Concept of Distance Protection
Concept of Distance Protection
PROTECTION
BY JAYANTA DUTTA
DEPUTY CHIEF ENGINEER
OS & U (SYSTEM) DVC KOLKATA
LIST OF TOPICS
Objective of Distance Protection
Short Lines
Current differential
Phase comparison
Permissive Overreach Transfer Trip (POTT)
Directional Comparison Blocking (DCB)
TYPICAL PROTECTION SCHEMES
Medium Lines
Phase Comparison
Directional comparison Blocking
Unblocking
Step Distance
Current Differential
TYPICAL PROTECTION SCHEMES
Long Lines
Phase Comparison
Directional comparison Blocking
Unblocking
Step Distance
Current Differential.
FAULT TYPES
TRANSIENT FAULTS
are common on transmission lines,
approximately 80-85%
lightning's are the most common reason.
can also be caused by birds, falling trees, Forest
growth, swinging lines, High velocity winds etc.
will disappear after a short dead interval
PERSISTENT FAULTS
can be caused by a broken conductor fallen
down
can be a tree falling on a line.
must be located and repaired before normal
service
TRANSMISSION LINE
FAULTS FAULT STATISTICS
SENSITIVITY
SELECTIVITY
DEPENDABILITY
SECURITY
RELIABILITY
MEASURING PRINCIPLES OF DIFFERENT
RELAYS OF TRANSMISSION LINES
Over current protection
Differential protection.
Distance protection
MEASURING PRINCIPLES OF
DISTANCE PROTECTION
Power lines have impedances
of size 0,3- 0,4 ohm/ km and
normal angles of 80 - 85
degrees in a 50Hz systems.
Directional angle
“slammed”
Directional
angle lowered
and “slammed”
+XL
Load
Trajectory
Operate No Operate area
area
Typical load characteristic
impedance
+R
Load Swings
“Lenticular”
Characteristic
Load swing
QUADRILATERAL CHARACTERISTICS
DISTANCE CHARACTERISTICS - SUMMARY
Circular Characteristics
Low measured reactance
Ratio between fault resistance jx
and reactance is high.
Quad. Char.
Distance protection with mho
characteristic can not see average
fault resistance.
Quadrilateral characteristic Cir.
Quadrilateral characteristic Char
improves sensitivity for higher Rf .
RF/XF ratio. Improves sensitivity
Xf R
for Higher Resistive Faults
Tele metering schemes improve
the total system behaviour.
Quadrilateral Characteristics
Ground Resistance
(Conductor falls on ground)
Mho
Lenticular Quadrilateral
JX JX JX
R R R
Better coverage for
Used for phase elements ground faults due
Standard for phase with long heavily loaded
elements to resistance added
lines heavily loaded to return path
DISTANCE ELEMENT POLARIZATION
The following polarization quantities are
commonly used in distance relays for
determining directionality:
Self-polarized
Memory voltage
Quadrature voltage
and QUAD)
Memory duration is a common distance settings
(all zones, phase and ground, MHO and QUAD)
STEP DISTANCE SCHEME
Local
Z1
Breaker
Tripped
Fault
Breaker
Closed Z1
Remote
STEP DISTANCE SCHEME
Local
Z2 (time delayed)
Z1
Z1
Z2 (time delayed)
Remote
STEP DISTANCE SCHEME …
Z3 (remote backup)
Z2 (time delayed)
Z1
PRINCIPLE OF DISTANCE PROTECTION
DISTANCE RELAY COORDINATION Over Lap
Local Relay – Z2
Remote Relay – Z4
Communication
Channel
PILOT COMMUNICATIONS CHANNELS
Distance-based pilot schemes traditionally
utilize simple on/off communications
between relays.
Typical communications media include:
Pilot-wire
Microwave
Radio
First Zone
PERMISSIVE UNDERREACHING
TRANSFER TRIP (PUTT)
Requires both under (RU) and overreaching (RO)
functions
Identical to DUTT, with pilot tripping signal
supervised by RO (Zone 2)
Second Zone
Bus First Zone Bus
LINE
First Zone
Second Zone
Rx
&
Zone 2
OR Local Trip
Zone 1
PERMISSIVE OVERREACHING TRANSFER
TRIP (POTT)
Requires overreaching (RO) functions (Zone 2).
GUARD frequency sent in stand-by
TRIP frequency when one RO function operates
LINE
First Zone
Second Zone
Z1 Tx
z1
Z1 Rx & OR Trip Line
Breakers
z2 t 0
POTT Scheme
Communication
Channel
POTT Scheme
Local Relay
FWD IGND Remote
Relay FWD
Local Relay – Z2 IGND
Remote Relay – Z2
Communication
TRIP Channel
POTT RX POTT TX
First Zone
Second Zone
Directional Comparison Blocking (DCB)
End Zone
Communication Channel
Directional Comparison Blocking
(DCB)
Internal Faults Local Relay – Z2
FWD IGND
TRIP
TRIP Timer
Start
Expired
Zone 2 PKP
NO Dir Block RX
OR
Local Relay GND DIR OC Fwd Remote Relay
Directional Comparison Blocking
(DCB)
External Faults Local Relay – Z2
FWD IGND
Remote Relay – Z4
TRIP Timer
REV IGND
Start No TRIP
Dir Block RX DIR BLOCK TX
Local Relay Remote Relay
Zone 2 PKP Communication Zone 4 PKP
Channel
OR OR
FIRST STAGE
Setting :- 110% voltage.
Time delay of 5 Secs
• SECOND STAGE
Setting:- 140% voltage
Time Delay:- Instantaneous
DIRECTIONAL E/F PROTECTION
RECOMMENDATIONS
Presently 1 phase high speed auto-reclosure (HSAR) at
400kV and 220kV level is widely practiced including on
lines emanating from Generating Stations and the same
is recommended for adoption.
If 3-phase auto-reclosure is adopted in 132KV system
excluding the lines emanating from Generating Stations.
Setting Criterion
DEAD TIME
Auto- reclosing requires a dead time which exceeds the de-
ionising time.
Time required for the de-ionising of the fault path depends
on:- arcing time, fault duration, wind conditions, circuit
voltage, capacitive coupling to adjacent conductors, etc.
Single phase dead time of 1.0 sec is recommended for both
400kV and 220kV system.
SETTING CRITERION FOR PROVISION OF AUTO
RECLOSURE
Setting Criterion
RECLAIM TIME
The time during which a new start of the auto-reclosing equipment
is blocked.
If reclosing shot has been carried out and the line is energized and
a new fault occurs before the reclaim time has elapsed, the auto-
reclosing equipment is blocked and a signal for definite tripping of
the breaker is obtained.
After the reclaim time has elapsed, the auto-reclosing equipment
returns to the starting position and a new reclosing sequence can
occur.
The reclaim time must not be set to such a low value that the
intended operating cycle of the breaker is exceeded, when two
faults incidents occur close together.
If the breaker is closed manually, the auto reclosing equipment is
blocked and cannot start again until the reclaim time has elapsed
For the breaker to be used for auto-reclosing, it is essential that it
has the operating mechanism and breaking capacity necessary for it
to be able to perform the auto-reclosing sequences required
CIRCUIT BREAKER REQUIREMENT
O + 0.3 s + CO + 3 min + CO