Design of Concrete Notes
Design of Concrete Notes
CHAPTER I. INTRODUCTION
A structure is any load bearing construction; in other words it is an organized assembly of connected parts designed
to provide mechanical resistance and stability.
Historical Perspective
Uganda being a former British protectorate has followed the British system of design; to 1972, the British system
was designing structures; using the elastic design/ Modular ratio method of designing.
CP 114
Multiplies a factor of a third (1 / 3) by the cube stress to obtain the permissible stress of concrete under
bending/flexure.
If divides the yield stress by factor of 1.8 to get the permissible stress in steel.
The permissible stress of steel was limited to 230 N / mm 2 whatever the grade of steel. This limitation aimed at
controlling the crack width since at the permissible stress of steel in tension, the surrounding concrete has cracked.
Page 1 of 9
CE311 STRUCTURAL DESIGN I CHAPTER I & II
Page 2 of 9
CE311 STRUCTURAL DESIGN I CHAPTER I & II
2.0 Introduction
Reinforced concrete consists of both concrete and steel.
Reinforced concrete is a strong durable building material that can be formed into many varied shapes and ranging
from a simple rectangular column, to a slender curved dome or shell, its utility and versatility are achieved by
combining the best features of concrete and steel.
Table 2-1: properties of steel and concrete
Property concrete steel
Strength in tension Poor Very good
Strength in compression Good Very good but slender bars will buckle
Strength in shear Fair Very good
Durability Good Poor, corrodes if unprotected
Fire resistance Good Poor-suffers rapid loss of strength at
high temperature
As seen from table 2-1, concrete is poor in tension, good in compression, and fair in shear. On the other hand, steel
is very good in tension, compression and shear. Thus, when they are combined, the steel is able to provide the
tensile strength and probably some of the shear strength while the concrete, strong in compression, protects the
steel to give durability and fire resistance.
i) In beams, slabs, and stair cases, where there is tension, the concrete must be reinforced by steel.
ii) In areas where the compression forces are very high such as columns, concrete must be reinforced by steel
and the steel must be tied and surrounded by concrete in order not to buckle.
Steel is poor in durability and fire resistance while concrete is good, therefore concrete must provide cover to
protect the steel.
2.1 Composite action
The tensile strength of concrete is only about 10 per cent of the compressive strength. Because of this , nearly all
reinforced concrete structures are designed on the assumption that the concrete does not resist any tensile forces.
Reinforcement is designed to carry these tensile forces, which are transferred from concrete to steel by bond which
is achieved by;
i) Using concrete with f ck ≥ 20 N / mm 2
ii) Well compacted concrete around reinforcement bars.
iii) Ribbed and twisted bars to give an extra mechanical grip
If this bond is not adequate, the reinforcing bars will just slip within the concrete and there will not be a composite
action. Composite action is achieved when there is perfect bond such that the strain in steel equals to that in the
adjacent concrete.
The coefficients of thermal expansion for steel and for concrete are nearly the same; therefore differential
expansion does not affect bond over normal temperature ranges.
Coefficients of Thermal Expansion, α
α for steel = 10 ×10 −6 per °C
α for concrete = (7 ~ 12) × 10 −6 per °C
Figure 2-1 illustrates the behavior of a simply supported beam subject to bending and shows the position of steel
reinforcement to resist the tensile forces, while the compression forces in the top of the beam are carried by the
concrete.
Load A
Compression
However, this cracking does not detract from the safety of the structure provided there is good reinforcement
bonding to ensure that the cracks are restrained from opening so that the embedded steel continues to be protected
from corrosion.
c <0
simplification
fc actual
cu fc peak stress
Modulus of Elasticity
The modulus of elasticity depends on;
i) Strength class of concrete
ii) Properties of aggregates used
iii) The mean value of the secant modulus Ecm for a particular class is obtained from table 3.2 of the code.
Page 4 of 9
CE311 STRUCTURAL DESIGN I CHAPTER I & II
Table 2.2 Values of the secant modulus of elasticity E cm (in kN/mm 2 ) (based on table 3.2 EC II)
Strength class C C12/15 C16/20 C20/25 C25/30 C30/37 C35/45 C40/50 C45/55 C50/60
E cm 26 27.5 29 30.5 32 33.5 35 36 37
The values in table 3.2 are based on the equation.
Ecm = 9.5[ f ck + 8]
1/ 3
where Ecm is in KN / mm 2
f ck is in N / mm 2 , f ck is strength at 28days
Thus Ecm is also for 28days.
The modulus of elasticity is required.
a) When investigating deflection of a structure.
b) When investigating cracking of a structure.
c) When considering both short term and long term effects of creep and shrinkage.
Poisson’s Ratio
For design purpose; the Poisson’s ratio for elastic strain is 0.2
0.2% proof
Yield stress
stress
stress
stress
B
stress
A low water-cement ratio will help to reduce drying shrinkage by keeping to a minimum the volume of moisture
that can be lost.
If the change in volume of the concrete is allowed to take place freely and without restraint, there will be no stress
change within the concrete. Restraint of the shrinkage, on the other hand, will cause tensile strains and stresses. The
restraint may be caused externally by fixity with adjoining members or friction against an earth surface, and
internally by the action of the steel reinforcement. For a long wall or floor slab, the restraint from adjoining
concrete may be reduced by constructing successive bays instead of alternate bays. This allows the free end of
every bay to contract before the next bay is cast.
When tensile stresses caused by shrinkage or thermal movement exceed the strength of concrete, cracking will
occur. To control cracking, steel reinforcement must be provided close to the concrete surface.
Reinforced concrete -
fully restrained
Page 6 of 9
CE311 STRUCTURAL DESIGN I CHAPTER I & II
Example 2.1
Calculation of shrinkage stresses in concrete that is restrained by reinforcement only
A member contains 1.0 per cent reinforcement, and the free shrinkage strain ε cs of the concrete is 200 × 10 −6 . For
steel, Es = 200 KN / mm 2 and for concrete Ecm = 15KN / mm 2 .
Determine the stresses in steel and concrete given that the member is restrained by reinforcement only.
Solution.
As A
1% = × 100 ⇒ s = 0.01
Ac Ac
From equation (3)
ε cs E s
stress in reinforcement f sc =
1+ nAs / Ac
Es 200
where Ecs = 200 × 10 −6 , Ecm = 15 KN / mm 2 , Es = 200 KN / mm 2 and ⇒ n = =
Ecm 15
200 × 10 −6 × 200 × 103
∴ f sc =
1 + 200 / 15 × 0.01
f sc = 35.3 N / mm 2 ( compression)
Page 7 of 9
CE311 STRUCTURAL DESIGN I CHAPTER I & II
As
stress in reinforcement f ct = f sc
Ac
= 0.01 × 35.3
= 0.35 N / mm 2 ( tension)
Note: The stresses produced in members free from external restraint are generally small as example 2.1, and can be
easily withstood both by the steel and the concrete.
Example 2.2
Calculation of fully restrained shrinkage stresses
If the member in example 2.1 above was fully restrained, determine the tensile stress in concrete.
Solution.
If the member in example 2.1 was fully restrained, the stress in the concrete would be given by
f ct = ε ct Ecm
where
ε ct = ε cs = 200 × 10 −6
then
f ct = 200 × 10 −6 × 15 × 103
= 3.0 N / mm 2
2.4 Creep φ
Creep is the continuous deformation of a member under sustained load. It is a phenomenon associated with many
materials, but it is particularly evident with concrete. It depends on;
i) The aggregates and the mix design (Composition of concrete).
ii) Ambient humidity
iii) Member cross-section.
iv) Age at first loading.
v) Duration of loading.
vi) Magnitude of loading.
Page 8 of 9
CE311 STRUCTURAL DESIGN I CHAPTER I & II
Values in table 2-4 (Table 3.3 of euro code II) can be considered as the final creep coefficient φ (∞, t o ) of a normal
weight concrete subjected to a compressive stress not exceeding 0.45 f ck .
Page 9 of 9
CE311 STRUCTURAL DESIGN I CHAPTER III
3.0 Introduction
Limit state design of an engineering structure must ensure that
(1) under the worst loadings the structure is safe
(2) during normal working conditions the deformation of the members does not detract from the appearance,
durability or performance of the structure.
Three methods have been developed for design of structures.
Page 1 of 19
CE311 STRUCTURAL DESIGN I CHAPTER III
i) Robustness
To be robust means that the layout of the structure should be such that damage to a small area or failure of a single
element will not lead to progressive collapse.
To achieve robustness;
i) The structure must be able to resist a minimum horizontal load.
ii) The elements of the structure must be provided with ties.
Design of Ties
• Detailed design information for ties is not given in Euro code II.
• NAD-National Application Document recommends that the design method for BS8110 should be used.
• The design of ties is given in clause 3.12.3 of BS8110.
The general stability and robustness of a building structure can be increased by providing reinforcement acting as
ties. These ties should act both vertically between roof and foundations, and horizontally around and across each
floor (figure 3.2), and all external vertical load-bearing members should be anchored to the floors and beams.
The types of ties are;
Vertical ties
Horizontal ties
Page 2 of 19
CE311 STRUCTURAL DESIGN I CHAPTER III
Horizontal ties
Horizontal ties should be provided for all buildings, irrespective of height, in three ways:
1. Peripheral ties.
2. Internal ties.
3. Column and Wall ties.
a) Peripheral ties.
• Peripheral tie must be provided by reinforcement at each floor or roof level.
• Peripheral tie must be continuous.
• This reinforcement must lie within 1.2m from the edge of building or within the perimeter wall.
• It should be capable of resisting a force of at least Ft .
Ft = (20 + 4no ) or 60 KN whichever is less.
no = number of storeys in structure.
b) Internal Ties
• Internal ties should be provided at each floor in two perpendicular directions.
• They should be continuous throughout their length.
• They should be anchored at each end, either to the peripheral tie or to the continuous column or wall ties.
• They may be located as follows;
a) Spread evenly in slabs
b) Grouped in beams
c) Grouped in walls. Where walls are used, the tie reinforcement must be within 0.5m of the top or bottom of
the floor slab.
Internal ties should be able to resist a tensile force T.
F (G + Qk ) Lr
T > t k or 1.0 Ft whichever is greater.
7.5 5
where (Gk + Qk ) = the characteristic load per m 2 of the floor considered.
Lr = the greatest horizontal distance in the direction of the tie between the centres of vertical load-
bearing members.
Page 3 of 19
CE311 STRUCTURAL DESIGN I CHAPTER III
If the ties are grouped in walls or beams, their maximum spacing should be limited to 1.5 Lr .
Spacing ≥ 1.5 Lr
Transverse beams
7m
4 bays @ 6.5m=26m
ii) Stability
Building structures are classified into two types.
a) Braced, and
b) Unbraced
A braced structure is one that resists lateral loads by means of bracing. Lateral loads include;
• wind loads, and
• seismic loads (earthquake loads)
Bracing in RC structures include;
• Shear walls
• RC lift shafts
• RC stair wells
The bracing must be able to transmit the horizontal loads down to foundation.
Page 5 of 19
CE311 STRUCTURAL DESIGN I CHAPTER III
iii) Strength
The structure should be adequately strong to carry all applied loads without collapse.
(b) Serviceability Limit State
Generally the most important serviceability limit states are:
i) Deflection- the appearance or efficiency of any part of the structure must not be adversely affected by
deflections nor should the comfort of the building users be adversely affected.
ii) Cracking- local damage due to cracking and spalling must not affect the appearance, efficiency or durability of
structure.
iii) Durability-This must be considered in terms of the proposed life of the structure and its conditions of exposure.
This is the resistance to wear, tear and environmental effects with time. Any reinforced concrete
structure must be designed to protect the embedded steel. Thus the durability of concrete is influenced
by;
a) Exposure conditions
b) Concrete quality and workmanship
c) Cover to reinforcement
d) Width of any crack
If durability is neglected, it will lead to increased expenditures on;
i) Inspection
ii) maintenance
iii) repair
Durability in R.C concerns the selection of the appropriate concrete grade and cover, for the conditions of;
a) Environmental exposure
b) Protection of reinforcement against a rapid rise in temperature and resultant loss of strength.
Exposure conditions are given in table 4.1 of the code and Minimum cover requirements for exposure conditions
are given in table 4.2.
Table 3-1 (Table 4.1 of Euro code II) Exposure classes related to environmental conditions
Exposure class Example of environmental conditions
1
dry environment interior of buildings for normal habitation or offices a
2 a - interior of buildings where humidity is high (e.g. laundries)
without - exterior components
humid frost - components in non-aggressive soil and/or water
environment b - exterior components exposed to frost
With frost - components in non-aggressive soil and/or water and exposed to frost
- interior components when the humidity is high and exposed to frost
3
humid environment with frost and Interior and exterior components to frost and de-icing agents
de-icing salts
4 a - components completely or partially submerged in seawater, or in the
without splash
frost - components in saturated salt air (coastal area)
seawater environment b - components partially submerged in seawater or in the splash zone and
With frost exposed to frost
- components in saturated salt air and exposed to frost
The following classes may occur alone or in combination with the above classes:
5 a - slightly aggressive chemical environment (gas, liquid or solid)
aggressive chemical - aggressive industrial atmosphere
environment b b moderately aggressive chemical environment (gas, liquid or solid)
c highly aggressive chemical environment (gas, liquid or solid)
a
This exposure class is valid only as long as during construction the structure or some of its components is not
exposed to more severe conditions over a prolonged period of time.
b
Chemically aggressive environments are classified in ISO/DP 9690. The following equivalent exposure
conditions may be assumed:
Exposure class 5a: ISO classification A1G,A1L,A1S
Exposure class 5b: ISO classification A2G,A2L,A2S
Exposure class 5c: ISO classification A3G,A3L,A3S
Page 6 of 19
CE311 STRUCTURAL DESIGN I CHAPTER III
Table 3-2 (Table 4.2 of Euro code II) Minimum cover requirement for normal weight concrete 1)
Exposure class, according to Table 4.1
1 2a 2b 3 4a 4b 5a 5b 5c
2)
Reinforcement 15 20 25 40 40 40 25 30 40
Minimum cover (mm)
Prestressing steel 25 30 35 50 50 50 35 40 50
NOTES
1. In order to satisfy the provisions of 4.1.3.3 P(3), these minimum values for cover should be associated with
particular concrete qualities, to be determined from Table 3 in ENV 206.
