06IC Sec11 Function-Relays
06IC Sec11 Function-Relays
06IC Sec11 Function-Relays
Contents
Temperature Monitoring Relays
Pages
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/4 Selection, 3RS10-11, 3RS20-21 Analog with One Threshold Value . . . . . . . . . . . . . . .11/5 Analog with Two Threshold Values . . . . . . . . . . . . . .11/5 Digital with Two Threshold Values . . . . . . . . . . . . . .11/6 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/7 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/8 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/9 Circuit Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/10 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/11
Thermistor Motor Protection
Coupling Relay Overview . . . . . . . . . . . . . . . . . . . . . .11/45 Selection/Technical Data . . . . . . . . . . . . . . . . . . . . . . .11/45 Interface Relay Overview . . . . . . . . . . . . . . . . . . . . . .11/47 Selection/Technical Data . . . . . . . . . . . . . . . . . . . . . . .11/48
Wide Input Interface Relay
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/12 Selection, 3RN10 . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/13 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . .11/1411/15 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/15 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/16 Circuit Diagrams . . . . . . . . . . . . . . . . . . . . . . . .11/1711/18 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/19
Solid-State Time Relays
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/5811/66 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . .11/6711/79 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/70 Circuit Diagrams . . . . . . . . . . . . . . . . . . . . . . . .11/7111/72 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . .11/7311/77
Interface Converters
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/20 Selection Standard Time Relay, 3RP20 . . . . . . . . . . . . . . . . . .11/21 Narrow Width Time Relays, 3RP15 . . . . . . . . . . . . .11/21 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/22 Front Panel Mount Relays, 7PV . . . . . . . . . . . . . . .11/23 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . .11/2411/25 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/2611/29 Circuit Diagrams . . . . . . . . . . . . . . . . . . . . . . . .11/3011/32 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11/33
Monitoring Relays
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/78 Selection, 3RS17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/79 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/80 Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/81 Circuit Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/82 Dimension Drawings . . . . . . . . . . . . . . . . . . . . . . . . . .11/82
Power Relays, 3TG10
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/34 For Line, Voltage and Insulation Monitoring Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/35 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/35 For Current, Power Factor Monitoring Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/47 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/48 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/48
Monitoring Relays for Non-Electrical Quantities
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/83 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/83 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . .11/8411/85 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/86 Circuit Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/86 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/86
For Level Monitoring of Conductive Liquids, 3UG3501 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/38 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/38 Principle of Operation . . . . . . . . . . . . . . . . . . . . . . .11/39 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11/40
For Underspeed Monitoring, 3UG3051
11/1
SIMIREL
11/2
SIMIREL
3UG3/4 monitoring relays
11/58
11/79
11/3
SIMIREL
Hysteresis switch
Digital evaluation units High-end evaluation unit for 1 or 1-3 sensor circuits Multifunctional digital display and three LEDs (for threshold values and Ready) Adjustable sensor types Adjustable overshoot, undershoot or window function Switchable open-circuit or closed-circuit principle Hysteresis for both threshold values (1 to 99 K) Memory function can be selected by means of an external control signal (Y1/Y2) One NO and two SPDT contacts Adjustable time delay from 0 to 999 s Wire-break and short-circuit detection with separate signalling contact (1 NO) Non-volatile storage of the set parameters 45 mm housing with 24 supply terminals Measuring principle for 2- and 3-wire sensors Electrical isolation (with the exception of AC/DC 24 V devices) In the 3-sensor design, the status of the individual sensors is indicated on limit value overshoot/undershoot
It clearly displays which of the connected sensors has overshot or undershot one or both threshold values. Advantages All devices are with Cage Clamp terminals All devices with the exception of AC/DC 24 V devices are electrically isolated Variants for the evaluation of 1 to 3 sensors in one unit, e.g. for multiple monitoring in a plant or for motor protection Easy operation without complex menu systems Graduated product range; the right device for every application High-end evaluation units with digital display can be used for a wide temperature range and for different sensor types Adjustable hysteresis Rapid fault diagnosis due to short-circuit monitoring and sensor wire-break detection Power packs with wide range of input voltage reduce the number of variants Easy configuration for either two-point or three-point closedloop control
Application The 3RS1/3RS2 SIMIREL temperature monitoring relays can be used in almost any application in which limit temperatures must not be overshot or undershot, e.g.: Monitoring of set limit temperatures and output of alarm messages for: Motor and plant protection Switchgear cabinet temperature monitoring Frost monitoring Temperature limits for process variables, e.g. in the packaging industry or galvanising equipment Control of plants and machines such as heating, airconditioning and ventilation systems, solar collectors, heat pumps or warm water supplies Monitoring of servo motors with KTY sensors Bearing and gearbox oil-level monitoring Monitoring of cooling liquids
11/4
SIMIREL
3RS10/3RS11 Temperature monitoring relays Sensor Function Measuring range Rated control supply voltage Vs 5060 Hz AC Order No. List Price $
Analog setting, 1 threshold value, 22.5 mm wide; analog closed-circuit principle, no holding on supply failure function; 1 NO + 1 NC 24 V AC/DC 3RS10 00- CD00 110/230 V AC 3RS10 00- CK00 0...+100 C 24 V AC/DC 3RS10 00- CD10 110/230 V AC 3RS10 00- CK10 0...+200 C 24 V AC/DC 3RS10 00- CD20 110/230 V AC 3RS10 00- CK20 Underrange 50...+50 C 24 V AC/DC 3RS10 10-1CD00 110/230 V AC 3RS10 10-1CK00 0...+100 C 24 V AC/DC 3RS10 10-1CD10 110/230 V AC 3RS10 10-1CK10 0...+200 C 24 V AC/DC 3RS10 10-1CD20 110/230 V AC 3RS10 10-1CK20 Typ J Overrange 0...+200 C 24 V AC/DC 3RS11 00- CD20 (thermocouple) 110/230 V AC 3RS11 00-1CK20 0...+600 C 24 V AC/DC 3RS11 00-1CD30 110/230 V AC 3RS11 00-1CK30 Typ K Overrange 0...+200 C 24 V AC/DC 3RS11 01- CD20 (thermocouple) 110/230 V AC 3RS11 01-1CK20 0...+600 C 24 V AC/DC 3RS11 01-1CD30 110/230 V AC 3RS11 01-1CK30 +500...+1000 C 24 V AC/DC 3RS11 01-1CD40 110/230 V AC 3RS11 01-1CK40 Analog setting for alarm and trip (2 threshold values), 22.5 mm wide; open-circuit closed-circuit current principle can be toggled between; no holding on supply failure function; 1 NO + 1 CO PT100 Overrange 50...+50 C 24 V AC/DC 3RS10 20-1DD00 (resistance sensor) 24240 V AC/DC 3RS10 20-1DW00 0...+100 C 24 V AC/DC 3RS10 20-1DD10 24240 V AC/DC 3RS10 20-1DW10 0...+200 C 24 V AC/DC 3RS10 20-1DD20 24240 V AC/DC 3RS10 20- DW20 Underrange 50...+50 C 24 V AC/DC 3RS10 30-1DD00 24240 V AC/DC 3RS10 30-1DW00 0...+100 C 24 V AC/DC 3RS10 30-1DD10 24240 V AC/DC 3RS10 30-1DW10 0...+ 200 C 24 V AC/DC 3RS10 30- DD20 24240 V AC/DC 3RS10 30-1DW20 Typ J Overrange 0...+200 C 24 V AC/DC 3RS11 20- DD20 (thermocouple) 24240 V AC/DC 3RS11 20-1DW20 0...+600 C 24 V AC/DC 3RS11 20-1DD30 24240 V AC/DC 3RS11 20-1DW30 Typ K Overrange 0...+200 C 24240 V AC/DC 3RS11 21-1DW20 (thermocouple) 0...+600 C 24240 V AC/DC 3RS11 21-1DW30 +500...+1000 C 24 V AC/DC 3RS11 21-1DD40 24240 V AC/DC 3RS11 21-1DW40 Analog setting evaluation devices with one and two threshold values. For analog setting devices, the threshold values and the hysteresis from 2 to 20% are set using a rotary potentiometer. For devices with 2 threshold values, the selectable hysteresis only acts on threshold value 1. For the second threshold value, the hysteresis is permanently set to 5%. This series of products was developed for applications where a setting accuracy of 5% is sufficient. Screw terminal 1 PT100 (resistance sensor) Overrange 50...+50 C 125.00 125.00 125.00 125.00 125.00 204.00 125.00 125.00 125.00 125.00 125.00 125.00 125.00 125.00 125.00 125.00 125.00 125.00 125.00 125.00 125.00 125.00
195.00 215.00 195.00 215.00 195.00 215.00 190.00 210.00 190.00 210.00 190.00 210.00 190.00 210.00 190.00 210.00 210.00 210.00 190.00 210.00
11/5
SIMIREL
Order No.
List Price $
Temperature monitor acc. to DIN 3440, digital settings, 2 threshold values, 45 mm wide; 1 CO + 1 CO + 1 NO, memory function can be enabled using an external jumper. Relay parameters have a holding on supply failure function 24 V AC/DC 3RS10 40- GD50 250.00 24240 V AC/DC 3RS10 40- GW50 250.00 50...+932 F 24 V AC/DC 3RS20 40- GD50 271.00 24240 V AC/DC 3RS20 40- GW50 289.00 99...+999 C 24 V AC/DC 3RS11 40- GD60 260.00 TYPE J, K, T, E, N 24240 V AC/DC 3RS11 40- GW60 270.00 (thermocouple) 99...+1830 F 24 V AC/DC 3RS21 40- GD60 271.00 24240 V AC/DC 3RS21 40- GW60 289.00 Temperature limiter and temperature monitor acc. to DIN 3440, digital settings, 2 threshold values, 45 mm wide; 1 CO + 1 CO + 1 NO, tripped state and relay parameters are saved using a holding on supply failure function PT100/1000; KTY83/84; NTC (resistance sensor) 1) 50...+500 C PT100/1000; KTY83/84; NTC (resistance sensor) 1) TYPE J, K, T, E, N, R, S, B (thermocouple) 50...+750 C 24 V AC/DC 24240 V AC/DC 24 V AC/DC 24240 V AC/DC 3RS10 42- GD70 245.00 3RS10 42- GW70 250.00 3RS11 42- GD80 245.00 3RS11 42- GW80 250.00
99...+1800 C
Motor monitoring relays, digital settings for up to 3 sensors, 45 mm wide; 1 CO + 1 CO + 1 NO Sensor No of sensors 1 to 3 sensors Measuring range Rated control supply voltage Vs 24240 V AC/DC 24240 V AC/DC Order No. List Price $ GW50 375.00 GW50 434.00 1
50...+500 C 50...+932 F
The short-circuit and wire breakage detection, as well as the measuring range are restricted, depending on the sensor type:
Measuring ranges in C for thermocouple Sensor type J K T E N S R B Shortcircuit Wire breakage x x x x x x x x 3RS11 40 measuring range 99...999 99...999 99...400 99...999 99...999 3RS11 42 measuring range 99...1200 99...1350 99...400 99...999 99...999 0...1750 0...1750 400...1800
Measuring ranges in C for resistance sensors Sensor type PT100 PT1000 KTY83-110 KTY84 NTC1) Shortcircuit x x x x x Wire breakage x x x x 3RS10 40 measuring range 50...500 50...500 50...175 40...300 80...160 3RS10 42 measuring range 50...750 50...500 50...175 40...300 80...160
Evaluation units with digital settings Temperature monitoring relays distinguish themselves due to the fact that they are extremely easy-to-use. The actual temperature is always displayed on the threedigit LED display. A dedicated relay with one NO contact is integrated to monitor the sensor. The relay is switched-out in the parameterizing mode. The following parameters can be set: Sensor type 2 threshold values J1, J 2 1 hysteresis; this acts on both thresholds (0 99 K) 1 delay time; this acts on both thresholds (0 9999 s) Either the open-circuit/closed-circuit principle can be selected Function: Overtemperature/Undertemperature (overrange/underrange) or window monitoring within a defined range Versions with a wide-range voltage have electrical isolation. The temperature ranges are dependant on the sensor type (refer to the function).
11
11/6
SIMIREL
Technical data General data
Type Sensor type
3RS11 00 TC Type J
3RS11 01 TC Type K
3RS.0 40 3RS.0 41
3RS.1 40
mm V W/VA
Auxiliary circuit
Contacts Rated operational current Ie AC15 at AC 230 V, 50 Hz DC13 at 24 V DC13 at 240 V Required DIAZED fuse Utilisation category Electrical endurance Mechanical endurance Mechanical operating cycles gL/gG AC 15 at 3 A A A A A 3 1 0.1 4 100,000 30 x 106 typically < 5% of upper limit of scale % ms 2 to 20 % of upper limit of scale 5 % of upper limit of scale <2 <5K <3 <2 <5K <3 < 2K 1 digit < 5K 1 digit <5K 1 SPDT + 1 SPDT + 1 NO
Tripping unit
Measuring accuracy at 20C ambient temperature (T20) Reference point accuracy Deviations due to ambient temperature in % of measuring range Measuring cycle Hysteresis adjustments for temperature 1 for temperature 2
0.05 C per K deviation from T20 500 1 to 99 Kelvin, for both values
Sensor circuit
Typical sensor current PT100 PT1000 / KTY83 / KTY84 / NTC Wire-break detection Short-circuit detection 3-wire connection mA mA Typically 1 Typically 0.2 No No Yes 2) Yes 2) Typically 1 Typically 0.2 Typically 1 Typically 0.2 Yes 1) Yes Yes 2) Yes No
Enclosure
Environmental effects Permissible ambient temperature Permissible storage temperature Permissible mounting position Degree of protection to EN 60 529 Rated insulation voltage Ui (pollution degree 3) Conductor cross-section Screw terminals solid finely stranded, with end sleeves solid or stranded AWG conductors Tightening torque Cage Clamp terminals solid finely stranded, with end sleeves finely stranded, without end-sleeves solid or stranded AWG conductors corresponding opening tool Vibration performance IEC 68-2-6 Shock resistance IEC 68-2-27 mm2 mm2 AWG Nm mm2 mm2 mm2 AWG M 3.5 (for standard screwdriver Size 2 and Pozidriv 2) 1 x (0.5 to 4) / 2 x (0.5 to 2.5) 1 x (0.5 to 2.5) / 2 x (0.5 to 1.5) 2 x (20 to 14) 0.8 to 1.2 2 x (0.25 to 1.5) 2 x (0.25 to 1) 2 x (0.25 to 1.5) 2 x (24 to 16) 8WA2 807 3) 5 to 26 Hz/0.75 mm 15 g/11 ms AC V C C 25 to 60 40 to 80 any Terminals: IP20; cover: IP40 300
1) Not for NTC (B57227-K333-A1 (100 C:1.8 k ; 25 C:32,762 k ). 2) 2-wire connection of resistance sensors with wire jumper between T2 and T3. 3) See Page 11/22
11/7
SIMIREL
EN 50 081-2 "Basic technical standard for emitted interference (industry)" EN 61 000-6-2 "Basic technical stand ard for interference immunity (industry)" DIN EN 50 042 "Terminal marking" UL/CSA under application
Specifications
Connection of resistance thermometers 2-wire measurement When 2-wire temperature senaccount when the parameters sors are used, the sensor reare set for the evaluation unit. A sistance is added to the wire jumper must be clamped resistance. The system error between terminals T2 an T3. that results must be taken into
The following table can be used to determine the temperature error when a PT100 is used.
