SCB9

The SC(B) series epoxy resin dry-type transformers are designed for high voltage applications (10KV) and offer features such as flame retardance, maintenance-free operation, and compact size. They are suitable for various environments including commercial buildings and harsh conditions like subways and marine drilling. The transformers comply with IEC standards and provide detailed specifications for capacity, performance, and operational conditions.

Uploaded by

Schwarz Chimunhu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
14 views6 pages

SCB9

The SC(B) series epoxy resin dry-type transformers are designed for high voltage applications (10KV) and offer features such as flame retardance, maintenance-free operation, and compact size. They are suitable for various environments including commercial buildings and harsh conditions like subways and marine drilling. The transformers comply with IEC standards and provide detailed specifications for capacity, performance, and operational conditions.

Uploaded by

Schwarz Chimunhu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

10KV Dry-type Transformer POWER TRANSMISSION AND

DISTRIBUTION PRODUCT SELECTION


PROFESSIONAL MANUFACTURER OF
HIGH AND LOW VOLTAGE PRODUCTS

10KV Dry-type Transformer


SC(B)□ Series Epoxy Resin Dry-type Transformer
The SC (B) series epoxy resin dry type transformers have the advantages of flame retardant, fireproof, explosion-proof,
maintenance free, and small size due to their coils being encapsulated with epoxy resin. They can be directly installed in load
centers and are widely used in power transmission and transformation systems, as important places as commercial residences,
public buildings, airports, as well as in harsh environments like subways, smelters, ships, and marine drilling.
Standard:IEC60076-1, IEC60076-11.

General

33 34
10KV Dry-type Transformer 10KV Dry-type Transformer
SC(B)□ Series Epoxy Resin Dry-type Transformer SC(B)□ Series Epoxy Resin Dry-type Transformer

Selection Structure
S C (B) - / ■ Iron core:
● The iron core is made of high-quality oriented cold-rolled silicon steel sheet, with a
High voltage level (KV):6~11KV laminated structure of 45° full oblique seam, and the core column is bound with
insulating tape.
● The surface of the iron core is sealed with insulating resin paint to prevent moisture
Rated capacity (KVA):30~2500KVA
and rust, and the clamps and fasteners are surface-treated to prevent rust.
Performance level code:9,11,13
Low voltage foil coil ■ Low voltage copper foil coil:
Fixed molding (resin casting) ● The low-voltage winding is wound with high-quality copper foil, so that zero axial
Three phase
short-circuit stress can be achieved in the case of short circuit. The interlayer and
winding end are insulated with thermosetting epoxy prepreg cloth. The whole winding
is placed in the oven. After heating, the winding is aggregated into a solid whole.
Scientific and reasonable design and pouring process make the product partial
Operating conditions
discharge less, noise lower, and heat dissipation capacity strong.
1. Ambient temperature: maximum temperature: +40°C, minimum temperature: -25℃.
2. Average temperature of the hottest month:+30℃, average temperature in the hottest year:+20℃. ■ High voltage winding:
3. Altitude not exceeding 1000m. ● The high-voltage winding adopts enamelled copper wire or film-coated copper wire, and
4. The waveform of the power supply voltage is similar to a sine wave. glass fiber and epoxy resin composite material are used for insulation. Its expansion
5. The three-phase supply voltage should be approximately symmetrical. coefficient is similar to that of copper conductor, and it has good impact resistance,
6. The relative humidity of the surrounding air should be lower than 93%. temperature change resistance, and crack resistance. All components of glass fiber and
7. And there should be no water droplets on the surface of the coil epoxy resin are self-extinguishing, flame retardant and non-polluting. Epoxy resin has
8. Where to use: indoors or outdoors. good insulation properties and is especially suitable for making high-voltage coils.

