17DNSO_FR

AJT35

100

15

AE17DNSO_FR

AJT35

100

15

AE17ENSO_FS

AJT50

100

20

AE17ENSO_FS

AJT50

100

20

AE17FNSO_FT

AJT60

100

25

AE17FNSO_FT

AJT60

100

25

AE17GNSO_KC

AJT80

100

30

AE17GNSO_KC

AJT80

100

30

AE17HNSO_KD

AJT110

100

40

AE17HNSO_KD

AJT110

100

40

AE17JNSO_KE

AJT110

100

50

AE17KNSO_KE

AJT110

100

50

AE17KNSO_KF

AJT110

100

_ Empty space designates where coil suffix must be added.


May be too small to allow some motors to start.

http://www.eaton.com/EatonCom/Markets/Electrical/Products/MotorControl/NEMAStartersContactors/FreedomNEMA/index.htm?ssSourceNodeId=3483&ssSourceSiteId=EatonCom

Disclaimer: Regarding information available in this document, Ferraz Shawmut, Inc. does not warrant or assume any legal liability or responsibility for the accuracy or usefulness of
any information disclosed. The content in this guide is for informational purposes only. All information has been gathered from the individual websites of the product manufacturers
listed in this document.

IEC Interchangeable Heater Starters on Reverse

Phone: 978-462-6662 Fax: 978-462-0181 us.ferrazshawmut.com

Square D TeSys D Line


(Telemecanique) IEC Class 10 Overload
Relay and Ferraz Shawmut Fuses

Type 2 Protection

Achieving Type 2 No Damage Motor Start Protection


Type 2 No Damage Protection - What Is It and Which Fuses Are Best?
Type 2 protection, also referred to as no damage protection, simply means that if a short circuit occurs, the short circuit protective device
will operate fast enough to prevent fault current damage to healthy equipment in the system. Tests show that current-limiting fuses are the best
choice for the protection of the motor controllers if damage-free performance is required. To ensure that correct fuse choices are made, short
circuit tests must be made on every possible combination of motor control and fuse. This sheet summarizes a major manufacturers motor
starter and the Ferraz Shawmut time-delay fuses which give Type 2 no damage protection. All combinations are UL witnessed and certified.
200 Volt, Three-Phase Motors

230 Volt, Three-Phase Motors

HP

CONTACTOR

OLR

CLASS J

CLASS CC SCCR (kA)

1/2

LC1D09

LRD07

AJT5

ATDR8

3/4

LC1D09

LRD08

AJT5

ATDR12

HP

CONTACTOR

OLR

CLASS J

100

1/2

LC1D09

LRD07

AJT5

CLASS CC SCCR (kA)


ATDR8

100

100

3/4

LC1D09

LRD08

AJT5

ATDR12

100

LC1D09

LRD10

AJT20

ATDR30

100

LC1D09

LRD10

AJT20

ATDR30

100

1 1/2

LC1D09

LRD12

AJT20

ATDR30

100

1 1/2

LC1D09

LRD12

AJT20

ATDR30

100

LC1D09

LRD12

AJT20

ATDR30

100

LC1D09

LRD12

AJT20

ATDR30

100

LC1D12

LRD16

AJT20

ATDR30

100

LC1D12

LRD16

AJT20

ATDR30

100

10

LC1D40

LRD3355

AJT60

100

10

LC1D40

LRD3355

AJT60

100

15

LC1D50

LRD3357

AJT70

100

15

LC1D50

LRD3357

AJT70

100

20

LC1D65

LRD3359

AJT100

100

20

LC1D65

LRD3359

AJT100

100

25

LC1D80

LRD3363

AJT110

100

25

LC1D80

LRD3363

AJT110

100

30

LC1D115

LR9D5569

AJT150

100

30

LC1D80

LRD3363

AJT110

100

40

LC1D150

LR9D5569

AJT200

100

40

LC1D115

LR9D5569

AJT150

100

HP

CONTACTOR

OLR

CLASS J

HP

CONTACTOR

OLR

CLASS J

CLASS CC SCCR (kA)

1/2

LC1D09

LRD06

AJT2

100

1/2

LC1D09

LRD05

AJT1-1/2

ATDR2-8/10

460 Volt, Three-Phase Motors

575 Volt, Three-Phase Motors

CLASS CC SCCR (kA)