2. For slab elements, a reduction of 5mm may be made for exposure classes 2-5.
3. A reduction of 5mm may be made where concrete of strength class C40/50 and above is used for reinforced
concrete in exposure classes 2a-5b, and for prestressed concrete in exposure classes 1-5b. However, the minimum
cover should be less than that for Exposure Class 1 in Table 4.2.
4. For exposure class 5c, the use of a protective barrier, to prevent direct contact with the aggressive media, should
be provided.
cover
bundle
Page 7 of 19
CE311 STRUCTURAL DESIGN I CHAPTER III
• Nominal Cover
This is the cover used in design and specify on drawing and nominal cover is given by nominal cover which is
equal to minimum cover + ∆h .
where ∆h is Tolerance on cover to reinforcement and given by; 5mm ≤ ∆h ≤ 10mm .
∆h depends on;
i) Type and size of structural element/member.
ii) Type of construction.
iii) Standards of workmanship.
iv) Quality control
v) Detailing practice.
f m = mean strength, f m =
∑f
n
f =values of cube strength
n = number of cubes tested.
σ = standard deviation, σ is a measure of quality control
1/ 2
∑ ( f − fm )2
σ =
n
The relationship between characteristic and mean values accounts for variations in results of test specimens and
will, therefore, reflect the method and control of manufacture, quality of constructions, and nature of the material.
Mean strength ( fm )
Characteristic
strength ( f k )
number of
test specimens
1.64
strength
Fig.3-4 Normal frequency distribution of strengths
Page 8 of 19
CE311 STRUCTURAL DESIGN I CHAPTER III
Table 3-3 shows the actual strength classes commonly used in reinforced concrete design.
Table 3-3 Concrete strength classes, characteristic compressive strength f ck (cylinders) , mean tensile strength
f ctm , and characteristic tensile strength f ctk of the concrete (in N / mm 2 ) (based Table 3.1,EC 2)
Strength Class of
C12/15 C16/20 C20/25 C25/30 C30/37 C35/45 C40/50 C45/55 C50/60
Concrete
f ck 12 16 20 25 30 35 40 45 50
f ck ,cube 15 20 25 30 37 45 50 55 60
f ctm 1.6 1.9 2.2 2.6 2.9 3.2 3.5 3.8 4.1
f ctk 0.05 1.1 1.3 1.5 1.8 2.0 2.2 2.5 2.7 2.9
f ctk 0.95 2.0 2.5 2.9 3.3 3.8 4.2 4.6 4.9 5.3
BS 8110 recommends that design should be based on the characteristic strength of the reinforcement ( f y ) and
gives typical values for mild steel and high yield steel reinforcement, the two reinforcement types available in the
UK, of 250 Nmm −2 and 500 Nmm −2 respectively. High-yield reinforcement is mostly used in practice nowadays.
In Euro Code II, Grade 500 ( 500 N / mm 2 characteristic strength) has replaced Grade 250 and Grade 460
reinforcing steel throughout Europe.
Grade 250 bars are hot-rolled mild-steel bars which usually have a smooth surface so that the bond with concrete
is by adhesion only. This type of bar can be more readily bent, so they have in the past been used where small
radius bends are necessary, such as links in narrow beams or columns, but plain bars are not now recognized in the
European Union and they are no longer available for general use in the UK.
High-yield bars are manufactured with a ribbed surface or in the form of a twisted square surface. Square twisted
bars have inferior bond characteristics and have been used in the past, although they are now obsolete. Deformed
bars have a mechanical bond with the concrete. The bending of high-yield bars through a small radius is liable to
cause tension cracking of the steel, and to avoid this the radius of the bend should not be less than two times the
nominal bar size for small bars( ≤ 16mm ). Ribbed high yield bars may be classified as:
Class A- which is normally associated with small diameter( ≤ 12mm ) cold-worked bars used in mesh and fabric.
This is the lowest ductility category and will include limits on moment redistribution which can be
applied and higher quantities for fire resistance.
Class B- which is most commonly used for reinforcing bars.
Class C- high ductility which may be used in earthquake design or similar situation.
Table 3-5(Table 5,Eurocode II): Differences between current British Standards and EN10080
Property BS4449 and BS4483 EN10080
2
Grade 460 N / mm 500 N / mm 2
Specific characteristic yield strength
Grade 250 N / mm 2 Not included
Bond strength for;
i) Ribbed bars/wires Deformed type 2 High bond
ii) Twisted bars Deformed type 1 Not included
iii) Plain bars Round plain bars Not included
Table 3-6
CP110 BS8110 EC2
High yield 460 Ribbed –T
410 High bond 500
425 Y 460 Twisted Y
460
485
Mild steel 460-R 250-R N/A
However in the UK, they still design using EC 2 but use T and Y bars.
Table 3-7 Tensile and other properties of steel for the reinforcement of concrete
Ductility Class
Property
A B C
−2
Characteristic yield strength, f yk ( Nmm ) 500
Young’s modulus KNmm −2 200
Characteristic strain at ultimate force, ε uk (%) ≥ 2.5 ≥ 5.0 ≥ 7.5
Page 10 of 19
CE311 STRUCTURAL DESIGN I CHAPTER III
characteriatic strength f
Design strength = = k
partial factor of safety γ m
Page 12 of 19
CE311 STRUCTURAL DESIGN I CHAPTER III
beam
permanent load 20 KN/m
A B C
foundation
(a) 6m 2m
1.1 permanent
0.9 permanent load load
A B C
A 7 per cent increase in the variable action will not endanger the structure, since the actual uplift will only be 7.3
KN as calculated previously. In fact in this case it would require an increase of 61 per cent in the load before the
uplift would exceed the weight of a 38 KN foundation.
Parts (a) and (b) of example 3.3 illustrate how the limit state method of design can ensure a safer result when the
stability or strength of a structure is sensitive to a small numerical difference between the effects of two opposing
action of a similar magnitude.
Combination of actions(Loads)
In general, the design value of an action ( Fd ) is obtained by multiplying the representative value ( Frep ) by the
appropriate partial safety factor for actions ( γ f ):
Fd = γ f × Frep (3.1)
Page 14 of 19
CE311 STRUCTURAL DESIGN I CHAPTER III
Tables 3.13 and 3.14 show the recommended values of partial safety factor for permanent, γ G , and variable
actions, γ Q , for the ultimate limit states of equilibrium (EQU) and strength (STR). It can be seen that the maximum
values of γ G and γ Q are 1.35 and 1.5 respectively. The comparable values in BS 8110 are 1.4 and 1.6. It can also
be seen that the partial safety factors for actions depend on a number of other aspects including the category of
limit state as well as the effect of the action on the design situation under consideration. For example, when
checking for the limit states of equilibrium and strength, the maximum values of γ G are 1.1 and 1.35, respectively.
However, when checking for equilibrium alone, γ G is taken to be 1.1 if the action increases the risk of instability
(unfavourable action) or 0.9 if the action reduces the risk of instability (favourable action). For a given limit state
several combinations of loading may have to be considered in order to arrive at the value of the design action on
the structure (see Table 3.13).
In equation 3.1, Frep may be the characteristic value of a permanent or leading variable action ( Fk ), or the
accompanying value (Ψ Fk ) of a variable action. In turn, the accompanying value of a variable action may be the
combination value ( Ψo Fk ), the frequent value ( Ψ1 Fk ) or the quasi-permanent value ( Ψ2 Fk ). The frequent
value and the quasi permanent values are used to determine values of accidental actions, e.g. impact and
explosions, and to check serviceability criteria (deflection and cracking). The combination value is given by
Combination value = Ψo Fk (3.2)
where Ψo is the combination factor obtained from Table 3.12 and is a function of the type of variable action. The
factor Ψo has been introduced to take account of the fact that where a structure is subject to, say, two independent
variable actions, it is unlikely that both will reach their maximum value simultaneously. Under these circumstances,
it is assumed that the ‘leading’ variable action (i.e. Qk .1 ) is at its maximum value and any ‘accompanying’ variable
actions will attain a reduced value, i.e. ΨoQk , i , where i > 1. Leading and accompanying variable actions are
assigned by trial and error as discussed below.
Table 3-13 Load combinations and partial safety/combination factors for the ultimate limit state of strength
Load Type
Limit state Permanent, G k Variable, Qk Wind, Wk
Unfavourable Favourable Unfavourable Favourable Unfavourable
Equilibrium 1.10 0.9 1.5 0 1.5 Ψ0
Page 15 of 19
CE311 STRUCTURAL DESIGN I CHAPTER III
Table 3-14 Load combinations and partial safety/combination factors for the ultimate limit state of strength
Load Type
Limit state/Load combination Permanent, G k Variable, Qk Wind,
Unfavourable Favourable Unfavourable Favourable Wk
Table 3-15 Load Combinations and Partial Safety Factors γ f at Serviceability Limit State
Load Combination Permanent Load, Gk Variable Load, Qk Wind Load, Wk
Permanent + Variable 1.0 1.0 -
Permanent + Wind 1.0 - 1.0
Permanent + Variable + Wind 1.0 0.9 0.9
COMBINATION EXPRESSIONS
• The design value of action effects, E d , assuming the structure is subjected to both permanent and a single
variable action (e.g. dead load plus imposed load or dead load plus wind load) can be assessed using the following
expression
∑
E d = γ G , jGk , j + γ Q ,1Qk ,1
j ≥1
(3.3)
Using the partial safety factors given in Table 3.14, the design value of the action effect is given by
E d = 1.35Gk + 1.5Qk
(load combinations 1 and 2, Table 3.14)
• The design value of an action effect due to permanent and two (or more) variable actions, e.g. dead plus imposed
and wind load, is obtained from equation 3.4.
∑j ≥1
∑
E d = γ G , jGk , j + γ Q ,1Qk ,1 + γ Q ,iψ 0,i Qk ,i
i >1
(3.4)
Note that this expression yields two (or more) estimates of design actions and the most onerous should be selected
for design. For example, if a structure is subjected to permanent, office and wind loads of G k , Qk and Wk the
values of the design actions are:
E d = 1.35Gk , j + 1.5Qk + 1.5 × 0.5Wk
(load combinations 3(b), Table 3.14)
and
E d = 1.35Gk , j + 1.5 × 0.7Qk + 1.5Wk
(load combinations 3(c), Table 3.14)
Figure 3.6 illustrates how the factors in table 3-10 and 3-12 can be applied when considering the stability of the
office building shown for overturning about point B. Figure 3-6(a) treats the wind load ( Wk ) as the leading
variable action and the live load ( Qk ) on the roof as the accompanying variable action. Figure 3-6(b) considers the
live load as the leading variable action and the wind as the accompanying variable action.
Page 16 of 19
CE311 STRUCTURAL DESIGN I CHAPTER III
B B
(a) (b)
Figure 3.6 Wind and imposed load acting on an office building-stability check
Equations 3.3 and 3.4 are based on expression 6.10 in EN 1990. This document also includes two alternative
expressions, namely 6.10a and 6.10b (reproduced as equations 3.5 and 3.6 respectively) for calculating the design
values of actions, use of which may improve structural efficiency, particularly for heavier structural materials such
as concrete.
∑j ≥1
∑
E d = γ G , jGk , j + γ Q ,1ψ 0,1Qk ,1 + γ Q ,iψ 0,i Qk ,i
i >1
(3.5)
Wind Loads
The following factors are considered;
i) The basic wind speed, V which depends on the location in the country.
ii) The design wind speed Vs = VS1 S 2 S 3
S1 = topography factor normally taken as in UK.
S 2 = depends on ground roughness, building size and height above the ground.
S 3 = statistical factor normally taken as 1.
• Ground roughness is given in four categories e.g. category 3 is the location in the suburbs of the city.
• The building size is in three classes e.g. a, b and c .
• The height refers to the height of the building.
• The wind load increases with height.
iii) The Dynamic pressure q = 0.613Vs2 N / mm 2 is the pressure on the surface normal to the wind. It is
modified by the dimensions of the building and openings in the building.
iv) Pressure coefficient
The pressure coefficients are given as;
• external pressure coefficients denoted by C pe . This depends on the dimensions and roof angle.
• Internal pressure coefficients which accounts for suctions inside the building, C pi .
Page 17 of 19
CE311 STRUCTURAL DESIGN I CHAPTER III
Example 3.4 Design actions for simply supported beam (EN 1990)
A simply supported beam for an office building has a span of 6 m. Calculate the values of the design bending
moments, M E ,d , assuming
(a) the beam supports uniformly distributed permanent and variable actions of 5 kNm −1 and 6 kNm −1 respectively
(b) in addition to the actions described in (a) the beam also supports an independent variable concentrated load of
20 kN at mid-span.
LOAD CASE A
g k =5KN/m ; q k =6KN/m
L=6m
Since the beam is subjected to only one variable action use equation 3.3 to determine E d where
E d = ∑ γ G , jGk , j + γ Q ,1Qk ,1
j ≥1
Qk =20KN
g k =5KN/m ; q k =6KN/m
L=6m
The extra complication here is that it is not clear if q k or Qk is the leading variable action. This can only be
determined by trial and error. This time use equation 3.4 to evaluate E d , since there are two independent variable
actions are present.