Error due to wiring The error that arises due to the wiring is approx. 2.5 Kelvin/ ohm. If the resistance of the wiring is not known and cannot be measured, the wiring error can be estimated by means of the following table.
Temperature error as a function of conductor length and cross-section with PT100 sensors and 20C ambient temperature, in K
Cable length in m 0 10 25 50 75 100 200 500 Cross-section mm2 0.5 0.75 0.0 1.8 4.5 9.0 13.6 18.1 36.3 91.6 0.0 1.2 3.0 6.0 9.0 12.1 24.2 60.8 1 0.0 0.9 2.3 4.5 6.8 9.0 18.1 45.5 1.5 0.0 0.6 1.5 3.0 4.5 6.0 12.1 30.2
3-wire measurement To minimise the effects of the wiring resistances, a 3-wire circuit is usually used.
Using the additional wire, it is possible for two measuring circuits to be formed of which one is used as a reference.
The evaluation unit can then automatically calculate the wiring resistance and take it into account.
Connection of thermoelements A differential temperature measurement is obtained from the thermo-electrical effect
This principle assumes that the evaluation unit knows the temperature at the terminal (T2). The 3RS11 temperature monitoring relays have a built-in reference point correction function that determines this reference temperature and uses it to generate the measurement result.
The absolute temperature is therefore calculated from the ambient temperature of the evaluation unit and the temperature difference measured by the thermoelement.
In this manner, temperature acquisition (T1) is possible without knowing the precise ambient temperature at the terminals of the evaluation unit (T2).
The connecting lead is only permitted to be extended using equalising conductors made from the same material as the thermoelement itself. If a different type of lead is used, the measurement will be inaccurate.
11/8
SIMIREL
Functions Temperature overshoot
Open-circuit principle
Closed-circuit principle
Digital evaluation units: After the temperature has reached the set threshold value 1, output relay K1 changes its switching state appropriately as soon as the set time t has elapsed (K2 responds to 2 similarly). Analog evaluation units: When the set threshold value is reached, output relay K1 changes its switching status. For devices with 2 threshold values, relay K2 responds to the second set threshold value. As soon as the temperature reaches the respective set hysteresis value, the relays return immediately to the original state. A time delay cannot be set (t = 0).
Temperature undershoot
Open-circuit principle Closed-circuit principle
Window monitoring
Open-circuit principle Closed-circuit principle
When the temperature has reached the upper threshold 1 and the set delay time t has elapsed, the output relay K1 changes its switching state. As soon as the temperature reaches the respective set hysteresis value, the relay returns immediately to the original state. In the same manner, K2 responds to the lower threshold value of 2.
Principle of operation with memory function, based on the example of temperature overshoot using the closed-circuit principle When the temperature has reached the set threshold 1 and the set delay time t has elapsed, the output relay K1 changes its switching state (similarly, K2 responds to 2.) The relays will only return to the original state when the temperature has fallen below the respective set hysteresis value and the connection Y1-Y2 was briefly interrupted.
11/9
SIMIREL
3RS11 00 3RS11 01
General equipment designations A1, A2, A3 Rated control supply voltage terminals K1, K2, K3 Output relays Equipment designations for: 3RS1000, 3RS1010, 3RS1101, 3RS1100, 3RS1110, 3RS1111, 3RS1020, 3RS1021, 3RS1030, 3RS1031 LED: "Voltage applied" LED: "Relay 1 switched" LED: "Relay 2 switched" T1 to T3 = Terminals for connection of resistance sensor T+ / T- = Terminals for connection of thermoelements
1 = 2 =
3RS10 20 3RS10 30
1 = 2 = Ready =
T1 to T3 = Terminals for connection of resistance sensor T+ / T- = Terminals for connection of thermoelements Y1/Y2 Terminals for memory jumper JBiq Equipment designations for: 3RS1041, 3RS2041
3RS10 40 3RS20 40
3RS10 41 3RS20 41
1 = 2 = Ready =
1T1 to 1T3 = Terminals for connection of resistance sensor 1 2T1 to 2T3 = Terminals for connection of resistance sensor 2 3T1 to 3T3 = Terminals for connection of resistance sensor 3 Y1/Y2 Terminals for memory jumper
Important! When resistance sensors are used in a 2-wire connection, a jumper must be installed between T2 and T3.
3RS11 40 3RS21 40
11/10
SIMIREL
Dimension drawings Temperature monitoring relay
3RS10/3RS11 . . with 22.5 mm enclosure
11/11
SIMIREL
control circuit and sensor circuit in the case of AC and UC control supply voltages (for DC control supply voltage: no electrical isolation). For units with a TEST button, the function of the device can be checked by pressing the button for longer than 2 s. Safe electrical isolation All electrical circuits (outputs, control circuit, sensor and Reset circuit) of the 3RN10131BW10 multifunction tripping unit (wide input voltage range, monostable output relay and screw terminals) are safely isolated from each other up to a rated voltage of 300 V acc. to DIN VDE 0100 Part 410/ DIN VDE 0106/DIN VDE 0160.
Device resets
3RN10 22 tripping unit "Warning and switch-off" Two sensor circuits can be connected to one 3RN10 22 tripping unit and act on one output relay with 1 NO for warning and 1 SPDT for switch-off. The functions "Warning" and "Switch-off" are implemented by means of temperature sensors with different rated response temperatures TNF. Activation of the sensor circuit for "Warning" is indicated by a yellow LED and for "Switch-off" by a red LED. The sensor circuits have different reset responses: "Warning" (terminals 2T1, T2) automatic RESET only "Switch-off" (terminals 1T1, T2); changeover from manual RESET to automatic RESET by bridging terminals Y1 and Y2. A remote RESET function is implemented by connecting an external pushbutton with an NO contact. 3RN10 62 tripping unit "Multiple motor protection" Up to six sensor circuits can be connected to one 3RN10 62 tripping unit which all act on one output relay. Simultaneous protection of several motors (up to 6) is an advantage in the case of group drives (e.g. if a motor is overloaded, all motors in the group can be switched off). Apart from the red LED "TRIPPED" that indicates the switching status of the tripping unit, a LED is assigned to each sensor circuit that is lit when the associated sensor circuit trips. Sensor circuits that are not required must be short circuited.
The reset response of the 3RN10 62 tripping units can be changed from manual RESET to automatic RESET by bridging terminals Y1 and Y2. A remote RESET function is implemented by connecting an external pushbutton with an NO contact.
3RN10 12-2C...
LED to indicate "Relay switched" LED to indicate "Voltage applied" Test and Reset buttons
Application The 3RN1 thermistor motor protection tripping units are thermal protective devices that can be used in conjunction with PTC thermistors Type A for the temperature monitoring of electrical drives, transformer windings, oils, bearings, air, etc. Principle of operation The 3RN1 tripping units operate according to the closed-circuit principle and therefore monitor themselves for a wire-break. A temporary voltage drop of less than 200 ms (for devices with a wide input voltage range < 100 ms) will not cause a change in status of the auxiliary contacts. The 3RN10 13 multifunction tripping unit also features short-circuit detection in the sensor circuit. The unit will trip if a short circuit arises in the sensor circuit (resistance in sensor circuit <20 ). The tripping units feature electrical isolation between the
Notes .For DC-activated tripping units, electrical isolation must be provided using a battery system or a safety isolating transformer to DIN VDE 0551. .When tripping units with an automatic RESET function are used in EEx e zones, the control circuit must be designed to ensure that the monitored machine cannot restart autonomously. .In the case of tripping units without short-circuit detection, the sensor circuit must be measured with a suitable measuring instrument during commissioning. For resistance < 50 Ohm, the sensor circuit must be checked for a short circuit. .When the 3RN10 00 unit (no Ready LED) and the 3RN10 13-1BW01 unit (no change in switching status for the auxiliary contacts on control voltage failure) are used to protect EEx e motors, separate monitoring of the control voltage is recommended.
11/12
SIMIREL
Thermistor motor protection relays for PTC thermistors (type A PTCs) All of the devices with the exception of 24 V AC/DC have electrical isolation Version Reset Contacts Control supply voltage Order No.. List Price $
Compact evaluation units, 22.5 mm wide, monostable, closed-circuit current principle, 1 LED Terminal A1 is connected to the common of the changeover contact Auto 1 CO 24 V AC/DC 110 V AC 3RN1000- AB00 134.00 3RN1000- AG00 134.00 3RN1000- AM00 134.00 3RN1010- CB00 169.00 3RN1010- CG00 169.00 3RN1010- CM00 169.00 3RN1010- CW00 223.00 3RN1010- BB00 3RN1010- BG00 3RN1010- BM00 3RN1010- GB00 3RN10113RN10113RN10113RN10113RN10113RN10113RN10123RN10123RN10123RN1012CB00 CK00 BB00 BG00 BM00 GB00 CB00 CK00 BB00 BG00 75.00 75.00 75.00 75.00 214.00 214.00 240.00 75.00 75.00 100.00 304.00 304.00 304.00 125.00
230 V AC Standard evaluation units, 22.5 mm wide, monostable, closed-circuit current principle, 2 LEDs Auto 1 NO + 1 NC 24 V AC/DC 110 V AC 230 V AC 24240 V AC/DC 2 CO 24 V AC/DC 110 V AC 230 V AC 230 V 2 CO hard-gold-plated Manual/ remote3) Short-circuits are detected in the sensor circuit Manual/ remote3) 1 NO + 1 NC 2 CO 24 V AC/DC 24 V AC/DC 110/230 V AC 24 V AC/DC 110 V AC 230 V AC 24 V AC/DC 24 V AC/DC 110/230 V AC 24 V AC/DC 110 V AC 230 V AC 2 CO hard-gold-plated Holding on supply failure2), short-circuits and wire breakage in the sensor circuit are detected and displayed, wide-range voltage with screw terminals with protective separation1) Manual/auto/ 2 CO remote 2 CO hard-gold-plated 24 V AC/DC 24 V AC/DC 24240 V AC/DC 24240 V AC/DC
2 CO hard-gold-plated Manual/auto/ 1 N + 1 NC remote Manual/auto/ 2 CO Holding on supply failure2), short-circuits are detected in the sensor circuit remote
3RN1012- BM00 125.00 3RN1012- GB00 125.00 3RN1013- BB00 3RN1013-1BW10 3RN1013-2BW00 3RN1013-1GW10 3RN1013-2GW00 392.00 448.00 473.00 150.00 150.00
Evaluation units for 2 sensor circuits, alarm and trip, 22.5 mm wide, monostable, closed-circuit current principle, 3 LEDs Test/reset button, holding on supply failure2); the evaluation circuit for alarm uses an NO contact in the open-circuit principle Manual/auto/ 1 NO + 1 NC remote 24240 V AC/DC 3RN1022- DW00 609.00
Evaluation units for 6 sensor circuits, multi-motor protection, 45 mm wide, monostable, closed-circuit current principle, 8 LEDs Test/reset button, holding on supply failure2) Bistable evaluation units, 22.5 mm wide Test/reset button, holding on supply failure2), short-circuits and wire breakage in the sensor circuit are detected and displayed, bistable version, not tripped when the control supply voltage fails Manual/auto/ 2 CO remote 24240 V AC/DC 3RN1013BW01 564.00 Manual/auto/ 1 NO + 1 NC remote 24240 V AC/DC 3RN1062- CW00 550.00
1) Protective separation up to 300 V according to DIN/VDE 0106 2) Information regarding the holding on supply failure, refer to Catalog LV 1, chapter 7 3) Reset using the reset button or by interrupting the control supply voltage
Screw terminal
11/13
SIMIREL
for type
Order No.
Weight approx. kg
Packing
Packs 1
Standard devices
3RN10 10
3RN10 11
Yes No Yes2) Yes Yes Yes3) No No Yes 0.145 0.145 0.145 0.145 No 0.260 Yes Yes
Tripping unit
Rated insulation voltage Ui (pollution degree 3) Permissible ambient temperature Permissible storage temperature EMC tests Class acc. to DIN 19 251, DIN V0801 Degree of protection acc. to DIN 40 050 Conductor cross-section Terminal screws Solid Finely stranded with end sleeves AWG conductor connections, solid or stranded Tightening torque Cage Clamp terminals Solid Finely stranded with end sleeves Finely stranded, without end sleeves AWG wires, solid or stranded Corresponding opening tool mm2 mm2 AWG Nm mm2 mm2 mm2 AWG M 3.5 (for standard screwdriver Size 2 and Pozidriv 2) 1 x (0.5 to 4) / 2 x (0.5 to 2.5) 1 x (0.5 to 2.5) / 2 x (0.5 to 1.5) 2 x (20 to 14) 0.8 to 1.2 2 x (0.25 to 1.5) 2 x (0.25 to 1) 2 x (0.25 to 1.5) 2 x (24 to 16) 8WA2 803 4) V C
Sensor circuit
Circuit burden at RF Tripping temperature (specified by sensor) Coupling time (due to mounting of sensor) Total cold resistance RF (per sensor loop) Triggering value Return value Triggering tolerance 1) 2) 3) 4) 1.5 k 1.5 k mW V C s k k k C 5 2 60 to 180 approx. 5 s 1.5 3.4 to 3.8 1.5 to 1.65 6 Voltage in sensor circuit at RF
See page 11/12. Remote RESET due to interruption of the control voltage. Indication of wire-break only for monostable designs (3RN10 13- . . . . 0). See page 11/22.
11/14
SIMIREL
Technical data
Standard devices
3RN10 10
3RN10 11
Control circuit
Rated control supply voltage Us Operating range AC AC/DC DC Rated power AC AC/DC DC W W W A <2 <2 <2 5 0.85 to 1.1 x Us 0.85 to 1.1 x Us 0.85 to 1.2 x Us
Auxiliary circuit
Conventional free-air thermal current Ith Rated operational current Ie AC-15 240 V DC-13 24 V Short-circuit protection acc. to Alpha/Lovag Utilisation category gL/gG A 50/60 Hz V V 300 300 R 300/B 300 3RN10 13 1BW10 6 A A 3 1 2 1 2) 1 2
3RN10 13-...0
3RN10 22 only
1) See selection and ordering data, page 11/13 2) For 3RN10 13- . BW01 (bistable output relay) 2 A.
