(Susol VCB) UL Type Catalog en 202005

The Susol VCB is a new line of ANSI Vacuum Circuit Breakers designed for medium voltage distribution, featuring high interrupting capacity and large current ratings. It offers a variety of models and accessories to enhance reliability and compatibility with existing systems, making it suitable for critical installations such as power plants and high-rise buildings. The product complies with various industry standards and includes advanced features for safety and convenience in switchgear configuration.

Uploaded by

chris.pena72ph
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
36 views96 pages

(Susol VCB) UL Type Catalog en 202005

The Susol VCB is a new line of ANSI Vacuum Circuit Breakers designed for medium voltage distribution, featuring high interrupting capacity and large current ratings. It offers a variety of models and accessories to enhance reliability and compatibility with existing systems, making it suitable for critical installations such as power plants and high-rise buildings. The product complies with various industry standards and includes advanced features for safety and convenience in switchgear configuration.

Uploaded by

chris.pena72ph
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 96

ANSI VCB

ANSI Vacuum Circuit Breakers


Susol VCB Contents

● Overview 04
● External structure 20
● Basic features and interrupting operation 22
● Standards and certification 25
● Types and ordering information 26
● Ratings 31
Susol VCB is full line-up new VCB which has the high
● Accessories 34
interrupting capacity, large current(~50kA, ~3000A), and ● Control circuit diagrams 66
maximized compatibility with existing products through ● Dimensions 69
the dual phases and compact sized models. ● Technical data 88

2
<< Susol VCB Series

3
Vacuum Circuit Breaker, VCB is installed in the medium voltage distribution
lines to protect life and load equipment. In case of accidents such as over
current, short circuit and ground fault current, VCB works by interrupting the
circuit through the inner Vacuum Interrupter which is acted by signal from the
outside separate relay.

Susol VCB responds.


- customer needs for the breakers with high interrupting capacity and large
current due to the integration and increase of the load capacity.
- worldwide trend of diversification in the medium voltage distribution lines.
- increase of the reliability for the temperature characteristics of circuit
breakers.

Premium-type products to improve convenience and reliability of medium


voltage switchgear configuration.
- full line-up modeling to the high interrupting capacity and large current.
- main structure with high reliability application.
- a variety of accessories and ability to maximize.

Suitable for use as the main circuit breaker to protect key installations in the
places such as device industry, power plants, high-rise buildings, large ships.

4
<< Susol VCB Series

▶ Strengthening of the high interrupting capacity and large


current models and full line-up new VCB models to high/
middle/low.
Voltage Interrupting current Rated current
05/15kV 25/31.5/40/50kA 1200/2000/3000A
27kV 25kA 1200A
38kV 31.5/40kA 1200/2000A

▶ Main circuit structure with high reliability.


•Maximizing the durability and reliability of the main circuit contactors
(Stego Tulip contactor).
•Strong structure for the temperature rise (Natural cooling system).

▶ Convenience of switchgear configuration and a variety of


accessories.
•CB compartment structure: Metal isolation structures to prevent the
accident spread and ensure safety. And the convenience of switchgear
building is extended by its module style.
•A variety of accessories: UVT, Locking Magnet, Plug Interlock, Key lock,
Temperature Sensor, MOC, TOC, Earthing S/W.
•Maximizing compatibility with existing products through the dualistic
deployment of phases and compact models.

※ Type testing is complete for all models according to latest standard,


IEEE Std C37.09, IEEE Std C37.20.2, ANSI C37.54, ANSI C37.55, UL (CSA)

5
4.76/15/27kV (UVL-05/15/27)
•Rated short-time (to withstand current ): 4sec
•Rated operating sequence: O-0.3s-CO-15s-CO
•Various cradle: Ha, Hb type
•CB Compartment for MCSG available
•A variety of control power
- DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V
- AC 48V, AC 100~130V, AC 220~250V
•A variety of accessories
- VCB part: Charge switch, UVT, Secondary trip coil, Latch checking
switch, Position switch, Locking magnet, Plug interlock, Key lock,
Button cover, Button padlock, Padlock (H type Door interlock), MOC
- Cradle part: MOC (Mechanical Operated Cell switch), TOC (Truck
Operated Cell switch), Temperature sensor, Earthing switch &
accessaries, Door, Door interlock, Door emergency button
- Others: Racking in/out handle,
UVT Time delay controller, CTD
(Condensor Trip Device),

Susol VCB Family


Temperature module
•Disconnected/Test/Connected Automatic Position Indicator
•Standards and certification
Susol VCB series are premium-type products - IEEE Std C37.09, ANSI C37.54,
featuring main structure with high reliability UL Listed & CSA
application and a variety of accessories and
ability to maximize to be suitable for use as the
main circuit breaker to protect key installations in
the places such as device industry, power plants,
high-rise buildings, large ships
Ur Isc Ir
(kV) (kA) (A)
4.76 25 1200
2000
31.5 1200
2000
15 25 1200
2000
31.5 1200
2000
27 25 1200

Full line–up & Compact


Full line-up new VCB models to the high interrupting
capacity and large current (~ 50kA, ~ 3000A) featuring
maximization of compatibility with existing products
through the dualistic deployment of phases and
compact models
<< Susol VCB Series

4.76/15kV (VH-05/15) 38kV (UVH-38)


•Rated short-time (to withstand current ): 2sec •Rated short-time (to withstand current ): 4sec
•Rated operating sequence: O-0.3s-CO-3min-CO •Rated operating sequence: O-0.3s-CO-15s-CO
•Various cradle: H type •Various cradle: H type
•CB Compartment for MCSG available •CB Compartment for MCSG available
•A variety of control power •A variety of control power
- DC 48V, DC 110V, DC 125V, DC 220~250V - DC 48V, DC 110V, DC 125V, DC 220~250V
- AC 48V, AC 110V, AC220V - AC 48V, AC 110V, AC220V
•A variety of accessories •A variety of accessories
- VCB part: Charge switch, UVT, Secondary trip coil, Latch checking - VCB part: Charge switch, UVT, Secondary trip coil, Latch checking
switch, Position switch, Locking magnet, Plug interlock, Key lock, switch, Position switch, Locking magnet, Plug interlock, Key lock,
Button cover, Button padlock, Padlock (H type Door interlock), MOC Button cover, Button padlock, Padlock (H type Door interlock), MOC
- Cradle part: MOC (Mechanical Operated Cell switch), TOC (Truck - Cradle part: MOC (Mechanical Operated Cell switch), TOC (Truck
Operated Cell switch), Temperature sensor, Earthing switch & Operated Cell switch), Temperature sensor, Earthing switch &
accessaries, Door, Door interlock, Door emergency button accessaries, Door, Door interlock, Door emergency button
- Others: Racking in/out handle, UVT Time delay controller, CTD - Others: Racking in/out handle, UVT Time delay controller, CTD
(Condensor Trip Device), Temperature module (Condensor Trip Device), Temperature module
•Disconnected/Test/Connected Automatic Position Indicator •Disconnected/Test/Connected Automatic Position Indicator
•Standards and certification •Standards and certification
- IEEE Std C37.09 - IEEE Std C37.09

Ur Isc Ir
(kV) (kA) (A)
4.76 40 1200
2000
3000
50 1200
2000
3000
15 40 1200
2000 Ur Isc Ir
(kV) (kA) (A)
3000
50 1200 38 31.5 1200
2000 2000
3000 40 1200
2000

Ha type He, Hf type VH type


7
Main circuit structure
with high reliability
 Susol




VCB

Breaker
 Insulation rod
 Lower terminal
 Shunt
 Vacuum interrupter
 Upper terminal
 Tulip contactor

Fixed
electrode
Fixed
Contacts
seal cup Vacuum Interrupter, VI
Arc shield
The vacuum rate within the VI is very high the contacts are made of special alloy (copper-
Bellows
shield (approximately 5x10-5 Torr) and the spacing chromium) and the interior is completely
Ceramic between fixed contact and movable sealed to prevent loss of vacuum.
contact is about 6~20mm, depending on Therefore the wearing of the contacts can be
Bellows
Movable
the voltage. minimized in the event of short-circuit and the
Movable seal cup
electrode The contacts are in a structure that arc can arc energy by overvoltage or switching can be
easily be extinguished and the surfaces of reduced effectively.

8
<< Susol VCB Series

Convenience and
Variety

•Maximizing the durability and reliability


of the main circuit contactors
(Stego Tulip contactor)
•Strong structure for the temperature rise
(Natural cooling system)

9
Stego Tulip
Main circuit structure with high reliability

•Maximizing the durability and reliability of the main circuit contactors (Stego Tulip contactor)
•Strong structure for the temperature rise (Natural cooling system)

Tulip finger

Tulip spring

Main circuit terminal


of the breaker

Plate understar :
Securing freedom of Tulip

Plate star: Supporting Tulip for maintaining position and torsional flow prevention

Structure of Stego Tulip Terminal

•Maintaining the connection between breaker and cradle for the optimum current path through securing freedom of Tulip.
•Increasing the heat dissipation area of the contactors and minimizing aging.

10
<< Susol VCB Series

4.76/15/27/38kV ...
(UVL-05/15/27, VH-05/15, UVH-38)

•Drawout / natural cooling system


•Improved temperature
characteristics and ensured high
reliability

UVL type Tulip contactor VH Type Tulip contactor UVH type Tulip contactor

11
CB Compartment
Convenience in building switchgears

•CB compartment structure: H type cradle


•Metal isolation structure to prevent the accident spread and ensure safety
•Convenience of switchgear building

4.76/15/27/38kV 25/31.5/40/50kA
•Metal isolation structure to prevent the accident spread and ensure safety
•Convenience of operation by Truck
- Drawable in the closed position of the switchgear door
- Racking-in/out positions indicated mechanically
•Equipped with safety devices and accessories
- Control power connected Interlock
- Earthing S/W and interlock, MOC/TOC (ANSI)
•Convenience in building switchgears
- Module assembly with CB compartment

12
<< Susol VCB Series

LV
CB Compartment
Compartment

Busbar & Cable


Compartment

Accessories of CB compartment
(H type cradle) PT
Compartment
■ MOC (Mechanism Operated Cell S/W)
■ TOC (Truck Operated Cell S/W) PT
Compartment
■ Shutter Padlock
■ Temperature Sensor
■ Door Emergency ON/OFF Button
■ Earthing switch & Accessaries
Key lock for Earthing S/W
Locking Magnet for Earthing S/W
Position S/W for Earthing S/W
■ TM (Temperature Monitoring Unit)

13
Accessories
A variety of accessories for UVL-05/15/27

If accessories are attached to


the breaker, the function of
the breaker is upgraded.
Susol VCB provides a variety of
accessories depending on the
purpose.

Breaker
 Motor  Key lock  CTD (Condenser trip device)
 Closing coil  Button padlock M OC
T rip coil  Button cover  Padlock
 Counter  Position switch  Plug Interlock
 Auxiliary contact  Racking in/out handle
 UVT coil  UVT Time delay controller

14
<< Susol VCB Series

A variety of accessories for UVCL-05/15/27

If accessories are attached to the


cradle, the function of
the breaker is upgraded.
Susol VCB provides a variety of
accessories depending on the
purpose.

Cradle (H type)
 TOC (Truck operated cell s/w)  Shutter padlock
 MOC (Mechanical operated cell s/w)  Emergency ON/OFF button
 Temperature sensor  TM (Temperature monitoring unit)
 Door  Lift Interlock
 Door interlock

15
Accessories
A variety of accessories for UVH-38

If accessories are attached to


the breaker, the function of
the breaker is upgraded.
Susol VCB provides a variety of
accessories depending on the
purpose.

Breaker
 Motor  Latch checking switch  Charge handle
 AC/DC coil rectifier  Auxiliary contact wire  Racking in/out handle
T rip coil/Closing coil  Key lock U VT Time delay controller
Secondary trip coil  Button cover/Push bar  CTD (Condenser trip device)
 AC/DC UVT coil rectifier  Button padlock
 UVT coil  Lifting hook

16
<< Susol VCB Series

A variety of accessories for UVCH-38

If accessories are attached to the


cradle, the function of
the breaker is upgraded.
Susol VCB provides a variety of
accessories depending on the
purpose.