Assuming q k is the leading variable action gives
E d = ∑ γ G , jGk , j + γ Q ,1Qk ,1 + ∑ γ Q ,iψ 0,i Qk ,i
j ≥1 i >1
Page 18 of 19
CE311 STRUCTURAL DESIGN I CHAPTER III
Page 19 of 19
CE311 STRUCTURAL DESIGN I CHAPTER IV
4.0 Introduction
A reinforced concrete structure is a combination of beams, columns, slabs and walls, rigidly connected together to
form a monolithic frame. Each individual member must be capable of resisting the forces acting on it, so that the
determination of these forces is an essential part of the design process. The full analysis of a rigid concrete frame is
rarely simple; but simplified calculations of adequate precision can often be made if the basic action of the structure
is understood.
There are several methods, of structural analysis, but the common ones are;
i) Moment distribution for manual methods
ii) Computer plain frame programs based on the matrix stiffness method of analysis
iii) Moment coefficients
Since the design of a reinforced concrete member is generally based on the ultimate limit state, the analysis is
usually performed for loadings corresponding to that state.
4.1 Actions
The actions (loads) on a structure are divided into two types: permanent actions, and variable (or imposed) actions.
Permanent action are those which are normally constant during the structure’s life. Variable actions, on the other
hand, are transient and not constant in magnitude, as for example those due to wind or to human occupants.
Permanent actions
Permanent actions include the weight of the structure itself and all architectural components such as exterior
cladding, partitions and ceilings. Equipment and static machinery, when permanent fixtures, are also often
considered as part of the permanent actions.
For most reinforced concretes, a typical value for the self-weight is 25KN per cubic metre, but a higher density
should be taken for heavily reinforced or dense concrete. In the case of a building, the weights of any permanent
partitions should be calculated from the architects’ drawings. A minimum partition loading equivalent to 1.0KN per
square metre is often specified as a variable action, but this is only adequate for lightweight partitions.
Variable actions
Variable actions are more difficult to determine accurately. For many of them, it is only possible to make
conservative estimates based on standard codes of practice or past experience. Examples of variable actions are: the
weights of its occupants, furniture, or machinery; the pressures of wind, the weight of snow, and of retained earth
or water; and the forces caused by thermal expansion or shrinkage of the concrete.
Although the wind load is a variable action, it is kept in a separate category when its partial factors of safety are
specified, and when the load combinations on the structure are being considered.
A C
Page 1 of 17
CE311 STRUCTURAL DESIGN I CHAPTER IV
Load combination 2, permanent + wind load is used to check the stability of a structure. A load combination of
permanent + variable + wind load could have the arrangement shown in figure 3.6.
Figure 4-2 shows the patterns of vertical loading on a multi-span continuous beam to cause (i) maximum design
moments in alternate spans and maximum possible hogging moments in adjacent spans, (ii) maximum design
hogging moments at support A, and (iii) the design hogging moment at support A as specified by the EC2 code for
simplicity.
1.35G k + 1.5Q k
1.35G k 1.35G k
A
Non-continuous beams
One-span, simply supported beams or slabs are statically determinate and the analysis for bending moments and
shearing forces is readily performed manually. For the ultimate limit state we need only consider the maximum
load of 1.35G k + 1.5Qk on the span.
Page 2 of 17
CE311 STRUCTURAL DESIGN I CHAPTER IV
1.35 40=54 KN
4.0 m
124.5 KN 27
27
124.5 KN
(b) Shearing Force Diagram
151.5 KNm
Figure 4-3 shows the values of ultimate load required in the calculation of the shearing forces and bending
moments.
54 195
Maximum shear force = + = 124.5 KN
2 2
54 × 4 195 × 4
Maximum bending moment = + = 151.5 KNm
4 8
The analysis is completed by drawing the shearing-force and bending-moment diagrams which would later be used
in the design and detailing of the shear and bending reinforcement.
Continuous beams
The method of analysis for continuous beams may also be applied to continuous slabs which span in one direction.
A continuous beam should be analysed for the loading arrangements which give the maximum stresses at each
section. The analysis to calculate the bending moments can be carried out manually by moment distribution or
equivalent methods, but tabulated shear and moment coefficient may be adequate for continuous beams having
approximately equal spans and uniformly distributed loads.
Continuous beams – the general case
Having determined the moments at the supports by, say, moment distribution, it is necessary to calculate the
moments in the spans and also the shear forces on the beam.
For a uniformly distributed load, the equations for the shears and the maximum span moments can be derived from
the following analysis.
Load = w/metre
A B
VAB S.F.D
VBA
MAB M BA
--
-- B.M.D
+ M max a2
a1
a3
Using the sign convention of figure 4-4 and taking moments about support B;
wL2
V AB L − + M AB − M BA = 0
2
therefore
wL ( M AB − M BA )
V AB = − (4.1)
2 L
and
VBA = wL − V AB (4.2)
Maximum span moment M max occurs at zero shear, and distance to zero shear
V AB
a3 = (4.3)
w
therefore
2
V AB
M max = + M AB (4.4)
2w
The points of contraflexure occur at M = 0 , that is
wx 2
V AB x − + M AB = 0
2
where x the distance from support A. Taking the roots of this equation gives
2
V AB ± (V AB + 2 wM AB )
x=
w
so that
2
V AB − (V AB + 2 wM AB )
a1 = (4.5)
w
and
2
V AB + (V AB + 2 wM AB )
a2 = L − (4.6)
w
Example 4.2 Analysis of a continuous beam
The continuous beam shown in figure 4-5 has a constant cross-section and supports a uniformly distributed
permanent action including its self-weight of G k = 25 KN / m and a variable action Qk = 10 KN / m .
The critical loading patterns for the ultimate limit state are shown in figure 4-5 where the ‘stars’ indicate the region
of maximum moments, sagging or possible hogging.
G k = 25 KN/m Q k = 10 KN/m
A B C D
6m 4m 6m
Page 4 of 17
CE311 STRUCTURAL DESIGN I CHAPTER IV
Table 4.1 is the moment distribution carried out for the first loading arrangement: simpler calculations would be
3I
required for each of the remaining load cases. It should be noted that the reduced stiffness of has been used for
4L
the end spans.
Table 4-1 Moment distribution for the first loading case
A B C D
Stiffness (k) 3 I I 3 I
4 L L 4 L
= 3 1 = 0.125 = 1 = 0.125 = 3 1 = 0.125
4 6 4 4 6
Distr. factors 0.125
0.125+0.25
= 1/3 2/3 2/3 1/3
Load (kN) 292 135 292
-292 6 + 135 4 292 6
F.E.M. 0 -- 12 + 0
8 8
0 -219.4 + 45.0 - 45.0 + 219.4 0
Balance +58.1 + 116.3 - 116.3 -58.1
The shearing forces, the maximum span bending moments, and their positions along the beam, can be calculated
using the formulae previously derived. Thus for the first loading arrangement and span AB, using the sign
convention of figure 4-4:
Load ( M AB − M BA )
Shear V AB = −
2 L
292.5 132.5
= − = 124.2 KN
2 6.0
VBA = Load − V AB
= 292.5 − 124.2 = 168.3 KN
2
V AB
Maximum moment, span AB = + M AB
2w
where w = 292.5 / 6.0 = 48.75 KN / m. Therefore:
124.2 2
M max = + 0 = 158.2 KNm
2 × 48.75
V
Distance from A, a3 = AB
w
124.2
= = 2.55 m
48.75
The bending-moment diagrams for each of the loading arrangements are shown in figure 4-6, and the
corresponding shearing-force diagrams are shown in figure 4-7. the individual bending-moment diagrams are
Page 5 of 17
CE311 STRUCTURAL DESIGN I CHAPTER IV
combined in figure 4-8a to give the bending-moment design envelope. Similarly, figure 4-8b is the shearing-force
design envelope. Such envelope diagrams are used in the detailed design of the beams.
In this example, simple supports with no fixity have been assumed for the end supports at A and D. Even so, the
sections at A and D should be designed for a hogging moment due to a partial fixity equal to 25 per cent of the
maximum moment in the span, that is 158 / 4 = 39.5 KNm .
133 133
(1) 65
158 158
108 108
11
(2)
103 103
151
100
(3)
151 109
151
100
(4)
109
151
Fig.4-6 Bending-moment diagrams (KNm)
124 168
67.5
(1)
67.5
124
168
83 97.5 119
(2)
119 97.5 83
(3)
85 85
171
171
85
85
(4)
Page 6 of 17
CE311 STRUCTURAL DESIGN I CHAPTER IV
151 151
65
KNm
11
158 158
124 110 171
110 124 KN
171
0.45 F 0.55 F
(b)
Shearing Forces
0.60 F 0.55 F
Page 7 of 17
CE311 STRUCTURAL DESIGN I CHAPTER IV
H2
(1)
H1
H2
(2)
H1
H2
(3)
H1
The substitute frame 1 in figure 4.11 consists of one complete floor beam with its connecting columns (which are
assumed rigidly fixed at their remote ends). An analysis of this frame wil1 give the bending moments and shearing
forces in the beams and columns for the floor level considered.
Substitute frame 2 is a single span combined with its connecting columns and two adjacent spans, all fixed at their
remote ends. This frame may be used to determine the bending moments and shearing forces in the central beam.
Provided that the central span is greater than the two adjacent spans, the bending moments in the columns can also
be found with this frame.
Substitute frame 3 can be used to find the moments in the columns only. It consists of a single junction, with the
remote ends of the members fixed. This type of subframe would be used when the beams have been analysed as
continuous over simple supports.
In frames 2 and 3, the assumption of fixed ends to the outer beams over-estimates their stiffnesses. These values are,
therefore , halved to allow for the flexibility resulting from continuity.
The various critical loading arrangements to produce maximum stresses have to be considered. In general these
loading arrangements for the ultimate limit state as specified by the code are:
(1) Alternate spans loaded with total ultimate load ( 1.35Gk + 1.5Qk ) and all other spans loaded with minimum
dead load ( 1.35Gk ); this loading will give maximum span moments and maximum column moments.
(2) All spans loaded with the total ultimate load ( 1.35Gk + 1.5Qk ) to provide the design moment at the supports.
When considering the critical loading arrangements for a column, it is sometimes necessary to include the case of
maximum moment and minimum possible axial load, in order to investigate the possibility of tension failure caused
by the bending.
Page 8 of 17
CE311 STRUCTURAL DESIGN I CHAPTER IV
J K L M
3.5m
A B C D
4.0m
Beam
600 300
E F G H
350
300
Typical column section
Fig 4.12 Substitute frame
• Stiffnesses, k
Beam Columns
3
0.3 × 0.6 0.3 × 0.353
I= = 5.4 × 10 −3 m 4 I= = 1.07 × 10 −3 m 4
12 12
Spans AB and CD Upper
−3
5.4 × 10 1.07 × 10 −3
k AB = k CD = = 0.9 × 10 −3 kU = = 0.31× 10 −3
6.0 3.5
Span BC Lower
−3
5.4 × 10 1.07 × 10 −3
k BC = = 1.35 × 10 −3 kL = = 0.27 × 10 −3
4.0 4.0
kU + k L = (0.31 + 0.27)10 −3 = 0.58 × 10 −3
• Distribution factors
Joints A and D
∑ k = 0.9 + 0.58 = 1.48
0.9
D.F. AB = D.F .DC = = 0.61
1.48
0.58
D.F. cols = = 0.39
1.48
Joints B and C
∑ k = 0.9 + 1.35 + 0.58 = 2.83
0.9
D.F. BA = D.F .CD = = 0.32
2.83
1.35
D.F. BC = D.F .CB = = 0.48
2.83
0.58
D.F. cols = = 0.20
2.83
The critical loading arrangements for the ultimate limit state are identical to those for the continuous beam in
example 4.2, and they are illustrated in figure 4.5. The moment distribution for the first loading arrangement is
shown in table 4.2. In the table, the distribution for each upper and lower column have been combined, since this
simplifies the layout for the calculations.
Page 9 of 17
CE311 STRUCTURAL DESIGN I CHAPTER IV
Bal. 56.9 89.1 32.3 20.2 48.5 48.5 20.2 32.3 89.1 56.9
Bal. 6.3 9.9 22.0 13.8 33.0 33.0 13.5 22.0 9.9 6.3
Bal. 4.3 6.7 6.9 4.3 10.3 10.3 4.3 6.9 6.7 4.3
Bal. 1.3 2.1 2.8 1.7 4.1 4.1 1.7 2.8 2.1 1.3
M (kN m) 68.8 68.8 135.0 40.0 95.0 95.0 40.0 135.0 68.8 68.8
The shearing forces and the maximum span moments can be calculated from the formulae of section Continuous
beams (page 3). For the first loading arrangement and span AB:
load ( M AB − M BA )
Shear V AB = −
2 L
292.5 (−68.8 + 135.0)
= − = 135KN
2 6.0
VBA = load − V AB
= 292.5 − 135 = 157 KN
2
V AB
Maximum moments, span AB = + M AB
2w
135 2
= − 68.8 = 118KNm
2 × 48.75
V 135
Distance from A, a3 = AB = = 2.8m
w 48.75
Figure 4.13 shows the bending moments in the beams for each loading arrangement; figure 4.14 shows the shearing
forces. These diagrams have been combined in figure 4.15 to give the design envelopes for bending moments and
shearing forces.