11/15
SIMIREL
Cable routing The measuring circuit cables must be routed as separate control cables. It is not permitted to use cores of the motor supply cable or other main supply cables. If extreme inductive or capacitive interference is expected to be generated by heavy current cables routed in parallel, shielded control cables must be used. Maximum cable length for sensor circuit:
Cross-section For tripping units 3RN10 00 3RN10 13 3RN10 10 3RN10 11 3RN10 12 3RN10 22 3RN10 62 mm2 2.5 1.5 0.5 m 2 x 2800 2 x 1500 2 x 500 m 2) 2 x 250 2 x 150 2 x 50
PTC temperature sensor With the tripping units, temperature sensors with characteristics according to DIN VDE 0660 Part 303, DIN 44 081 and DIN 44 082 (e. g. EPCOS AG single and triple sensors, Type No. B 591 .. or B 593 ..) can be used. The number of temperature sensors that can be connected in series is dependent on the total cold resistance. The total cold resistance must not exceed 1.5 k. Resistance/temperature characteristic of a PTC thermistor with a characteristic (Type A) according to DIN VDE 0660 Part 303
Installation The 3RN1 tripping units are suitable for snapping on to 35 mm standard mounting rails acc. to DIN EN 50 022 or for screw mounting using adapters. Any mounting position is possible. Specifications The tripping units are suitable for use in any climate and safe from touch to DIN VDE 0106 Part 100. The 3RN1 tripping units meet the requirements of the basic technical standard EN 50 081-2; IEC 61000-6-2 "Electromagnetic compatibility of I&C equipment in industrial process engineering" and DIN VDE 0660 Parts 302 and 303, IEC 60 034-11-2 Section 1 and 2 "Built-in thermal protection of rotating electrical machines, thermal detectors and tripping units" and "PTC thermistors and tripping units". The terminal designations of the auxiliary contacts complies with EN 50 005.
Protecting the windings of three-phase transformers To protect the windings of threephase dry transformers with PTC thermistors in cases where the operating voltage of the thermistor motor protection tripping unit must be tapped from the mains voltage, a 3RN10 22 thermistor protection unit for warning and tripping and, for example, a 3RP15 time relay can be used. The auxiliary contactor K4 operates on the shunt release of the high-voltage circuit-breaker. Working principle for transformer protection When voltage is applied to the line-side of the transformer, the voltage on the secondary side rises to the final value within 1.5 s. The 3RN1 tripping unit does not trip until 0.8 x Us, so as long as the operating voltage is applied to the closed contacts 95-98 on contactor K4, it would cause breaking of the
circuit-breaker via its shunt release. In order to prevent this, the voltage is only applied to terminals 07 and 95 once the 3RN1 tripping units have definately picked up and the auxiliary switches have switched to the "Ready" position. The K3 and K4 contactors are not controlled until the respective rated response temperature TNF of the sensor is exceeded. The tripping unit should be switched to "Automatic RESET" (jumper must be placed between terminals Y1 and Y2). This ensures that the 3RN1 tripping unit is reset when the transformer is reconnected following tripping. The time-delay relay is set to a delay time of 1.5 s.
F1 Fuse F2 3RN10 22 K3, K4 Auxiliary contactors (e. g. 3RH1) K5 Time relay (e. g. 3RP15) H5 Indicator light Protective circuit ready
1) Electrical isolation exists with devices with a wide input voltage range of 24 to 240 V UC even in the case of DC operation. 2) Devices with short-circuit detection in the sensor circuit. Up to this maximum cable length, a short-circuit in the sensor circuit will be detected. When short-circuit detection is not required, the cable lengths shown on the left can be used.
11/16
SIMIREL
Circuit diagrams Connection diagrams
Position of the output relay "Ready, not tripped" 3RN10 00 3 R N1 0 1 0 General equipment designations A1, A2 Control voltage terminals N Amplifier T/R TEST/RESET button Y1, Y2 Terminals for remote RESET (jumpered = Auto RESET) The double-headed arrow indicates an operating state of the contact element that deviates from the standard presentation according to DIN 40 900, Part 7 (In this case: Position of the contact elements when the control voltage is applied to terminals A1 and A2) Equipment designations for 3RN10 H1 LED "READY" H2 LED "TRIPPED" K Output relay T1, T2 Terminals of the sensor loop 3RN10 13-. . . . 1 (bistable)
3RN10 111)
3RN10 121)
3RN10 13-. . . . 0
3RN10 22
Equipment designations for 3RN10 22 H1 LED "READY" H2 LED "TRIPPED" H3 LED "ALARM" K1, K2 Output relay 1T1 and T2 Terminals of the sensor 2T1 and T2 loop
3RN10 62
Equipment designations for 3RN10 62 H1 to H6 LEDs for tripped sensor loops H7 LED "READY" H8 LED "TRIPPED" K Output relay 1T1, 1T2 Terminals for to 1st sensor loop 6T1, 6T2 Terminals for 6th sensor loop
1) For dual voltage devices AC 230 V/110 V (3RN10 11- . CK00 and 3RN10 12- . CK00): A1 and A2: AC 230 V, A3 and A2: AC 110 V.
11/17
SIMIREL
General equipment designations A1, A2 F4 N S0 S1 S2 S3 T/R Y1, Y2 Control voltage terminals1) Back-up fuse Amplifier OFF pushbutton ON pushbutton Main switch Remote RESET button TEST/RESET button Terminals for remote RESET (jumpered = Auto RESET) The double-headed arrow indicates an operating state of the contact element that deviates from the standard presentation according to DIN 40 900, Part 7 (In this case: Position of the contact elements when the control voltage is applied to terminals A1 and A2)
Switching off a three-phase motor via a Switching off a three-phase motor via a Switching off a three-phase motor via a contactor, pushbutton control contactor, maintained-contact control contactor, pushbutton control The contact elements are shown The contact elements are shown The contact elements are shown for voltage applied to terminals A1 for voltage applied to terminals A1 for voltage applied to terminals A1 and A2 of the tripping unit and A2 of the tripping unit and A2 of the tripping unit
Equipment designations for 3RN10 H1 H2 H3 K K1 1T, T2 LED "READY" LED "TRIPPED" Signalling light Output relay Contactor Terminals of the sensor loop
3RN10 13-. . . . 0 tripping unit Switching off a three-phase motor via a contactor, pushbutton control The contact elements are shown for voltage applied to terminals A1 and A2 of the tripping unit
3RN10 22 tripping unit (warning + switch-off) Switching off a three-phase motor via a contactor, warning via output relay, pushbutton control The contact elements are shown for voltage applied to terminals A1 and A2 of the tripping unit
Equipment designations for 3RN10 22 H1 LED "READY" H2 LED "TRIPPED" H3 LED "ALARM" H4 Signalling light H5 Signalling light "ALARM" K1, K2 Output relay K3 Contactor 1T1 and T2 Terminals of the sensor 2T1 and T2 loop
3RN10 62 tripping unit (multiple motor protection) Switching off 6 three-phase motors via contactors, pushbutton control The contact elements are shown for voltage applied to terminals A1 and A2 of the tripping unit Equipment designations for 3RN10 62 H1 to H6 H7 H8 H9 K K6 1T1, 1T2 to 6T1, 6T2 LEDs for tripped sensor loops LED "READY" LED "TRIPPED" Signalling light Output relay Contactor Terminals for 1st sensor loop Terminals for 6th sensor loop
1) For dual voltage devices AC 230 V/110 V (3RN10 11- . CK00 and 3RN10 12- . CK00): A1 and A2: AC 230 V, A3 and A2: AC 110 V.
11/18
SIMIREL
Dimension drawings
3RN10 00
3 R N1 0 1 0
3 R N1 0 6 2
11/19
SIMIREL
Sealable cap
Operating time adjuster Display window for selected time setting range
Function Standards, specifications The time relays comply with: IEC 60 721-3-3 "Environmental conditions" IEC 61 812-1/DIN VDE 0435 Part 2021 "Electrical relays, time relays" IEC 61 000-6-2/EN 50 081-1 "Electromagnetic capability" IEC 60 947-5-1; DIN VDE 0660 Part 200 "Low-voltage switchgear and controlgear" Application Time relays are used in control, starting protective and control circuits for all switching operations involving time delays.
They guarantee a high level of functionality and a high repeat accuracy of timer settings. Housing design All time relays are suitable for snap-on mounting onto 35 mm standard mounting rails according to EN 50 022 or for screw fixing. Configuration Changing the time setting ranges and the functions will only be effective when being carried out in de-energised state Start input B1 or B3 must only be triggered when the supply voltage is applied
The same potential must be applied to A1 and B1, or A3 and B3 With the two-voltage version, only one voltage range must be connected The activation of loads parallel to the start input is not permissible when using AC control voltage (see adjacent diagrams) Surge suppression is integrated in the time relay. This prevents supply voltage spikes occurring when the relay switches. No damping mechanisms have been integrated for the contacts The 3RP15 05-.R should not be used near heat sources > 60 C
11/20
SIMIREL
3RP1/3RP2 Time relays electronic 3RP20 Time relays in the SIRIUS design, 45 mm Function 8 functions 8 functions On delay On delay 16 functions Contact elements 1 CO changeover contact) 1 CO 1 CO 1 CO 2 CO Time range 0.05 s100 h 0.05 s100 h 0.05 s100 h 0.05 s100 h 0.05 s100 h Control supply voltage AC DC 24 100127 V AC AC DC 24 200240 V AC AC DC 24 100127 V AC AC DC 24 200240 V AC 24240 V AC DC Order No. 3RP20053RP20053RP20253RP20253RP2005List Price $ 110.00
3RP1/3RP2 Time relays electronic 3RP15 Time relays in an industrial housing, 22.5 mm 8 functions 8 functions 8 functions 8 functions 8 functions 16 functions 16 functions 16 functions 16 functions On delay On delay On delay On delay On delay On delay On delay On delay On delay On delay On delay On delay On delay, 2-wire On delay, 2-wire Off delay with auxiliary voltage Off delay with auxiliary voltage Off delay with auxiliary voltage Off delay with auxiliary voltage Off delay with auxiliary voltage Off delay with auxiliary voltage Off delay without auxiliary voltage Off delay without auxiliary voltage Off delay without auxiliary voltage Off delay without auxiliary voltage Off delay without auxiliary voltage Off delay without auxiliary voltage Clock-pulse relay Clock-pulse relay Clock-pulse relay Star delta with run-on function Star delta with run-on function Star delta Star delta Star delta Star delta 1 CO changeover contact) 1 CO 1 CO 1 CO 2 CO 2 CO 2 CO 2 CO 2 CO 1 CO 1 CO 1 CO 1 CO 1 CO 1 CO 1 CO 1 CO 2 CO 2 CO 2 CO 2 CO 1 NO contact, solid-state 1 NO contact, solid-state 1 CO 1 CO 1 CO 1 CO 1 CO 1 CO 1 CO 1 CO 1 CO 2 CO 2 CO 2 CO 1 CO 1 CO 1 CO 3 x 1 NO contact 3 x 1 NO contact 1 NO contact + 1 NO contact 1 NO contact + 1 NO contact 1 NO contact + 1 NO contact 1 NO contact + 1 NO contact 0.05 s100 h 12 V DC 0.05 s100 h AC DC 24 100127 V AC 0.05 s100 h AC DC 24 200240 V AC 0.05 s100 h 24240 V AC DC 0.05 s100 h 24240 V AC DC 0.05 s100 h AC DC 24 100127 V AC 0.05 s100 h AC DC 24 200240 V AC 0.05 s100 h 24240 V AC DC 0.05 s100 h 400440 V AC 0.510 s AC DC 24 100127 V AC 0.510 s AC DC 24 200240 V AC 1.530 s AC DC 24 100127 V AC 1.530 s AC DC 24 200240 V AC 5100 s AC DC 24 100127 V AC 5100 s AC DC 24 200240 V AC 0.05 s100 h AC DC 24 100127 V AC 0.05 s100 h AC DC 24 200240 V AC 0.05 s100 h 4248 60 V AC DC 0.05 s100 h AC DC 24 100127 V AC 0.05 s100 h AC DC 24 200240 V AC 0.05 s100 h 24240 V AC DC 0.05240 s 2466 V AC DC 0.05240 s 90240 V AC DC 0.510 s AC DC 24 100127 V AC 0.510 s AC DC 24 200240 V AC 1.530 s AC DC 24 100127 V AC 1.530 s AC DC 24 200240 V AC 5100 s AC DC 24 100127 V AC 5100 s AC DC 24 200240 V AC 0.05100 s 24 V AC DC 0.05100 s 100127 V AC DC 0.05100 s 200240 V AC DC 0.05100 s 24 V AC DC 0.05100 s 100127 V AC DC 0.05100 s 200240 V AC DC 0.05 s100 h 4248 60 V AC DC 0.05 s100 h AC DC 24 100127 V AC 0.05 s100 h AC DC 24 200240 V AC 120 s, 30600 s ru n-on) AC DC 24 100127 V AC 120 s, 30600 s ru n-on) AC DC 24 200240 V AC 120 s AC DC 24 100127 V AC 120 s AC DC 24 200240 V AC 360 s AC DC 24 100127 V AC 360 s AC DC 24 200240 V AC 3RP15053RP15053RP15053RP15053RP150595.00 AA40 AQ30 95.00 AP30 95.00 95.00 AW30 RW301) 135.00 110.00 110.00 135.00 135.00 50.00 50.00 50.00 50.00 50.00 50.00 65.00 65.00 70.00 70.00 70.00 70.00 50.00 50.00 85.00 85.00 85.00 85.00 85.00 85.00 110.00 110.00 110.00 125.00 125.00 125.00 120.00 120.00 120.00 132.00 132.00 65.00 65.00 65.00 65.00
3RP1505- BQ30 3RP1505- BP30 3RP1505- BW30 3RP1505- 1BT202) 3RP1511- AQ30 3RP1511- AP30 3RP1512- AQ30 3RP1512- AP30 3RP1513- AQ30 3RP1513- AP30 3RP1525- AQ30 3RP1525- AP30 3RP1525- BR30 3RP1525- BQ30 3RP1525- BP30 3RP1525- BW30 3RP1527- EC30 3RP1527- EM30 3RP1531- AQ30 3RP1531- AP30 3RP1532- AQ30 3RP1532- AP30 3RP1533- AQ30 3RP1533- AP30 3RP1540- AB30 3RP1540- AJ30 3RP1540- AN30 3RP1540- BB30 3RP1540- BJ30 3RP1540- BN30 3RP1555- AR30 3RP1555- AQ30 3RP1555- AP30 3RP1560- SQ30 3RP1560- SP30 3RP1574- NQ30 3RP1574- NP30 3RP1576- NQ30 3RP1576- NP30 1
1) Positively-driven and hard-gold-plated relay contacts 2) This device is only available with screw terminals
Screw terminal
11/21
SIMIREL
Function
Order No.
List Price $ (Order No. and price for one packing unit)
Weight approx.