ATDR5

100

3/4

LC1D09

LRD06

AJT2

ATDR5

100

3/4

LC1D09

LRD06

AJT2

ATDR5

100

LC1D09

LRD07

AJT5

ATDR8

100

LC1D09

LRD07

AJT5

ATDR8

100

1 1/2

LC1D09

LRD08

AJT5

ATDR12

100

1 1/2

LC1D09

LRD07

AJT5

ATDR8

100

LC1D09

LRD08

AJT5

ATDR12

100

LC1D09

LRD08

AJT5

ATDR12

100

LC1D09

LRD10

AJT20

ATDR30

100

LC1D09

LRD08

AJT5

ATDR12

100

LC1D09

LRD14

AJT20

ATDR30

100

LC1D09

LRD12

AJT20

ATDR30

100

7 1/2

LC1D12

LRD16

AJT20

ATDR30

100

7 1/2

LC1D12

LRD16

AJT20

ATDR30

100

10

LC1D18

LRD21

AJT25

100

10

LC1D18

LRD16

AJT20

ATDR30

100

15

LC1D25

LRD22

AJT35

100

15

LC1D25

LRD21

AJT25

100

15

LC1D32

LRD22

AJT40

100

20

LC1D32

LRD22

AJT40

100

25

LC1D40

LRD3355

AJT60

100

30

LC1D40

LRD3355

AJT60

100

30

LC1D40

LRD3355

AJT60

100

40

LC1D50

LRD3357

AJT70

100

30

LC1D40

LRD3357

AJT60

100

50

LC1D65

LRD3359

AJT100

100

40

LC1D50

LRD3359

AJT70

100

75

LC1D115

LR9D5367

AJT125

100

50

LC1D65

LRD3359

AJT100

100

100

LC1D115

LR9D5569

AJT150

100

125

LC1D150

LR9D5569

AJT200

100

60

LC1D80

LRD5363

AJT110

100

75

LC1D115

LR9D5569

AJT150

100

100

LC1D150

LR9D5569

AJT200

100

www.squared.com/.../iec_contactors_starters.nsf/unid/B7D67A0C9FB16F8285256F6900567C4E/$file/
Shawmutt10.htm - 22k

IEC Class 20 Overload Relay on Reverse

Phone: 978-462-6662 Fax: 978-462-0181 us.ferrazshawmut.com

Square D TeSys D Line


(Telemecanique) IEC Class 20 Overload
Relay and Ferraz Shawmut Fuses

Type 2 Protection

200 Volt, Three-Phase Motors


HP

CONTACTOR

OLR

CLASS J

230 Volt, Three-Phase Motors

CLASS CC SCCR (kA)

HP

CONTACTOR

OLR

CLASS J

CLASS CC SCCR (kA)

1/2

LC1D09

LRD07

AJT5

ATDR8

100

1/2

LC1D09

LRD07

AJT5

ATDR8

100

3/4

LC1D09

LRD08

AJT5

ATDR12

100

3/4

LC1D09

LRD08

AJT5

ATDR12

100

LC1D09

LRD10

AJT20

ATDR30

100

LC1D09

LRD10

AJT20

ATDR30

100

1 1/2

LC1D09

LRD12

AJT20

ATDR30

100

1 1/2

LC1D09

LRD12

AJT20

ATDR30

100

LC1D09

LRD12

AJT20

ATDR30

100

LC1D09

LRD12

AJT20

ATDR30

100

LC1D12

LRD16

AJT20

ATDR30

100

LC1D12

LRD16

AJT20

ATDR30

100

10

LC1D40

LRD3355

AJT60

100

10

LC1D40

LRD3355

AJT60

100

15

LC1D50

LRD3357

AJT70

100

15

LC1D50

LRD3357

AJT70

100

20

LC1D65

LRD3359

AJT100

100

20

LC1D65

LRD3359

AJT100

100

25

LC1D80

LRD3363

AJT110

100

25

LC1D80

LRD3363

AJT110

100

30

LC1D115

LR9D5569

AJT150

100

30

LC1D80

LRD3363

AJT110

100

40

LC1D150

LR9D5569

AJT200

100

40

LC1D115

LR9D5569

AJT150

100

HP

CONTACTOR

OLR

CLASS J

HP

CONTACTOR

OLR

CLASS J

CLASS CC SCCR (kA)