The moment in each column is given by
k col
M col = ∑ M col ×
∑ k col
Thus, for the first loading arrangement and taking ∑M col from table 4.2 gives
0.31
Column moment M AJ = 68.8 × = 37 kNm
0.58
0.27
M AE = 68.8 × = 32 kNm
0.58
Page 10 of 17
CE311 STRUCTURAL DESIGN I CHAPTER IV
0.31
M BK = 40 × = 21 kNm
0.58
0.27
M BF = 40 × = 19 kNm
0.58
This loading arrangement gives the maximum column moments, as plotted in figure 4.16.
135 157
135 135
69 95 95 69
67.5
28
(1) (1)
67.5
(2) (2)
10
97.5 91
77 77
147 133 111
115 102 111
106
67 80
46
(3) (3)
1
79 89 92
114
160 160
147
102 115
80 67 92 89
46
(4) (4)
1
79 106
114 111
133
Fig 4.13 Beam bending moment diagrams (kNm) Fig.4.14 Beam shearing-force diagrams (kN)
147 147
69 115 115 69
28
kN m
10
118 118
37 21 21 37
160 32 32
135 19 19
106
kN
106
135
160
Fig 4.15 Bending-moment and shearing-force Fig.4.16 Column bending moments (kNm)
envelopes
Page 11 of 17
CE311 STRUCTURAL DESIGN I CHAPTER IV
3.5m
1.35G k + 1.5 Q k halved. Thus
1.35G k
= 292.5kN = 135kN 1
A B C k AB = × 0.9 × 10 −3 = 0.45 × 10 −3
2
4.0m
1
k BC = × 1.35 × 10 −3 = 0.675 × 10 −3
2
−3
Upper column kU = 0.31 × 10
6.0m 4.0m
Lower column k L = 0.27 × 10 −3
Fig 4.17 Substitute frame ∑ k = (0.45 + 0.675 + 0.31 + 0.27) ×10 −3
= 1.705 × 10 −3
6
Fixed-end moment M BA = 292.5 × = 146 kNm
25
4
Fixed-end moment M BC = 135 × = 45 kNm
25 18
Column moments are 16 kNm
0.31
Upper column M U = (146 − 45) × = 18 kNm
1.705
0.27
Lower column M L = (146 − 45) × = 16 kNm
1.705
Fig 4.18 Column moments
The column moments are illustrated in figure 4.18. They should be compared with the corresponding moments for
the internal column in figure 4.16.
Page 12 of 17
CE311 STRUCTURAL DESIGN I CHAPTER IV
5.25kN
3.5
10.5kN 4 th
3.5
10.5kN
3.5
11.25kN 2 nd
4.0
12.0kN 1 st
4.0
6.0kN
CL
1.75
s
H1= 0.93 H2= 1.70 H3= 1.70 H4= 0.93
N1= 4.0P N2= 1.0P N3= 1.0P N4= 4.0P
= 0.54 = 0.135 = 0.135 = 0.54
(a) Roof
10.5
t t'
2.78 5.1 5.1 2.78
2.70 0.68 0.68 2.70
(b) 4th floor
Fig 4.20 Subframes at the roof and 4th floor
Thus
Axial force in exterior column: axial force in interior column = 4.0 P : 1.0 P
The analysis of the frame continues by considering a section through the top-storey columns: the removal of the
frame below this section gives the remainder shown in figure 4.20a. The forces in this subframe are calculated as
follows.
(a) Axial Forces in the Columns
Taking moments about point s, ∑
M s = 0 , therefore
5.25 × 1.75 + P × 6.0 − P × 10.0 − 4 P × 16.0 = 0
and therefore
P = 0.135 kN
Page 13 of 17
CE311 STRUCTURAL DESIGN I CHAPTER IV
thus
N1 = − N 4 = 4.0 P = 0.54kN
N 2 = − N 3 = 1.0 P = 0.135kN
(b) Vertical Shearing Forces F in the Beams
For each part of the subframe, ∑
F = 0 , therefore
F1 = N1 = 0.54kN
F2 = N1 + N 2 = 0.675kN
Page 15 of 17
CE311 STRUCTURAL DESIGN I CHAPTER IV
147
115 102
67 80
46
79
114
(a) Original Moments (kNm)
79
118
(b) Redistributed Moments (kNm)
134
105 111
90 92
158.5
(c) Shears (kN)
Figure 4.22a duplicates the original bending-moment diagram (part 3 of figure 4.13) of example 4.3 while figure
4.22b shows the redistributed moments, with the span moment set at 118 kN m. The moment at support B can be
calculated, using a rearrangement of equations 4.4 and 4.1 . Thus
V AB = [( M max − M AB )2 w]
and
wL
M BA = V AB − L + M AB
2
For span AB, w = 48.75kN/m , therefore
V AB = [(118 + 67) × 2 × 48.75] = 134kN
48.75 × 6.0
M BA = 134 − 6.0 − 67 = 140kNm
2
and
VBA = 292.5 − 134 = 158.5kN
Reduction in M BA = 147 − 140
= 7 kNm
7 ×100
= = 4.8 per cent
147
In order to ensure that the moments in the columns at joint B are not changed by the distribution, moment M BC
must also be reduced by 7 kN m. Therefore
M BC = 115 − 7 = 108kNm hogging
For the revised moments in BC:
(108 − 80) 195
VBC = + = 105kN
4 2
Page 16 of 17
CE311 STRUCTURAL DESIGN I CHAPTER IV
Page 17 of 17
CE311 STRUCTURAL DESIGN I CHAPTER V
c2 cu2
0.0020 0.0035
Strain
Fig.5-1 Parabolic-rectangular stress-strain diagram for concrete in compression
Reinforcing steel
The representative short-term design stress-strain curve for reinforcement is given in figure 5.2. the behaviour of
the steel identical in tension and compression, being linear in the elastic range up to the design yield stress of
f yk / γ s where f yk is the characteristic yield stress and γ s is the partial factor of safety.
f yk
S
Tension and
compression
2
Stress N/mm
2
200 KN/mm
Strain
Fig.5-2 Short-term design stress-strain curve for reinforcement
Within the elastic range, the relationship between the stress and strain is
Stress = elastic modulus × strain
= Es × ε s (5-1)
Page 1 of 18
CE311 STRUCTURAL DESIGN I CHAPTER V
f yk
so that the design yield strain is ε y = / E s
γs
at the ultimate limit for f yk = 500 N / mm 2
ε y = 500 /(1.15 × 200 × 10 3 )
= 0.00217
d' s=0.8x
A's sc x
neutral
d axis
As
Figure 5.3 shows the cross-section of a member subjected to bending, and the resultant strain diagram, together
with three different types of stress distribution in the concrete:
1. The triangular stress distribution applies when the stresses are very nearly proportional to the strains, which
generally occurs at the loading levels encountered under working conditions and is, therefore, used at the
serviceability limit state.
2. The rectangular-parabolic stress block represents the distribution at failure when the compressive strains are
within the plastic range, and it is associated with the design for the ultimate state.
3. The equivalent rectangular stress block is a simplified alternative to the rectangular-parabolic distribution.
where b = beam width
d = effective depth of the beam
d ′ = depth of the compression steel
As = Area of tension steel
′
As = Area of compression steel
ε cc = ultimate strain of concrete in compression
ε sc = strain of steel in compression
ε st = strain of steel in tension
x = depth of neutral axis
s = 0.8 x = depth of equivalent stress block
As there is compatibility of strains between the reinforcement and the adjacent concrete, the steel strains ε st in
tension and ε sc in compression can be determined from the strain diagram. The relationships between the depth of
neutral axis (x) and the maximum concrete strain ( ε cu 2 ) and the steel strains are given by
d − x
ε st = ε cu 2 (5-2)
x
and
Page 2 of 18
CE311 STRUCTURAL DESIGN I CHAPTER V
x − d′
ε sc = ε cu 2 (5-3)
x
Having determined the strains, we can evaluate the stresses in the reinforcement from the stress-strain curve of
figure 5-2, together with the equations developed in section reinforcing steel.
For analysis of a section with known steel strains, the depth of the neutral axis can be determined by rearranging
equation 5-2 as
d
x= (5-4)
ε
1 + st
ε cu 2
At the ultimate limit state the maximum compressive strain in the concrete is taken as ε cu 2 = 0.0035 for concrete
class ≤ 50 / 60 .
For steel with f yk = 500 N / mm 2 the yield strain is ε y = 0.00217 .
Inserting these values for ε cu 2 and ε y into equation 5-4:
d d
x= = = 0.617 d
ε st 0.00217
1+ 1+
ε cu 2 0.0035
Hence, to ensure yielding of the tension steel at the ultimate limit state:
x ≤ 0.617 d
At the ultimate limit state it is important that member sections in flexure should be ductile and that failure should
occur with the gradual yielding of the tension steel and not by a sudden catastrophic compression failure of the
concrete. Also, yielding of the reinforcement enables the formation of plastic hinges so that redistribution of
maximum moments can occur, resulting in a safer and more economical structure. To ensure rotation of the plastic
hinges with sufficient yielding of the tension steel and also to allow for other factors such as the strain hardening of
the steel, EC2 limits the depth of neutral axis to
x ≤ 0.45d
for concrete class ≤ 50 / 60 .
This is the limiting maximum value for x given by EC2 with no redistribution applied to the moments calculated by
an elastic analysis of the structure. When moment redistribution is applied these maximum values of x are reduced.
s/2
x s=0.8x
neutral Fcc
d axis z
As
st Fst
The design equations derived bellow are for zero redistribution of moments. When moment redistribution is
applied, reference should be made to section 5.7 which describes how to modify the design equations.
5.4 Singly reinforced rectangular section in bending at the ultimate limit state
Design equations for bending
Bending of the section will induce a resultant tensile force Fst in the reinforcing steel, and a resultant compressive
force in the concrete Fcc which acts through the centroid of the effective area of concrete in compression, as shown
in figure 5-4.
For equilibrium, the ultimate design moment, M , must be balanced by the moment of resistance of the section so
that
M = Fcc z = Fst z (5.5)
where z the lever arm between the resultant forces Fcc and Fst
Fcc = stress × area of action
= 0.567 f ck × bs
and
z = d −s/2 (5.6)
so that substituting in equation 5.5
M = 0.567 f ck bs × z
and replacing s from equation 5.6 gives
M = 1.134 f ck b(d − z ) × z (5.7)
Rearranging and substituting K = M / bd 2 f ck :
( z / d ) 2 − ( z / d ) + K / 1.134 = 0
Solving this quadratic equation:
[
z = s 0.5 + (0.25 − K / 1.134) ] (5.8)
in equation 5.5
Fst = ( f y / γ s ) As with γ s = 1.15
= 0.87 f yk As
Hence
M
As = (5.9)
0.87 f yk z
Equations 5.8 and 5.9 can be used to design the area of tension reinforcement in a singly reinforced concrete
section to resist an ultimate moment, M .
Page 4 of 18
CE311 STRUCTURAL DESIGN I CHAPTER V
100 As bal f ck
= 23.4 per cent
bd f yk
which is the steel percentage for a balanced section which should not be exceeded for a ductile singly reinforced
section.
Thus, for example, with f ck = 25 N / mm 2 and f yk = 500 N / mm 2
100 As bal 25
= 23.4 × = 1.17 per cent
bd 500
The ultimate moment of resistance of the balanced section is M bal = Fcc bal z bal where
z bal = d − s / 2 = 0.82d
Substituting for Fcc bal and z:
M bal = 0.167 f ck bd 2 (5.10)
and
Md
= 0.167 = K bal
f ck bd 2
Md
When the design moment M d is such that > K bal = 0.167 then the section cannot be singly reinforced
f ck bd 2
and compression reinforcing steel is required in the compression zone of the section.
M
K=
bd 2 f ck
d=440
185 × 10 6
= = 0.147 < 0.167
260 × 440 2 × 25
therefore compression steel is not required. As
Lever arm:
K
z = d 0.5 + 0.25 − Fig.5-5 Design example-singly reinforced section
1.134
0.147
= 4400.5 + 0.25 −
1.134
= 373 mm
Area of tension reinforcement:
M
As =
0.87 f yk z
185 × 10 6
=
0.87 × 500 × 373
= 1140 mm 2
Page 5 of 18
CE311 STRUCTURAL DESIGN I CHAPTER V
b=300 0.567fck
x s
neutral Fcc
d=520
axis z
2
A s =1470mm
Fst
Fig.5-6 Analysis example –singly reinforced section
For equilibrium of the compressive and tensile forces on the section
Fcc = Fst
therefore
0.567 f ck b × s = 0.87 f yk As
0.567 × 25 × 300 × s = 0.87 × 500 × 1470
therefore
s = 150 mm
and
x = s / 0.8 = 150 / 0.8
= 188 mm
This value of x is less than the value of 0.617d derived from section 5.2, and therefore the steel has yielded and
f st = 0.87 f yk as assumed.
Moment of resistance of the section is
M = Fst × z
= 0.87 f yk As (d − s / 2)
= 0.87 × 500 × 1470(520 − 150 / 2) × 10 −6 = 284 KNm
Page 6 of 18
CE311 STRUCTURAL DESIGN I CHAPTER V
5.5 Rectangular section in bending with compression reinforcement at the ultimate limit state
(a) Derivation of basic equations
It should be noted that the equations in this section have been derived for the case of zero moment redistribution.