Pack.
kg
units
Label set
Accessories for 3RP15 05 (not included in the scope of supply). The label set offers the possibility of labeling time relays with the set function in English and German. Complete set with 8 functions ON-delay OFF-delay with auxiliary voltage ON-delay and OFF-delay with auxiliary voltage flashing, starting with interval passing make contact passing break contact with auxiliary voltage pulse shaping with auxiliary voltage additive ON-delay with auxiliary voltage Complete set with 16 functions ON-delay OFF-delay with auxiliary voltage ON-delay and OFF-delay with auxiliary voltage flashing, starting with interval passing make contact passing break contact with auxiliary voltage pulse shaping with auxiliary voltage A B C D E F G H A B C D E F G for relays with 2 SPDT for relays with 1 SPDT and 3RP15 05 .RW30
PG 101
3RP19 01-0A
21.00
0.020
3RP19 01-0B
29.00
0.030
10
additive ON-delay with auxiliary voltage H and instantaneous contact ON-delay and instantaneous contact OFF-delay with auxiliary voltage and instantaneous contact ON-delay and OFF-delay with auxiliary voltage and instantaneous contact flashing, starting with interval, and instantaneous contact passing make contact and instantaneous contact passing break contact with auxiliary voltage and instantaneous contact A B C D E F
pulse shaping with auxiliary voltage and G instantaneous contact star-delta function *
PG 101
3RP19 02 18.00 0.020 5
3RP19 03
1.40
0.020
10
P G 102
8WA2 803 5.40 0.012 0.029 1
0.022
11/22
SIMIREL
Selection and ordering data
Electronic time relay for flush-mounting in panels 48 x 48; panel cutout 45 x 45 mm; 11-pin connector
Design Time setting range t Rated control supply voltage AC 50-60 Hz V DC V 24 PG 101 7PV33 48-2AX34 115.00 kg 0.110 Order No. List Price $ Weight approx.
Accessories
Design Function Order No. List Price $ Weight approx. kg
Plug-in base
Plug-in base 7PX9 921 11-pin plug-in base with rear connection 7PX9 921 12.00 0.080
LZX: MR78750
LZX:MT78750
6.20
0.056
11/23
SIMIREL
Rated insulation voltage Pollution degree 3 Overvoltage category III acc. to DIN VDE 0110 Working range of excitation 1) Rated power Power consumption at 230 V AC, 50 Hz Rated operational current Ie AC-15 at AC 230 V, 50 Hz AC-14; DC-13 DC-13 at 24 V DC-13 at 48 V DC-13 at 60 V DC-13 at 110 V DC-13 at 230 V Required DIAZED fuse 4) Utilisation category gL/gG
AC V
0.85 to 1.1 x Us for AC; 0.8 to 1.25 x Us for DC 0.95 to 1.05 x rated frequency W VA A 1 4 3 3) 1 0.45 0.35 0.2 0.1 4 2500 5000 150 5) 35 35 6) 200 7) 300 5 3.5 10 (up to 10 ms) typical 5 % v 1 % operating cycles in operation when stored C C 30 x 106 25 to + 60 40 to + 85 cover IP 40 terminals IP 20 Main conductors, auxiliary conductors solid mm2 2x (0.5 to1.5) 2x (0.75 to 4) 2x (0.5 to 2.5) 2x (18 to 14) M3 Nm mm2 0.8 to 1.2 2 x (0.25 to 2.5) 2x (0.25 to 1) 2x (0.25to1.5) 2x (24 to 14) 2 x (0.25 ... 1.5) 1 x (0.5 ... 4) 2 x (0.5 ... 2.5) 1 x (0.5 ... 2.5) 2 x (0.5 ... 1.5) solid or stranded AWG conductors terminal screw tightening torque AWG 2 x (20 ... 14) M 3.5 100 x 106 150 2 6 2 6 2 2 2) 2 6 2 6 1 1 0.01 to 0.6 5000 5000 50
A 1/h 1/h ms ms mA V A
Operating frequency when loaded with Ie AC 230 V when loaded with 3RT10 16 contactor, AC 230 V Recovery time Minimum ON period Off-state current with non-conducting output Voltage drop with conducting output Short-time loading capacity Setting accuracy referred to upper limit of scale Repeat accuracy Mechanical endurance Permissible ambient temperature Degree of protection acc. to EN 60 529 Conductor cross-sections Screw connection (to connect 1 or 2 conductors for standard screwdriver size 2 and Pozidriv 2)
mm2
Cage Clamp connection (1 or 2 wire connection; for 22.5 mm time-delay relay use screwdriver with blade width 3 mm or 8WA2 803 opening tool 8)
solid finely stranded with end sleeve without end sleeve solid or stranded AWG conductors
2 x (0.25 ... 1) 2 x (0.25 ... 1.5) 2 x (24 ... 16) 7) For correct operation, observe minimum ON period. 8) Opening tool for Cage Clamp connections, see page 11/22.
1) If nothing else is stated. 2) Maximum inrush current 1 A/100 ms. 3) For 3RP15 05-.R: NC contact Ie = 1 A 4) Without any welds acc. to IEC 60 947-5-1.
5) With 3RP15 05-.BW30/ .AW30/ .RW30 and 3RP15 25-.BW30, 10 to 250 ms, voltagedependent. 6) Minimum ON period with 3RP15 00-. BW30, 150 ms until instantaneous contact has switched.
11/24
SIMIREL
Permissible mounting position Shock resistance Half sine acc. to IEC 60 068-2-27 Vibration performance acc. to IEC 60 068-2-6 EMC tests acc. to basic specification g/ms
any 15/11
Type Rated insulation voltage Overvoltage category C acc. to DIN VDE 0110 Working range of excitation Rated power Power consumption at AC 230 V, 50 Hz Rated operational current Ie AC-1 at AC 230 V, 50 Hz Operating frequency when loaded with Ie, AC 230 V when loaded with 3RT10 16 contactor, AC 230 V Recovery time Minimum ON period Setting accuracy with reference to upper limit of scale Repeat accuracy Mechanical endurance Permissible ambient temperature Degree of protection acc. to EN 60 529 Permissible mounting position operating cycles in operation when stored C C W VA A 1/h 1/h ms ms AC V
7PV33 48 250 + 10 ... 15 % 1 11 8 600 50 50 0.03 %, 10 ms 0.03 %, 10 ms 5 x 106 10 ... +60 30 ... +70 IP 65 any
7PV41 48
7PV43 48
11/25
SIMIREL
Function diagram
3RP20 time relays and 7PX9 coding plug 3RP20 05 3RP20 25 7PX9 904
3RP15 05-.A
3RP19 01-0A
3RP15 25
3RP15 27
3RP15 40
3RP15 55
3RP15 1.
3RP15 3.
3RP15 7.
1 changeover contact
ON-delay 7 7 7 A 7 7 7
> 35 ms
NSB00859
Code letter
B 1)
7 3)
15/18 15/16 t
NSB00860
> 200 ms
A1/A2
NSB00861
ON-delay and OFF-delay with auxiliary voltage (t = ton = toff) flashing, starting with interval (pulse/interval 1:1) clock-pulse, starting with interval (dead interval, pulse time and time setting ranges each separately adjustable)
A1/A2 B1/A2
C 1)
NSB00862
7 2)
15/18 15/16 t
NSB00864
A1/A2
7 4)
> 35 ms
NSB00865
F 1)
t
NSB00866
pulse shaping with auxiliary voltage (pulse generation at the output does not depend on duration of energising) additive ON-delay with auxiliary voltage
>35 ms
NSB00867
G 1)
7 5)
t1
t2
t3
NSB00868
H 1)
11/26
7PV33
SIMIREL
Functions Function table
Function
Function diagram
3RP20 time relays and 7PX9 coding plug 3RP20 05-.B 3RP20 25 7PX9 904
3RP19 01-0B
3RP15 05-.B
3RP15 05-.R
3RP19 01-0A
3RP15 25
3RP15 27
3RP15 40
3RP15 55
3RP15 3.
3RP15 60
3RP15 1.
2 changeover contacts
ON-delay
A1/A2 15/18 15/16 25/28 25/26
7
NSB00871
t
A1/A2 15/18 15/16 t 21/24 21/22
NSB00872
A!
A1/A2
> 35 ms
B1/A2 15/18 15/16 25/28 25/26 t
B 1)
NSB00873
B ! 1)
> 200 ms
A1/A2 15/18 15/16 25/28 25/26 t A1/A2 B1/A2 15/18 15/16 25/28 25/26 t t
NSB00877 NSB00876
NSB00875
C 1)
ON-delay and OFF-delay with auxiliary voltage and instantaneous switching (t = ton = toff)
C ! 1)
NSB00878
flashing, starting with interval (pulse/interval 1:1) and instantaneous contact passing make contact
NSB00879
A1/A2
D!
NSB00880
A1/A2
1) Note on function with start contact: another control signal at terminal B after the operating time has started resets the operating time to zero. This does not apply to G, G! and H, H!, that cannot be retriggered.
NSB00881
E!
11/27
3RP15 7.
Code letter
SIMIREL
Function diagram
3RP20 time 3RP15 time relays relays and 7PX9 and 3RP19 label set coding plug 3RP19 01-0B 3RP20 05-.B 3RP19 01-0A 3RP15 05-.B 3RP15 05-.R 3RP20 25 3RP15 25 3RP15 27 3RP15 40 7PX9 904 3RP15 55 3RP15 3. 3RP15 60 7 3RP15 1. 3RP15 7. 7
2 changeover contacts
35ms B1/A2 15/18 15/16 25/28 25/26 t
NSB00882
A1/A2
> 35ms
B1/A2 15/18 15/16 t 21/24 21/22
NSB00883
A1/A2
F ! 1)
pulse shaping with auxiliary voltage (pulse generation at the output does not depend on duration of energising)
NSB00884
A1/A2
pulse shaping with auxiliary voltage and instantaneous contact (pulse generation at the output does not depend on duration of energising)
>35ms
B1/A2 15/18 15/16 t 21/24 21/22
NSB00885
A1/A2
G ! 1)
H ! 1)
star-delta function *
A1/A2
1) Note on function with start contact: another control signal at terminal B after the operating time has started resets the operating time to zero. This does not apply to G, G! and H, H!, that cannot be retriggered. 2) For function diagrams showing the various possibilities of operation of the 3RP15 60-1S.30 see page 11/29.
11/28
NSB00888
star-delta function
A1/A2
Code letter F 1) G 1) H 1) *
SIMIREL
Functions Function table
Operation 1:
Start contact B./A2 is opened when supply voltage A./A2 is applied. The supply voltage is applied to A./A2 and there is no control signal on B./A2. The * time rundown is started in this manner. By applying the control signal to B./A2, the idling time (overtravel time) is started. When the set time tIdling (30 to 600 s) has elapsed, the output relays (17/16 and 17/28) are reset. If the control signal on B./A2 is switched off (minimum duration of switch-off 270 ms), a new time rundown starts. Remarks: When the supply voltage is switched on, a response time (deadtime) of 400 ms must be allowed for before contacts 17/18 and 17/16 close.
Operation 2
Operation 2:
Start contact B./A2 is closed when supply voltage A./A2 is applied. If the control signal is applied to B./A2 when the supply voltage A./A2 is applied, no time rundown will take place. The time rundown will only be started when the control signal on B./A2 is switched off.
Operation 3:
Start contact B./A2 closes while star time is running. During the wye time, if the control signal is applied again on B./A2, the idling time starts and the time rundown will be terminated normally.
Operation 3
Operation 4:
Start contact B./A2 opens while the delta time is running and the control signal is applied again. If the control signal is applied again on B./A2 during the delta time and switched off again even before the idling time has elapsed, the idling time (follow-on time) will be reset to zero. If the control signal is applied to B./A2 again, the idling time is restarted.
Operation 4
For every operation: The pressure switch controls the time rundown via B./A2.
11/29
SIMIREL
ON-delay
Flashing
3RP15 05-.A
3RP15 27
U = AC/DC 2466 V AC/DC 90240 V
Clock-pulse relay
3RP15 05-.B
ON-delay, 3RP15 25-1B, also for 42 to 48/60 V AC/DC (see page 11/31 3RP15 25-1BR30) 3RP15 05-.B
Flashing
3RP15 05-.B
3RP15 05-.B
3RP15 05-.B
11/30
SIMIREL
Circuit diagrams
ON-delay and OFF-delay with auxiliary voltage and instantaneous contact 3RP15 05-.B
3RP15 05-.B
3RP15 05-.B
Passing break contact with auxiliary voltage and instantaneous contact 3RP15 40-.B
Pulse shaping with auxiliary voltage and instantaneous contact 3RP15 05-.BW30 / -1BT20 /-.RW30 3R920 05-.B
Star-delta function
ON-delay
ON-delay
Star delta time relay with overtravel function (idling) 7PV33 48-2AX34 7PV33 48-2AX34 7PV33 48-2AX34
7PV33 48-2AX34
ON-delay (A)
7PV33 48-2AX34
11/31
SIMIREL
3RP15 05-1B.
3RP15 05-1BT
3RP15 05-1BW
3RP15 05-1RW
for 1 CO
for 2 COs
for 2 COs
for 2 COs
for 2 COs
3RP15 1.
3RP15 27
3RP15 3.
3RP15 40
for 1 CO
for 1 CO
for 2 COs
for 1 CO
for 1 CO
for 2 COs
3RP15 55
3RP15 60
3RP15 7.
for 1 CO
for 1 CO
for 1 CO
Note: The diagrams show the view onto the connection terminals Circuit diagrams for star-delta circuits
Control circuits (typical circuits) with 3RP15 74 and 3RP15 76 time relays with star-delta function for momentary-contact operation Sizes S00 to S3 for maintained-contact operation Sizes S00 to S3 Control circuit (typical circuit) with 3RP15 60 star-delta time relay Legend: S0 OFF pushbutton S1 ON pushbutton S maintained-contact switch K1 line contactor K2 star contactor K3 delta contactor K4 timing element or time relay F0 fuse F1 overload relay P1 pressure switch
The 17/18 contact is only closed in the star state; it is open both in the delta state and in the de-energised state.
1) Depending on the version.
11/32
SIMIREL
Dimension drawings
3RP20
1 changeover contact without auxiliary voltage, not 3RP15 05-1A.30 two-wire version, clock-pulse relay, star-delta function 7PV33
1) Push-in lug for screw fixing. 2) Coding plug (with 3RP10) or identification label.
3) Drilling diagram.
4) Identification label.
11/33
SIMIREL
The new 3UG4 line monitoring relays permit a maximum degree of protection to be achieved for machines, plants and systems. This means that line and voltage faults can be detected early on and the appropriate response is initiated before far more significant subsequent damage can occur.
Your advantages: Thanks to the wide voltage range, it can be used on all line supplies around the world from 160 V to 690 V without an auxiliary voltage Can be variably set to above range, below range or window monitoring Freely parameterizable delay times and reset behavior Reduced width for all versions for line and voltage monitoring For the digital versions, the actual value and fault type are permanently displayed Automatic direction of rotation correction by differentiating between line faults and incorrect phase sequence All versions have removable terminals All versions have either screw terminals or alternatively innovative Cage Clamp terminals Applications: The applications are listed in the following table. These tables indicate the various plant system conditions that can be detected using the monitoring parameters.