Cradle (H type)
 MOC (Mechanism operated cell switch)  Door
 TOC (Truck operated cell switch) Emergency ON/OFF button
 Shutter padlock  TM (Temperature monitoring unit)
 Temperature sensor

17
Accessories
A variety of accessories for VH-05/15

If accessories are attached to


the breaker, the function of
the breaker is upgraded.
Susol VCB provides a variety of
accessories depending on the
purpose.

Breaker
 Motor  Mechanical position indicator
 Trip coil/Closing coil  Auto connection
 Auxiliary Contact  Code plate
 Position padlock  Charge interlock

18
<< Susol VCB Series

A variety of accessories for VCL-05/15

If accessories are attached to the


cradle, the function of
the breaker is upgraded.
Susol VCB provides a variety of
accessories depending on the
purpose.

Cradle (H type)
 Auto connection
 Charge interlock
 Mechanically operated cell switch (MOC)
 Truck operated cell switch (TOC)

19
External structure of VCB

Breaker ... UVL type

Name of each part


❶ CLOSE Button
❷ OPEN Button
❸ Charge/Discharge Indicator
❹ CLOSED/OPEN Indicator
❺ ❺ Manual Charging Handle
❶ ❻ Operation Counter

❼ 3 Position Indicator
❷ (Disconnected, Test, Connected)

Back side

20
Breaker ... UVH type

Name of each part


❶ CLOSE Button
❷ OPEN Button

❸ Charge/Discharge Indicator
❻ ❹ CLOSED/OPEN Indicator
❺ Manual Charging Handle
❸ ❻ Key Lock

❼ Operation Counter

❽ 3 Position Indicator

(Disconnected, Test, Connected)

Back side

21
Basic functions and interrupting operation

Basic functions

Manual operation
① Manual Charge
a) UVL type: operate the charge handle 7-8 times as a fully stroke.
b) UVH type: Insert the charge handle into the handle slot first. Rotate the handle clockwise 40 times more and
then charge will be complete with a click sound.
- When the closing spring is charged fully "CHARGED" is displayed at the charge indicator.

② Manual closing
a) Pressing the CLOSE Button the breaker is closed.
b) With the closing of the breaker "CLOSE" is displayed at CLOSED/OPEN Indicator and "DISCHARGED" at the
charge indicator.

③ Manual trip
a) Pressing the OPEN Button the breaker is opened.
b) "OPEN" is displayed at CLOSED/OPEN Indicator.

Electric operation
① Electric charge
The breaker is remotely closing with charging of closing spring.
If the breaker trips the closing spring is automatically charged by gear motors.

② Electric closing
Remote closing is operated by the closing coil.

③ Electric trip
Remote trip can be operated by the trip coil or UVT coil.

Main contacts are operated by the energy of the spring mechanism and closing spring is charged by the motor in the
mechanism.
Breaker is closed by closing coil and tripped by trip coil.
These operations are repeated in VCB as shown in the below sequence chart.

Start closing Complete closing


Closing signal Trip(Open) signal
Control power ON Start opening
Charging time of closing spring Complete
(VL type : 5 sec, VH type : 12 sec.) opening

Motor

Closing spring

Opening spring

Closing coil

Opening coil

Main contact
Closing time Opening time

Sequence of the switching mechanism

22
The interruption of vacuum interrupters

The interruption of VCB is carried out by the vacuum interrupters.


Interrupter contacts as a key part made of copper - chromium (CuCr) material with spiral shape have low contact
wear characteristics and withstand voltage is excellent.
Spiral contacts make the arc generated between the surfaces of contacts rotated around the surface of contact by
the induced magnetic field generated due to the spiral contact structure, which results in preventing local heating,
thereby corruption and interrupting instantaneously.

Fixed electrode

Fixed seal cup

Fixed shield

Contacts Arc shield

Ceramic

Bellows shield

Bellows

Movable seal cup

An example of oscillogram obtained through the interrupting test using LC resonant circuit

23
Basic functions and interrupting operation

The interruption of vacuum interrupters

In case of using the flat contact


any of the designs do not reflect
on when contacts are opening the
arc with high temperature is
contracted and fixed in the center
of the contacts,Which is called
pinch effect.
To prevent the effect two kinds of
contact shapes are designed.
One is Axial magnetic field which
spreads the arc before its
contraction, and the other is
Radial magnetic field which
permits the contraction of the arc
but makes it rotated to disperse
the energy.
Because contracted arc is shaped
like a cylinder it is called
Contracted arc or columnar arc.

Arc voltage waveforms and arc image captured during arcing time

Spiral contact structure (Radial magnetic field), using the


force (F = j×B) generated by the interaction of the radial Radial magnetic field type contact
magnetic field caused by the current flowing through the arc
between two contacts, disperse the arc energy evenly on the
surface of contact by rotating the arc that is contracted by
the pinch effect so as to minimize contact damage.
The images show arc behavior during the arcing time of
about 8ms by shooting with high-speed camera capable of
shooting 10,000 frames per sec. (0.1ms/frame) by focusing
on parts of the arcing time on the above graph and
simultaneously measured arc voltage also represented to
show arc state by section. Columnar arc Direction of
rotating arc
Current

Arc driving principle in the contacts of


Radial magnetic field

24
Standards and certification

Susol VCB has been type tested and obtained certifications according to the latest IEC standard at international
testing laboratory and can be installed and applied at the environment and conditions in accordance with the
standard.

 Standard
- IEEE Std C37.09, ANSI C37.54, UL Listed & CSA

 Test and certification


•Test report (KERI)
•Test report (KEMA)

25
Types and ordering information

UVL-05/15/27
Breaker

UVL 15 H 32 A 12

Basic model name Rated voltage (kV) Version Interrupting current (kA) Phase distance/Compatibility Rated current (A)
UVL Susol VCB 05 4.76 P Fixed 25 25 A 150mm 12 1200A
15 15 H H type drawout (for MCSG) 32 31.5 B 210mm 20 2000A
27 27 C 254mm
D 275mm
R 150mm (Compact MCSG)
S 210mm (Compact MCSG)&CI
P type
- 4.76/15kV 25/31.5kA 1200/2000A (Phase 150/210/254)
- 27kV 25kA 1200A (Phase 254)
H type
- 4.76/15kV 25/31.5kA 1200A (Phase 150/210)
- 4.76/15kV 25/31.5kA 2000A (Phase 210)
- 4.76/15kV 25/31.5kA 1200A (Phase 150/210, Compact MCSG)
- 4.76/15kV 25/31.5kA 2000A (Phase 210, CI)

UVL-15H32A12 M1 C1 T1 SB2 U1 A 13...

Motor control voltage Trip coil voltage UVT Other accessories Note)
M0 Without motor T0 Without trip coil U0 Without UVT A1 Secondary Trip coil
M1 DC 110V T1 DC 110V U1 DC 110V A2 Secondary Trip Coil with TCS Contact
M2 DC 200~250V T2 DC 200~250V U2 DC 200~250V A3 Position s/w (Test: 1a1b, Service: 2b)
M3 DC 125V T3 DC 125V U3 DC 125V A4 Position s/w (Test: 2a, Service: 2a)
M4 DC 24V~30V T4 DC 24V~30V U4 DC 24V~30V A5 Position s/w (Test: 1a1b, Service: 1a1b)
M5 AC 48V~60V T5 AC 48V~60V U5 AC 48V~60V A7 Keylock
M6 AC 48V T6 AC 48V U6 AC 48V A8 Button Padlock
M7 AC 100V~130V T7 AC 100V~130V U7 AC 100V~130V A9 Button cover
M8 AC 200V~250V T8 AC 200V~250V U8 AC 200V~250V AA Lead Wire
Note) U
 VT is only applicable for AB User Plug (Part)
Fixed type (P Type)
Note) AC Plug Interlock
1. In case of selecting accessories such as A1(Secondary coil),
A4(position S/W 2a2a), A7(key lock), A147 is type name in the
Closing coil voltage Connector and wire AD Padlock (H type)
ordering. C0 Without closing coil SA2 A type connector, 4a4b
2. Unable to select A1(Secondary Trip Coil),U1~U8(UVT) AE MOC
simultaneously. C1 DC 110V SA4 A type connector, 10a10b AI Mecha Shaft Interlock Lever
3. A3(Position S/W 1a3b), A4(Position S/W 2a2b) and A5(Position Standard
S/W 2a2b) can not be selected simultaneously. C2 DC 200~250V SB2 B type connector, 4a4b AL Energy Release
4. A1(Secondary Trip Coil) and A2(Secondary Trip Coil with TCS
Contact) can not be selected simultaneously. C3 DC 125V SB4 B type connector, 10a10b AM Keylock (KirkKey, CAMLOCK type)
5. A8(Button Padlock) and A9(Button Cover), AP(Button Padlock
In Open) can not be selected simultaneously.
C4 DC 24V~30V AN Keylock (KirkKey, CN22 type)
6.A7(Keylock), AM(KirkKey, CAMLOCK Type), AN(KirkKey, CN22 C5 DC 48V~60V
type),AX(Double Keylock) can not be selected simultaneously. AP Keylock (KirkKey, Double CAMLOCK type)
7. When A1(Secondary Trip Coil) is selected the maximum C6 AC 48V AV CT operated coil 1A
available auxiliary contacts are 9a9b.
8. When A2(Secondary Trip Coil with TCS Contact) is selected the C7 AC 100V~130V AW CT operated coil 5A
maximum available auxiliary contacts are 4a3b, 9a8b.
9. H type breaker includes options such as AC(Plug Interlock), C8 AC 200V~250V AX Button Padlock In Open
AD(Padlock(H type)), AE(MOC) as standard.
10. A  I (Mecha Shaft Interlock Lever) is available only for 12kV, P type

26
Cradle

UVCL 15 H 32 A 12 A EF...

Basic model name Rated voltage (kV) Interrupting current (kA) Rated current (A)
Susol VCB 05 4.76 25 25 12 1200A
UVCL
Cradle 15 15 32 31.5 20 2000A

Version Phase distance/Compatibility Other accessories


Ha MCSG Cradle type A 150mm AE Shutter padlock

He Compact MCSG drawout (Arc) B 210mm AF TOC


P 150mm AG MOC
Hf Compact MCSG drawout (Non-Arc)
S 210mm AH Door

P and S types available for version Ha AJ Door Interlock


- P type: Phase distance 150. Bushing CT installation
impossible AK Door Emergency Push Button
- S type: Phase distance 210. Bushing CT installation
impossible
AM H type¸ Lead Wire 4a4b (Standard)

A and B types available for version He AN H type¸ Lead Wire 10a10b (Standard)
- A type: Phase distance 150. For 1200A only
- B type: Phase distance 210. For 1200A and 2000A

A and B types available for version Hf


(Bushing CT installable)
- B type: Phase distance 210. For 1200A and 2000A

Note) 1. H
 a type cradle cannot use a door and door options. You can use a door for He, Hf type cradle only.
2. AJ and AK can not be selected without door(AH).
3. T M(Temperature Monitoring) should be used with AL(Temperature Sensor).
4. H type lead wire(AM, AN) is required for cradle in case of using H type breaker.
5. If H type breaker options A8 (Button Padlock) and A9 (Button Cover), AP(Button Padlock In Open)
are selected the cradle option AK (Door Emergency Push Button) is not available.
6. H type breaker includes options such as AE(Shutter padlock), AE(TOC), AG(MOC), AH(Door),
AJ(Door Interlock) as standard.

27
Types and ordering information

UVH-38
Breaker

UVH 38 H 32 E 12

Basic model name Rated voltage (kV) Version Interrupting current (kA) Phase distance/Compatibility Rated current (A)
UVH Susol VCB 38 38 P Fixed 32 31.5 E 300mm 12 1200A
H H type drawout (for MCSG) 40 40 20 2000A

UVH-38H32E12 M1 C1 T1 SB2 U1 A 16...