■ Temperature control device and air cooling system:

Features ● The temperature control device has the functions of failure alarm, over-temperature
alarm, over-temperature trip, automatic/manual start and stop of the fan, and is
1. The carefully designed coil structure and vacuum immersion treatment ensure that the SG (B) 10 transformer operates without
connected to the computer through the RS485 interface for centralized monitoring and
partial discharge and will not exhibit crack performance throughout its service life. Its insulation level will remain in good condition
control.At the same time, it also has the function of "black gate", which can record the
as before.
winding temperature of the transformer when it is powered off.
2. The high-voltage part adopts continuous wire winding, low-voltage foil winding, vacuum immersion, curing treatment, and ● The air-cooling system adopts a cross-flow top-blowing cooling fan, which has the
high-strength ceramic support, which has good resistance to sudden short circuit currents. characteristics of low noise, high wind pressure, and beautiful appearance. It can run
3. Flame retardant, explosion-proof, non-toxic, self-extinguishing, and fireproof for a long time under the condition of forced air cooling at 125% of the rated load.
4. The SG (B) 10 transformer produces almost no smoke when burned in a high-temperature open flame
5. The insulation level of the transformer is Class H (180℃). ■ Shell:
6. The insulation layer is very thin, with strong short-term overload capacity, without the need for forced cooling, and can overload ● Protect the shell and provide further safety protection for the transformer,with protection
by 120% for long term use, 140% lasting for 3 hours. Due to its elasticity and non aging properties, this insulation material can be levels such as IP20, IP23, etc.
fully loaded at one time at ± 50℃. ● The shell materials include cold-rolled steel plate, stainless steel plate, aluminum alloy,
etc. for users to choose from.

35 36
10KV Dry-type Transformer 10KV Dry-type Transformer
SC(B)□ Series Epoxy Resin Dry-type Transformer SC(B)□ Series Epoxy Resin Dry-type Transformer

Structure SCB9-30~2500/10KV technical data


■ The factory configuration of SCB without protective shell (IP00) is as follows Voltage combination No-load Dimensions Total
Rated Connection No-load Load Short circuit
● 4 bi-directional flat wheels (when requested by the customer) capacity High Tapping Low Loss (w) current weight
(KVA) voltage voltage group label loss(W) 120℃ (%)
impedance(%)
L W H (kg)
● 4 lugs range (KV)
(KV)
● Towing holes on the base
30 220 750 2.4 700 350 620 250
● 2 grounding points
50 310 1060 2.4 710 350 635 295
● 1 nameplate
● 2 "Electric Hazard" warning signs 80 420 1460 1.8 860 730 780 430

● No load voltage regulating tap, operated when the transformer is powered off, to adapt 100 450 1670 1.8 940 710 795 520

the transformer to the actual supply voltage 125 530 1960 1.6 1000 710 860 670
● High voltage side connecting rod with connecting wire from above 160 610 2250 1.6 1080 710 1020 840
● Low-voltage outgoing busbar with upward outlet 4.0
200 700 2680 1.4 1100 710 1060 960
250 6 810 2920 1.4 1150 710 1100 1120
6.3
315 990 3670 1.2 1150 770 1125 1230
6.6 ±5 Dyn11
400 0.4 1100 4220 1.2 1190 870 1175 1485
10 ±2×2.5 Yyn0
500 1310 5170 1.2 1230 870 1265 1580
10.5
630 11 1510 6220 1.0 1465 870 1245 1840
■ The factory configuration of SCB with IP21, IP23 metal protective shell is as follows
630 1460 6310 1.0 1465 870 1245 1840
● All contents mentioned above for SCB without protective casing (Ip00)
800 1710 7360 1.0 1420 870 1395 2135
● 1 set of IP21 metal protective housing, standard anti-corrosion protection
1000 1990 8610 1.0 1460 870 1420 2500
1250 2350 10260 1.0 6.0 1580 970 1485 2970
1600 2760 12400 1.0 1640 1120 1715 3900
2000 3400 15300 0.8 1780 1120 1710 4225
2500 4000 18180 0.8 1850 1120 1770 4790

Overall and mounting dimensions(mm)

W H

L
Note:The dimensions and weights provided are only for reference in design and selection.
The final size and weight are subject to our prodect drawings.