Possible plant or system fault Direction of rotation of the drive A fuse has blown Control supply voltage has failed Single-phase operation of a motor with the corresponding overheating Motor overheating as a result of non-symmetrical voltages or phase failure Line supplies with non-symmetrical load are detected A phase failure is detected in spite of regenerative feedback
Phase failure
Phase dissymmetry
Undervoltage
Motor draws an increased current and in turn overheats A device is undesirably reset Line supply dips, especially when supplied from a battery Threshold value switch for analog signals 0 to 10 V
Direction of rotation
Overvoltage
A plant is protected against destruction due to supply overvoltages A plant or system switches-in above a certain voltage Threshold value switch for analog signals 0 to 10 V
Insulation monitoring
11/34
SIMIREL
NE
W!
Contacts Line supply voltage Order No. List Price $
22.5 mm wide 3UG4514 to 3UG3518 can be digitally set, with fault memory and with LCD display Yes 1 CO 160260 320500 420690 160260 320500 420690 160690 160690 160690 160690 160690 3UG45113UG45113UG45113UG45113UG45113UG45113UG45123UG45123UG4513AN20 52.00 AP20 52.00 AQ20 52.00 BN20 60.00 BP20 60.00 BQ20 60.00 AR20 54.00 BR20 75.00 BR20 175.00
2 CO
Yes Yes
Yes Yes
5% 120 V
1 CO 2 CO Off delay 020 s 2 CO On and off delay 020 s 020 s for Vmin and Vmax 020 s for V min and Vmax 2 CO 1CO for Vmin and Vmax 1 CO for Vmin and Vmax
Selectable Yes
Using 120 V threshold values 120 V Using threshold values 020% 120 V
Yes
020%
120 V
Yes
Off delay 020 s 1 CO for line 160690 3UG4617- CR20 135.00 faults and 1 W for phase sequence Off delay 020 s 1 CO for line 160690 3UG4618- CR20 145.00 faults and 1 W (90400 for phase sequence w.r.t. N) Screw terminal 1
Return voltage due to coupling between the individual phases Loads connected to the three-phase line supply such as motor windings, lamps, transformers result in a coupling between the individual phases. As a result of this coupling, there is always a return voltage at the equipment terminal of the phase that has failed.
NE
W!
Contacts Delay time Auxiliary voltage Order No. List Price $
22.5 mm wide, all of the devices can be digitally set and have an LCD display, a fault memory that can be switched-in, simultaneous monitoring for overvoltage and undervoltage over the complete measuring range 1 CO 020 s Selfsupplied 17275 V AC DC 0.1150 V 24 V AC DC 020 s 1 CO 0.160 V AC DC 0.130 V 10600 V AC DC 0.1300 V 1 CO 020 s 24240 V AC DC 24 V AC DC 24240 V AC DC
3UG46333UG46313UG46313UG46323UG46321
Screw terminal
Cage Clamp terminal 2 Insulation monitoring for IT line supplies Line supply AC DC Measuring range 1110 k 10110 k Auto reset fault memory Selectable Selectable Contacts 1 CO 1 CO Width 45 mm 45 mm Auxiliary voltage 115 230 V AC 24240 V AC 24240 V AC Order No. 3UG3081-1AK20 3UG3081-1AW30 3UG3082-1AW30 List Price $ 160.00 160.00 190.00
11/35
SIMIREL
Monitoring the load of motors and the functionality of electronic loads a clear case for our 3UG relays that monitor current and cos . These devices detect the effect of wear and faults early on. This means that the appropriate actions can be taken before far more significant damage can occur.
Your advantages: 22.5 mm wide Can be digitally set and with LCD display Fault memory that can be switched-in Simultaneous monitoring for current overrange underrange over the complete measuring range
Current monitoring: Wide-voltage versions reduce stock inventory costs Only two versions from 2 mA to 10 A Can be variably set to overrange, underrange or window monitoring Freely parameterizable delay times and reset switch Actual value and fault type are permanently displayed All of the versions have removable terminals All of the versions have screw terminals or, alternatively, innovative Cage Clamp terminals cos cos monitoring: is monitored for overrange and underrange
Fault memory that can be switched-in Selectable starting bypass and delay time for threshold value out of range Applications: The applications can be seen in the adjacent table. These tables show the various plant system states can be detected using the monitoring parameters.
11/36
NE
W!
Order No. List Price $
StartingOff delay Auxiliary voltage bypass time 22.5 mm wide, all of the devices can be digitally set and have an LCD display, a fault memory that can be switched-in, simultaneous monitoring for overcurrent and undercurrent over the complete measuring range 2.0 mA AC/DC 0.1 mA250 mA up to 500 mA AC/DC 0.05 A AC/DC 0.01 A5 A up to 10 A AC/DC 1 CO 1 CO 020 s 020 s 020 s 020 s 24 V AC/DC 24240 V AC/DC 24 V AC/DC 24240 V AC/DC
3UG46213UG46213UG46223UG46221
Screw terminal
Cage Clamp terminal 2 cos monitoring Max. contin- Overcurrent Contacts Starting Off delay Hysteresis, fixed bypass time uous current Undercurrent 0,33 s 10% for cos 0,4 14 A Window (upper 1 CO + 0.520 s 1030% for cos < 0,4 1 CO and lower threshold values) List Price $ AC 3 x 230 V 3UG3014-1BL60 177.00 AC 3 x 400 V 3UG3014-1BP60 177.00 AC 3 x 480 V 3UG3014-1BR60 177.00 AC 3 x 575 V 3UG3014-1BS60 177.00 Voltage Order No.
cos I
0,4 0,2
Rule of thumb: cos changes significantly below the rated load; the current increases overproportionally above the rated load
Rated load
cos
0 0
Motor load
Plant s ystem states Overload monitoring Underload monitoring close to the rated torque Monitoring the functionality of electric loads Wire breakage monitoring Energy management (phase current monitoring) Threshold value switch for analog signals up to 20 mA
cos monitoring
No-load monitoring Underload monitoring in the lower power range monitoring of line supplies to control compensation equipment Interrupted cable between the cabinet and the motor Extremely simple cos
11/37
SIMIREL
Level monitoring relay for conductive liquids inlet or outlet monitoring adjustable sensitivity adjustment by potentiometer 1 yellow LED for indicating the relay state 1 green LED for indicating applied control supply voltage 1 SPDT contact
Rated control supply voltage Us AC 50/60 Hz V 24 120 230 3UG35 01-1AC20 3UG35 01-1AG20 3UG35 01-1AL20 86.00 86.00 86.00 Order No. List Price $ Weight approx. kg 0.26
Design
Sensitivity
Technical data
Rated control supply voltage Us Voltage tolerance Maximum power consumption Function mode setting Sensitivity Setting accuracy Repeat accuracy Electrode voltage Electrode current Conductor capacitance Delay time Mains buffering time inlet or outlet monitoring adjustable at maximum sensitivity at constant parameters max. max. of the sensor cable 1) k % % V mA nF ms ms ms W/VA V see selection data (electrical isolation with transformer) 0.85 to 1.15 Us 3/6 UNDER/OVER slide switch at the front 5 to 100 30 0.5 24 (50/60 Hz) 1 (50/60 Hz) 10 typically 500 (ON-delay with OVER, OFF-delay with UNDER) typically 300 (OFF-delay with OVER, ON-delay with UNDER) 300
1) The sensor cable need not necessarily be shielded, but it is not recommended to lay this cable parallel to the power supply lines. It is also possible to use a shielded cable, whereby the shield has to be connected to the M terminal.
11/38
SIMIREL
Principle of operation Description The principle of operation is based on measuring the electrical resistance of the liquid between two immersion sensors and a reference terminal. If the measured value is lower than the sensitivity set at the front panel, the output relay changes its switching state. In order to exclude electrolytic phenomena in the liquid, the sensors are supplied with alternating current.
Note Two-level control: The output relay changes its switching state as soon as the liquid level reaches the maximum sensor, while the minimum sensor is submerged. The relay returns to its original switching state as soon as the minimum sensor no longer has contact with the liquid. To be sure of resetting, the supply voltage must be interrupted for at least 0.5 s (T3). The delay times T1 and T2 of the output relay have not been included in the diagram in order to enhance clarity. Other resistance sensors within the range from 5 to 100 k may also be connected to the Min and Max terminals, for example, photoresistors, temperature sensors, displacement sensors operating on a resistance basis etc. The monitoring relay is therefore suitable for the monitoring of levels of other substances apart from liquids.
Maximum level 1) Minimum level 1) Monitored level Output relay, OVER function Output relay, UNDER function 1) Determined by the vertical positions of the sensors in the monitored liquid.
11/39
SIMIREL
Order No.
List Price $
Weight approx. kg
PG 101 Three-pole wire electrode, brown 500 mm long, with Teflon insulation (PTFE), screw-in gland white width A/F 22 mm, 3/8 inch thread, green PVC connecting cable, 3 x 0.5 mm2, 2 m long, max. operating temperature 90 oC, max. operating pressure 10 bar Two-pole wire electrode, brown 500 mm long, with Teflon insu- white lation (PTFE), screw-in gland width A/F 22 mm, 3/8 inch thread, PVC connecting cable, 3 x 0.5 mm2, 2 m long, max. operating temperature 90 oC, max. operating pressure 10 bar Two-pole bow electrode for lat- brown eral fitting, white screw-in gland width A/F green 22 mm, 3/8 inch thread, PVC connecting cable, 3 x 0.5 mm2, 2 m long, max. operating temperature 90 oC, max. operating pressure 10 bar Single-pole bow electrode for lateral fitting, screw-in gland width A/F 22 mm, 3/8 inch thread, PVC connecting cable, 3 x 0.5 mm2, 2 m long, max. operating temperature 90 oC, max. operating pressure 10 bar Single-pole, rugged design, screw-in gland width A/F 22 mm, 3/8 inch thread, PVC connecting cable, 3 x 0.5 mm2, 2 m long, max. operating temperature 90 oC, max. operating pressure 10 bar brown white centre The electrodes can be cut or electrode bent to the required length before or after installation. not The Teflon insulation must be assigna- removed over a length of apble prox. 5 mm. Application: for 2-point liquidlevel control in an insulating tank. One electrode each for the min. and max. value and a common reference electrode. not assignable For installation, see 3UG32 07-3A Application for alarm indication in the event of overflow or low level and for 2-step liquidlevel control, when the conductive tank is used as the reference electrode. 3UG32 07-3A 73.00
0.150
3UG32 07-2A
66.00
0.150
Thanks to the small space requirements due to lateral fitting, ideal for use in small containers and pipes, as a leak monitor and level monitor or for warning of water entering a housing.
3UG32 07-2B
66.00
0.110
gland
As a max. value electrode for electrode lateral fitting or for alarm indication with conductive tanks or pipes.
3UG32 07-1B
59.00
0.110
brown white
gland
3UG32 07-1C
104.00
0.130
11/40
SIMIREL
Selection and ordering data
Underspeed monitoring relay underspeed monitoring 4 effective ranges adjustable on front panel 1 green LED for indicating applied control supply voltage 1 yellow LED for indicating the relay state, flashes during operating time T 1 SPDT contact
Rated control supply voltage Us AC 50/60 Hz V 24 120 230 24 DC kg 3UG30 51-1AC20 3UG30 51-1AG20 3UG30 51-1AL20 3UG30 51-1AC40 194.00 194.00 194.00 194.00 0.26 Order No. List Price $ Weight approx.
Design
Effective range
revolutions/min Effective range with or without memory, start override 0.3 to 30 s electrical isolation AC: Yes DC: No 0.1 ... 600 (4 ranges)
Technical data
Rated control supply voltage Us Voltage tolerance Maximum power consumption Set value Hysteresis Setting accuracy Repeat accuracy Deviation ON-delay T Signal input IN1 2) Signal input IN2 2) Voltage level for reliable operation Sensor supply Effective ranges, selectable (rotary switch on front) (input resistance 16 k) (input resistance 1 k) level 1 level 0 +24 V/0 V +8V2 time setting range frequency revolutions minimum pulse duration of signal minimum interval between 2 pulses with or without memory ms ms Hz min-1 ms ms V V at constant parameters with temperature fluctuations W/VA % % % % V See selection data (for AC, electrical isolation by means of transformer; for DC 24 V without electrical isolation) 0.85 to 1.5 Us 4/5 adjustable to 10 ... 100 % of the selected time setting range typically 5 % of the set value 10 % referred to upper limit of time setting range 0.5
% / C 0.1 s V adjustable to 0.3 ... 30 10 % max. voltage 30 V, 3-wire sensor, pnp operation floating contact, 2-wire NAMUR sensor 4.5 ... 30 0 ... 1 DC 24 V (20 to 35 V), max. 50 mA DC 8.2 V 0.1 ... 1 s 10 ... 1 600 ... 60 5 5 1 ... 10 s 1 ... 0.1 60 ... 6 5 5 0.1 ... 1 min 0.17 ... 0.017 10 ... 1 5 5 1 ... 10 min 0.017 ... 0.0017 1 ... 0.1 5 5
1) Rated control supply voltage and measurement circuit are not electrically isolated. 2) The sensors are not included in the scope of supply.
11/41
SIMIREL
11/42
SIMIREL
Circuit diagrams
Level monitoring relay 3UG35 01
Relay for p.f. monitoring, single and three-phase, 3UG30 14 for operation on three-phase supply, I < 10 A UC
L1 L2 L3 L1 L2 L3 IN1
<cos >cos <
NSB01130b
Relay for p.f. monitoring, single and three-phase, 3UG30 14 for operation on three-phase supply, I > 10 A UC
Relay for p.f. monitoring, single and three-phase, 3UG30 14 for operation on single-phase supply, 230 V AC
11 >cos
21
12
14 22 24
11/43
SIMIREL
11/44
SIMIREL
3TX0 interface relays are available in two basic versions. The 3TX7004/05 is just 6.2 mm wide: This series means that the interface relays take up a lot less space in the electrical cabinet. Then there is our 3TX7002/03 series: These devices are suitable for mounting in small electrical cabinets with a low depth and short distances between the mounting rails. Both series are available with an extensive range of input and output interfaces.
Your advantages: 3TX7002/03 and 3TX7004/05 Operating range from 0.7 to 1.25 Vs at 24 V DC up to 60 C Protective circuit is integrated in the input Connection comb and cable to connect voltages at the same potential Manual-0-automatic switch for easier commissioning Your advantages: 3TX7014 and 3TX7015 Plug-in relays that can be quickly replaced with preassembled wiring Conductors are introduced and clamped from the front therefore shorter wiring times Tested, complete devices reduce installation times Individual relays are available as spare parts Relay version with hard-gold-plated contacts therefore achieving a high contact reliability
Applications: Electrically isolation Voltage conversion e.g. from 24 V DC to 230 V AC Signal amplification Contact multiplication General relay controls Overvoltage and EMC protection of controls Engineering information: When selecting the interface for rated control supply voltages of 110 V AC and 230 V AC, the maximum permissible cable length must be carefully observed. The special 3TX700- 05 relay can be used for longer cables.
Input interface
Output interface
11/45
SIMIREL
NE
W!