Motor control voltage Trip coil voltage UVT


M0 Without motor T0 Without trip coil U0 Without UVT
M1 DC 110V T1 DC 110V U1 DC 110V
M2 DC 220~250V T2 DC 220~250V U2 DC 220~250V
M3 DC 125V T3 DC 125V U3 DC 125V
M5 DC 48V T5 DC 48V U5 DC 48V
M6 AC 48V T6 AC 48V U6 AC 48V
M7 AC 110V T7 AC 110V U7 AC 110V
M8 AC 220V T8 AC 220V U8 AC 220V
Note) U
 VT is only applicable for
Fixed type (P type)

Closing coil voltage Connector and wire Other accessories


C0 Without closing coil SA2 Standard A type connector, 4a4b A1 Secondary Trip coil
C1 DC 110V SA4 Standard A type connector, 10a10b A2 Secondary Trip Coil with TCS Contact
C2 DC 220V~250V SB2 Standard B type connector, 4a4b A6 Latch checking s/w
C3 DC 125V SB4 Standard B type connector, 10a10b A7 Keylock
C5 DC 48V SC2 Standard AutoCon. connector, 4a4b A8 Button padlock
C6 AC 48V SC4 Standard AutoCon. connector, 10a10b A9 Button cover
C7 AC 110V 1. H type is for SC2 and SC4 only. (Auto connection type) AA Lead Wire
2. P type corresponds to both SA and SB type
C8 AC 220V AB User Plug(Part)

Note) AE MOC
1. In case of selecting accessories such as A1(Secondary coil), A7(key lock), A8(Button
Padlock) A178 is type name in the ordering. Optional
2. Unable to select A1(Secondary Trip Coil),U1~U8(UVT) simultaneously.
3. A1(Secondary Trip Coil) and A2(Secondary Trip Coil with TCS Contact) can not be selected CTD1 Condenser Trip Device (AC110V)
simultaneously. CTD2 Condenser Trip Device (AC220V)
4. A8(Button Padlock) and A9(Button Cover) can not be selected simultaneously.
5. When A2(Secondary Trip Coil with TCS Contact) is selected the maximum available UDC1 UVT Time Delay Controller (ADC110V)
auxiliary contacts are 4a3b, 9a9b.
6. H type breaker includes options such as AE(MOC) as standard. UDC2 UVT Time Delay Controller (ADC220V)
7. In case of selecting UVT A6 (Latch checking S/W) is not allowed. A6 (Latch checking UDC3 UVT Time Delay Controller (ADC48V)
S/W) is installed by default to make electrical interlock with UVT.
CTU Coil Test Unit

28
Cradle

UVCH 38 H 32 E 12 A EF...

Basic model name Rated voltage (kV) Interrupting current (kA) Rated current (A)
Susol VCB 38 38 32 31.5 12 1200A
UVCH
Cradle 40 40 20 2000A

Version Phase distance/Compatibility Other accessories Note1)


H H type drawout (for MCSG) E 300mm AE Shutter padlock
AF TOC
AG MOC
AH Door
AJ Door Interlock
AK Door Emergency Push Button
AL Temperature Sensor
AM H type Lead Wire 4a4b
AN MH type Lead Wire 10a10b

Optional
TM Temperature Monitoring Note3)

Note) 1. AJ and AK can not be selected without door (AH).


2. TM (Temperature Monitoring) should be used with AL (Temperature Sensor).
3. H type lead wire - one of AM, AN is required for cradle in case of H type breaker.
4. If H type breaker options A8 (Button Padlock) and A9 (Button Cover) are selected the
cradle option AK (Door Emergency Push Button) is not available.
5. H type breaker includes options such as AE (Shutter padlock), AE (TOC, AG (MOC), AH
(Door), AJ (Door Interlock) as standard.

29
Types and ordering information

VH-05/15
Breaker

VH 15 H 50 C 30

Basic model name Rated voltage (kV) Version Interrupting current (kA) Phase distance/Compatibility Rated current (A)
VH Susol VCB 05 4.76 H H type drawout (for MCSG) 40 40 C 254mm 12 1200A
15 15 50 50 20 2000A
Note) In case of 4.76kV, only 50kA is available. 30 3000A

VH-15H50C30 M1 C1 T1 SC1 U0 A 16E...

Motor control voltage Trip coil voltage UVT


M0 Without motor T0 Without trip coil U0 Without UVT
M1 DC 110V T1 DC 110V
M2 DC 220~250V T2 DC 220~250V
M3 DC 125V T3 DC 125V
M5 DC 48V T5 DC 48V
M6 AC 48V T6 AC 48V
M7 AC 110V T7 AC 110V
M8 AC 220V T8 AC 220V

Closing coil voltage Connector and wire Other accessories


C0 Without closing coil SC1 Standard AutoCon. connector, 3a3b A1 Secondary trip coil
C1 DC 110V A6 Latch checking switch
Note) Optional
C2 DC 220V~250V A7 Keylock
1. In case of selecting accessories such as A1(Secondary
coil), A7(Key lock), A8(Button padlock), A178 is type C3 DC 125V CTD1 Condenser Trip Device (AC110V) A8 Button padlock
name in the ordering.
2. In case of selecting A1(Secondary coil), make sure to C5 DC 48V CTD2 Condenser Trip Device (AC220V) A9 Button cover
select AN (3a3b Auto Con.+Secondary trip coil) in Cradle
accessory. C6 AC 48V CTU Coil Test Unit AE MOC
3. A8(Button Padlock) and A9(Button Cover) can not be
selected simultaneously. C7 AC 110V
4. This breaker includes option AE(MOC) as standard. So
C8 AC 220V
pleased add it to the ordering information.

Cradle

VCH 15 H 50 C 30 A AFGM...

Basic model name Rated voltage (kV) Interrupting current (kA) Rated current (A) Other accessories
Susol VCB 05 4.76 40 40 12 1200A AF TOC
VCH
Cradle 15 15 50 50 20 2000A AG MOC
30 3000A AM 3a3b Auto connection
Note) 3a3b Auto connection
AN
1. This cradle includes option AF(TOC), AG(MOC), + Secondary trip coil
AM(Lead Wire 3a3b Auto Con.). So pleased add it to Version Phase distance/Compatibility
the ordering information. (ex. AFGM)
2. In case of selecting A1(Secondary coil) for the breaker, Ha MCSG Cradle type C 254mm Optional
make sure to select AN (3a3b Auto Con.+Secondary
trip coil). (ex. AFGN)
TM Temperature Monitoring

30
Ratings - 4.76/15/27kV 25/31.5kA 1200/2000A

UVL-05/15/27

Item UVL–05 25,32 12,20 UVL–15 25,32 12,20 UVL–272512


Rated maximum voltage (kV) 4.76 15 27
Rated continuous current (A) 1200 2000 1200 2000 1200
Rated power frequency (Hz) 50/60
Power frequency withstand voltage (kV) 19 36 60
Full wave lightning impulse withstand voltage (kV) 60 95 125
Rated short-time r.m.s. (kA) 25/31.5 25
current Peak (kA) 65/81.9 65
Short-time current duration (sec) 4
Rated short-circuit Breaking (kA) 25/31.5 25
current Making (kA) 65/81.9 65
Rated interrupting capacity (MVA) 207/260 650/820 1170
Rated Interrupting time (cycle) 3
Standard operating duty O-0.3s-CO-15s-CO
apacitance current switching C2
Rated closing control voltage (V) DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V, AC 48V, AC 100~130V, AC 220~250V
Rated trip control voltage (V) DC 24~30V, DC 48~60V, DC 110V, DC 125V, DC 220V, AC 48V, AC 100~130V, AC 220~250V
Mechanical endurance (Operations) M2 (10,000)
Electrical endurance Reference Standard (page 88)
Type 4a4b, 10a10b
Rated Continuous current DC 10A
Standard aux. Baeaking capacity 600W
contacts
Endurance
(Mechanical, (Operations) 10,000
Interrupting)
Low -40°C
Operate temperature
High -40°C
Rated opening time (sec) ≤ 0.04
Rated closing time (sec) ≤ 0.06 ≤ 0.07
Fixed P type
Installation
Draw-out H type
Phase distance (mm) 150 210 254 150 210 254 150 210 254 150 210 254 254
Ha, Cradle 1) (kg) 90 - - - 100 - 90 - - - 100 - -
He, Cradle 2) (kg) 375 405 - - 425 - 375 405 - - 425 - -
Hf, Cradle 3) (kg) 310 340 - - 360 - 310 340 - - 360 - -
Weight
H, Circuit Breaker 4) (kg) 130 140 - - 160 - 130 140 - - 160 - -
H, Circuit Breaker 5) (kg) 115 120 - - 145 - 115 120 - - 145 - -
P, Circuit Breaker (kg) 85 100 110 100 115 125 85 100 110 100 115 125 125
Applicable standard IEEE Std C37.09, ANSI C37.54 IEEE Std C37.09
1) MCSG Cradle type 2) Compact MCSG type(Arc)
3) Compact MCSG type(Non-Arc) 4) VCB for Compact MCSG type(Arc)
5) VCB for Compact MCSG type(Non-Arc)
* H type is a box type cradle with CB compartment style structure.

31
Ratings - 38kV 31.5/40kA 1200/2000A

UVH-38

Item UVH–38 32,40 12,20


Rated maximum voltage (kV) 38
Rated continuous current (A) 1200 2000
Rated power frequency (Hz) 60
Power frequency withstand voltage (kV) 80
Full wave lightning impulse withstand voltage (kV) 170
Rated short-time r.m.s. (kA) 31.5/40
current Peak (kA) 81.9/104
Short-time current duration (sec) 4
Rated short-circuit Breaking (kA) 31.5/40
current Making (kA) 81.9/104
Rated interrupting capacity (MVA) 2074/2633
Rated Interrupting time (cycle) 3
Standard operating duty O-0.3s-CO-15s-CO
apacitance current switching C2
Rated closing control voltage (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC220V
Rated trip control voltage (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC220V
Mechanical endurance (Operations) M2 (10,000)
Electrical endurance Reference Standard (page 88)
Type 4a4b, 10a10b
Rated Continuous current DC 10A
Standard aux. Baeaking capacity 600W
contacts
Endurance
(Mechanical, (Operations) 10,000
Interrupting)
Low -40°C
Operate temperature
High -40°C
Rated opening time (sec) ≤ 0.04
Rated closing time (sec) ≤ 0.06
Fixed P type
Installation
Draw-out H type
Phase distance (mm) 300
Ha, Cradle1) (kg) 350
Weight He, Cradle2) (kg) 400
Hf, Cradle3) (kg) 360
Applicable standard IEEE Std C37.09

32
Ratings - 4.76/15kV 40/50kA 1200/2000/3000A

VH-05/15

Item VH–05 40,50 12,20,30 VH–15 40,50 12,20,30


Rated maximum voltage (kV) 4.76 15
Rated continuous current (A) 1200 2000 3000 1200 2000 3000
Rated power frequency (Hz) 60
Power frequency withstand voltage (kV) 19 36
Full wave lightning impulse withstand voltage (kV) 60 95
Rated short-time r.m.s. (kA) 40/50
current Peak (kA) 104/130
Short-time current duration (sec) 2
Rated short-circuit Breaking (kA) 40/50
current Making (kA) 104/130
Rated interrupting capacity (MVA) 330/412 1040/1300
Rated Interrupting time (cycle) 3
Standard operating duty O-0.3s-CO-3min-CO
apacitance current switching C2
Rated closing control voltage (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC220V
Rated trip control voltage (V) DC 48V, DC 110V, DC 125V, DC 220~250V, AC 48V, AC 110V, AC220V
Mechanical endurance (Operations) M2 (10,000)
Electrical endurance Reference Standard (page 88)
Type 4a4b, 10a10b
Rated Continuous current DC 10A
Standard aux. Baeaking capacity 600W
contacts
Endurance
(Mechanical, (Operations) 10,000
Interrupting)
Low -30°C
Operate temperature
High 40°C
Rated opening time (sec) ≤ 0.04
Rated closing time (sec) ≤ 0.06
Fixed P type
Installation
Draw-out H type
Phase distance (mm) 254
H, Cradle (kg) 248 248 286 248 248 286
Weight
H, Circuit Breaker (kg) 230 230 265 230 230 265
Applicable standard IEEE Std C37.09