37 38
10KV Dry-type Transformer 10KV Dry-type Transformer
SC(B)□ Series Epoxy Resin Dry-type Transformer SC(B)□ Series Epoxy Resin Dry-type Transformer

SCB10-30~2500/10KV technical data SCB11-30~2500/10KV technical data


Voltage combination Dimensions Voltage combination No-load Dimensions Total
Rated Connection Load No-load Short circuit Total Rated Connection No-load Load Short circuit
No-load capacity High Tapping Low
capacity High Tapping Low Loss (w) current impedance weight Tapping Loss (w) current weight
(kVA) voltage voltage group label loss(W) 120℃ (%) (%) L W H (kg) (KVA) voltage voltage group label loss(W) 120℃ (%)
impedance(%)
L W H (kg)
range (KV) range (KV)
(KV) (KV)
30 190 710 2.0 580 450 650 300 30 170 710 2.3 955 750 840 270
50 240 1000 2.2 970 750 860 340
50 270 1000 2.0 600 450 650 380
80 330 1380 1.7 1015 750 925 460
80 370 1380 1.5 880 500 800 470
100 360 1570 1.7 1030 750 960 530
100 400 1570 1.5 970 500 820 560
125 420 1850 1.5 1060 750 1000 605
125 470 1850 1.3 970 500 860 650 160 480 2130 1.5 1090 900 1045 730
4.0
160 540 2130 1.3 980 650 950 780 200 550 2530 1.3 1105 900 1080 825
4.0
200 620 2530 1.1 1000 650 970 880 250 640 2760 1.3 1180 900 1125 1010

250 6 720 2760 1.1 1040 760 1070 1030 315 6 790 3470 1.1 1225 900 1140 1165
6.3 400 6.3 880 3990 1.1 1330 900 1195 1490
315 880 3470 1.0 1100 760 1110 1250
6.6 ±5 Dyn11 500 6.6 ±5 Dyn11 1040 4880 1.1 1345 900 1255 1650
400 0.4 980 3990 1.0 1170 760 1235 1400 0.4
10 ±2×2.5 Yyn0 630 10 ±2×2.5 Yyn0 1200 5880 0.9 1540 1150 1175 1915
500 1160 4880 1.0 1190 760 1250 1600
10.5 630 10.5 1170 5960 0.9 1540 1150 1175 1915
630 11 1340 5880 0.85 1220 760 1250 1900 800 11 1360 6960 0.9 1600 1150 1220 2305
630 1300 5960 0.85 1220 760 1250 1900 1000 1590 8130 0.9 1645 1150 1285 2690

800 1520 6960 0.85 1330 760 1330 2580 1250 1880 9690 0.9 6.0 1705 1150 1345 3225
1600 2200 11700 0.9 1765 1150 1405 3805
1000 1770 8130 0.85 1350 920 1450 2850
2000 2740 14400 0.7 1840 1150 1475 4435
1250 2090 9690 0.85 6.0 1440 920 1550 3200
2500 3240 17100 0.7 1900 1150 1560 5300
1600 2450 11700 0.85 1510 1170 1620 3800
1600 2200 12900 0.9 1765 1150 1405 3805
2000 3060 14400 0.7 1530 1170 1785 4280 2000 2740 15900 0.7 8.0 1840 1150 1475 4435
2500 3600 17100 0.7 1560 1170 1930 5250 2500 3240 18800 0.7 1900 1150 1560 5300

Overall and mounting dimensions(mm) Overall and mounting dimensions(mm)

W H H
W

L L

Note:The dimensions and weights provided are only for reference in design and selection. Note:The dimensions and weights provided are only for reference in design and selection.
The final size and weight are subject to our prodect drawings. The final size and weight are subject to our prodect drawings.

39 40
10KV Dry-type Transformer 10KV Dry-type Transformer
SC(B)□ Series Epoxy Resin Dry-type Transformer SC(B)□ Series Epoxy Resin Dry-type Transformer