1/2

LC1D09

LRD06

AJT2

ATDR5

100

1/2

LC1D09

LRD05

AJT1-1/2

ATDR2-8/10

100

3/4

LC1D09

LRD06

AJT2

ATDR5

100

3/4

LC1D09

LRD06

AJT2

ATDR5

100

460 Volt, Three-Phase Motors

575 Volt, Three-Phase Motors

CLASS CC SCCR (kA)

LC1D09

LRD07

AJT5

ATDR8

100

LC1D09

LRD07

AJT5

ATDR8

100

1 1/2

LC1D09

LRD08

AJT5

ATDR12

100

1 1/2

LC1D09

LRD07

AJT5

ATDR8

100

LC1D09

LRD08

AJT5

ATDR12

100

LC1D09

LRD08

AJT5

ATDR12

100

LC1D09

LRD10

AJT20

ATDR30

100

LC1D09

LRD08

AJT5

ATDR12

100

LC1D09

LRD14

AJT20

ATDR30

100

LC1D09

LRD12

AJT20

ATDR30

100

7 1/2

LC1D12

LRD16

AJT20

ATDR30

100

7 1/2

LC1D12

LRD16

AJT20

ATDR30

100

10

LC1D18

LRD21

AJT25

100

10

LC1D18

LRD16

AJT20

ATDR30

100

15

LC1D25

LRD22

AJT35

100

15

LC1D25

LRD21

AJT25

100

15

LC1D32

LRD22

AJT40

100

20

LC1D32

LRD22

AJT40

100

25

LC1D40

LRD3355

AJT60

100

30

LC1D40

LRD3355

AJT60

100

30

LC1D40

LRD3355

AJT60

100

40

LC1D50

LRD3357

AJT70

100

30

LC1D40

LRD3357

AJT60

100

50

LC1D65

LRD3359

AJT100

100

40

LC1D50

LRD3359

AJT70

100

75

LC1D115

LR9D5367

AJT125

100

50

LC1D65

LRD3359

AJT100

100

100

LC1D115

LR9D5569

AJT150

100

60

LC1D80

LRD5363

AJT110

100

125

LC1D150

LR9D5569

AJT200

100

75

LC1D115

LR9D5569

AJT150

100

100

LC1D150

LR9D5569

AJT200

100

www.squared.com/.../iec_contactors_starters.nsf/unid/B7D67A0C9FB16F8285256F6900567C4E/$file/Shawmutt10.htm - 22k

IEC Class 10 Overload Relay on Reverse

Phone: 978-462-6662 Fax: 978-462-0181 us.ferrazshawmut.com

Square D NEMA Motor Starters


and Ferraz Shawmut Fuses

Type 2 Protection

Achieving Type 2 No Damage Motor Start Protection


Type 2 No Damage Protection - What Is It and Which Fuses Are Best?
Type 2 protection, also referred to as no damage protection, simply means that if a short circuit occurs, the short circuit protective
device will operate fast enough to prevent fault current damage to healthy equipment in the system. Tests show that current-limiting
fuses are the best choice for the protection of the motor controllers if damage-free performance is required. To ensure that correct fuse
choices are made, short circuit tests must be made on every possible combination of motor control and fuse. This sheet summarizes a
major manufacturers motor starter and the Ferraz Shawmut time-delay fuses which give Type 2 no damage protection. All combinations
are UL witnessed and certified.
200 Volt, Three-Phase Motors
HP

STARTER

CAT. #

230 Volt, Three-Phase Motors

HEATER
CLASS RK1 CLASS J
SIZE

SCCR
(kA)

HP

STARTER

CAT. #

HEATER
CLASS RK1 CLASS J
SIZE

SCCR
(kA)