33
Accessory

Mounting Supplied as
Type Accessory Remarks page
Position UVL-05/15/27 UVH-38 VH-05/15
M Motor ● ● ● Attached at the factory 36
CC Closing Coil ● ● ● Attached at the factory 37
TC Trip Coil ● ● ● Attached at the factory 38
A1 Secondary Trip Coil Option Option Option Attached at the factory 39
SA Auxiliary Contact 4a4b ● ● -
Attached at the factory 41
(SB) Auxiliary Contact 10a10b Option Option -
SC1 Auxiliary Contact 3a3b - - ● Attached at the factory 42
SC2 Auxiliary Contact 4a4b - ● - Attached at the factory 42
SC4 Auxiliary Contact 10a10b - Option - Attached at the factory 42
U Under Voltage Trip Coil Option Option - Attached at the factory 43
A3 Position S/W(Test: 1a1b, Connect: 2b) Option - - Attached at the factory 44
A4 Position S/W(Test: 2a, Connect: 2a) Option - - Attached at the factory 44
A5 Position S/W(Test: 1a1b, Connect: 1a1b) Option - - Attached at the factory 44
A6 Latch Checking Switch - Option Option Attached at the factory 44
- Counter ● ● ● Attached at the factory 42
A7 Keylock Option Option Option Attached at the factory 45
A8 Button Padlock Option Option Option Attached at the factory 46
A9 Button cover Option Option Option Attached at the factory 47
Breaker
AA Lead Wire: A/B type connector Option Option Option Attached at the factory 48
(Internal)
AB Plug/Terminal for Lead Wire Option Option Option Attached at the factory 48
AC Plug Interlock ● - - Attached at the factory 49
AD Padlock (H type) ● - - Attached at the factory 49
AE MOC(Mechanical Operated Cell Switch ● ● ● Attached at the factory 50
AI Mecha Shaft Interlock Lever Option - - - -
AM Keylock(KirkKey, CAMLOCK Type) Option - - Attached at the factory 45
AN Keylock(KirkKey, CN22 Type) Option - - Attached at the factory 45
AP Keylock(KirkKey, Double CAMLOCK Type Option - - Attached at the factory 45
AV CT operated coil 1A Option - - Attached at the factory 40
AW CT operated coil 5A Option - - Attached at the factory 40
AX Button Padlock In Open Option - - Attached at the factory 46
Position padlock - ● ● Attached at the factory 51
Mechanical position indicator ● ● ● Attached at the factory 51
Auto connection - ● ● Attached at the factory 52
Code plate - - ● Attached at the factory 52
Charge interlock ● - ● Attached at the factory -
Auto discharge - ● - Attached at the factory -
Trip coil monitoring contact ● ● ● Attached at the factory 53
CTD1 Condenser Trip Device(AC110V) Option Option Option - 55
CTD2 Condenser Trip Device(AC220V) Option Option Option - 55
UDC1 UVT Time Delay Controller(AD110V) Option Option Option - 56
Breaker
UDC2 UVT Time Delay Controller(AD220V) Option Option Option - 56
(External)
UDC3 UVT Time Delay Controller(AD48V) Option Option Option - 56
CTU Coil Test Unit Option Option Option - 54
TM Temperature Monitoring Option Option Option - 57

* ●: Basic Installation

34
Mounting Supplied as
Type Accessory Remarks page
Position UVL-05/15/27 UVH-38 VH-05/15
AE Shutter padlock ● ● - Attached at the factory 58
AF TOC(Truck Operated Cell Switch) ● ● ● Attached at the factory 58, 64
AG MOC(Mechanical Operated Cell Switch) ● ● ● Attached at the factory 59, 63
AH Door Option Option - Attached at the factory 59
AJ Door Interlock Option Option - Attached at the factory 60
AK Door Emergency Push Button Option Option - Attached at the factory 60
Cradle
AL Temperature Sensor Option Option Option Attached at the factory 61
AM Type H Lead Wire 3a3b - - ● Attached at the factory 62
AM Type H Lead Wire 4a4b Option ● - Attached at the factory 62
AN Type H Lead Wire 10a10b Option Option - Attached at the factory 62
AS Bushing Barrier(170kV for 38kV) - Option - Attached at the factory -
Door padlock ● - - Attached at the factory 62
Auto connection - ● ● Attached at the factory 52
Charge interlock ● - ● Attached at the factory 63
Auto discharge - ● - Attached at the factory -

35
Accessory

Motor: M Installed inside of a breaker as standard

UVL type Motor

•Charge the closing spring of a circuit breaker by


the external power source. When the charging
is complete, control power of the motor will be
"OFF" by the built-in Limit S/W. Without the
external power source, charge manually.
Gear

Main
shaft

Charge completion
contact

Motor

UVL type
DC 24~ DC 48~ DC 220~ AC 100~ AC 200~
Input voltage (Vn) DC 110V DC 125V AC 48V
30V 60V 250V 130A 250V
Load current (A) ≤5 ≤3 ≤1 ≤ 1 ≤ 0.5 ≤3 ≤1 ≤ 0.5
Starting current (A) 5 times of load current
Charge time Within 5 sec.
Note) Rated operation and control voltage range, see page 40.

VH/UVH type

Motor

VH/UVH type
Input voltage (Vn) DC 48V DC 110V DC 125V DC 220~250V AC 48V AC 110V AC 220V
Load current (A) ≤6 ≤3 ≤3 ≤ 2.6 ≤6 ≤3 ≤ 2.6
Starting current (A) ≤ 30 ≤ 20 ≤ 20 ≤ 17 ≤ 30 ≤ 20 ≤ 17
Charge time Within 12 sec.
Note) Rated operation and control voltage range, see page 40.

36
Closing Coil: CC Installed inside of a breaker as standard

UVL type
•It is a control device which closes a circuit
breaker, when applying voltage continuously or
instantaneously over 200ms to the coil control
terminals.

Closing coil


UVL type
DC 24~ DC 48~ DC 220~ AC 100~ AC 200~
Input voltage (Vn) DC 110V DC 125V AC 48V
30V 60V 250V 130V 250V
Power consumption (inrush, VA) 200
Power consumption (steady, VA) ≤5
Note) Rated operation and control voltage range, see page 40.

VH/UVH type
•It is a control device which closes a circuit
breaker, when applying voltage continuously
about 45ms to the coil control terminals.
Electrical pumping preventing circuit is built in.

Closing coil

VH/UVH type

Input voltage (Vn) DC 48V DC 110V DC 125V DC 220~250V AC 48V AC 110V AC 220V
Rated current (A) ≤8 ≤3 ≤3 ≤ 2.5 ≤8 ≤3 ≤ 2.5
Note) Rated operation and control voltage range, see page 40.

37
Accessory

Trip Coil: TC Installed inside of a breaker as standard

UVL type
•It is a control device which trips a circuit
breaker from remote place, when applying
voltage continuously or instantaneously over
35ms to coil control terminals.
•When UVT coil is installed, its location is
changed.

Trip coil


UVL type
DC 24~ DC 48~ DC 220~ AC 100~ AC 200~
Input voltage (Vn) DC 110V DC 125V AC 48V
30V 60V 250V 130V 250V
Power consumption (inrush, VA) 200 400 200
Power consumption (steady, VA) ≤ 5 - ≤5
Note) Rated operation and control voltage range, see page 40.

VH/UVH type
•It is a control device which trips a circuit
breaker, when applying voltage continuously or
instantaneausly over 35ms to the coil control
terminals.

Trip coil

VH/UVH type
Input voltage (Vn) DC 48V DC 110V DC 125V DC 220~250V AC 48V AC 110V AC 220V
Rated current (A) ≤8 ≤3 ≤3 ≤ 2.5 ≤8 ≤3 ≤ 2.5
Note) Rated operation and control voltage range, see page 40.

38
Secondary Trip Coil: A1 Installed inside of a breaker as an option

UVL type
•It is a control device which trips a circuit
breaker doubly from the outside. If the trip coil
(T ) fails, it can trip a circuit breaker safely.
•Trip coil: Install it at existing location.
•Secondary trip coil: Install it on the right side of
the trip coil.
•It is not available with UVT coil when installing
secondary trip coil.

Secondary
Trip coil


UVL type
DC 24~ DC 48~ DC 220~ AC 100~ AC 200~
Input voltage (Vn) DC 110V DC 125V AC 48V
30V 60V 250V 130V 250V
Power consumption (inrush, VA) 200 400 200
Power consumption (steady, VA) ≤ 5 - ≤5

VH/UVH type
•It is a control device which trips a circuit
breaker doubly from the outside. If the trip coil
(T) fails, it can trip a circuit breaker safely.
•It is not available with UVT coil when installing
secondary trip coil.

Secondary
Trip coil

VH/UVH type

Input voltage (Vn) DC 48V DC 110V DC 125V DC 220~250V AC 48V AC 110V AC 220V
Rated current (A) ≤8 ≤3 ≤3 ≤ 2.5 ≤8 ≤3 ≤ 2.5

39
Accessory

Rated operation and control voltage range

DC Voltage range AC Voltage range


Rated control voltage range Remarks Rated control voltage range Remarks
Motor, Closing Trip Motor, Closing, Trip
24 - 14~28 24 -

48 38~56 28~56 48 -

125 100~140 70~140 120 104~127

250 200~280 140~280 240 208~254

Applied standard IEEE C37.09 Applied standard IEEE C37.09

CT operated coil Installed inside of a breaker as an option

UVL type : AV, AW


Current Trip Coil
•This trip coil uses the output of the CT as its
control power source and is used with over
current relay in combination. Two current trip
coils are supplied.
•Coil impedance(Z) is like below
- 1A: 160Ω or less, Operating current AC 1A (AV)
- 5A: 6Ω or less, Operating current is AC 5A (AW)
•CT must be installed at load side.
If it is installed at bus side there is the danger of
malfunction or damage to CT.
•Don’t disconnect the control power connector
on main power is live condition at connect
position.
Otherwise there is the danger of malfunction or
damage to CT.
* CT is recommended to use 15VA 5P10 and more.
* This coil is applicable to non-effectively grounded neutral systems.

40
Auxiliary Contact: SA Installed inside of a breaker as an option

UVL type
Auxiliary contact
•It is a contact used to monitor ON/OFF status
of a breaker from remote place.
•The auxiliary contacts supplied as standard
configuration is 4a4b. 10a10b is also available
on request.

Item UVL/VH/UVH-27 type


Standard 4a4b
Optional 10a10b

VH/UVH type

Auxiliary contact

UVL/VH/UVH type
Item Resistive load (A) Inductive load (A) Remarks
250V 10 5
AC
125V 10 5
Contact
250V 10 5 For all models
configuration
DC 125V 10 5
30V 10 5

41
Accessory

Auxiliary Contact: SC1 Installed inside of a breaker as an option

VH-05/15 type
•It is a contact used to monitor ON/OFF status
of a breaker from remote place.
•The auxiliary contacts supplied as standard
configuration is 3a3b.
•Two(2) “Early b” auxiliary contact is provided.
(Terminal No. 56-57, 58-59)

Auxiliary contact

Item Resistive load(A) Inductive load(A)


Contact configuration DC 125V 10 5

Counter: C Installed inside of a breaker as standard

UVL/VH/UVH type
•It displays the total number of ON/OFF
operations of a breaker.

42
Under Voltage Trip Coil: U Installed inside of a breaker as an option

UVL type UVH type

UVL type

Under Voltage Under Voltage


Trip Coil Trip Coil

•It is installed inside of a breaker to trip when the main power or control power voltage drops below certain value.
Instantaneous type is only available with UVT coil and Time delay type is available by connecting UVT coil and UVT
time delay controller.
•The closing of a circuit breaker is impossible mechanically or electrically if control power is not supplied to UVT.
To close the circuit breaker, 65~85% of rated voltage should be applied.
•UVT and secondary trip coil will not be selected together.
* UVT is only applicable for Fixed type (P type)

1. UVT rated voltage and characteristic VH/UVH type


- Operating voltage range: Pick up 0.65~0.85Vn, Drop out 0.4~0.6Vn
- Operating voltage ranges based on the minimum value of each rated voltage (Vn)


UVL type
DC 24~ DC 48~ AC 100~ AC 200~
Input voltage (Vn) DC 110V DC 125V DC 220V AC 48V
30V 60V 130V 250V

Power consumption (inrush, VA) 200

Power consumption (steady, VA) ≤5

UVH type
Input voltage (Vn) DC 48V DC 110V DC 125V DC 220V AC 48V AC 110V AC 220V

Power consumption (inrush, VA) 350

Power consumption (steady, VA) ≤ 10

43
Accessory

Position Switch: A3, A4, A5 Installed inside of a breaker as an option

UVL type - H Cradle

UVL VH/UVH

Large model (VH/UVH)

Position
switch
Position
switch

•This switch is used to indicate the breaker position (CONNECT, TEST), and contact configuration
is 2a2a or 2a2b, 1a3b.