When this is not the case, reference should be made to section 5.7 which deals with the effect of moment
redistribution.
b
0.0035 0.567fck
d' Fsc
A's sc x=0.45d s=0.8x
neutral Fcc
d axis
Z bal
As
st Fst
From the section dealing with the analysis of a singly reinforced section and for concrete class not greater than
C50/60 when M > 0.167 f ck bd 2 the design moment exceeds the moment of resistance of the concrete ( M bal )
and therefore compression reinforcement is required. For this condition the depth of neutral axis, x < 0.45d , the
maximum value allowed by the code in order to endure a tension failure with a ductile section. Therefore
z bal = d − s bal / 2 = d − 0.8 x bal / 2
= d − 0.8 × 0.45d / 2
= 0.82d
For equilibrium of the section in figure 5-7
Fst = Fcc + Fsc
so that with the reinforcement at yield
0.87 f yk As = 0.567 f ck bs + 0.87 f yk As′
or with
s = 0.8 × 0.45d = 0.36d
0.87 f yk As = 0.204 f ck bd + 0.87 f yk As′ (5.13)
and taking moments about the centroid of the tension steel,
M = Fcc × z bal + Fsc (d − d ′)
= 0.204 f ck bd × 0.82d + 0.87 f yk As′ (d − d ′)
= 0.167 f ck bd 2 + 0.87 f yk As′ (d − d ′) (5.14)
From equation 5.14
M − 0.167 f ck bd 2
As′ = (5.15)
0.87 f yk (d − d ′)
Multiplying both sides of equation 5.13 by z = 0.82d and rearranging gives
0.167 f ck bd 2
As = + As′ (5.16)
0.87 f yk × z bal
with z bal = 0.82d .
Hence the areas of compression steel, As′ , and tension steel, As , can be calculated from equations 5.15 and 5.16.
Substituting K bal = 0.167 and K = M / bd 2 f ck into these equations would convert them into:
( K − K bal ) f ck bd 2
As′ = (5.17)
0.87 f yk (d − d ′)
Page 7 of 18
CE311 STRUCTURAL DESIGN I CHAPTER V
K bal f ck bd 2
As = + As′ (5.18)
0.87 f yk × z bal
In this analysis it has been assumed that the compression steel has yielded so that the steel stress f sc = 0.87 f yk .
From the proportions of the strain distribution diagram:
ε sc 0.0035
= (5.19)
x − d′ x
so that
x − d′ ε sc
=
x 0.0035
or
d′ ε sc
= 1−
x 0.0035
At yield with f yk = 500 N / mm 2 , the steel strain ε sc = ε y = 0.00217 . Therefore for yielding of the compression
steel
d′ 0.00217
< 1− < 0.38 (5.20)
x 0.0035
or with x = 0.45d
d′
< 0.171 (5.21)
d
The ratio of d ′ / d for yielding of other grades of steel can be determined by using their yield strain in equation
5.19, but for values of f yk less than 500 N / mm 2 , the application of equation 5.21 will provide an adequate safe
check.
If d ′ / d > 0.171 , then it is necessary to calculate the strain ε sc from equation 5.19 and then determine f sc from
f sc = E s × ε sc
= 200000ε sc
This value of stress for the compressive steel must then be used in the denominator of equation 5.15 in place of
0.87 f yk in order to calculate the area As′ of compression steel. The area of tension steel is calculated from a
modified equation 5.16 such that
0.167 f ck bd 2 f sc
As = + As′ ×
0.87 f yk × z bal 0.87 f yk
The above equations apply for the case where the concrete class is less than or equal to C50/60. The constants for
concretes up to class C50/60 are tabulated in table 5.1.
Page 8 of 18
CE311 STRUCTURAL DESIGN I CHAPTER V
Example 5.3 Design of a rectangular section with compression reinforcement (no moment redistribution)
The section shown in figure 5-8 is to resist an ultimate design moment of 285 KNm . The characteristic material
strengths are f yk = 500 N / mm 2 and f ck = 25 N / mm 2 . Determine the areas of reinforcement required.
b=260 M
K=
bd 2 f ck
d ' =50
285 × 10 6
A's = = 0.226
260 × 440 2 × 25
d=440
> 0.167
therefore, compression steel is required
As d ′ / d = 50 / 440 = 0.11 < 0.171
as in equation 5.21 and the compression steel will have yielded.
Compression steel:
( K − K bal ) f ck bd 2
As′ =
0.87 f yk (d − d ′)
(0.226 − 0.167)25 × 260 × 440 2
=
0.87 × 500(440 − 50)
= 438 mm 2
Tension steel:
K bal f ck bd 2
As = + As′
0.87 f yk × z bal
0.167 × 25 × 260 × 440 2
= + 438
0.87 × 500(0.82 × 440)
= 1339 + 438 = 1777 mm 2
As =2410
Fst
Section Stress block
Fig.5.9 Analysis example, doubly reinforced section
Page 9 of 18
CE311 STRUCTURAL DESIGN I CHAPTER V
Flanged section- the depth of the stress block lies within the flange, s < h f
bf 0.567f ck
s/2
hf s=0.8x
x
neutral axis
Fcc
d z
As
Fst
bw
Section Stress block
Page 10 of 18
CE311 STRUCTURAL DESIGN I CHAPTER V
z = d −s/2
or
s = 2(d − z )
If s is less than the flange thickness ( h f ), the stress block does lie within the flange as assumed and the area of
reinforcement is given by
M
As =
0.87 f yk z
s/2
h f =150 neutral axis
x s
Fcc
d=420
As =1470mm2
Fst
Section Stress block
Flanged section- the depth of the stress block extends below the flange, s > h f
For the design of a flanged section, the procedure described in section above (Flanged section- the depth of the
stress block lies within the flange, s < h f ) will check if the depth of the stress block extends below the flange.
Page 11 of 18
CE311 STRUCTURAL DESIGN I CHAPTER V
An alternative procedure is to calculate the moment of resistance, M f , of the section with s = h f , the depth of the
flange(see equation 5.22 of example 5.6 following). Hence if the design moment, M d , is such that
Md > M f
then the stress block must extend below the flange, and
s > hf
In this case the design can be carried out by either:
(a) using an exact method to determine the depth of the neutral axis, as in example 5.6 or
(b) designing for the conservative condition of x = 0.45d , which is the maximum value of x for a singly
reinforced section and concrete class ≤ C 50 / 60.
Example 5.6 Design of a flanged section with the depth of the stress block below the flange
The T-section beam shown in figure 5.12 is required to resist an ultimate design moment of 180KNm. The
characteristic material strengths are f yk = 500 N / mm 2 and f ck = 25 N / mm 2 .
Calculate the area of reinforcement required.
bf =400
0.567fck
Fcf
hf =100 x s
neutral sw
Fcw
d =350
axis z1
z2
As
Fst
bw =200
Fcf
hf =150
s=0.8x
neutral
axis
Fcw
d =550
As =2592
Fst
b w=300
Example 5.8 Design of a flanged section with depth of neutral axis x = 0.45d
A safe but conservative design for a flanged section with s > h f can be achieved by setting the depth of neutral
axis to x = 0.45d , the maximum depth allowed in the code. Design equations can be derived for this condition as
follows.
bf 0.567f ck
Fc2
hf 2 2 s=0.8x
1 x=0.45d
neutral Fc1
axis z1 z2
As
Fst
bw
Section Stress block
Fig.5-14 Flanged section with depth of neutral axis x = 0.45d
Before using equation 5.23 for calculating As , it is necessary to confirm that compression reinforcement is not
required. This is achieved by using equation 5.24 to check that the moment of resistance of the concrete, M bal , is
greater than the design moment, M.
M bal bw hf bw h f
= 0 .167 + 0 .567 1 − 1 − (5.25)
f ck b f d 2 bf d b 2d
f
If the applied design moment, M > M bal , compression reinforcement is required. In this case the area of
compression steel can be calculated from
M − M bal
As′ = (5.26)
0.87 f yk (d − d ′)
and considering the equilibrium of forces on the section
Fst = Fc1 + Fc 2 + Fsc
so that the area of tension steel is
0.2 f ck bw d + 0.567 f ck h f (b f − bw )
As = + As′ (5.27)
0.87 f yk
Again, d ′ / x < 0.38 , otherwise the design compressive steel stress is less than 0.87 f yk .
Page 16 of 18
CE311 STRUCTURAL DESIGN I CHAPTER V
For a section requiring compression steel, the lever arm can be calculated from equation 5.29 or by using the
equation
[
z = d 0.5 + (0.25 − K bal / 1.134) ] (5.34)
which is similar to equation 5.8 but with K bal replacing K .
Example 5.9 Design of a section with moment redistribution applied and δ = 0.8
The section shown in figure 5.15 is subject to an ultimate design moment of 230 KNm after a 20% reduction due
to moment redistribution. The characteristic material strengths are f yk = 500 N / mm 2 and f ck = 25 N / mm 2 .
Determine the areas of reinforcement required using the constants k1 and k 2 .
d=490
Stress block depth s bal = 0.8 x bal = 0.8 × 141 = 113 mm
As
Lever arm z bal = d − s bal / 2 = 490 − 113 / 2 = 434 mm
Moment of resistance of the concrete
M bal = Fcc × z bal = 0.567 f ck bs bal × z bal Fig.5-15 Design example with moment
= 0.567 × 25 × 260 ×113 × 434 ×10 −6 redistribution, δ = 0.8
= 181 KNm
< 230 KNm , the applied moment
therefore compression steel is required.
d ′ / x bal = 50 / 141 = 0.35 < 0.38 (see equation 5.20)
therefore compression steel has yielded.
Compression steel:
M − M bal
As′ =
0.87 f yk (d − d ′)
(230 − 181) × 10 6
=
0.87 × 500(490 − 50)
= 256 mm 2
Tension steel:
M bal
As = + As′
0.87 f yk z bal
181 × 10 6
= + 256
0.87 × 500 × 434
= 959 + 256 = 1215 mm 2
Page 17 of 18
CE311 STRUCTURAL DESIGN I CHAPTER V
M
K=
bd 2 f ck
230 × 10 6
=
260 × 490 2 × 25
= 0.147 > K bal = 0.116
Therefore compression steel required.
Compression steel:
( K − K bal ) f ck bd 2
As′ =
0.87 f yk (d − d ′)
(0.147 − 0.116)25 × 260 × 490 2
=
0.87 × 500(490 − 50)
= 244 mm 2
Tension steel:
[
z bal = d 0.5 + (0.25 − K bal / 1.134) ]
= d [0.5 + ]
(0.25 − 0.116 / 1.134) = 0.89d
K bal f ck bd 2
As = + As′
0.87 f yk z bal
0.116 × 25 × 260 × 490 2
= + 244
0.87 × 500 × 0.89 × 490
= 954 + 244 = 1198 mm 2
Page 18 of 18
CE311 STRUCTURAL DESIGN I CHAPTER VI
The variable strut inclination method for sections that do require shear reinforcement
In order to derive the design equations the action of a reinforced concrete beam in shear is represented by an
analogous truss as shown in figure 6.2. The concrete acts as the top compression member and as the diagonal
compression members inclined at an angle θ to the horizontal. The bottom chord is the horizontal tension steel and
the vertical links are the transverse tension members. It should be noted that in this method of shear behaviour all
shear will be resisted by the provision of links with no direct contribution from the shear capacity of the concrete
itself.
X Y
b
z
zc
os
compression Fc
on on
ssi VEd ssi
tension
e e
z = 0.9d
r r
d mp mp
co co VEd / sin
tension
tension
tension Fs
zcot Section
X Y
VEd
Fig.6-2 Assumed truss for the variable strut inclination method
The analysis of the truss to derive the design equation will be carried out in the following order:
1. Consideration of the compressive strength of the diagonal concrete strut and its angle θ ;
2. Calculation of the required shear reinforcement Asw / s for the vertical ties;
3. Calculation of the additional tension steel As1 required in the bottom chord member.
The following notation is used in the equations for the shear design
Asw = the cross-sectional area of the two legs of the link
s = the spacing of the links
z = the lever arm between the upper and lower chord members of the analogous truss
f ywd = the design yield strength of the link reinforcement
f yk = the characteristic strength of the link reinforcement
VEd = the shear force due to the actions at the ultimate limit state
VEf = the ultimate shear force at the face of the support
Vwd = the shear force in the link
VRd , s = the shear resistance of the links
VRd ,max = the maximum design value of the shear which can be resisted by the concrete strut
Page 1 of 8
CE311 STRUCTURAL DESIGN I CHAPTER VI
Page 2 of 8
CE311 STRUCTURAL DESIGN I CHAPTER VI
VEd
θ = 0.5 sin −1 ≤ 45° (6.8b)
VRd ,max( 45)
where V Ef is the shear force at the face of the support and the calculated value of the angle θ can then be used to
determine cot θ and calculate the shear reinforcement Asw / s from equation 6.9 below (when 22° < θ < 45° ).
If it is assumed that half of this force is carried by the reinforcement in the tension zone of the beam then
the additional tensile force to be provided in the tensile zone is given by
∆Ftd = 0.5VEd cot θ (6.12)
To provide for this longitudinal force, at any section it is necessary to provide longitudinal reinforcement additional
to that required at that section to resist bending. In practice, increasing the curtailment lengths of the bottom-face
tension reinforcement can usually provide the required force.
Bent-up bars
To resist shearing forces, longitudinal tension bars may be bent up near to the supports as shown in figure 6.3. the
bent-up bars and the concrete in compression are considered to act as an analogous lattice girder and the shear
resistance of the bars is determined by taking a section X-X through the girder.
Anchorage
length
X
com
p
X
s
s=0.9d(cot + cot )
(a) Single system (b) Multiple system
Fig.6.3 Bent up bars
From the geometry of part (a) of figure 6.3, the spacing of the bent-up bars is:
s = 0.9d (cot α + cot θ )
and at the section X-X the shear resistance of a single bent-up bar ( Vwd ) must equal the shear force ( VEd ).
f yk
Vwd = VEd = f ywd Asw sin α = Asw sin α = 0.87 f yk Asw sin α
1.15
where Asw is the cross-sectional area of the bent-up bar.