1 1/2

SB02V02S

B10.2

A6D12R

AJT10

100

1 1/2

SB02V02S

B8.20

A6D10R

AJT8

SB02V02S

B12.8

A6D15R

AJT12

100

SB02V02S

B11.5

A6D15R

AJT12

100
100

SB02V02S

B19.5

A6D20R

AJT17-1/2

100

SB02V02S

B15.5

A6D17-1/2R

AJT15

100

SC03V02S

B32

A6D30R

AJT30

100

SC03V02S

B28.0

A6D30R

AJT25

100

7 1/2

SC03V02S

B50

A6D50R

AJT45

100

7 1/2

SC03V02S

B45

A6D40R

AJT40

100

10

SD01V02S

B62

A6D60R

AJT60

100

10

SD01V02S

B50

A6D50R

AJT50

100

15

SE01V02S

CC81.5

A6D90R

AJT80

100

15

SE01V02S

CC68.5

A6D70R

AJT70

100

20

SE01V02S

CC112

A6D110R

AJT110

100

20

SE01V02S

CC94.0

A6D100R

AJT90

100

25

SE01V02S

CC180

A6D150R

AJT125

100

25

SE01V02S

CC132

A6D125R

AJT110

100

30

SF01V02S

CC156

A6D175R

AJT150

100

30

SE01V02S

CC196

A6D150R

AJT150

100

40

SF01V02S

CC208

A6D200R

AJT200

100

40

SF01V02S

CC180

A6D175R

AJT175

100

50

SG01V02SY500

B3.70

A6D250R

AJT250

100

50

SG01V02SY500

B3.30

A6D225R

AJT225

100

60

SG01V02SY500

B4.15

A6D350R

AJT300

100

60

SG01V02SY500

B3.70

A6D250R

AJT250

100

75

SG01V02SY500

B5.50

A6D400R

AJT400

100

75

SG01V02SY500

B4.15

A6D350R

AJT300

100

100

SG01V02SY500

B6.25

A6D400R

AJT400

100

460 Volt, Three-Phase Motors

575 Volt, Three-Phase Motors

HEATER
CLASS RK1 CLASS J
SIZE

SCCR
(kA)

HP

STARTER

CAT. #

HEATER
CLASS RK1 CLASS J
SIZE

SCCR
(kA)

HP

STARTER

CAT. #

SB02V02S

B7.70

A6D9R

AJT8

100

SB02V02S

B6.25

A6D7R

AJT6

SB02V02S

B12.8

A6D15R

AJT12

100

SB02V02S

B10.2

A6D12R

AJT10

100

7 1/2

SC03V02S

B19.5

A6D20R

AJT17-1/2

100

7 1/2

SC03V02S

B15.5

A6D17-1/2R

AJT15

100

10

SC03V02S

B25

A6D25R

AJT25

100

10

SC03V02S

B19.5

A6D20R

AJT17-1/2

100

15

SD01V02S

B36

A6D35R

AJT35

100

15

SD01V02S

B28.0

A6D30R

AJT25

100

20

SD01V02S

B45

A6D50R

AJT45

100

20

SD01V02S

B40

A6D40R

AJT40

100

25

SD01V02S

B70

A6D60R

AJT60

100

25

SD01V02S

B45

A6D50R

AJT45

100

30

SE01V02S

CC64.3

A6D70R

AJT70

100

30

SE01V02S

CC50.1

A6D60R

AJT50

100

100

40

SE01V02S

CC87.7

A6D90R

AJT90

100

40

SE01V02S

CC68.5

A6D70R

AJT70

100

50

SE01V02S

CC121

A6D125R

AJT110

100

50

SE01V02S

CC87.7

A6D90R

AJT90

100

60

SF01V02S

CC121

A6D150R

AJT125

100

60

SF01V02S

CC103

A6D110R

AJT110

100

75

SF01V02S

CC167

A6D175R

AJT175

100

75

SF01V02S

CC121

A6D150R

AJT125

100

100

SG01V02SY500

B3.00

A6D225R

AJT225

100

100

SF01V02S

CC167

A6D175R

AJT175

100

125

SG01V02SY500

B3.70

A6D250R

AJT250

100

125

SG01V02SY500

B3.00

A6D225R

AJT225

100

150

SG01V02SY500

B4.15

A6D350R

AJT300

100

150

SG01V02SY500

B3.70

A6D250R

AJT250

100

200

SG01V02SY500

B6.25

A6D400R

AJT400

100

200

SG01V02SY500

B4.15

A6D350R

AJT300

100

* These overloads were not tested. Maximum fuse sizes are for the lower value of over-load which was tested.
** Y500
Sized larger than code max for single motor.
Disclaimer: Regarding information available in this document, Ferraz Shawmut, Inc. does not warrant or assume any legal liability or responsibility for the accuracy or usefulness of
any information disclosed. The content in this guide is for informational purposes only. All information has been gathered from the individual websites of the product manufacturers
listed in this document.