Contact configuration
1 3 5 7 1 3 5 7 1 3 5 7

2 4 6 8 2 4 6 8 2 4 6 8
1a1b(TEST) 2b(SERVICE) 2a(TEST) 2a(SERVICE) 1a1b(TEST) 1a1b(SERVICE)

Latch checking switch: A6 Installed inside of a breaker as an option

VH/UVH type
•This switch works in conjunction with the
mechanism of the breaker. It checks if the
breaker is ready to be closed.
•When the mechanism is OFF and the closing
spring is at charged status the switch becomes
"ON", which means the mechanism is ready to
be closed.
•If the latch is not in a proper position the switch
prevents the breaker from closing.
In case of VH type it is connected internally in
series with the closing coil.

Latch checking
switch

44
Keylock: A7, AM, AN, AP
s
Installed inside of a breaker as an option

UVL type
•The key is to unlock the locking device first to
close the breaker electrically and mechanically.

*How to operate
- It is not possible to pull out the key in the
horized users
ized users unlocked position, possible only in locked
reaker
ker whenwhentwo two
status.
euse
in use at the
at the - Pushing "OFF" switch of a breaker turn the key
counter-clockwise to the locked position and
pull it out.
- It is not possible to close the breaker
echanical closing
hanical closing electrically and mechanically in the locked
MLOCK
OCK type) type)position.
LOCK
CK type)- Insert the key and turn clockwise and then the
type) breaker can be closed electrically and
2pe)
type) mechanically. <K1>
<K1> <K5> <K5>
Keylock
1. A7: KEYLOCK(NORMAL Type)
2. AM: KIRKKEY LOCK(CAMLOCK Type)
3. AN: KIRKKEY LOCK(CN22 Type)
4. AP: KIRKKEY LOCK(DOUBLE CAMLOCK Type)
*T
 he KIRKKEY is not provided separately when ordering AM,
AN or AP option. The assembling bracket and instruction
manual are provided.

K1 K1 A7 AM<K6>
<K6> <K7>
<K7>AN AP

VH/UVH type

et [K2]*How
[K2] to operate
- It is not possible to pull out the key in the
unlocked position, possible only in locked status.
- Trip the breaker first and then turn the key
arranged counter-clockwise
continuous to the locked position and pull
anged for for
continuous
side
e andand
it out.
interlocked
interlocked
Wiring
Wiring
- It is not possible to close the breaker electrically
ks embedded
embedded and in each in the locked position.
mechanically
in each

Status
Status
LOAD1
LOAD1 LOAD2
LOAD2
OFFOFF OFFOFF
ONON ONON
Keylock
ONON ONON
ONON ONON
OFFOFF OFFOFF
OFFOFF ONON
ACB
ACB 1 1 ACB
ACB 2 2
ONON OFFOFF

45

ACB3
Accessory

Button Padlock: A8, AX Installed outside of a breaker as an option

UVL type
•It is to prevent manual operation of ON/OFF
button due to user’s wrong handling.
•A8 option: It is not possible to handle ON/OFF
manual operation under the “Button lock”
status.
•AX option :It is not possible to handle ON/OFF
manual/electrical operation under the “Button
lock” status.
* Key lock is not supplied.

1. A8: KEYLOCK(NORMAL Type)


2. AX: Button Padlock In Open

Button Padlock

VH/UVH type

Button Padlock

46
Button Cover: A9 Installed outside of a breaker as an option

UVL type
•It is a protection cover to prevent an accident
due to unintended operation of ON/OFF button.
•Use the push-bar to operate the ON/OFF
button.

Push Bar
Button Cover

VH/UVH type

Push Bar
Button Cover

47
Accessory

Lead wire: AA Supplied separately from a breaker as an option

UVL/UVH type
Lead wire
•It is to connect with the control circuit of a
breaker from outside. (supply wire length: 2m)
•A type connector is supplied for P/E/F/G type of
UVL VCB.
A type connector
•B type connector is supplied for P type of VH/
UVH VCB.
•In case of H type breaker of VL and VH models
the Lead wire is installed in the cradle when
supplied. B type connector

Supply ways of Lead wires by VCB model

Cradle type P E F G H
VCB model
Enclosed in the breaker
UVL Enclosed in the breaker
Installed in the cradle (option)

Enclosed in the breaker


VH/UVH Enclosed in the breaker
Installed in the cradle (option)

Plug/Terminal for lead wire Supplied separately from a breaker as an option

UVL/UVH type

A type connector B type connector

•It is connector to connect with the connector installed in the breaker. (supply connectors and terminal only for lead wire)
•Type of connector is depends on the type of connector installed in the breaker- A or B.

48
Plug interlock: AC Installed inside of a breaker as an option

UVL type
Plug interlock
•It checks if the control power connector on the
cradle (H type) is connected with the
connecting terminal of the breaker before the
proceeding of draw-in or out.
•It is not allowed to seperate the control power
connector from the breaker in the position of
draw-in /out or CONNECT, but TEST position.

Padlock/Door racking interlock: AD Installed outside of a breaker as an option

UVL type
•With this door options for H type cradle draw-
in/out is allowed only when the door is closed.
•If draw-in /out is necessary when the door is
open, use the operation lever put in the slot of
the breaker handle.
Insert it into the hole in the bottom of door
interlock.
•Padlock is also optional, which can lock to
prevents the draw-in/out of the breaker in the
position of TEST and CONNECT.

Door interlock

49
Accessory

MOC drive device: AE Installed inside of a breaker as an option

UVL type
•It must be installed in the breaker to drive the
MOC installed in H type cradle.
•MOC, Mechanically operated cell switch is the
device to indicates the Closed/Trip status of
VCB in 'CONNECT' position only.
•This MOC drive device in the breaker should be
installed when MOC in the cradle is used.

MOC

VH/UVH type

MOC

50
Position padlock Installed inside of a breaker as an option

VH/UVH type
•It is located at the screw hole to prevent the
draw-in and out of a breaker from the present
position(Disconnected, Test or Connected)

Position padlock

Mechanical position indicator Installed inside of a breaker as an option

VH/UVH type
•It is located in the lower part of a breaker to
check the present position - Disconnected,
Test or Connected- easily.

Mechanical position indicator

51
Accessory

Auto connection Installed inside of a breaker as an option

VH/UVH type
•When the breaker is moved to ‘Test’ position
from ‘Disconnected’ position the connector for
control powers is automatically connected. In
case of reverse moving of the breaker the
connector is automatically disconnected.

Auto connection

Code plate Installed inside of a breaker as an option

VH-05/15 type
•When the breaker is inserted to the cradle, if the
ratings does not match with the cradle, it
mechanically prevents the breaker from being
inserted into the cradle.

Code plate

52
Trip coil monitoring contact Installed inside of a breaker as an option

UVL type
•Device for monitoring the functions of the trip
coils.
•Supplied as standard for VL model and optional
for VH model.
•To monitor the trip coils connect its terminals
with the trip coil monitoring relay as shown on
the circuit diagram.
- If the trip coil is normal: closed-circuit
consisting
- If the trip coil is damaged: open circuit
1) Terminals A5 and A6 monitor the trip coils in
closed position of the breaker.
2) Terminal A6 and aux. contact terminal 34
monitor the trip coils in trip position of the
breaker.
•Coil Test Unit is opional, which enable monitoring
the coils by connecting in parallel with the trip
coil operation switch.
•In case of UVL type this contact works with the
trip coils such as T1, T2, T3, T4 and T5.
For VH/UVH type it works with all trip coils.

UVH type
Secondary trip coil with TCM Contact

53
Accessory

Coil Test Unit: CTU Installed outside of a breaker as an option

UVL/VH/UVH type
•When no current flows through the coil it gives the test current which does not cause the coil to operate to check
whether the coil is disconnected or not.
- If the test current flows normally: coil normal
- If the test current does not flow through: coil disconnected

※ As it is connected in parallel with the control part of the coil the normal operation of the coil is not affected.
※ Monitoring of the running coils is not possible.
※ One test unit can monitor up to two coils.

1. Input voltage: AC/DC 75V~264V


2. Contact output
1) 2×a contacts for Fail indication and 2×a contacts for Alarm
2) 250Vac/10A Resistive, 30Vdc/10A Resistive
3. Disconnection test cycle is 12 seconds (Test LED blinks)
4. The default operation
If Fail happens (coil disconnected), Fail LED turns on and the Fail contacts become short state.
If Fail happens three times in series, Alarm LED turns on and the Alarm contacts become short state.
In order to clear the Alarm status push up DIP switch on the front and then push down it (Off → On → Off)

Input voltage
AC/DC 75~264V

Fail 1

24~250V
(AC/DC) Alarm 1
Shunt 1
Coil
Test
Fail 2
Unit
24~250V
(AC/DC) Alarm 2
Shunt 2

CTU CTU
Input voltage Input voltage
Coil drive power(+) (+) (+)

1 2
Coil drive power
5 Fail (LED)
Fail (RELAY)
7
Coil Alarm (LED)
Coil test current Alarm (RELAY)
Coil Test Unit
Coil drive power(-)

54
Condenser trip device: CTD Installed outside of a breaker as an option

Ratings
Ratings Specification UVL/VH/UVH type
Model CB - T1 CB - T2
•It gets a circuit breaker tripped electrically
Rated input voltage (V) AC 100/110 AC 200/220 within regular time when control power supply
Frequency (Hz) 50/60 50/60 is broken down and is used with Shunt coil,
SHT. In case there is no DC power, It can be
Rated charge voltage (V) 140/155 280/310
used as the rectifier which supplies DC power
Charging time Within 10sec. Within 10sec. to a circuit breaker by rectifying AC power.
Trip possible time Within 30sec. Within 30sec. •Tripping within 30 seconds on the power failure
Range of Input voltage 85%~110% 85%~110% is possible. However after that automatic trip
circuit must be configured separately in the
Condenser capacity (μF) 1,000 560 switchgear.

Terminal arrangement External dimension

(Mounting hole)

Circuit diagram

55
Accessory

UVT Time delay: UDC Installed outside of a breaker as an option

UVL/VH/UVH type
•UVT time delay, UDC is to delay the trip signal from UVT.
Without UDC the breaker will be tripped instantaneously by the trip signal from UVT installed inside of the breaker
even in the the momentary power failure.
•UDC can delay the trip time to avoid this unintended instantaneous trip in the event of such power failure.
•It can be installed on the cradle or inside of the switchgear.
•UDC provides output contacts for indication of trip status due to the UVT coil inside of the breaker.
b contact is closed at normal state and a contact is closed at trip.

1. Characteristics

Rated voltage (Vn) Opration voltage range (V) Consumption (VA or W) Time delay
DC (V) AC (V) Pick up Drop out Inrush Steady - state (ms)

48~60 48
100~130 100~130 0.65~0.85 Vn 0.4~0.65 Vn 200 ≤5 0.5, 1, 1.5, 3
200~250 200~250

- Operating voltage ranges are based on the minimum value of each rated voltage (Vn)

2. Ratings of output contacts

Rated voltage (V) Rated current (A), Resistive load Max. switching voltage (A) Max. switching current (A)
24V DC ≤ 12
110V DC
120V AC ≤ 12 15
250V AC
250V AC ≤ 10

3. Wiring diagram

Delayed
trip signal

5 7

14 16
18(a)
Operating UVT Delay
UVT output 19(c)
18 19 20 contact 20(b) Controllor
a c b
0.5
1
Signal for 1.5
tripping 14 16
3

DC48~60V
AC48
[sec]
Instantaneous
5 7 trip signal
Time Delay for UVT
D1

D2
UVT

56
Temperature sensor and Installed outside of a breaker as an option

monitoring unit: TM

UVL/VH/UVH type
•Temperature Alarm Unit displays the input
temperature detected through the temperature
sensor installed in H-type cradle.
Temperature
•Temperature sensor can be installed up to three Sensor
(R, S, T phase).
•Temperature Alarm Unit converts the
temperatures detected from the senser in the
cradle and displays the maximum value and
can transmit it throug communication.
•If the input temperature is above standard it
may cause alarm.
Temperature Alarm Unit supports Modbus/
RS-485 communication and contact us
Profibus-DP communication.