For a multiple system of bent-up bars, as in part (b) of figure 6.3, the shear resistance is increased proportionately
to the spacing, s. Hence:
0.9d (cot α + cot θ )
VEd = 0.87 f yk Asw sin α ×
s
0.9d (cot α + cot θ )
= number of bars crossing the crack
s
or
Asw VEd
= (6.13)
s 0.78df yk (cot α + cot θ ) sin α
This equation is analogous to equation (6.9) for the resistance of shear links. In a similar way it can be shown that,
based on crushing of the concrete in the compressive struts, the analogous equation to (6.4) is given by:
(cot θ + cot α )
VRd ,max ≤ 0.36bw d (1 − f ck / 250) f ck × (6.14)
(1 + cot 2 θ )
and the additional tensile force to be provided by the provision of additional tension steel is given by a modified
version of equation 6.12:
∆Ftd = 0.5VEd (cot θ − cot α ) (6.15)
EC2 also requires that
i) the maximum longitudinal spacing of bent-up bars limited to 0.6(1 + cot α ) ;
ii) at least 50 per cent of the required shear reinforcement should be in the form of shear links.
Page 4 of 8
CE311 STRUCTURAL DESIGN I CHAPTER VI
1. either placed in members whose depth in the direction of concreting does not exceed 250mm or
2. embedded in members with a depth greater than 250mm and are either in the lower 250mm of the member or at
least 300mm from the top surface when the depth exceeds 600mm.
These conditions are illustrated in figure 6.5. When bond conditions are poor then the specified ultimate bond
stresses should be reduced by a factor 0.7.
The design value of the ultimate bond stress is also dependent on the bar size. For all bar size ( φ ) greater than
32mm the bond stress should additionally be multiplied by a factor (132 − φ ) / 100 .
Table 6.1 gives the design values of ultimate bond stresses for ‘good’ conditions. These depend on the class of
concrete and are obtained from the equation f bd = 1.5 f ctk where f ctk is the characteristic tensile strength of the
concrete.
Table 6.1 Design values of bond stresses f bd ( N / mm 2 )
f ck N / mm 2 12 16 20 25 30 35 40 45 50 55 60
Plain bars 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7
Bars ≤ 32mm diameter and
1.6 2.0 2.3 2.7 3.0 3.4 3.7 4.0 4.3 4.5 4.7
good bond conditions
Bars ≤ 32mm diameter and
1.1 1.4 1.6 1.9 2.1 2.4 2.6 2.8 3.0 3.1 3.3
poor bond conditions
c c
Straight bars Bent or hooked bars Looped bars
cd = min (a / 2, c1 , c) cd = min (a / 2, c1 ) cd = c
Fig.6.6 values of c d for beams and slabs
Page 6 of 8
CE311 STRUCTURAL DESIGN I CHAPTER VI
d=650
H12
Section
2
2H25: As =982mm
Fig.6.7 Beam with stirrups
Total ultimate load on beam = 200 × 8.0 = 1600 KN
Support reaction = 1600 / 2 = 800 KN
Shear, VEf at face of support = 800 − 200 × 0.3 / 2 = 770 KN
Shear, VEd distance d from face of support = 770 − 200 × 0.65 = 640 KN
1. Check the crushing strength VRd ,max of the concrete diagonal strut at the face of the beams support.
From equation 6.6 with θ = 22°
VRd ,max( 22 ) = 0.124bw d (1 − f ck / 250) f ck
= 0.124 × 350 × 650(1 − 30 / 250)30
= 745 KN (< VEf = 770 KN )
From equation 6.7 with θ = 45°
VRd ,max( 45) = 0.18bw d (1 − f ck / 250) f ck
= 0.18 × 350 × 650(1 − 30 / 250)30
= 1081KN (> VEf = 770 KN )
Therefore: 22° < θ < 45° .
2. Determine angle θ
From equation 6.8(a)
VEf
θ = 0.5 sin −1 ≤ 45°
0.18bw d (1 − f ck / 250) f ck
or alternatively from equation 6.8(b)
VEf −1 770
θ = 0.5 sin −1 = 0.5 sin = 22.7°
VRd ,max( 45) 1081
From which cot θ = 2.39 and tan θ = 0.42 .
Page 7 of 8
CE311 STRUCTURAL DESIGN I CHAPTER VI
Asw
VRd ,s = × 0.78df yk cot θ
s
= 1.29 × 0.78 × 650 × 500 × 2.39 × 10 −3 = 781KN
Therefore shear resistance of links = 781KN .
Design shear, VEd distance d from the face of the support = 640 KN (< 781KN ) . Therefore, the beam can support,
in shear, the ultimate load of 200 KN / m .
Page 8 of 8
CE311 STRUCTURAL DESIGN I CHAPTER VII
Page 1 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
The strength of a beam is affected considerably more by its depth than its breadth. The span-depth ratios usually
vary between say 14 and 30 but for larger spans the ratios can be greater. A suitable breadth may be one-third to
one-half of the depth; but it may be much less for a deep beam. At other times wide shallow beams are used to
conserve headroom. The beam should not be too narrow; if it is much less than 200mm wide there may be
difficulty in providing adequate side cover and space for the reinforcing bars.
Suitable dimensions for b and d can be decided by a few trial calculations as follow:
Page 3 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
Table 7.5 shows basic span/depth ratio for commonly occurring reinforced concrete members and support
conditions. They have been obtained using equations 7.1 and 7.2.
3/ 2
l ρ0 ρ0
= K 11 + 1.5 f ck + 3.2 f ck − 1 if ρ ≤ ρ 0 (7.1)
d ρ ρ
l ρ0 1 ρ′
1/ 2
= K 11 + 1.5 f ck + f ck if ρ > ρ 0 (7.2)
d ρ − ρ ′ 12 ρ0
where
l / d is the limiting span/depth ratio
K is the factor to take into account the different structural systems, given in Table 7.5
Page 4 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
ρ 0 = f ck × 10 −3
ρ is the required tension reinforcement ratio
ρ ′ is the required compression reinforcement ratio
The values in Table 7.5 assume the steel stress at the critical section, σ s , is 310 N mm −2 , corresponding roughly to
the stress under characteristic load when f yk = 500 Nmm −2 . Where other steel stresses are used, the values in the
table can be multiplied by 310 / σ s . It will normally be conservative to assume that
310 f yk As ,req
σs = (7.3)
500 As , prov
where
As ,req is the area of steel required
As , prov is the area of steels provided
l ρ0 1 ρ′
1/ 2
0.005 1 0
1/ 2
= 214 KN
Therefore maximum design shear force
VEd = 107 KN Fig.7.3 Beam dimensions
Assuming a triangular load distribution for the preliminary analysis, we have
F × span 214 × 4.0
M = = = 143KNm
6 6
For such a relatively minor beam the case with no compression steel should be considered
M
K= < K bal = 0.167
bd 2 f ck
therefore
143 × 10 6
< 0.167
230 × d 2 × 25
Rearranging, d > 386mm .
Assume a concrete cover of 25mm to the reinforcing steel. So for 10mm links and, say, 32mm bars
Overall beam depth h = d + 25 + 10 + 32 / 2
= d + 51
Therefore make h = 525mm as an integer number of brick courses. So that
d = 525 − 51 = 474mm
Maximum shear resistance is
VRd ,max = 0.18bw d (1 − f ck / 250) f ck
= 0.18 × 230 × 474 × (1 − 25 / 250) × 25 × 10 3
= 446 KN > VEd = 107 KN
4000
Basic span-effective depth = = 8.44 <≈ 20 (for a lightly stressed beam in C25 concrete- table 7.5)
474
A beam size of 230mm by 525mm deep would be suitable.
Weight of beam = 0.23 × 0.525 × 4.0 × 25 = 12.1KN which is sufficiently close to the assumed value.
Bar areas
Table 7.7 Sectional areas of groups of bars ( mm 2 )
Bar size Number of bars
(mm) 1 2 3 4 5 6 7 8 9 10
6 28.3 56.6 84.9 113 142 170 198 226 255 283
8 50.3 101 151 201 252 302 352 402 453 503
10 78.5 157 236 314 393 471 550 628 707 785
12 113 226 339 452 566 679 792 905 1020 1130
16 201 402 603 804 1010 1210 1410 1610 1810 2010
20 314 628 943 1260 1570 1890 2200 2510 2830 3140
25 491 982 1470 1960 2450 2950 3440 3930 4420 4910
32 804 1610 2410 3220 4020 4830 5630 6430 7240 8040
40 1260 2510 3770 5030 6280 7540 8800 10100 11300 12600
s/2
x s=0.8x
neutral Fcc
d axis z
As
st Fst
Page 7 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
Example 7.3 Design of tension reinforcement for a rectangular sections, no moment redistribution
The beam section shown in figure 7.5 has characteristic material strengths of f ck = 25 N / mm 2 for the concrete
and f yk = 500 N / mm 2 for the steel. The design moment at the ultimate limit state is 165KNm which causes
sagging of the beam.
b=230
M 165 × 10 6
1. K = = = 0.12
bd 2 f ck 230 × 490 2 × 25
This is less than K bal = 0.167 therefore compression steel is not required.
d=490
h=550
2. From the lever-arm equation
[
z = d 0.5 + (0.25 − K / 1.134) ]
[
= 490 0.5 + (0.25 − 0.12 / 1.134) = 431mm ] As 3-H20
6
M 165 × 10
3. As = = = 880mm 2 Fig.7.5 Singly reinforced beam example
0.87 f yk z 0.87 × 500 × 431
4. Provide three H20 bars, area = 943mm 2 .
100 As 100 × 943
5. For the steel provided = = 0.84 (> 0.13%)
bd 230 × 490
and
100 As 100 × 943
= = 0.75 (< 4.0%)
bh 230 × 550
therefore the steel percentage is within the limits specified by the code.
d' s=0.8x
A's sc x
neutral
d axis
As
st Fst
Equivalent
rectangular
Section Strain Stress block
Fig. 7.6 Beam doubly reinforced to resist a sagging moment
Page 8 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
In order to have a ductile section so avoiding a sudden compressive failure of the concrete it is generally required
that the maximum depth of the neutral axis is xbal = 0.45d and this is the value used in the design of a section
with compression steel.
f sc = 0.87 f yk
From equation 7.6 A's
2
( M − K bal f ck bd ) d ' =50
Compression steel As′ =
f sc (d − d ′)
( M − 0.167 f ck bd 2 )
= Fig.7.7 Beam doubly reinforced to resist a hogging moment
0.87 f yk (d − d ′)
(165 × 10 6 − 0.167 × 25 × 230 × 330 2 )
= = 496mm 2
0.87 × 500(330 − 50)
Provide two H20 bars for As′ , area = 628mm 2 , bottom steel.
3. From equation 7.7
K bal f ck bd 2 f sc
Tension steel As = + As′
0.87 f yk z 0.87 f yk
Page 9 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
0.167 f ck bd 2
= + As′
0.87 f yk z
0.167 × 25 × 230 × 330 2
= + 496
0.87 × 500 × 0.82 × 330
= 888 + 496 = 1384mm 2
Provide three H25 bars for As , area = 1470mm 2 , top steel.
4. Check equation 7.8 for the areas of steel required and provided for the compression and tension reinforcement to
ensure ductility of the section
( As′, prov − As′,req ) ≥ ( As , prov − As ,req )
That is
628 − 496(= 132) > 1470 − 1384(= 86)mm 2
5. The bar areas provided are within the upper and lower limits specified by the code. To restrain the compression
steel, at least 8mm links at 300mm centres should be provided.
• Rectangular sections with tension and compression reinforcement with moment redistribution applied
(based on the UK Annex to EC2)
The steps in the design are:
1. Calculate x bal ≤ (δ − 0.4)d
2. Calculate K = M / bd 2 f ck
3. Take K bal from table 5.2 or alternatively calculate
K bal = 0.454(δ − 0.4) − 0.182(δ − 0.4) 2 for ≤ C 50
If K > K bal , compression steel is required.
4. Calculate the area of compression steel from
( K − K bal ) f ck bd 2
As′ =
f sc (d − d ′)
where f sc is the stress in the compression steel
If d ′ / x ≤ 0.38 the compression steel has yielded and f sc = 0.87 f yk
If d ′ / x > 0.38 then the strain ε sc in the compressive steel must be calculated from the proportions of the strain
diagram and f sc = E s ε sc = 200 × 10 3 ε sc .
5. Calculate the area of tension steel required from
K bal f ck bd 2 f sc
As = + As′ (7.9)
0.87 f yk z 0.87 f yk
Page 10 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
Example 7.5 Design of tension and compression reinforcement, with 20 per cent moment redistribution,
δ = 0.8 (based on the UK Annex to EC2)
The beam section shown in figure 7.8 has characteristic material strengths of f ck = 25 N / mm 2 and
f yk = 500 N / mm 2 . The ultimate moment is 370KNm, causing hogging of the beam.
b=300
st
As sc
d=540
neutral
A's axis
x=216
d '=100
0.0035
Section Strain
Fig.7.8 Beam doubly reinforced to resist a hogging moment
1. As the moment reduction factor δ = 0.8 , the limiting depth of the neutral axis is
x = (δ − 0.4)d
= (0.8 − 0.4) × 540 = 216mm
2. K = M / bd 2 f ck = 370 × 10 6 /(300 × 540 2 × 25) = 0.169
3. K bal = 0.454(δ − 0.4) − 0.182(δ − 0.4) 2
= 0.454(0.8 − 0.4) − 0.182(0.8 − 0.4) 2 = 0.152
K > K bal therefore compression steel is required.
