Method Statement For Programming of Fire Alarm System For Interfacing Module

This Method Statement outlines the procedure for reprogramming the fire alarm system to interface with the AHU unit and troubleshoot issues with Annunciator-2. It includes preventive maintenance steps, responsibilities, and references to relevant safety codes. The successful completion of this task will ensure an effective fire alarm system is handed over to the client.

Uploaded by

joewell01986
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2 views1 page

Method Statement For Programming of Fire Alarm System For Interfacing Module

This Method Statement outlines the procedure for reprogramming the fire alarm system to interface with the AHU unit and troubleshoot issues with Annunciator-2. It includes preventive maintenance steps, responsibilities, and references to relevant safety codes. The successful completion of this task will ensure an effective fire alarm system is handed over to the client.

Uploaded by

joewell01986
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

METHOD STATEMENT MSS:

LOGO PROGRAMMING OF FIRE ALARM SYSTEM FOR INTERFACING Rev.: 00


MODULE OF AHU UNIT AND NEED TO CHECK AND Date:
TROUBLESHOOT EXACT FAULT OF ANNOUNCIATOR

1. Purpose
This Method Statement document explains the method for Reprogramming of fire alarm system (FAS) for
interfacing module of AHU Unit and needs to check the exact fault of Annunciator-2 at (Project/Facility Name) and
Annunciator.

2. Scope
The scope of works detailed within this MS document applies to method for Reprogramming for a fire alarm
system (FAS) for Interfacing module of AHU and require to examine the exact defects of Annunciator-2 whereby
upon satisfactory accomplishment, inspection of works, the below mentioned Project requirement and effective &
efficient system is handed Over to the Client.

3. Reference
 NFPA 101Life Safety Code
 NFPA 72 Fire alarm system
 NFPA 70 (2014 Edition)- Electrical
4. Procedure
Sr Activity Responsible Person Controlling Document
Preventive maintenance:
1. Authorized PTW SHALL be Issued by the client before the start of works Worksite Engineer
2. Personnel conducting works SHALL wear appropriate PPE
3. Safety warning signs SHALL be provided and the area cleared of non-
essential personnel
4. The programmer will connect the software with the fire alarm panel in Worksite Engineer
MODE-1.
5. The Programmer already added the existing interfacing module as per
the fire alarm panel Node and they will provide cause and effect (During
fire alarm activation AHU module will be activated after 180 seconds
time latency) for the Existing Module (EM).
6. The programmer will do the changing of caution and effect as per the Worksite Engineer
site standard to activate the Existing module.
7. After completing programming and updating the fire system. We require
to do the Fire Alarm Testing (FAT) to check the cause and effect of the
Exiting module.
8. The programmer will connect the software with fire alarm master panel
in (specified Room) and he will check and troubleshoot exact fault of
annunciator -2 Trouble.
Date: Signatures:

Contractor:

Issued for Approval:

Reviewed by:

Approved by:

MOS/Programming of Fire Alarm System for Interfacing Module