Temperature sensor and


monitoring unit

LED temperature display (℃): 10 ~150℃,


Warning
Display maximum value of temperatures

57
Accessory

Shutter padlock: AE Built-in a cradle as an option

UVL/UVH type
It is the locking device to lock the primary and
secondary shutter in closed state for safety while
the breaker is drawn out for maintenance.
•When the breaker is drawn in, the shutter is
automatically opened.
•There is a hole for padlock to lock the shutter.
•It can be applied only to H type cradle.

Shutter
padlock

Truck operated cell switch (TOC: AF) Built-in a cradle as an option

UVL/UVH type
•This auxiliary switch is used to indicate the
'CONNECT' position of VCB. It is installed in
the bottom of a H type cradle and operated by
the frame of a breaker.
VL type
•TOC is consisted of 4 cell switches with
changeover contacts as below diagram.

Circuit diagram
121 122 124 125 127 128 130 131
VH Type
TOC

123 126 129 132

a Contact: 122-123, 125-126, 128-129, 131-132,


b Contact: 121-123, 124-126, 127-129, 130-132

58
Mechanical Operated Cell Switch Built-in a cradle as an option

(MOC)

UVL/UVH type
•This auxiliary switch is used to indicate the
Close/Trip of VCB. It is operated mechanically
at the CONNECT position and installed in the
bottom of a H type cradle and operated by the
frame of a breaker.
•MOC is consisted of 4 cell switches with
changeover contacts as below diagram.
VL type

Circuit diagram
102 101 105 104 108 107 111 110

MOC

103 106 109 112

VH Type
a Contact: 101-103, 104-106, 107-109, 110-112,
b Contact: 102-103, 105-106, 108-109, 111-112

Door: AH Built-in a cradle as an option

UVL/UVH type
•It is outside door for H type cradle.
•Accessories are available for the door.

Door

59
Accessory

Door Interlock: AJ Built-in a cradle as an option

UVL/UVH type
•When the Door is installed to H type cradle, this
door interlock prevents opening it at CONNECT
position.

Door Emergency Push button: AK Built-in a cradle as an option

UVL/UVH type
•It is used to enable the Close/Trip of the breaker
manually from outside of the door installed to H
type cradle during an emergency.
•Push the ON/OFF button by ON/OFF handle
supplied seperately.

Door Emergency Push button

60
Temperature Sensor: AL Built-in a cradle as an option

UVL/UVH type
•This sensor is used to detect the temperature in
H-type cradle combined with Temperature
monitoring unit. Temperature
Sensor
•It can be installed up to three (R, S, T phase).

Racking In/Out handle


Susol VCB offers various kinds of handle suitable for each use of types and models. The order can be proceeded with
the code below and ordering quantity is flexibly adjustable.

Cradle Racking in/out handle Charging handle


Type
Type Code Appearance Description Code Appearance

A 55223172407 Normal type

Extention type
B 55223172403
(Normal)
UVL Ha, He, Hf Not required

C 55223172405 Universal type

Extention type
D 55223172406
(Universal)

VH/UVH Ha, H E 55213163003 Universal type 55213143006

Racking in/out handle for cradle

A B
C, E D

61
Accessory

Type H Cradle Lead Wire: AM, AN Built-in a cradle as an option

UVL/UVH type
•In case of H type breaker of UVL and UVH
models the Lead wire is installed in the cradle
when supplied.
•4a4b or 10a10b contacts are selectable
according to the auxiliary contact of the
breaker. Flame retardant cable is used for 4a4b.
Lead
Wire

Door Padlock Built-in a cradle as an option

UVL/UVH type
•It is supplied with a door for H type cradle as
standard.
•It can be locked by seperate padlock to prevent
entering the maunal handle.

Door
Padlock

62
Charge interlock Installed inside of a breaker as an option

VH-05/15 type
•In case the breaker is drawn-out when the
closing spring is charged in the ‘Disconnected’
position, it prevents the complete withdrawal of
the circuit breaker from the housing.

Charge interlock

Mechanically operated cell switch Installed inside of a breaker as an option

(MOC)
VH-05/15 type
•This 6a6b switch indicates the 'ON' or 'OFF'
condition of a VCB and is operated in the
positions of ‘Connected’ and 'Test'.
Below circuit diagram is based on 'OFF' status
of VCB.

M6 M22 M24 M26 M28 M40 M30 M34 M36 M38 M50 M52

M7 M23 M25 M27 M29 M41 M31 M35 M37 M39 M51 M53 Mechanically
operated cell
switch

T30 T34 T36 T38 T50 T52 T6 T22 T24 T26 T28 T40

T31 T35 T37 T39 T51 T53 T7 T23 T25 T27 T29 T41

63
Accessory

Truck operated cell switch (TOC) Built-in a cradle as an option

M6 M22 M24 M26 M28 M40 M30 M34 M36 M38 M50 M52
VH-05/15 type
•This 6a6b switch indicates the ‘Connected’
state of a VCB and is operated by the
movement of a VCB frame.
Below circuit diagram is based on 'Test' status
of VCB.
M7 M23 M25 M27 M29 M41 M31 M35 M37 M39 M51 M53

T30 T34 T36 T38 T50 T52 T6 T22 T24 T26 T28 T40

T31 T35 T37 T39 T51 T53 T7 T23 T25 T27 T29 T41
Truck operated
cell switch

64
Auxiliary guide frame

•Auxiliary guide frame is provided in order to move safely


36/40.5kV breaker into the switchgear.
•It can be used in combination with the hand pallet which
meets the requirement shown below.

Applicable hand pallet

B If dimension A in Fig. 1 is
less than 120mm B type
pallet can be used.
Width :≤ 550mm In case of more than 120mm
550

Min. height:≤90mm C type must be applied.

Upper side of guide rail in switchgear C


A

Bottom

<Fig 1>

65
66
Auxiliary switch
Trip coil monitoring contact
Secondary trip coil with TCM Contact
10a(9a) 10b(9b)
P P P
4a 4b Position switch
<2a(TEST),2a(CONNECT)> UVL-05/15/27
TEST CONNECT
D1 11 22 24 26 28 40 42 44 46 48 60 34 36 38 50 52 54 56 58 70 72 74 1 3 5 7
A1 9 A3 13 A5
Position switch
<1a1b(TEST),1a1b(CONNECT)>
1 3 5 7
LS4 LS5 LS6 LS7

2 4 6 8

M Position switch
<1a1b(TEST),2b(CONNECT)>
Control circuit diagram

C 1 3 5 7

TRIP POWER SOURCE


LS4 LS5 LS6 LS7

CLOSE POWER SOURCE

MOTOR POWER SOURCE


CTC2 UVT TC1 TC

2 4 6 8

A2 10 14 D2 12 23 25 27 29 41 43 45 47 49 61 37 39 51 53 55 57 59 71 73 75 2 4 6 8
A4 A6
N N N
Current Trip Coil(1A,5A) indicating contact
* Above the circuit diagram is based on the “ OPEN” state of the VCB and the closing spring is charged.
* Note 12
Closing Spring Contact(Charge complete indicating contact)

22
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
23
42
43

22
23
A1
A2

A1
A2
Ø : External terminal of the VCB CS : Closing spring charged indication limit switch A
24
25
44
45

24
25
A4

A4
A3

A3
B
52 : Vacuum circuit breaker LS4, LS5 : Position S/W (TEST position)
46
47

26
27

26
27
A5

A5
C
D
9

9
M : Spring charging motor LS6, LS7 : Position S/W (CONNECT position)
48
49

28
29

28
29
40
41
60
61

D1
A6 10 D2

D1
A6 10 D2
/11
/12

/11
/12
TC : Trip coil (SHT)
TC1 : Secondary Trip coil (SHT1)
34

34
TEST : 1a1b TEST : 2a TEST : 1a1b (4a4b)
C : Closing coil (CC) S/W
14

14
13

13
36
37

36
37
56
57

CONNECT : 2b CONNECT : 2a CONNECT : 1a1b


No. 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
1
2

1
2
38
39
58
59

38
39
UVT : Under Voltage Trip A3 A4 A5 A
4

4
3

3
50
51
70
71

50
51

52a : Auxiliary switch (NO) B


LS4 Closed at TEST position Close at TEST position Close at TEST position
5

5
6

6
C
52
53

52
53
72
73

52b : Auxiliary switch (NC)


LS5 Open at TEST position Closed at TEST position Open at TEST position D
7
8

7
8
74
75

54
55

LS2 : Motor stop limit switch


LS6 Open at CONNECT position Closed at CONNECT position Closed at CONNECT position
CTC2 : Current Trip coil (1A, 5A) C
A B A B
CTC3 : Current Trip coil (1A, 5A) LS7 Open at CONNECT position Closed at CONNECT position Open at CONNECT position (10a10b)
(4a4b) (10a10b)
<Connector Terminal Configuration>
Note) 1. CTC2 : Current Trip Coil(1A,5A) (Terminal No.: 13,14) Option
2. Positiob S/W - TEST 2a, CONNECT 2a_Terminal N0.: 1, 2, 3, 4, 5, 6, 7, 8)
- TEST position 1a1b, CONNECT position 1a1b/2b are available. A Type B Type
(*marked contact is b contact.)
3. UVT - Under Voltage Trip (Terminal No.: D1, D2)
4. TC1 - Secondary Trip Coil (Terminak No.: 11, 12) 13 D1

In case TC1 is selected and auxiliary switch is 10a10b, Some 'a' contact
(Terminal No.: 40, 41) and 'b' contact (Terminal No.: 54, 55) are not available
5. Secondary Trip Coil Monitoring Contact (Terminal No.: 36)
CTC2 CTC3
In case Secondary Trip Coil TCM Contact is Selected and auxiliary switch is 9a8b, Some 'a' contact
(Terminal No.: 40, 41)and 'b' contact (Terminal No.: 36, 37) are not available.
6. CTC2 - Current Trip Coil (Terminal No.: 13, 14)
CTC3 - Current Trip Coil (Terminal No.: D1, D2)
7. Close and Trip coil is One Pulse type, excluding Trip coil (DC110, 220V) 14 D2
8. In above optional accessories, UVT, CTC and TC1 can not be selected simultaneously.t
9. CTC Ccontrol Circuit
Trip coil monitoring contact

Auxiliary switch

UVH-38
Secondary trip coil with TCM Contact Note6)

P P P P 10a 10b
Note2)
Position switch
4a 4b <2a(TEST),2a(SERVICE)>
CS CS TEST SERVICE

A1 9 A3 D1 11 A5 15 22 24 26 28 40 42 44 46 48 60 34 36 38 50 52 54 56 58 70 72 74 1 3 5 7

Position switch
LS2 3 1 LS3 1 3 4 <1a1b(TEST),1a1b(SERVICE)>
Ya
4 2 2 4 6
1 Note5) 1 3* 5 7*
1
LM LS4 LS5 LS6 LS7
Yb
5 2
Note1) 1 2 4* 6 8*
LCS1
2
22 24 26 28 40 42 44 46 48 60 34 36 38 50 52 54 56 58 70 72 74
5 82 6 1 3 5 7
30
52b 52a LS4 LS5 LS6 LS7 Position switch
M
6 31 2
<1a1b(TEST), 2b(SERVICE)>
83 6' 4 6 8
23 25 27 29 41 43 45 47 49 61 35 37 39 51 53 55 57 59 71 73 75
3 7
1 3* 5* 7*
C Y Note4) LS4 LS5 LS6 LS7