SCB12-30~2500/10KV technical data SCB13-30~2500/10KV technical data


Voltage combination Dimensions Total Voltage combination No-load Dimensions Total
Rated Connection No-load Load No-load Short circuit Rated Connection No-load Load Short circuit
capacity High Tapping Low Loss (w) weight capacity High Tapping Low Loss (w) current weight
(KVA) voltage voltage group label loss(W) 120℃ current(%) impedance(%) L W H (kg) (KVA) voltage voltage group label loss(W) 120℃ (%)
impedance(%)
L W H (kg)
range (KV) range (KV)
(KV) (KV)
30 150 710 2.3 955 750 840 270 30 135 640 2.3 955 750 840 270
50 215 1000 2.2 970 750 860 340 50 195 900 2.2 970 750 860 340
80 295 1380 1.7 1015 750 925 460 80 265 1240 1.7 1015 750 925 460
100 320 1570 1.7 1030 750 960 530 100 290 1410 1.7 1060 750 960 560
125 375 1850 1.5 1060 750 1000 605 125 340 1660 1.5 1075 750 1000 630
160 430 2130 1.5 1090 900 1045 730 160 385 1910 1.5 1105 900 1045 770
4.0 4.0
200 495 2530 1.3 1105 900 1080 825 200 445 2270 1.3 1120 900 1105 875
250 575 2760 1.3 1180 900 1125 1010 250 515 2480 1.3 1195 900 1125 1055
315 6 705 3470 1.1 1225 900 1140 1165 315 6 635 3120 1.1 1555 1150 1175 1190
400 6.3 785 3990 1.1 1330 900 1195 1490 400 6.3 705 3590 1.1 1225 900 1140 1500
500 6.6 ±5 Dyn11 930 4880 1.1 1345 900 1255 1650 500 6.6 ±5 Dyn11 835 4390 1.1 1315 900 1190 1700
0.4 0.4
630 10 ±2×2.5 Yyn0 1070 5880 0.9 1540 1150 1175 1915 630 10 ±2×2.5 Yyn0 965 5290 0.9 1345 900 1265 1985
630 10.5 1040 5960 0.9 1540 1150 1175 1915 630 10.5 935 5360 0.9 1555 1150 1175 1985
800 11 1210 6960 0.9 1600 1150 1220 2305 800 11 1090 6260 0.9 1600 1150 1220 2360
1000 1410 8130 0.9 1645 1150 1285 2690 1000 1270 7310 0.9 1660 1150 1285 2775
1250 1670 9690 0.9 6.0 1705 1150 1345 3225 1250 1500 8720 0.9 6.0 1720 1150 1350 3310
1600 1960 11700 0.9 1765 1150 1405 3805 1600 1760 10500 0.9 1780 1150 1405 3940
2000 2440 14400 0.7 1840 1150 1475 4435 2000 2190 13000 0.7 1840 1150 1475 4595
2500 2880 17100 0.7 1900 1150 1560 5300 2500 2590 15400 0.7 1900 1150 1565 5495
1600 1960 12900 0.9 1765 1150 1405 3805 1600 1760 11600 0.9 1780 1150 1405 3940
2000 2440 15900 0.7 8.0 1840 1150 1475 4435 2000 2190 14300 0.7 8.0 1840 1150 1475 4595
2500 2880 18800 0.7 1900 1150 1560 5300 2500 2590 17000 0.7 1900 1150 1565 5495

Overall and mounting dimensions(mm) Overall and mounting dimensions(mm)

W H H
W

L L

Note:The dimensions and weights provided are only for reference in design and selection. Note:The dimensions and weights provided are only for reference in design and selection.
The final size and weight are subject to our prodect drawings. The final size and weight are subject to our prodect drawings.
10KV Dry-type Transformer
SC(B)□ Series Epoxy Resin Dry-type Transformer

Carry
● The transformer is equipped with safe handling devices.

● For transformers without enclosures and transformers with top door openings, use the four lifting lugs of the transformer for
lifting (must be lifted vertically, not diagonally); For transformers with 2 lifting lugs in the center of the top of the casing, use 2
lifting lugs for lifting. The angle formed by the sling should not exceed 60°.

● Firstly, the forking capacity of the forklift should be checked. If appropriate, the fork arm should be inserted into the base channel
steel after removing the rollers.

● Pulling and moving the transformer should be carried out from the base. For this purpose, holes with a diameter of 27 mm are
made on each side of the base. Dragging is possible in two directions: the axis of the base and the direction perpendicular to this
axis.

Contact roller

Sleeper
Lfting jack

Figure 1- Lifting with a sling or forklift Figure 2- Installation of the roller

43