Hard-gold-plated M-0-A switch Order No. 3TX701 3TX701 3TX701 3TX701 3TX701 3TX701 3TX701 3TX701 3TX701 -1AM00 -1BM00 -1BB00 -1BE00 -1BF00 -1BM02 -1BB02 -1BE02 -1BF02 List Price$ 15.00 17.00 20.00 25.00 25.00 20.00 22.00 28.00 28.00 4.00 2.00
Width
24 V DC 6.2 mm 24 V DC 6.2 mm 24 V AC/DC 6.2 mm 115 V AC/DC 6.2 mm 230 V AC/DC 6.2 mm Plug-in socket interface relay, complete with relay and hard-gold-plated contacts 1 CO 24 V DC 6.2 mm yes 24 V AC/DC 6.2 mm yes 115 V AC/DC 6.2 mm yes 230 V AC/DC 6.2 mm yes Accessories Connecting comb, 16 pin Potential isolation plate
3TX7014-7AA00 3TX7014-7CE00 4
Screw terminal
3TX700 relay interfaces, cannot be plugged-in 3TX7004 05 output interface with relay output Contact 1 CO Rated control supply voltage Width 24 V AC/DC 6.2 mm Hard-gold-plated M-0-A switch yes Order No. 3TX700 -1LB00 3TX700 -1LB02 3TX7004-1BB10 3TX700 -1LF00 3TX7004-1BF051) 3TX700 -1MB00 3TX700 -1MF00 3TX700 -2MF02 3TX7004-2ME02 3TX700 -2MB02 Screw terminal 4 List Price $ 25.00 30.00 49.00 37.00 61.00 37.00 37.00 49.00 49.00 42.00
230 V AC/DC 1 NO
24 V AC/DC 6.2 mm 230 V AC/DC 6.2 mm 3TX7004 0 5 input interface with relay output 1 NO 230 V AC/DC 6.2 mm 110 V AC/DC 6.2 mm 24 V AC/DC 6.2 mm
Cage Clamp terminal 5 3TX7002 0 3 for low heights between tiers output interface with relay output Output Voltage Width Hard-gold-plated 1 NO 24 V AC/DC 11.5 mm 11.5 mm yes 1 CO 24 V AC/DC 17.5 mm 230 V AC/DC 17.5 mm 2 NO 24 V AC/DC 22.5 mm 2 CO 24 V AC/DC 22.5 mm yes 3TX7002 0 3 input interface with relay output 1 NO 230 V AC/DC 11.5 mm 230 V AC/DC 11.5 mm 110 V AC/DC 11.5 mm 24 V AC/DC 11.5 mm 1 CO 230 V AC/DC 17.5 mm yes Accessories Connecting cable with 24 connecting points for 3TX70 Connecting comb with 24 connecting points for 3TX7004, 6.2 mm wide
1) For longer cables up to 350 m
Order No. 3TX700 -1AB00 3TX700 -1AB02 3TX700 -1BB00 3TX7002- 1BF00 3TX700 -1CB00 3TX700 -1FB02 3TX700 -2AF00 3TX7002-2AF05 3TX7002-2AE00 3TX7002-2AB00 3TX7002-2BF02 3TX7004-8BA00 3TX7004-8AA00 2
List Price $ 44.00 48.00 49.00 49.00 51.00 58.00 48.00 56.00 48.00 44.00 63.00 16.00 12.00
Screw terminal
11/46
SIMIREL
Interface modules are available either with relays or semiconductors. Semiconductor interfaces offer some significant advantages: The electronic components are extremely reliable and have an extremely long service life (refer to the diagram below). The input interface combines the best of both worlds improved technical features and a lower price. When considering output interfaces, the question of relay or semiconductor needs to be taken into account as well as the making/breaking capacity and the number of operating cycles. If a relay has to be replaced just once during the complete lifetime of a machine, then a semiconductor interface will already have paid for itself. Your advantages: Favorably priced and reliable: Input interfaces with semiconductor output Graduated series of output interfaces with semiconductors Extremely long electrical life Extremely high contact reliability High DC making/breaking capacity Short switching times Applications: Providing electrical isolation, converting voltages Switching DC loads Switching capacitive loads High number of switching cycles Overvoltage and EMC protection of controls
Lebensdauervergleich
Comparison of lifetimes
High
Start of wear for mechanical components Probability of failure Average Probability of failure for electronic components
Low Lifetime
Electronic interface modules have a significantly higher lifetime than electromechanical devices.
11/47
SIMIREL
3TX7004/05 the narrow space saver output interfaces with semiconductor output, 1 NO contact Control supply voltage 24 V DC Max. switch- Switching ing current voltage 6.2 mm 0.5 A 48 V DC 6.2 mm 1.5 A 30 V DC 12.5 mm 5A 30 V DC 12.5 mm 5A 30 V DC 12.5 mm 2A 24250 V AC 110230 V AC 6.2 mm 3A 30 V DC Input interfaces with semiconductor output, 1 NO contact 110230 V AC 6.2 mm 0.1 A DC 30 V Width Min. load current 0.5 A 0.5 A 0.05 A Short-time load capacity 1.5 A/20 ms Short-circuit proof Short-circuit proof Short-circuit proof 100 A/20 ms Short-circuit proof 0.2 A/3 ms M-0-A Order No. List switch Price $ 3TX700 -3AB04 60.00 3TX700 -3PB54 44.00 3TX700 -3AC04 69.00 yes 3TX700 -3AC14 79.00 3TX700 -3AC03 83.00 3TX700 -3PG74 63.00 3TX700 -4PG24 4 39.00
Screw terminal
3TX7002 for low tier heights output coupler with semiconductor output, one NO contact Control supply Width Max. switch- Switching Min. load voltage ing current voltage current 24 V DC 12.5 mm 1.8 A 48264 V AC 0.06 A 24 V DC 11.5 mm 1.5 A 60 V DC Input interfaces with semiconductor output, 1 NO contact 110230 V AC 12.5 mm 0.1 A 60 V DC 24 V AC/DC 12.5 mm 0.1 A 30 V DC Accessories Connecting cable with 24 connecting points for 3TX70 Connecting comb with 24 connecting points for 3TX7004, 6.2 mm wide Short-time load capacity Order No. 20 A/20 ms 4 A/0.2 ms 1 A/20 ms 1 A/20 ms List Price $ 3TX7002-3AB00 62.00 3TX7002-3AB01 62.00 3TX7002-4AG00 3TX7002-4AB00 3TX7004-8BA00 3TX7004-8AA00 76.00 70.00 16.00 12.00
Using the accessories it is easy to insert a jumper between the same voltage levels.
11/48
SIMIREL
General data
Rated insulation voltage Ui (pollution degree 3)
V AC V
300 up to 300 IP 20 IP 30
Safe isolation acc. to DIN VDE 0106 Part 101 between coil and contacts Degree of protection Short-circuit protection (weld-free protection at Ik 1 kA) Fuse links, utilisation category gL/gG Permissible ambient temperature Conductor cross-sections Screw terminals (for 3TX7 004): solid finely stranded with or without end sleeves Terminal screws Cage Clamp connections (for 3TX7 005): solid/finely stranded finely stranded with end sleeve in operation when stored Connections Enclosure
A C C
mm2 mm2
1 x (0.25 ... 4) 1 x (0.5 ... 2.5) M3 1 x (0.08 ... 2.5) 1 x (0.25 ... 1.5)
mm2 mm2
Control circuit
Working range at DC 17 to 40 V at Us = AC/DC 24 V at Us = AC/DC 110 and 230 V 0.7 to 1.25 x Us 0.8 to 1.1 x Us approx. 0.5 W/channel; 3TX7 00 .-...05: 1 W for DC/6 VA for AC mA mA Overall w. from 12.5 mm mA exception: 3TX7 00.-1LH00 mA 3TX7 00.-1BF05 mA Overall width 6.2 mm Us = 24 V; 2 Us > 24 V; 0.5 2.5 1.5 5 (Us = AC 230 V) 0.5 (Us = DC 230 V) < 8 < 15 Yellow LED 3TX7 00 . -1 . F00 -2ME02 -2MF02 AC DC m m 40 2000 3TX7 00 . -1 . B. . -2MB02 400 2000 3TX7 00 . -1 . H0. 3TX7 00 . -1BF05
Operating times at Us ON-delay OFF-delay Status indication Max. permissible cable lengths (min. cross-section: 0.75 mm 2)
ms ms
on request
350 2000
Load side
Rated operational current 1) Conventional thermal current Ith Rated operational current Ie acc. to utilisation category (DIN VDE 0660) A at 24 V 110 V 230 V A A A 3TX7 00 .-1A/-1B/-1C/-1H/-1G 6 AC-15 DC-13 3 3 3 AC-12 at 24 V 110 V 230 V A A A 6 6 6 AC/DC 17 V, 5 mA AC/DC 1 V, 0.1 mA 30 V/20 mA AC/DC 17 to 250 V 20 x 106 operating cycles 1.0 0.2 0.1 DC-12 6 0.3 0.2 3TX7 00 .-. L/- .M 6 AC-15 2 2 2 AC-12 6 6 6 AC/DC 17 V, 5 mA AC/DC 1 V, 0.1 mA 30 V/20 mA AC/DC 17 to 250 V 20 x 106 operating cycles 0.5 105 operating cycles 5000 operating cycles
Switching current with resistive load acc. to DIN VDE 0435 (relay standard) and DIN VDE 0660
Min. contact loading for 3TX7 00 . -1. . . 0/5 Min. contact loading for 3TX7 00 . -. . . 02 (hard gold-plated) Output limit for hard gold-plating Switching voltage Mechanical endurance Electrical endurance at Ie Operating frequency 1/h
Note: The service life of the coupling relays can be increased by connecting inductive loads.
11/49
SIMIREL
1 x (0.25 ... 4) 1 x (0.5 ... 2.5) M3 1 x (0.08 ... 2.5) 1 x (0.25 ... 2.5)
Type
3AB04/ 4AB04
3AC.4
3AC03
3PB54
4PG24
Control circuit
Working range Power consumption at 24 V DC AC 230 V Release voltage W W V 0.5 6 2.3 0.5 5 2.6 0.25 6 1.5 0.2 9 1.5 1.5 20 0.4 V 11 ... 30 DC 11 ... 30 DC 11 ... 30 DC 11 ... 30 DC 110 ... 230 AC/DC
Permissible residual current of the electronics mA (with 0 signal) Operating times ON-delay OFF-delay Status indication Max. permissible cable lengths (min. cross-section: 0.75 mm 2) m ms ms
1 6 Yellow LED 40
3P . 74
3PB41
Release voltage
Permissible residual current of the electronics mA (with 0 signal) Operating times ON-delay OFF-delay Status indication Max. permissible cable lengths (min. cross-section: 0.75 mm 2) m ms ms
11/50
SIMIREL
Technical data
Type
3AB04/ 4AB04
3AC.4
3AC03
3PB54
Load side
Switching voltage Switching current Short-time load rating Contacts Minimum load current Conductive voltage drop Residual current of the electronics (with 0 signal) Operating frequency with resistive load mA V mA Hz V A A ms DC 48 0.5 1.5 20 1 NO transistor 1 < 0.1 50 DC 30 5 Short-circuit proof 1) 1 NO transistor 500 3) 0.5 < 0.1 50 AC 24 ... 250 2 100 20 1 NO Triac 50 1.6 <6 1 DC 30 1.5 Short-circuit proof 2) 1 NO transistor 0.5 < 0.1 500
Type Switching voltage Switching current Short-time load rating Contacts Mininum load current Conductive voltage drop Residual current of the electronics (with 0 signal) Operating frequency with resistive load
1) The semiconductor output switches off in the case of a short-circuit or overload. Before the device can be operated again, it must be disconnected briefly from the supply voltage.
2) The current is limited by the semiconductor output in the case of a short-circuit or overload.
3) Below the minimum load current, the built-in semiconductor detects a wire-break in the load circuit. To reset this, the control circuit must be briefly deactivated.
11/51
SIMIREL
Optocouplers switch by means of semiconductors. These are not subject to wear, so welding of contacts is not possible. The 6.2 mm wide optocouplers have an opening on the righthand side of the enclosure. They can be like the relay couplers mounted in a row without gaps. Functions Surge suppression The coupling devices are tested with 1 x 105 operating cycles in AC-15 operation with the values specified in the technical data. The service life of the relay connector can be increased by connecting inductive loads. Note When capacitive loads are switched in the absence of components (series resistors) that limit the brief peak currents, this can cause micro welding of the relay contacts.
To guarantee shock hazard protection in modules of the 6.2 mm series with enclosure opening (e. g. 3TX7 004-3AB04), the individual module or the final module in a row must be fitted with an end plate.
11/52
SIMIREL
The new 3RS18 interface relays set new standards: They have a wide-range voltage extending from 24 V AC D C to 240 V. This makes them absolutely unique in the interface market. All of these devices are accommodated in a well-proven, rugged 22.5 mm wide enclosure. Relays with 1, 2 and 3 changeover contacts are available in both screw and Cage Clamp terminal versions. Not only this, also in combination and wide-range voltage with hard-gold-plated contacts for an especially high contact reliability even at low current levels. Thanks to the well-proven, rugged enclosure, you can enjoy the benefits of user-friendly connection systems, including Cage Clamp terminals just the same as delete our time relays. 2 conductors can be connected at each terminal point.
Your advantages: New, worldwide: One device for all voltages Lower costs due to fewer versions User-friendly wiring Especially high contact reliability even at low currents Applications: Everywhere that contacts which are electronicscompatible are required and where devices with widerange voltage are used Thanks to the hard-gold-plated contacts, predestined for PLC I/O
3RS18 interface relays in a rugged, industrial enclosure 22.5 mm wide Rated control supply voltage Vs Contact versions 50 60 Hz 2 CO Wide-range voltage 24240 V AC/DC 3 CO 3 CO hard-gold-plated 1 CO Combination voltage 24 V AC/DC and 2 CO 110120 V AC 3 CO 3 CO hard-gold-plated 1 CO 24 V AC/DC and 220240 V AC 2 CO 3 CO 3 CO hard-gold-plated
Order No.
List Price $ BW00 HW00 HW01 AQ00 BQ00 HQ00 HQ01 AP00 BP00 HP00 HP01 1 30.00 35.00 40.00 20.00 25.00 30.00 35.00 20.00 25.00 30.00 35.00
3RS18 003RS18 003RS18 003RS18 003RS18 003RS18 003RS18 003RS18 003RS18 003RS18 003RS18 00-
Screw terminal
11/53
SIMIREL
-1CB00
-1FB02
-2BF02
-1B . 00
-1CB00
Semiconductor interfaces
Terminal designations according to EN 50 005 3TX7 002-3AB00 -3AB01 -4AB00 -4AG00
Semiconductor interfaces
Output interfaces 3TX7 002-3AB0 . Input interfaces 3TX7 002-4A . 0 .
11/54
SIMIREL
Circuit diagrams Terminal diagrams Relay interfaces
Output interfaces 3TX7 00 .-1M . 00
3TX7 00 .-1AB10
3TX7 00 .-1L . 0.