TRIP POWER SOURCE

CLOSE POWER SOURCE

MOTOR POWER SOURCE


1 1 1
4 8
1 Note3)
UVT TC1 TC

LOCKING MAGNET POWER SOURCE


2 4* 6* 8*
LS1
2 2 2
2

A2 10 A4 D2 12 A6 16 23 25 27 29 41 43 45 47 49 61 37 39 51 53 55 57 59 71 73 75 2 4 6 8

N N N N
charge completion indicating contact
<Connecting terminal arrangement>

A type connector B type connector


16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Ø: External terminal of VCB LS3: Anti-close, anti-pumping limit switch A1 A2 38 39 A1 A2 38 39 40 41
29 28 27 26 25 24 23 22 A6 A5 A4 A3 A2 A1 A
A3 A4 50 51 A3 A4 50 51 42 43
52: Vacuum circuit breaker LCS1: Trip latch checking switch 39 38 37 36 34 B
53 52 51 50 C
M: Spring charging motor (preventing closing unless the trip latch is properly reset) A5 A6 52 53 A5 A6 52 53 44 45 12 11
D2 D1 10 9 16 15 8 7 6 5 4 3 2 1 D
9 10 9 10 54 55 46 47
TC: Trip coil LS4, LS5: Position S/W (close in TEST position)
22 23 22 23 56 57 48 49
TC1: Secondary trip coil LS6, LS7: Position S/W (close in SERVICE position)
C: Close coil
TEST : 1a1b TEST : 2a TEST : 1a1b 24 25 11 12
24 25 11 12
58 59
Y: Anti-pump relay S/W D1 D2 D1 D2
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
SERVICE : 2b SERVICE : 2a SERVICE : 1a1b 26 27 1 2 26 27 1 2 60 61
UVT: Under voltage trip No. 41 40 29 28 27 26 25 24 23 22 A6 A5 A4 A3 A2 A1 A
A3 A4 A5 28 29 3 4 28 29 3 4 70 71
52a: Auxiliary switch (a) 39 38 37 36 34 61 60 49 48 47 46 45 44 43 42 B
LS4 Close at TEST position Close at TEST position Close at TEST position 75 74 73 72 71 70 59 58 57 56 55 54 53 52 51 50 C
52b: Auxiliary switch (b) 34 5 6 34 5 6 72 73 12 11
D2 D1 10 9 16 15 8 7 6 5 4 3 2 1 D
LS5 OPEN at TEST position Close at TEST position OPEN at TEST position 36 37 7 8 36 37 7 8 74 75
LS1: Close interlock limit switch (only
LS6 OPEN at SERVICE position Close at SERVICE position Close at SERVICE position
withdrawable type) A B A B C
LS7 OPEN at SERVICE position Close at SERVICE position OPEN at SERVICE position
LS2: Motor stop, close spring
charged indication limit switch LM: Locking magnet (only withdrawable type)

Note) 1. LCS1 : Latch Checking Switch


2. Position S/W - TEST 2a, SERVICE 2a(Terminal No. 1, 2, 3, 4, 5, 6, 7, 8)
1a1b at TEST position and 1a1b at SERVICE position are also available.
(In case of 1a1b *marked contact is b - nomally open contact)
3. UVT - Under Voltage Trip (Terminal No. D1, D2) Option
4. TC1 - Secondary Trip Coil (Spare trip coil, terminal No. 11, 12)
5. LM - Locking Magnet (Terminal No. 15, 16), Type H only withdrawable type.
6. Secondary Trip Coil monitoring contact (Terminal No. 36)
b contact(36, 37) is not available if Trip Coil monitoring contact is applied to Secondary Trip Coil.
7. Above options TC1 and UVT can not be used simultaneously.
8. LS1(closing-interlock Limit-switch) is not available for fixed version
9. Above circuit diagram is based on ‘OFF’ status of VCB and closing spring is charged.
10. Please make sure that keep the direction of P, N on this circuit diagram.

67
68
VH-05/15
Control circuit diagram

Note 3)

Ø : External terminal of VCB


52 : Vacuum circuit breaker
M : Spring charging motor
TC : Trip coil
TC1 : Secondary trip coil(Option)
C : Closing coil
Y : Anti-pump relay
52a : Auxiliary switch (NO)
52b : Auxiliary switch (NC)
LS1 : Close interlock limit switch
LS2 : Motor stopping limit switch
LS3 : Anti-closing, Anti-pumping limit swich
LS4 : Motor charging interlock limit swich

Note) 1. Above circuit diagram is based on 'OFF' status of VCB and closing spring is charged.
2. TC1(Option) - Secondary Trip Coil(Spare trip coil, terminal No.11,12)
3. Two(2) "Early b" auxiliary contact is provided.(Terminal No.56-57, 58-89)
4. Please follow direction of P,N marked in the above circuit diagram.
Dimensions - UVL type UVL-05/15/27

4.76/15kV, 25/31.5kA, 1200A


Withdrawable (H type unit, phase distance 150mm)
490
150 150

589
642
359.5
492 301 Stroke:220

310
Ø35
691

643.5
300
185
96
Ø19.5
41.5
36
503 7 284 45
53 338
436 * Ha, Hf type cradle applied
469

4.76/15kV 25/31.5kA 1200A


Withdrawable (H type unit, phase distance 210mm)
640
210 210
589
648
359.5

642 301 Stroke: 220


Ø92
310
Ø35
691

651.5
643
300
185
96

653 7 284
Ø19.5
41.5
36

53 338
436
469 * Hf type cradle applied

69
Dimensions

4.76/15kV 25/31.5kA 1200A


Withdrawable (H type unit, phase distance 150mm)
490
150 150

589
642
359.5

492
301 Stroke: 220

310
Ø95
Ø48
(691)
691

643.5
300
89
185
503 7 284 45

Ø19.5
36
41.5
3.5
53 338
436 * He type cradle applied

Withdrawable (H type unit, phase distance 210mm)


640
210 210
589
642
359.5

642 301 Stroke: 220


310
Ø95
Ø48
(691)
691

643.5
300
89
185

653 7 284
Ø19.5
36
41.5
3.5

53 338
* He type cradle applied
436

70
UVL-05/15/27

4.76/15kV, 25/31.5kA, 2000A


Withdrawable (H type unit, phase distance 210mm)
640
210 210

642
589
359.5
642
301 Stroke:220

310
Ø79
691

666.5
300
185
96
Ø19.5
41.5
653 7 284 36
53 338
436 * He type cradle applied
469

4.76/15kV 25/31.5kA 2000A


Withdrawable (H type unit, phase distance 210mm)
640
210 210
589
648
359.5

301 Stroke: 220


642
Ø101
310
Ø54
691

666.5
300
185
96

653 7 284
Ø19.5

53 338
36
41.5

436 * Ha, Hf type cradle applied


469

71
Dimensions

4.76kV, 25/31.5kA, 1200A


Fixed (P type, Phase distance 150mm)
553
150 150
60 2-Ø14

4-Ø13

152 40

178
212
10
M12

509
(Earthing hole)

281
96.5

46.8
450 212

295
670

650
10
320
470 315 156
589 523.5

15kV, 25/31.5kA, 1200A


Fixed (P type, Phase distance 150mm)
553
150 150
60
179.5 2-Ø14
152 40

178
212
10

4-Ø13 M12
509

(Earthing hole)
281

96.5
46.8

280
450 212
295

690
670

670

650
556.5

10
320

470 315 156


589 523.5
606.5

72
UVL-05/15/27

4.76/15kV 25/31.5kA 1200A


Fixed (P type, Phase distance 210mm)

753
210 210
4-Ø13 60 2-Ø14

40
212
178
10
152
M12
(Earth hole)

523.5
271
96.5

46.8
600 212

295
10
670

650
320
670 156
789 523.5

4.76/15kV 25/31.5kA 1200A


Fixed (P type, Phase distance 254mm)
783
254 254
60 2-Ø14

4-Ø13
152 40

178
212
10

M12
509

(Earth hole)
281

96.5
46.8

700 212
295
670

650
10
320

700 315 156


819 523.5

73
Dimensions

4.76/15kV 25/31.5kA 2000A


Fixed (P type, Phase distance 150mm)

553
150 150
80
40 4-Ø14

4-Ø13

152 40

178
212
M12

10
(Earth hole)

523.5
281
96.5

46.8
450 212

295
20

690
670

650
320
470 315 156
589 523.5
606.5

4.76kV, 25/31.5kA, 2000A


Fixed (P type, Phase distance 210mm)

753
210 210
40 80
4-Ø14
40

4-Ø13
178
212
152
10

M12
523.5

(Earthing
281

hole)
46.8

96.5

600 212
295
670

650
20
320

670 315 156


789 523.5

74
UVL-05/15/27

15kV, 25/31.5kA, 2000A


Fixed (P type, Phase distance 210mm)
753
210 210
80
40
4-Ø14

4-Ø13

40

178
212
10
M12
(Earthing

523.5
hole)

152

281
96.5

46.8
455
600 212

295

690
650
670

20
320
670 315 156
789 523.5
606.5

4.76/15kV, 25/31.5kA, 2000A


Fixed (P type, Phase distance 254mm)
783
254 254
4-Ø13 80 4-Ø14
40
40

178
212
10
152

M12
509

(Earth hole)
281

96.5
46.8

700 212
295
670

650
20
320

700 315 156


819 523.5

75
Dimensions

27kV 25kA 1200A


Fixed (P type, Phase distance 254mm)

790
254 254
60
4-Ø14 4-Ø14
30

182 40

188.5
M12

247
(Earth hole)

542.5
300

84
115

700 247

340
10
846.5

809
404
700 335 171
830 558.5

76
UVL-05/15/27

4.76/15kV 25/31.5kA 1200A


Withdrawable (Ha type cradle, phase distance 150mm)
665 M12(DP: 25mm)
150 150 5
Ø12
(Mounting hole)

61.5
61.5
300
550
800
860
DETAIL A

700

30
1037
600 692
22.5 400
A

Ø35
310
900
1010
86.3

345
185.5
A
56.3 371
110

340 722.5
504 SEE DETAIL A
782.2
SECTION A-A

4.76/15kV 25/31.5kA 2000A


Withdrawable (Ha type cradle, phase distance 210mm)
815 2-M12(DP: 25mm)
210 210 5
Ø12
(Mounting hole)
64
25
300
550
800
860

DETAIL A
850
30

1037
750 692 DETAIL A
A 22.5 400 SCALE 1/3
Ø54
310
900
1010
86.3

345±2
185.5

A
56.3 371
110

210 SEE DETAIL A


722.5
654
782.2

SECTION A-A

77
Dimensions

4.76/15kV 25/31.5kA 1200A


Withdrawable (He type cradle, Arc, phase distance 150mm)

90 260 190 165 105 137 190 14-M8

150
M10(DP: 25)

560
550

150
9
Ø4
590 477 4-M16 #A
(For assembly
1174 178 of lifting hook)
1467

7-Ø11
600 65 410 335 100 (Mounting hole) 560 8-Ø8
(Mounting hole)

40
#A
120

240
315
350

310
240
950

315

240
370

440
6-M8 275

190

50 400 400 6-Ø12


(Mounting hole)
558

78
UVL-05/15/27

4.76/15kV 25/31.5kA 1200A


Withdrawable (He type cradle, Arc, phase distance 210mm)

90 260 190 165 105 137 190 37 14-M8

M10(DP: 25)

210
710
700

210
9
Ø4
#A
590 477
1174 188
4-M16
1467 (For assembly
of lifting hook)

750 65 410 335 100 710 8-M8

45

40
#A
120

240
315
350

310
240
950

315

240
370

440
6-M8

275
110

745

50 400 400 6-Ø12


(Mounting hole)
708

79
Dimensions

4.76/15kV 25/31.5kA 2000A


Withdrawable (He type cradle, Arc, phase distance 210mm)

90 260 190 165 105 137 190 37 14-M8

30 4-M10(DP: 25)

210
210

30
0
Ø8
590 477
4-M16 #A
1174 188 (For assembly
of lifting hook)
1464.2

750 65 410 335 100 7-Ø11 710 8-M8


(Mounting hole)

40
40
#A
120

240
315
350

310
240
950

315

240
370

440
6-M8

275
110

745

50 400 400 6-Ø12


(Mounting hole)
708

80
UVL-05/15/27

4.76/15kV 25/31.5kA 1200A


Withdrawable (Hf type cradle, Non-Arc , phase distance 210mm)

90 235 395 165 105

35 M12(DP: 25)

210
710

700

700
210

103
Ø35

815
#A
1090 2-M16
(For assembly
of lifting hook)

15-Ø11 710 8-M8


750
87.5

683 80 292 (Mounting hole)

30
#A

200 87.5

237.5
200

310
237.5
275
275
950

253
200

200
125

125

192
62.5

62.5

50 400 400 6-Ø12


(Mounting hole)
708

81
Dimensions UVL-05/15/27

4.76/15kV 25/31.5kA 2000A


Withdrawable (Hf type cradle, Non-Arc , phase distance 210mm)