4. d ′ / x = 100 / 216 = 0.46 > 0.38
therefore f sc < 0.87 f yk
From the proportions of the strain diagram
0.0035( x − d ′)
Steel compressive strain ε sc =
x
0.0035(216 − 100)
= = 0.00188
216
Steel compressive stress = E s ε sc
= 200000 × 0.00188 = 376 N / mm 2
( K − K bal ) f ck bd 2
′
Compression steel As =
f sc (d − d ′)
(0.169 − 0.152)25 × 300 × 540 2
= = 224 mm 2
376(540 − 100)
Provide two H20 bars for As′ , area = 628mm 2 , bottom steel.
Page 11 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
5. Tension steel
K bal f ck bd 2 f sc
As = + As′
0.87 f yk z 0.87 f yk
where
z = d − 0.8 x / 2 = 540 − 0.8 × 216 / 2 = 454mm
therefore
0.152 × 25 × 300 × 540 2 376
As = + 224 ×
0.87 × 500 × 454 0.87 × 500
2
= 1683 + 194 = 1877 mm
Provide four H25 bars for As , area = 1960mm 2 , top steel.
6. Check equation 7.8 for the areas of steel required and provided for the compression, and tension reinforcement to
ensure ductility of the section
( As′, prov − As′,req ) ≥ ( As , prov − As ,req )
That is
628 − 224(= 404) > 1960 − 1877(= 83) mm 2
7. These areas lie within the maximum and minimum limits specified by the code. To restrain the compression
steel, at least 8mm links at 300mm centres should be provided.
d h
Transverse steel in flange
beff 1 bw beff 2 bw
Section Section
Fig 7.9 T-beam and L-beam
At intermediate supports of continuous beams where hogging moments occur the total area of tension
reinforcement should be spread over the effective width of the flange as shown in figure 7.9.
The effective flange width beff is specified by the following equation:
beff = bw + ∑ beff,i
where
beff,i = 0.2bi + 0.1l0 ≤ 0.2l0 and also beff,i ≤ bi
2bi is the clear distance between the webs of adjacent beams
l0 is the distance between the points of contraflexure along the beam as shown in figure 7.10.
So that for the interior span of a symmetrical T-beam with b1 = b2 = b′ and l 0 = 0.7l
beff = bw + 2[0.2b′ + 0.07l ] ≤ bw + 2[0.14l ]
For sagging moments the flanges act as a large compressive area. Therefore the stress block for the flanged beam
section usually falls within the flange thickness. For this position of the stress block, the section may be designed as
an equivalent rectangular section of breadth bf (= beff ) .
Page 12 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
Transverse reinforcement should be placed across the full width of the flange to resist the shear developed between
the web and the flange.
l1 l2 l3
Note: (i) the length of the cantilever should be less than half the length of the adjacent span
(ii) the ratio of adjacent span lengths should be between 0.67 and 1.50
eff
beff 1 beff 2
b1 b1 b2 b2
bw
b
Fig.7.11 Effective flange width parameters
2. If s ≤ h f the stress block falls within the flange depth, and the design may proceed as for a rectangular section,
breadth b f .
3. Design transverse steel in the top of the flange to resist the longitudinal shear stresses at the flange-web interface.
Page 14 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
600
H10 at 300
150
d=530
h=580
As 2-H25
250
Fig 7.12 T-beam
44 × 6 2
Maximum bending moment at mid-span is M = = 198 kNm
8
(1) Longitudinal reinforcement
M 198 × 10 6
= = 0.047
b f d 2 f ck 600 × 530 2 × 25
[ ]
z = d 0.5 + (0.25 − K / 1.134) = d [0.5 + (0.25 − 0.047 / 1.134) ] = 0.956d > 0.95d
Therefore z = 0.95d = 0.95 × 530 = 503mm
Depth of stress block s = 2(d − z ) = 2(530 − 503) = 54mm (< h f = 150mm)
Thus the stress block lies within the flange
M 198 × 10 6
As = = = 905 mm 2
0.87 f yk z 0.87 × 500 × 503
Provide two H25 bars, area = 982 mm 2 . For these bars
100 As 100 × 982
= = 0.74 per cent > 0.13
bw d 250 × 530
Thus the steel percentage is greater than the minimum specified by the Code of practice.
Page 15 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
∆Fd 96 × 10 3
v Ed = = = 0.43 N / mm 2
(h f × ∆x) 150 × 1500
(ii) Check the strength of the concrete strut
From equation 7.11, to prevent crushing of the compressive strut in the flange
0.6(1 − f ck / 250) f ck
v Ed ≤
1.5(cot θ f + tan θ f )
The moments are sagging so the flange is in compression and the limits for θ f are
26.5° ≤ θ f ≤ 45°
with θ f = the minimum value of 26.5°
0.6(1 − 25 / 250) × 25
∴ v Ed (max) = = 3.6 (> 0.43 N / mm 2 )
1.5(2.0 + 0.5)
and the concrete strut has sufficient strength with θ = 26.5° ( for a flange in tension the limits on θ are
38.6° ≤ θ ≤ 45° or 1.0 ≤ cot θ ≤ 1.25 .)
Page 16 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
480
50
2H16
540
2H32+2H25
0.08L 0.08L
L
Page 18 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
5. Calculate the additional longitudinal tensile force caused by the shear force
∆Ftd = 0.5VEd cot θ (7.15)
This additional tensile force increases the curtailment length of the tension bars as shown in section 7.9.
The minimum spacing of the links is governed by the requirements of placing and compacting the concrete and
should not normally be less than about 80mm. EC2 gives the following guidance on the maximum link spacing:
(a) Maximum longitudinal spacing between shear links in a series of links
s1,max = 0.75d (1 + cot α )
where α is the inclination of the shear reinforcement to the longitudinal axis of the beam.
(b) Maximum transverse spacing between legs in a series of shear links
sb ,max = 0.75d (≤ 600mm)
Page 19 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
1.45 m
308KN
SR nominal links
151KN
151KN
308KN
S.F diagram
540
300
6.0m
Page 20 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
Asw
Vmin = × 0.78df yk cot θ
s
= 0.287 × 0.78 × 540 × 500 × 2.5 × 10 −3 = 151KN
(d) Extent of shear links
Shear links are required at each of the beam from the face of the support to the point where the design shear force is
Vmin = 151KN as shown on the shear force diagram of figure 7.12.
From the face of the support
VEd − Vmin 308 − 151
distance x = = = 1.45 metres
wu 108
Therefore the number of H8 links at 200mm centres required at each end of the beam is
1 + ( x / s ) = 1 + (1450 / 200) = 9
Spaced over a distance of (9 − 1)200 = 1600mm .
(e) Additional longitudinal tensile force
∆Ftd = 0.5VEd cot θ
= 0.5 × 308 × 2.5
= 385KN
This additional longitudinal tensile force is provided for by extending the curtailment point of the mid-span
longitudinal reinforcement as discussed in section 7.8.
Page 21 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
0 -523 -523 0
Moment M (kNm) =
428 333 428
A B C D
F=1.35Gk +1.5Qk
Fig.7.13 Continuous beam with ultimate design bending moments and shear forces shown
Page 22 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
0.167 f ck bd 2
Tension steel, As = + As′
0.87 f yk z
0.167 × 30 × 300 × 580 2
= + 79 = 2444 + 79 = 2523mm 2
0.87 × 500 × 475.6
Provide four H25 bars plus two H20 bars, area = 2588mm 2 (top steel). The arrangement of the reinforcement is
shown in figure 7.14. At end support A two H25 bars have been provided as top continuity steel to meet the
requirement.
H8 @ 200 H8 @ 300 H10 @ 200
2-H20
4-H25
2-H25
A B
3-H25
300 2-H16 300
L= 5.0m
25 20 25
180
H8 H10
h=660
16 16 16 16
25 25 25 25 25 25
b w=300
Page 24 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
Asw VEd
=
s 0.78df yk cot θ
380 × 10 3
= = 0.65
0.78 × 600 × 500 × 2.5
Using table 7.8
Provide 10mm links at 225mm centres, Asw / s = 0.65 .
Additional longitudinal tensile force is
∆Ftd = 0.5VEd cot θ
= 0.5 × 380 × 2.5
= 475 KN
f bd is the design bond strength which, for a beam, depends on the concrete strength and the bar size and
whether the bar is in the top or bottom of the beam.
6
Curtailment anchorage
5 M Ed / z envelope diagram
Ftd (hogging region)
4 a1
M Ed / z
4 5 6
Beam
2,3
1 1 2 3
M Ed / z M Ed / z envelope diagram
a1
3
(sagging region)
Ftd
2
1
For a straight bar with φ ≤ 32mm , the order of anchorage lengths are lbd = 52φ for a top bar and lbd = 36φ for a
bottom bar with class C30 concrete.
The curtailment of the tension reinforcement is based upon the envelope of tensile forces, Fs , derived from the
bending moment envelope as shown in figure 7.15 such that at any location along the span
Fs = M Ed / z + ∆Ftd
where
M Ed is the design bending moment from the moment envelope
z is the lever arm
∆Ftd is the additional tensile force obtained from the design for shear
∆Ftd is a maximum where the shear force is a maximum at section of zero moment, and ∆Ftd is zero at the
maximum moment near to mid-span and the interior support.
For members where shear reinforcement is not required the tensile force envelope may be estimated by simply
‘shifting’ the bending moment envelope diagram horizontally by a distance a1 (= d ) as shown in figure 7.15.
To determine the curtailment positions of each reinforcing bar the tensile force envelope is divided into sections as
shown, in proportional to the area of each bar.
When considering the curtailment the following rules must also be applied:
1. At least one-quarter of the bottom reinforcement should extend to the supports
2. The bottom reinforcement at an end support should be anchored into the supports as shown in figure 7.16.
3. At an end support where there is little or no fixity the bottom steel should be designed to resist a tensile
force of 0.5VEd to allow for the tension induced by the shear with a minimum requirement of 25% of the
reinforcement provided in the span.
4. At an end support where is fixity but it has been analysed as a simply support, top steel should be designed
and anchored to resist at least 25 per cent of the maximum span moment.
5. At internal supports the bottom steel should extend at least 10 bar diameters φ beyond the face of the
support. To achieve continuity and resistance to such factors as accidental damage or seismic forces, splice
bars should be provided across the support with a full anchorage lap on each side as shown in figure 7.17.
Page 26 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VII
6. Where the loads on a beam are substantially uniformly distributed, simplified rules for curtailment may be
used. These rules only apply to continuous beams if the characteristic variable load does not exceed the
characteristic permanent load and the spans are approximately equal. Figure 7,18 shows the rules in
diagrammatic form.
l bd l bd l bd l bd
10
0.08L 0.08L
L
Simply supported
C=0.25L
C=0.15L
C 45
0.15L
0.1L
L
Continuous beam
Fig 7.18 Simplified rules for curtailment of bars in beams
Page 27 of 27
CE311 STRUCTURAL DESIGN I CHAPTER VIII
8.0 Introduction
Reinforced concrete slabs are used in floors, roofs and walls of buildings and as the deck of bridges.
Classification of Slabs
i) By support conditions
• Slabs supported on beams
• Slabs supported on columns (Flat slabs)
• Slabs supported on walls or steel beams
ii) By Form Cross-section
• Solid slabs
• Ribbed slabs
iii) By Spanning Method
• One way spanning slabs
• Two way spanning slabs
iv) By Fixing
• Simply supported slabs
• Continuous slabs
Page 1 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
Since shear forces in slabs subject to uniformly distributed loads are generally small, shear reinforcement will
seldom be required and it would be usual to design the slab such that the design ultimate shear force, V Ed , is less
than the shear strength of the unreinforced section, V Rd ,c . In this case it is not necessary to provide any shear
reinforcement. This can conveniently be checked using Table 8.1 which has been derived from Equations 8.1 and
8.2 for class C30 concrete on the basis that the allowable shear stress in the unreinforced slab is given by
VRd ,c
v Rd ,c =
bd
In this case, the applied ultimate shear stress
VEd
vEd = ≤ vRd ,c
bd
Table 8.1 Shear resistance of slabs without shear reinforcement v Rd ,c N / mm 2 (Class C30/35 concrete)
Effective depth, d (mm)
ρ1 = As / bd
≤ 200 225 250 300 350 400 500 600 750
0.25% 0.54 0.52 0.50 0.47 0.45 0.43 0.40 0.38 0.36
0.50% 0.59 0.57 0.56 0.54 0.52 0.51 0.48 0.47 0.45
0.75% 0.68 0.66 0.64 0.62 0.59 0.58 0.55 0.53 0.51
1.00% 0.75 0.72 0.71 0.68 0.65 0.64 0.61 0.59 0.57
1.25% 0.80 0.78 0.76 0.73 0.71 0.69 0.66 0.63 0.61
1.50% 0.85 0.83 0.81 0.78 0.75 0.73 0.70 0.67 0.65
2.00% 0.94 0.91 0.89 0.85 0.82 0.80 0.77 0.74 0.71
Where different concrete strengths are used, the values in table 8.1 may be modified by the factors in table 8.2
provided ρ1 ≥ 0.4% .
Table 8.2 Concrete strength modification factor
2
f ck ( N / mm ) 25 30 35 40 45 50
Modification factor 0.94 1.00 1.05 1.10 1.14 1.19
a
Critical
Section Loaded
b area
Plan
Load
d h
Elevation
Fig.8.1 Punching shear
The maximum force that can be carried by the slab without shear reinforcement ( V Rd ,c ) can be obtained using the
values of v Rd ,c given in table 8.1 based on equations 8.1 and 8.2 for normal shear in beams and slabs, where
ρ1 = ( ρ y ρ z ) where ρ y and ρ z are the reinforcement ratios, As / bd in the two mutually perpendicular
directions then
VRd ,c = v Rd ,c du (8.3)
where
Page 2 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
dy + dz
d = effective depth of section [average of the two steel layers in perpendicular directions = ]
2
u = length of the punching shear perimeter.