3TX7 00 .-1BB10
3TX7 00 .-1CB00
3TX7 00 .-1HB00
3TX7 00 .-1GB00
Semiconductor interfaces
Output interfaces 3TX7 00 . -3AB04 -3PB41 3TX7 00 . -3PB54 -3PG74 3TX7 00 . -3AC04
3TX7 00 .-3AC14
3TX7 00 .-3AC03
3TX7 00 .-3RB43
11/55
SIMIREL
Semiconductor interfaces
Output interfaces 3TX7 004 -3AB04, -3PB41 -3PB54, -3PG74 -3AC04 -3AC14 -3AC03 -3RB43 Input interfaces 3TX7 004 -4AB04 -4P . 24
-3PB54, -3PG74
-3AC04
-3AC14
-3AC03
-3RB43
11/56
SIMIREL
Dimension drawings
Semiconductor interfaces 3TX7 00 .-3AB04, 3TX7 00 .-4AB04, 3TX7 00 .-3PB . ., 3TX7 00 .-3PG74, 3TX7 00 .-3RB43, 3TX7 00 .-4P . 24
1) Dimension for 3TX7 004 interfaces (screw connections). 2) Dimension for 3TX7 005 interfaces (Cage Clamp connections).
11/57
SIMIREL
Contact configuration
Contact rating
Order no.
List Price $
Weight approx. kg
Pack
units
3TX7111-3LC13
3TX7114-5LC13
3TX7144-1E7
3TX7144-1E6
Socket for 3TX7110 Socket for 3TX7111 Socket for 3TX7109/7114 Socket for 3TX7116 Socket for 3TX7117
Accessories
3TX7144-4E6 Flange adapter for 3TX7110 DIN adapter for 3TX7110 Hold/eject clip for 3TX7111 and 3TX7114 Flange adapter for 3TX7111 and 3TX7114 DIN adapter for 3TX7111 and 3TX7114 Flange adapter for 3TX7116 DIN adapter for 3TX7116 Flange adapter for 3TX7117 DIN adapter for 3TX7117 Accessories for 3TX7144-4E6 only MOV suppressor 24 VAC/VDC MOV suppressor 120 VAC/VDC MOV suppressor 240 VAC/VDC Protection diode 6-250 VDC LED, green 24 VAC/VDC LED, green 120/240 VAC/VDC Jumper bar 3TX7144-3L5 3TX7144-3L4 3TX7144-1L1 3TX7144-3L5 3TX7144-3L4 3TX7144-1M3 3TX7144-1M4 3TX7144-1M35 3TX7144-1M6 3TX7144-H9 3TX7144-H10 3TX7144-H11 3TX7144-H12 3TX7144-H13 3TX7144-H14 3TX7144-H15 0.75 1.25 0.75 0.75 1.25 0.75 1.25 0.75 1.25 3.00 3.00 3.00 2.00 1.00 1.00 1.00
11/58
SIMIREL
Selection and ordering data
AC and DC operation
Version Rated control supply voltage Contact configuration Contact rating Order no. List Price $ Weight approx. kg Pack
units
3TX7111-3HC13C
3TX7117-5HC13C
3TX7144-1E7
3TX7144-1E6
Socket for 3TX7110 Socket for 3TX7111 Socket for 3TX7109/7114 Socket for 3TX7116 Socket for 3TX7117
Accessories
3TX7144-4E6 Flange adapter for 3TX7110 DIN adapter for 3TX7110 Hold/eject clip for 3TX7111 and 3TX7114 Flange adapter for 3TX7111 and 3TX7114 DIN adapter for 3TX7111 and 3TX7114 Flange adapter for 3TX7116 DIN adapter for 3TX7116 Flange adapter for 3TX7117 DIN adapter for 3TX7117 Accessories for 3TX7144-4E6 only MOV suppressor 24 VAC/VDC MOV suppressor 120 VAC/VDC MOV suppressor 240 VAC/VDC Protection diode 6-250 VDC LED, green 24 VAC/VDC LED, green 120/240 VAC/VDC Jumper bar 3TX7144-3L5 3TX7144-3L4 3TX7144-1L1 3TX7144-3L5 3TX7144-3L4 3TX7144-1M3 3TX7144-1M4 3TX7144-1M5 3TX7144-1M6 3TX7144-H9 3TX7144-H10 3TX7144-H11 3TX7144-H12 3TX7144-H13 3TX7144-H14 3TX7144-H15 0.75 1.25 0.75 0.75 1.25 0.75 1.25 0.75 1.25 3.00 3.00 3.00 2.00 1.00 1.00 1.00
11/59
SIMIREL
Contact rating
Order no.
List Price $
Weight approx. kg
Pack units
11/60
SIMIREL
Selection and ordering data
AC and DC operation
Version Rated control supply voltage Contact configuration Contact rating Order no. List Price $ Weight approx. kg Pack
units
Accessories
3TX7144-1E2 8 pin socket for 3TX7112 and 3TX7120 (DPDT) 11 pin socket for 3TX7112 and 3TX7120 (3PDT) 8 pin Touchsafe socket for 3TX7112 and 3TX7120 11 pin Touchsafe socket for 3TX7112 and 3TX7120 Accessories for 3TX7144-4E2 and 4E3 3TX7144-1E3 MOV suppressor 24 VAC/VDC MOV suppressor 120 VAC/VDC MOV suppressor 240 VAC/VDC RC suppressor 6-24 VAC/VDC RC suppressor 110-240 VAC/VDC Protection diode 6-250 VDC LED, green 24 VAC/VDC LED, green 120/240 VAC/VDC Jumper bar 3TX7144-1E2 3TX7144-1E3 3TX7144-4E2 3TX7144-4E3 4.75 10.00 7.00 7.00
11/61
SIMIREL
Contact configuration
Contact rating
Order no.
List Price $
Weight approx. kg
Pack
units
Accessories
3TX7144-1E2 8 pin socket for OND 11 pin socket for OFD 8 pin Touchsafe socket for OND 11 pin Touchsafe socket for OFD Accessories for 3TX7144-4E2 and 4E3 MOV suppressor 24 VAC/VDC 3TX7144-1E3 MOV suppressor 120 VAC/VDC MOV suppressor 240 VAC/VDC RC suppressor 6-24 VAC/VDC RC suppressor 110-240 VAC/VDC Protection diode 6-250 VDC LED, green 24 VAC/VDC LED, green 120/240 VAC/VDC Jumper bar 3TX7144-H1 3TX7144-H2 3TX7144-H3 3TX7144-H4 3TX7144-H5 3TX7144-H6 3TX7144-H7 3TX7144-H8 3TX7144-H15 3.00 3.00 3.00 2.00 2.00 2.00 1.00 1.00 1.00 3TX7144-1E2 3TX7144-1E3 3TX7144-4E2 3TX7144-4E3 4.75 10.00 7.00 7.00
11/62
SIMIREL
Selection and ordering data
AC and DC operation
Version Rated control supply voltage Contact configuration Contact rating Order no. List Price $ Weight approx. kg Pack
units
1) Applications above 15 amps must use quick connect terminals and not 3TX7144-1E4 sockets.
Accessories
Version Order no. List Price $
11/63
SIMIREL
Contact configuration
Contact rating
Order no.
List Price $
Weight approx. kg
Pack
units
30 A 30 A 30 A 30 A 30 A
30 A 30 A 30 A 30 A
11/64
SIMIREL
Selection and ordering data
AC and DC operation
Version Rated control supply voltage Contact configuration Contact rating Order no. List Price $ Weight approx. kg Pack
units
3TX7113-5DF13
units
11/65
SIMIREL
Contact configuration
Contact rating
Order no.
List Price $
Weight approx. kg
Pack
units
units
11/66
SIMIREL
Technical data
Relay type
3TX7110
3TX7111/ 3TX7114
3TX7116/ 3TX7117
3TX7126
3TX7127
3TX7123
3TX7109
Contact data
contact material silver alloy silver alloy 3A-silver 5A-silver alloy contact resistance 50 milliohms max. @ 10A, 120V AC or 24V DC 15 A 15 A 10 A 1/2 HP 1 HP 100mA @ 5VDC or 0.5 W 100 milliohms max. @ 10A, 6V AC 1 amp 15A 12A 12A 1/3 HP 1/2 HP 100mA @ 5VDC or 0.5 W 100 milliohms max. @ 5A, 6V AC 1 amp 5A 5A 5A 1/6 HP 1/16 HP 100mA @ 5VDC or 0.5 W (3A)100 milliohms max. @ 120 V AC (5A)500 milliohms max. @ 120 V AC 3A / 5A 3A / 5A N/A / N/A 100mA @ 5VDC or 0.5 W silver alloy 5A-silver alloy 100 milliohms max. @ 10A, 6V AC 1 amp 15A 15A 15A 1/3 HP 1/2 HP 100mA @ 5VDC or 0.5 W 50 milliohms max. @ 10A, 120V AC or 24V DC 15 A 15 A 10 A 1/2 HP 1 HP 100mA @ 5VDC or 0.5 W silver alloy
contact rating 110-120V AC 28V DC 220-277V AC single phase horse power rating 110-120V AC 220-250V AC minimum recommended load
Miscellaneous
timing operate time release time dielectric strength coil to contacts (1 min.) across open contacts (1 min.) contact to frame (1 min.) insulation resistance @ 500V DC ambient temperature vibration resistance 25 ms 25 ms 1500V rms 1000V rms 1500V rms 100 Megohms -40 C + 70 C 6Gs, 10 to 55 Hz, 1mm (double amplitude) 10 Gs 10 million 150,000 min. 10 million 200,000 min. 25 ms 25 ms 1500V rms 1000V rms 1500V rms 100 Megohms -40 C + 70 C 6Gs, 10 to 55 Hz, 1mm (double amplitude) 10 Gs 50 million 200,000 min. 10 Gs 10 million 100,000 min. 50 million 200,000 min. 13 ms 6 ms 1240V rms 500V rms 1240V rms 100 Megohms -45 C + 70 C 25 ms 25 ms 1500V rms 1000V rms 1500V rms 100 Megohms -40 C + 70 C 6Gs, 10 to 55 Hz, 1mm (double amplitude) 10 Gs 10 million 150,000 min.
11/67
SIMIREL
3TX7120
3TX7115
3TX7121
3TX7122
Contact data
contact material contact resistance silver alloy 50 milliohms max 10 A 120 AC or 24 DC 50 milliohms max at rated current 120 AC or 24 DC 2 pole 16 A 16 A 16 A 1/3 HP 1/2 HP 100mA @ 5VDC or 0.5 W 12 A 10 A 8A 1/3 HP 1/2 HP 3 pole 10 A 10 A 6A 1/3 HP 1/2 HP silver alloy 50 milliohms max 10 A 120 V AC or 24 V DC 2 pole 16 A 16 A 16 A 1/3 HP 1/2 HP 3 pole 16 A 16 A 16 A 1/3 HP 1/2 HP 50 milliohms max at rated current 2p 3p 2p 3p 15 A 15 A 10 A 10 A 15 A 15 A 1/3 HP 1/2 HP
contact rating 110-120V AC 28V DC 220-277V AC single phase horse power rating 110-120V AC 220-250V AC minimum recommended load
25 A 20 A 13 A 13 A 20 A 10 A 1 HP 1 1/2 HP
Miscellaneous
timing operate time release time dielectric strength coil to contacts (1 min.) across open contacts (1 min.) contact to frame (1 min.) insulation resistance @ 500V DC ambient temperature vibration resistance shock resistance functional life expectancy mechanical electrical 20 ms 15 ms 2500 V rms 1500 V rms 2500 V rms 1000 Megohms -40 C + 65 C 6Gs, 10 to 55 Hz, 1mm (double amplitude) 10 Gs 5 million 200,000 10 Gs 5 million 100,000 25 ms 20 ms 1500 V rms 1000 V rms 1500 V rms 1000 Megohms -10 C + 60 C 20 ms 20 ms 2500 V rms 1500 V rms 2500 V rms 150 Megohms -40 C + 50 C AC -40 C + 65 C DC 6Gs, 10 to 55 Hz, 1mm (double amplitude) 10 Gs 5 million 100,000 10 Gs 5 million 100,000 2000 V rms 500 V rms 2000 V rms 1000 Megohms -30 C + 50 C AC -30 C + 65 C DC
11/68
SIMIREL
Technical data
Relay type
3TX7113
3TX7125
3TX7136
3TX7130
Contact data
contact material contact resistance contact rating 110-120V AC 28V DC 220-277V AC single phase horse power rating 110-120V AC 220-250V AC minimum recommended load silver alloy 50 milliohms max at rated current DPDT 13 - 20 A 20 - 25 A 3/4 to 1 HP 1 to 1 1/2 HP 3PDT 13 - 16 A 16 - 20 A 10 A 10 A 10 A 12 A 12 A 12 A N/A N/A 30 A 30 A 30 A 1 1/2 to 2 HP 1 1/2 to 2 HP silver alloy 50 milliohms max at rated current
Miscellaneous
timing operate time release time dielectric strength coil to contacts (1 min.) across open contacts (1 min.) contact to frame (1 min.) insulation resistance @ 500V DC ambient temperature vibration resistance shock resistance functional life expectancy mechanical electrical 20 ms 20 ms 2000 V rms 500 V rms 2000 V rms 1000 Megohms -30 C + 50 C AC -30 C + 65 C DC 6Gs, 10 to 55 Hz, 1mm (double amplitude) 10 Gs 5 million 100,000 10 million 100,000 30 ms 30 ms 1500 V rms 500 V rms 1500 V rms 1000 Megohms -45 C + 70 C AC 6Gs, 10 to 55 Hz, 1mm (double amplitude) 10 Gs 10 million 100,000 1 million 100,000 20 ms 40 ms 30 ms 2200 V rms 1500 V rms 2200 V rms 1000 Megohms -30 C + 50 C AC -30 C + 60 C DC
11/69
SIMIREL
Throw is the number of different closed contact positions per pole. In other words a throw describes the total number of different circuits each pole controls. The following abbreviations are used to indicate contact configurations: SPST Single-pole, single-throw SPDT Single-pole, double-throw DPST Double-pole, single-throw DPDT Double-pole, double-throw
Contact arrangement - break Break is the number of separate contacts the switch uses to open or close an individual circuits. If the relay breaks the circuit in one place, then it is a single break relay. If the relay breaks the circuit in two places, then it is a double break relay.
Contact arrangements overview This illustration shows various contact arrangement types.