90 235 395 165 105

35
2-M12(DP: 25)

210
710

700

103
210
Ø54

815 #A
1090 2-M16
(For assembly
of lifting hook)

#A 8-M8
15-Ø11 710
750
87.5

683 80 292 (Mounting hole)

30

30
87.5

237.5
237.5
200

200

237.5
237.5

310
275
275
950

253

253
200
200

125
125

192

192
62.5

62.5

50 400 400 6-Ø12


(Mounting hole)
708

82
UVH-38

38kV 31.5/40kA 1200/2000A


Fixed (P type, Phase distance 300mm)
300 300 157
298

M12 50

247
M12
(Earthing hole)

50
420

115.5
Ø79 157

4-Ø13
(Mounting hole)
914

830 392

400
1042.5

1041.5
551.5
866 500 207
944 837
951.5

Withdrawable (H type unit, phase distance 300mm)


959.4
300 300
937.7
1001.5
582.5

556.5 Stroke: 490


966
Disconnect - Test: 50
Test - Connected: 440
100
Ø48
Ø95
1100.5

1095
605
391
281

956 655.5
36

963 11.5 53 712


802

83
Dimensions UVH-38

38kV 31.5/40kA 1200/2000A


Withdrawable (H type cradle, phase distance 300mm)

USE 16-M8
Self bolt 125 190

22

25
25

233
300
300
233
22
25

25
50 300 250 260 260 260 41 70

632 862 317


35 557 80 583 80 159 22-Ø10 25 USE 23-M8 25
PNL Connection hole Self bolt

30
175 164.5

240 60 213.5 213.5


5 237

599
M12 DP25

350

40
USE Specific
8-M8 Bolt

400

85
1410

450

245
245
103 75 160 115 160 115 160 75 103

978
450
778

245
187.5

200
25
128
125

1066 40 1494 50 133 200 200 200 200 133

50
125 190
27 11.5

323
27
11.5

35 Ø14

84
VH-05/15

4.76/15kV, 40/50kA, 1200/2000A


Withdrawable (H type unit, phase distance 254mm)
254 254
153 153

195 195

11.5 722

698

101
54
360
815

359
696 53 532 60

10
648
718

4.76/15kV, 40/50kA, 3000A


Withdrawable (H type unit, phase distance 254mm)
254 254
137 137

171 171

11.5 722

698
117
79
360
815

359

696 53 532 60
10

658
728

85
Dimensions

4.76/15kV, 40/50kA, 1200/2000A


Withdrawable (Ha type cradle, phase distance 254mm)

254
2-M12

745.4
776
(DP:25)

54
254

36
540 350 4- 14 117 123
(Mounting hole)

287.5 710
250 12- 14
(Mounting hole)

370

360
1035
212.8

370

449
212.5
165.5

89
816 1019.3 6.7 14 233
1156.8 (Earting hole)

190 350 350


150 6- 14
(Mounting hole)
776

86
VH-05/15

4.76/15kV, 40/50kA, 3000A


Withdrawable (Ha type cradle, phase distance 254 mm)

254
4-M12

745.4
776
(DP:25)

79
254

50
540 350 4- 14 117 123 50
(Mounting hole)

287.5 710
250 12- 14
(Mounting hole)

370

360
1035
212.8

370

449
212.5
165.5

89
816 1019.3 6.7 14 233
1156.8 (Earting hole)

190 350 350


6- 14
150
(Mounting hole)
776

87
Technical data

Electrical endurance by interrupting current


Number[ops.]

Number[ops.]

Interrupting current [kA] Interrupting current [kA]

VI model LV6□ at 5/15kV VI model LV8 at 5/15kV


•N : Operation numbers •N : Operation numbers
•I : Interrupting current •I : Interrupting current
Number[ops.]

Number[ops.]

Interrupting current [kA] Interrupting current [kA]

VI model LV14-P1 at 27kV VI model LV8-P at 38kV


•N : Operation numbers •N : Operation numbers
•I : Interrupting current •I : Interrupting current

Note) 1. A
 bove graphs represent the characteristics of the electrical life of LS Susol VCB.
2. Life characteristics of each model in each rating represents the LOG-LOG graphs.

88
Standard Use Environment for Susol VCB
The operation characteristic of Vacuum Circuit Breaker such as insulation and endurance is often influenced
largely by external environment and thus should be applied appropriately with conditions of the place where
it is used taken into consideration.

The following values are the limits have been set in accordance with IEC 62271-100 (IEC 62271-1)

Ambient Temperature
- maximum temperature: +40℃
- 24-hour average maximum temperature: +35℃
- minimum temperature: -5℃

Altitude
- 1000m or less above sea level

Relative Humidity
- 24 hours average value: 95% or less
- One month average: 90% or less

■ If a standard circuit breaker is used in high temperature exceeding 40℃,


you are advised to use it according to the current corrected for each level
of ambient temperature in catalog.
■ If used in conditions of high humidity, the dielectric strength or electric
performance may be degraded.

■ It is highly recommended to use a dust cover or anti-humid agent if it is


used in dusty and humid conditions.
■ Excessive vibration may cause a trip breaker such as connection fault or
flaw on mechanical parts.

■ If it is left ON or OFF for a long time, it is recommended to switch load


current on a regular basis.
■ It is recommend to put it in the sealed protection if corrosive gas is
prevalent.

89
Technical data

Special Use Environment

The circuit breaker is designed for use in standard use environment specified in Section 2. 1 of IEC62271-1.
Concerning the special use environments as below the special use conditions are
required to be considered, thus please contact us in advance.

- where altitude and ambient temperature are out of standard use environment.(-40℃)
- where a strong sea breeze blows
- when usually used in a humid place
- where a lot of steam or oil steam exists
- where explosive, flammable and other harmful gases might permeate the breaker
- In a dusty place
- where abnormal vibration or shock exists
- where a lot of ice and snow exist
- other special conditions

Withstand voltage compensation according to altitude


If the breaker is used in areas of sea level higher than 1000m the degradation of insulation
performance should be taken into consideration.

70 36 170
50(65) 24 125
38 17.5 95
28(42) 12 75(82)
20 7.2 60
Ud [kV/1min] Ur[kV] Up [kV/1.2 50 ]
Power Frequency Impulse Withstand Voltage
Withstand Voltage

<Table 1> Criteria of withstand voltages by rated voltages specified in IEC62271-1

90
Special Use Environment

Withstand voltage compensation according to altitude


1.5

Correction parameter 1
1.45

1.4

1.35

1.3

1.25

1.2

1.15

1.1

1.05

1
1000 1500 2000 2500 3000 3500 4000
Altitude (m)

<Fig.1 > withstand voltage correction parameter 1 by altitude (based on a required withstand voltage)

1
Correction parameter 2

0.95

0.9

0.85

0.8

0.75

0.7

0.65

0.6

0.55

0.5
1000 1500 2000 2500 3000 3500 4000
Altitude (m)

<Fig.2 > withstand voltage correction parameter 2 by altitude (based on a applicable withstand voltage)

Ex) Selecting a breaker to be used in a place of 2500m above sea level with a rated voltage 7.2kV
(correction parameter 1 applied)
- correction parameter at 2500m is 1.2
- c riteria of withstand voltage by rated voltage:
Power Frequency Withstand Voltage (Ud) = 20kV, Impulse Withstand Voltage (Up) = 60kV
- r equirements withstand voltage criteria:
Power Frequency Withstand Voltage (Ud) = 20×1.2 = 24kV, Impulse Withstand Voltage (Up) = 72kV
Therefore rated voltage 12kV breaker shall apply to satisfy the required withstand voltage.

Ex) To apply a breaker with a rated voltage 12kV to the place of 2,500m above sea level
(correction parameter 2 applied)
- correction parameter at 2500m is 0.825
-d ielectric strength of VCB : Power Frequency Withstand Voltage (Ud) = 28×0.825 = 23.1kV,
Impulse Withstand Voltage (Up) = 75×0.825 = 62kV/1.2×50 ㎲
Therefore above breaker with rated voltage 12kV shall apply to rated voltage system 7.2kV at the altitude.

91
Technical data

Rated current compensation in accordance with ambient temperature


When normal ambient temperature exceeds the temperature specified in the environment
the following formula help to select the applicable current.

Ia= Ir ( (Θmax - Θa)/Θr)1/2


Ia: allowable continuous current in the actual ambient temperature Θa
Ir: rated current at 40℃ ambient temperature
Θmax: acceptable overall temperature of the hottest spot
Θa: the actual ambient temperature expected at -30℃ and 60℃
Θr: allowable temperature in the hottest place at rated current

Ex) The calculation of the applicable load current value when a breaker with rated current
2000A is used at 55 ℃ ambient temperature
Ia = 2000×((105-55)/65)1/2 = 2000×0.87 = 1754A

Ambient temperature (℃)


Rated current (A)
20 25 30 35 40 45 50 55 60
3000 3000 3000 3000 3000 3000 2882 2760 2631 2496
2000 2000 2000 2000 2000 2000 1922 1840 1754 1664
1200 1200 1200 1200 1200 1200 1153 1104 1052 998

<Table 2> Allowable load current by ambient temperature

3500

3000

2500

2000

1500

1000

500

0
20 25 30 35 40 45 50 55 60

<Figure 3> Allowable load current by ambient temperature

92
Memo

93
Memo

94
95
www.lselectric.co.kr/USA

 LS ELECTRIC America Inc. Chicago Head Office  Overseas Branches


980 Woodlands Parkway, Vernon Hills, IL 60061 USA • LS ELECTRIC Tokyo Office (Japan)
Tel: 1-800-891-2941 E-Mail: [email protected] Tel: 81-3-6268-8241 E-Mail: [email protected]
 Headquarter
• LS ELECTRIC Beijing Office (China)
127 LS-ro (Hogye-dong) Dongan-gu, Anyang-si, Gyeonggi-Do, 14119, Korea Tel: 86-10-5095-1631 E-Mail: [email protected]
 Seoul Office • LS ELECTRIC Shanghai Office (China)
LS Yongsan Tower, 92, Hangang-daero, Yongsan-gu, Seoul, 04386, Korea Tel: 86-21-5237-9977 E-Mail: [email protected]
Tel. 82-2-2034-4916, 4684, 4429
• LS ELECTRIC Guangzhou Office (China)
 Overseas Subsidiaries
Tel: 86-20-3818-2883 E-Mail: [email protected]
• LS ELECTRIC Japan Co., Ltd. (Tokyo, Japan)
Tel: 81-3-6268-8241 E-Mail: [email protected] • LS ELECTRIC Chengdu Office (China)
Tel: 86-28-8670-3201 E-Mail: [email protected]
• LS ELECTRIC (Dalian) Co., Ltd. (Dalian, China)
Tel: 86-411-8730-5872 E-Mail: [email protected] • LS ELECTRIC Qingdao Office (China)
• LS ELECTRIC (Wuxi) Co., Ltd. (Wuxi, China) Tel: 86-532-8501-2065 E-Mail: [email protected]
Tel: 86-510-6851-6666 E-Mail: [email protected]
• LS ELECTRIC Nanjing Office (China)
• LS ELECTRIC Vietnam Co., Ltd. Tel: 86-25-8467-0005 E-Mail: [email protected]
Tel: 84-93-631-4099 E-Mail: [email protected] (Hanoi)
Tel: 84-24-3823-7890 E-Mail: [email protected] (Hochiminh) • LS ELECTRIC Bangkok Office (Thailand)
• LS ELECTRIC Middle East FZE (Dubai, U.A.E.) Tel: 66-90-950-9683 E-Mail: [email protected]
Tel: 971-4-886-5360 E-Mail: [email protected] • LS ELECTRIC Jakarta Office (Indonesia)
• LS ELECTRIC Europe B.V. (Hoofddorf, Netherlands) Tel: 62-21-2933-7614 E-Mail: [email protected]
Tel: 31-20-654-1424 E-Mail: [email protected]
• LS ELECTRIC Moscow Office (Russia)
Tel: 7-499-682-6130 E-Mail: [email protected]
• LS ELECTRIC America Western Office (Irvine, USA)
Tel: 1-949-333-3140 E-Mail: [email protected]

Specifications in this catalog are subject to change without notice due to


2020. 06 continuous product development and improvement.