11/70
SIMIREL
Circuit diagrams
3TX7110 SPD T
3TX7111 DPDT
3TX7111 3PDT
3TX7114 DPDT
3TX7116 3PDT
3 T X711 7 4PDT
3TX7126/3TX7127 4PDT
3TX7123 DPDT
3TX7112 DPDT
3TX7112 3PDT
3TX7120 DPDT
3TX7120 3PDT
11/71
SIMIREL
3TX7130 DPST-NO
3TX7130 SPST-NC
3TX7130 DPDT
3TX7115 DPDT
3TX7115 3PDT
3TX7125 DPDT
3TX7136 DPDT
11/72
SIMIREL
Dimension drawings
3TX7110
3TX7111 DPDT
3TX7111 4PDT
3TX7114
3TX7144-1E7
3TX7144-1E5
11/73
SIMIREL
3TX7117
3TX7144-1E6
3TX7126
3TX7127
3TX7123
11/74
SIMIREL
Dimension drawings
3TX7112
3TX7120
3TX7144-1E2
3TX7144-1E3
11/75
SIMIREL
3TX7113
3TX7121/3TX7122
3TX7123
3TX7127
3TX7144-1E4
11/76
SIMIREL
Dimension drawings
3TX7130 SPST NC
3TX7130 SPST NO
3TX7130 SPDT
3TX7130 DPST NO
3TX7130 DPDT
3TX7136
11/77
Interface Converters
3RS17
Overview In automation and closed-loop control, working with analog signals is unavoidable. Interfaces of 0 to 10 V and 0/4 to 20 mA have become established in this field. Interface converters load the coupling function for analog signals on the input side as well as on the output side. They are indispensible Application Converters are used in analog signal processing for: Electrical isolation Conversion of normalised and non-normalised signals Amplification, impedance adjustment Conversion to frequency for processing by a digital input Overvoltage and EMC protection Short-circuit protection of the outputs
SIMIREL
where analog values are processed with electronic controls. In the harsh industrial environment, signals often have to be transferred over large distances. Electrical isolation is necessary due to the various different power supplies. Potential differences and losses due to cable resistance must be
prevented. Electromagnetic disturbances and overvoltages can affect the signals especially at the input end and even destroy the analog modules. With regard to the output, shortcircuit protection is of particular importance. The devices are EMC-tested acc. to EN 50081 (emission)
11/78
SIMIREL
Interface Converters
3RS17
Selection and ordering data Screw and Cage Clamp connection All converters with the exception of the passive individual interface converters are equipped with a yellow LED for indication of "Voltage applied".
Input Output Width Supply voltage mm V AC/DC 24 AC/DC 24 AC/DC 24 AC/DC 24 AC/DC 24 AC/DC 24 AC/DC 24 AC/DC 24 AC/DC 24 AC/DC 24 AC/DC 24 to 240 AC/DC 24 AC/DC 24 to 240 2 way 2 way 2 way 2 way 2 way 2 way 2 way 2 way 2 way 2 way 3 way 2 way 3 way 3RS17 00-1AD00 3RS17 00-1CD00 3RS17 00-1DD00 3RS17 02-1AD00 3RS17 02-1CD00 3RS17 02-1DD00 3RS17 03-1AD00 3RS17 03-1CD00 3RS17 03-1DD00 3RS17 05-1FD00 3RS17 05-1FW00 3RS17 05-1KD00 3RS17 05-1KW00 3RS17 00-2AD00 3RS17 00-2CD00 3RS17 00-2DD00 3RS17 02-2AD00 3RS17 02-2CD00 3RS17 02-2DD00 3RS17 03-2AD00 3RS17 03-2CD00 3RS17 03-2DD00 3RS17 05-2FD00 3RS17 05-2FW00 3RS17 05-2KD00 3RS17 05-2KW00 Electrical isolation Screw terminals Order No. Cage Clamp terminals Order No. List Weight Price $ approx. kg 130.00 0.03 130.00 0.03 130.00 0.03 130.00 0.03 130.00 0.03 130.00 0.03 130.00 0.03 130.00 0.03 130.00 0.03 167.00 0.03 240.00 0.1 180.00 0.1 255.00 0.1
0 ... 20 mA 0 ... 10 V
0 ... 20 mA 0 ... 20 mA 6.2 0 ... 20 mA 4 ... 20 mA 6.2 4 ... 20 mA 0 ... 10 V 6.2 4 ... 20 mA 0 ... 20 mA 6.2 4 ... 20 mA 4 ... 20 mA 6.2
Multi-range converters,selectable, with Manual/Automatic switch and setting potentiometer as manual analog signal encoder
0 ... 10 V 0 ... 20 mA 4 ... 20 mA selectable 0 ... 10 V 17.5 0 ... 20 mA 4 ... 20 mA selectable AC/DC 24 AC/DC 24 to 240 2 way 3 way 3RS17 25-1FD00 3RS17 25-1FW00 3RS17 25-2FD00 3RS17 25-2FW00 190.00 0.1 310.00 0.1
Input
Output
Electrical isolation
List
11/79
Interface Converters
3RS17
Technical data General data
Type Supply voltage range Rated power (own requirements) Electrical isolation input/output
SIMIREL
AC/DC 24 V DC: 0.7 to 1.25 Un AC: 0.8 to 1.2 Un W Typically 0.3 Active disconnector: 1500 V, 50 Hz, 1 min Passive disconnector: 500 V, 50 Hz, 1 min
AC/DC 24 to 240 V DC: 0.7 to 1.1 Un AC: 0.8 to 1.1 Un Typically 0.75 4000 V, 50 Hz, 1 min
Rated insulation voltage Pollution degree 2, overvoltage category III acc. to DIN VDE 0110 Ambient temperature for operation for storage
V C C mm2 mm2
50 20 ... + 60 40 ... + 85
300
Conductor cross-sections Screw connections solid finely stranded with or without end sleeves Terminal screws Cage Clamp terminals solid/finely stranded finely stranded with end sleeve Enclosure degree of protection Terminal degree of protection Permissible mounting position Mounting onto standard rails Vibration performance Shock resistance EN 50 022 IEC 68-2-6 IEC 68-2-27 IEC 529 IEC 529
mm2 2 mm
mm
35 10 55 Hz/0.35 mm 15 g/11 ms Voltage inputs Current inputs active 100 30 0/4 to 20 mA active 400 Current inputs passive 100/250 (6.2 mm overall width 2.7 V at 20 mA 0 to 20 mA passive 1000 at 20 mA 400 at 20 mA (6.2 mm overall width) Corresponds to the input current Short-circuit proof Passive disconnector Load < 600 : < 50 ppm/K from measured value Load < = 600 : < 175 ppm/K from measured value 0.1 0.06 %/100 50 <8 Frequency 2400
Input
330 k AC/DC V 30 0 to 10 V Output impedance Max. output load
Output
mA mA
55
Max. output current Short-circuit current Protection of the outputs Max. overvoltage at output AC/DC
21 40 Short-circuit proof
Short-circuit proof 30 Active disconnector (frequency) 0.1 0.02 0 to 50 Hz; 7.5 mHz/K 0 to 100 Hz; 15 mHz/K 0 to 1 KHz; 0.15 Hz/K 0 to 10 KHz; 1.5 Hz/K 30 10 + 1 periods 30 + 1 periods
10 15 Short-circuit proof 30
Accuracy
% %
Transmission error Load error from measured value Limit frequency 3 dB Rise time (10 to 90 %) Settling time to 1 % accuracy, typically Residual ripple
% Hz ms ms
30 10 30
mV rms < 5
Unless stated otherwise, the accuracy is specified with reference to the upper range limit
11/80
SIMIREL
Configuration Active interface converters Active interface converters offer the widest application flexibility due to the use of an external supply voltage. Project engineering with active interface converters is easy, because Passive interface converters Passive interface converters do not require an external supply voltage. This advantage can only be utilised in the case of current signals that are transferred 1:1. Amplification or
Interface Converters
3RS17
input and output resistances and voltage drops are balanced by the auxiliary power. They provide pure electrical isolation as well as conversion between the different signal
conversion is not possible.The converters are used for clear electrical isolation of signals and for protecting the inputs and outputs. Passive disconnectors do not operate reac-
tion free, i.e.any load on the output affects the input signal to the same degree. When the passive converter is used, an analysis of the output power of the encoder and the input
resistance of the analog input must be performed. For pure currentis being used more and more.
. Important:
When passive disconnectors are used, it is important to note that: The current-driving voltage of the measuring transmitter UE must be sufficient to drive the maximum current of 20 mA through the passive disconnector with a voltage drop of UV = 2.7 V and the resistive load RB. This means that: UB UE = 2.7 V + 20 mA x RB
The following diagram shows the input voltage UE as a function of the resistive load RB taking into account the voltage drop UV. If the resistive load is known, the minimum voltage that the current source has to produce in order to drive the maximum current of 20 mA via the passive disconnector and resistive load can be read off the Y-axis. Current-carrying capacity of the outputs A maximum output load is specified in the case of current signals. This resistance value specifies the maximum input resistance for the subsequent device for which the output of the converter is adequate. For voltage signals, the maximum current that can be drawn from the output is the decisive factor.
2-way isolation In the case of 2-way isolation, the input is electrically isolated from the output. The "zero potential" for the supply voltage is the same as that on which the analog output signal is referenced.
3-way isolation In the case of 3-way isolation, each circuit is electrically isolated from the others, i.e. the input, output and supply voltage have no common potential.
11/81
Interface Converters
3RS17
Circuit diagrams
3RS17 00- . . D . . 3RS17 02- . . D . . 3RS17 03- . . D . . 3RS17 05- . . D . .
SIMIREL
3RS17 0 .- . .W00
1) Overall depth for 3RS17 25 is approx. 90 mm. 2) Dimension for screw connection. 3) Dimension for Cage Clamp connection.
11/82
SIMIREL
Overview Version The 3TG10 contactors with 4 main contacts are available with screw-type terminals or with 6.3 mm to 0.8 mm tab connectors. The designs with screw-type terminals are suitable for use in any climate and safe from touch to DIN VDE 0106 Part 100. The 3TG10 contactors have a compact design. Their overall width is 36 mm. Selection and ordering data
Ratings Utilization category AC-1 maximum resistive load A Horsepower ratings of three-phase loads at 50 Hz 400 V kW
Application They are suitable for use in household appliances as well as for distribution boards in offices and residential buildings, owing to their hum-free construction. They can further be used in all areas where there is only a limited amount of space available, e.g. in air conditioners, heating systems, pumps and fans - basically in all simple electrical controls.
AC and DC operation EN 60 947-4-1 (VDE 0660 Part 102). Surge suppression The 3TG10 contactors are fitted with an integrated protective circuit for damping opening surges.
Overload and short-circuit protection The 3UA7 overload relay can be used for overload protection (see NS E catalogue, available in German). This applies both for contactor mounting and for mounting as a single unit. The data for short-circuit protection of the contactors without using an overload relay are provided in the technical data.
Main Rated control contacts supply voltage Us AC-3 maximum inductive current A Design
Order No.
List Price $
Weight approx.
Pack
NO NC
kg
Units
With screw connections, 4-pin for screwing and snapping onto 35 mm standard mounting rail hum-free
AC operation 3TG10 ..-0 20 5 8.4 4 230 V, 45 450 Hz 110 V, 45450 Hz 24 V, 45450 Hz 230 V, 45450 Hz 110 V, 45450 Hz 24 V, 45450 Hz 3TG10 10-0AL2 3TG10 10-0AG2 3TG10 10-0AC2 3TG10 01-0AL2 3TG10 01-0AG2 3TG10 01-0AC2 63.00 63.00 63.00 63.00 63.00 63.00 0.15 10
0.15
10
With tab connectors 6.3 x 0.8 mm, 4-pin for screwing and snapping onto 35 mm standard mounting rail hum-free
AC operation 3TG10 ..-1 16 5 8.4 4 230 V, 45 450 Hz 110 V, 45450 Hz 24 V, 45450 Hz 230 V, 45450 Hz 110 V, 45450 Hz 24 V, 45450 Hz 3TG10 10-1AL2 3TG10 10-1AG2 3TG10 10-1AC2 3TG10 01-1AL2 3TG10 01-1AG2 3TG10 01-1AC2 43.00 43.00 43.00 43.00 43.00 43.00 0.14 10
0.14
10
1) The links for paralleling can be reduced by one pole. The rated operational currents are valid for each pole. The links for paralleling are insulated.
11/83
SIMIREL
3 mill. 0.1 million 0.4 million 400 4 up to 300 25 ... +55 50 ... +80 IP 00, coil system IP 20 VA W 4.4 0.9 (hum-free) 4 0.85 to 1.1 x Us AC operation NO NC NO NC ms ms ms ms ms 10 ... 50 5 ... 45 20 ... 30 20 ... 30 10 to 15 5.1/5 and 3.5/10 7.9/5 and 5.2/10 10000 1000 500 1000 DC operation 11 ... 50 5 ... 45 19 ... 35 21 ... 39
Safe isolation acc. to DIN VDE 0106 Part 101 and A1 (draft 2/89) between coil and contacts Permissible ambient temperature
Degree of protection acc. to IEC 60 947-1 and IEC 60 529 (VDE 0470 Part 1) Power consumption of the coils (with coil in cold state and 1.0 x Us) AC operation 45 450 Hz p.f. DC operation Coil voltage tolerance Operating times (break-time = opening time + arcing time) Closing Opening Arcing time Shock resistance rectangular pulse sine pulse Operating frequency z in operating cycles per hour Rated operation AC and DC operation AC and DC operation No-load op. frequency for AC-1 for AC-2 for AC-3 closing time opening time opening time closing time
Short-circuit protection
Fuse links Utilisation category gL/gG acc. to IEC 60 947-4-1 (DIN VDE 0660 Part 102) Miniature circuit-breaker NH DIAZED NEOZED Type 3NA Type 5SB Type 5SE A A A 25 10 10
1) If the three main conducting paths are loaded with 20 A and I > 10 A for the fourth conducting
11/84
SIMIREL
Technical data Load ratings with AC
AC-2 and AC-3 utilisation categories Rated operational currents Ie up to 400 V
A kW 0.5
8.4 4
Ratings of motors with slipring or squirrel-cage rotor at 50 Hz and 60 Hz and at 400 V AC-5a utilisation category (permissible supply impedance: Switching gas discharge lamps per main conducting path at 50 Hz 230 V Rating per lamp Rated operational current per lamp Number of lamps Switching gas discharge lamps with correction, electronic ballast per main conducting path at 50 Hz 230 V Rating per lamp Capacitor Rated operational current per lamp Number of lamps AC-5b utilisation category, switching incandescent lamps per main conducting path at 50 Hz 230 V
2 x 26 2 x1
DC-3 and DC-5 utilisation categories, shunt and series motors Rated operational current Ie
L ( --R
3-phase 3 3 5 5
1 11/2
Short-circuit protection for overload, see "Overload relays and protective devices".
11/85
SIMIREL
Design Max. rated operational currents Ie/AC-1 (at 55 C) of contactors Max. conductor cross-sections mm2
Order No.
List Price $
Weight approx.
Pack
Type
PG 101
kg
Units
3-pole with terminal 1)3) 3TG10 4-pole with 3TG10 terminal 1)4) 50 25 3RT1 916-4BB41 15.00 0.02 1 40 25 3RT1 916-4BB31 12.35 0.013 1
52 42,5
35 5)
52 42,5
35 5)
62
62
NSB00786a
3,5x4,7
3,5x4,7
1) The links for paralleling can be reduced by one pole. The rated operational currents are valid for each pole. The links for paralleling are insulated.
2) 3) 4) 5)
Replacement type for 3TX44 90-2C. Replacement type for 3TX44 90-2A. Replacement type for 3TX44 90-2B. Can be snapped onto 35 mm standard mounting rails.
11/86