Checks must be undertaken to ensure that the maximum permissible shear force ( V Rd ,max ) is not exceeded at the
face of the loaded area.
The maximum permissible shear force is given by V Rd ,max = 0.5v1 f cd ud = 0.5v1 ( f ck / 1.5)ud
where
u is the perimeter of the loaded area
v1 is the strength reduction factor given by v1 = 0.6(1 − f ck / 250) .
Page 3 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
necessary distance from the loaded area can be calculated. If this is less than 3d from the face of the loaded area,
then reinforcement should be placed in the zone between 0.3d and 1.5d from this face.
Vertical links will normally be used and provided around at least two perimeters not more than 0.75d apart. Link
spacing around a perimeter within 2d of the face of the loaded area should not be greater than 1.5d.
Provide that the slab is greater than 200mm thick overall then the amount of reinforcement :
v Rd ,cs − 0.75v Rd ,c
Asw sin α ≥
d × f ywd ,ef
1.5
s r × u1 d
where
Asw is the total area of shear reinforcement in one perimeter ( mm 2 )
s r is the radial spacing of perimeters of shear reinforcement
f ywd ,ef is the effective design strength of the reinforcement and is given by
f ywd ,ef = 250 + 0.25d ≤ f ywd .
v Rd ,cs is the punching shear resistance of the reinforced slab
α is the angle between shear reinforcement and the plane of the slab, so that sin α = 1 for critical
reinforcement.
This expression effectively allows for a 75 per cent contribution from the unreinforced concrete slab, and for
vertical kinks can be expressed as:
v Rd ,cs − 0.75v Rd ,c
Asw ≥
f ywd ,ef
1.5
s r u1
VEd
Where the required v Rd ,cs would be given by .
u1 d
A check must also be made that the calculated reinforcement satisfies the minimum requirement that:
0.08 f ck ( s r st ) 0.053 f ck ( s r st )
Asw,min ≥ =
1.5 f yk f yk
where s t is the spacing of links around the perimeter
Asw,min is the area of an individual link leg.
Page 4 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
hence for concrete without shear reinforcement the shear capacity is given by:
VRd ,c = v Rd ,c × 3902 × 215 = 83890v Rd ,c
bending steel ratio
As 905
ρ1 = = = 0.0042 (> 0.40 per cent )
bd 1000 × 215
hence from table 8.1, v Rd ,c = 0.56 for class C30 concrete and, from table 8.2, modification factor for class C25
concrete = 0.94 then
V Rd ,c = 83890 × 0.56 × 0.94 × 10 −3
= 442 KN (< V Ed = 650 KN )
and punching shear reinforcement is required.
(iii) Check outer perimeter at which reinforcement is not required.
VEd 650 × 10 3
u out,ef = = = 5743mm
v Rd ,c d 0.56 × 0.94 × 215
This will occur at a distance xd from the face of the loaded area, such that
5743 = 2(300 + 300) + 2π × 215 × x
and x = 3.36 (> 3.0)
(iv) Provision of reinforcement
Shear reinforcement should thus be provided within the zone extending from a distance not greater than 0.5d and
less than (3.36 − 1.5)d = 1.86d from the loaded face.
For perimeters ≤ 0.75d apart, 3 perimeters of steel will thus be adequate loaded area (i.e. s r ≈ 0.75d = 160mm
apart).
Since all perimeters lie within 2d (= 430mm) of the loaded and maximum link spacing, ( s t ) , is limited to
1.5d (= 323mm) .
The minimum link leg area is therefore given by:
0.053 f ck ( s r st ) 0.053 25 (160 × 323)
Asw,min = =
f yk 500
= 27.3mm 2 which is satisfied by a 6mm diameter bar ( 28.3mm 2 )
Hence the assumed 8mm links will be adequate.
The area of steel required/perimeter is thus given by:
v Rd ,cs − 0.75v Rd ,c
Asw ≥
f ywd ,ef
1.5
s u
r 1
where, for the outer perimeter
VEd 650 × 10 3
VRd ,cs = = = 0.775 N / mm 2
u1 d 3902 × 215
v Rd ,c = 0.94 × 0.56 = 0.526 N / mm 2 (as above)
f ywd ,ef = 250 + 0.25 × 215 = 303 N / mm 2 (≤ 500)
and s r = 160mm
(0.775 − 0.75 × 0.526) × 160 × 3902
thus Asw ≥
1.5 × 303
2
= 523mm
(v) Number of links
The area of one leg of an 8mm link is 50.3mm 2 . Hence the number of link-legs required = 523 / 50.3 = 11 on the
outer perimeter. The same number of links can conveniently be provided around each of the 3 proposed perimeters
as summarized in the table below. The table indicates the number of single-leg 8mm diameter links
(area = 50.3mm 2 ) proposed for each of the three reinforcement perimeters taking account of the maximum
Page 5 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
required spacing and practical fixing considerations. Bending reinforcement is spaced at 125mm centres in both
directions; hence link spacing is set at multiples of this values.
Distance from Length of Required link Proposed link Proposed
load face (mm) perimeter (mm) spacing (mm) spacing (mm) number of links
85 1734 158 125 14
245 2739 249 250 11
400 3713 323 250 15
For simplicity, take the effective span to be 4.5m between centrelines of supports.
H10-300
H10-150
300
4.5m
Page 7 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
Table 8.4 Anchorage and lap length coefficients (length L = K A × bar size) for good bond conditions
K A for concrete strength, f ck ( N / mm 2 )
20 25 30 35 40 45 50
Straight bars
Anchorage in tension and compression 47 40 36 32 29 27 25
Curved bars
Anchorage in tension 33 28 25 22 20 19 18
Anchorage in compression 47 40 36 32 29 27 25
% of bars lapped
at section
< 25% 47 40 36 32 29 27 25
Compression and tension laps
33% 54 46 42 37 33 31 29
50% 66 56 51 45 41 38 35
> 50% 71 60 54 48 44 41 38
Notes:
1. For poor bond conditions divide the coefficients by 0.7.
2. For bars greater than 32mm divide the coefficients by [(132 − φ )100] where φ is the bar size.
Page 8 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
ii) neutral axis depth, x, should be no greater than 0.25 of the effective depth
iii) there are at least three spans that do not differ in length by more than 15 per cent
iv) Qk should be less than or equal to 1.25G k and also less than 5 KN / m 2
Table 8.5 Ultimate bending moment and shear force coefficients in one-way spanning slabs
End support condition
Pinned Continuous At first At middle
At interior
Near interior of interior
Outer supports
middle of End support End span support spans
support
end span
Moment 0 0.086 Fl − 0.04 Fl 0.075 Fl − 0.086 Fl 0.063Fl − 0.063Fl
Shear 0.40 F 0.46 F 0.60 F 0.50 F
Notes:
1. F is the total design ultimate load, F = (1.35G k + 1.5Qk ) L
2. L is the span length
Beam
Beam
Beam
Beam
Span Span Span Span
7m
Plan
Elevation
Page 10 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
Beam A
Load on beam A
Beam D
Beam C
Load on Load on
beam C beam D
Load on beam B
Beam B
Fig.8.5 loads carried by supporting beams
Page 11 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
Bending-long span
M sy = a sy nl x2 = 0.051 × 22.43 × 4.5 2 = 23.16 KNm
Since the reinforcement for this span will have a reduced effective depth, take z = 176 − 12 = 164mm . Therefore
M sy 23.16 × 10 6
Asy = = = 325mm 2 / m
0.87 f yk z 0.87 × 500 × 164
Provide H10 at 200mm centres, Asy = 393mm 2 / m .
100 As ,req 100 × 393
ρ2 = = = 0.24%
bd 1000 × 164
which is greater than 0.13, the minimum for transverse steel, with class C25/30 concrete.
The arrangement of the reinforcement is shown in figure 8.6.
H10-200
H12-175
4.5m
Table 8.7 Bending moment coefficients for two-way spanning rectangular slabs supported by beams
Short span coefficients, β sx for values of l y / l x Long-span
Type of panel and coefficients, β sy for
moments considered 1.0 1.1 1.2 1.3 1.4 1.5 1.75 2.0
all value of l y / l x
Interior panels
Negative moment at continuous edge 0.031 0.037 0.042 0.046 0.050 0.053 0.059 0.063 0.032
Positive moment at mid-span 0.024 0.028 0.032 0.035 0.037 0.040 0.044 0.048 0.024
One short edge discontinuous
Negative moment at continuous edge 0.039 0.044 0.048 0.052 0.055 0.058 0.063 0.067 0.037
Positive moment at mid-span 0.029 0.033 0.036 0.039 0.041 0.043 0.047 0.050 0.028
One long edge discontinuous
Negative moment at continuous edge 0.039 0.049 0.056 0.062 0.068 0.073 0.082 0.089 0.037
Positive moment at mid-span 0.030 0.036 0.042 0.047 0.051 0.055 0.062 0.067 0.028
Two adjacent edges discontinuous
Negative moment at continuous edge 0.047 0.056 0.063 0.069 0.074 0.078 0.087 0.093 0.045
Positive moment at mid-span 0.036 0.042 0.047 0.051 0.055 0.059 0.065 0.070 0.034
Two short edges discontinuous
Negative moment at continuous edge 0.046 0.050 0.054 0.057 0.060 0.062 0.067 0.070 -
Positive moment at mid-span 0.034 0.038 0.040 0.043 0.045 0.047 0.050 0.053 0.034
Two long edges discontinuous
Negative moment at continuous edge - - - - - - - - 0.045
Positive moment at mid-span 0.034 0.046 0.056 0.065 0.072 0.078 0.091 0.100 0.034
Three edges discontinuous (one
long edge continuous)
Negative moment at continuous edge 0.057 0.065 0.071 0.076 0.081 0.084 0.092 0.098 -
Positive moment at mid-span 0.043 0.048 0.053 0.057 0.060 0.063 0.069 0.074 0.044
Three edges discontinuous (one
short edge continuous)
Negative moment at continuous edge - - - - - - - - 0.058
Positive moment at mid-span 0.042 0.054 0.063 0.071 0.078 0.084 0.096 0.105 0.044
Four edges discontinuous
Positive moment at mid-span 0.055 0.065 0.074 0.081 0.087 0.092 0.103 0.111 0.056
Page 13 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
ly ly
lx
8
Edge strip
Middle strip
Edge strip
Edge strip
Middle strip 3lx
lx
4
Edge strip
ly 3ly ly lx
8 4 8 8
support
Discontinuous
a b supported edge
l y =6.25m
support
d c
support
Page 14 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
Cross-sections through a ribbed and hollow block floor slabs are shown in figure 8.9.
They would not be suitable for structures having a heavy loading, such as Warehouses and garages.
Design
• The slab is designed as a T-section with the effective flange breadths. Near the supports the slab is made solid at
about 0.5 ~ 1.0m from the support to increase shear strength.
• The slabs are usually made solid under partitions and concentrated loads.
• During construction the hollow tiles should be well soaked in water prior to placing the concrete, otherwise
shrinkage cracking of the top concrete flange is liable to occur.
• The thickness of the concrete flange should not be less than:
1. 40mm or one-tenth of the clear distance between ribs, whichever is the greater, for slabs with permanent
blocks;
2. 50mm or one-tenth tenth of the clear distance between ribs, whichever is the greater, for slabs without
permanent blocks.
Page 15 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
Supporting beam
light mesh
Fig.8.9 Sections through ribbed and hollow block floors, and waffle slab
d =160 h =200
60
125 400
Cross-section at mid-span
Fig.8.10 Ribbed slab
Page 16 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
Table 8.8 Minimum dimensions and axis distance for RC slabs for fire resistance
Minimum dimensions (mm)
Standard fire Two-way spanning
One-way Ribs in two-way spanning ribbed
resistance
spanning l y / l x ≤ 1.5 1.5 < l y / l x ≤ 2.0 slab
hs = 80 80 80 bmin = 100 120 ≥ 200
REI 60
a= 20 10 15 a= 25 15 10
hs = 100 100 100 bmin = 120 160 ≥ 250
REI 90
a= 30 15 20 a= 35 25 15
hs = 120 120 120 bmin = 160 190 ≥ 300
REI 120
a= 40 20 25 a= 45 40 30
hs = 175 175 175 bmin = 450 700 -
REI 240
a= 65 40 50 a= 70 60 -
The calculations are for an end span (which will be most critical) for which the moments and shears can be
determined from the coefficients in table 8.5.
Considering a 0.4m width of floor as supported by each rib:
Ultimate load = 0.4(0.35 g k + 1.5q k )
= 0.4(0.35 × 4.5 + 1.5 × 2.5)
= 3.93KN / m
Ultimate load on the span, F = 3.93 × 5.0 = 19.65 KN
Bending
1. At mid-span design as a T-section:
M = 0.086 Fl = 0.086 × 19.65 × 5.0 = 8.45 KNm
The effective breadth of flange = bw + beff 1 + beff 2 where
beff 1 = beff 2 = 0.2b1 + 0.1l 0 ≤ 0.2l 0 ≤ b1
with b1 = (400 − 125) / 2 = 137 mm and l 0 = 0.85 × 5000 = 4250mm
thus
bw + beff 1 + beff 2 = 125 + 2(0.2 × 137 + 0.1 × 4250) = 1030mm
or 0.2 × 4250) = 850mm
which both exceed the rib spacing of 400mm, which governs
M 8.45 × 10 6
= = 0.033
bd 2 f ck 400 × 160 2 × 25
From the lever arm equation
z = d [0.5 + (0.25 − K / 1.134) ] = d [0.5 + (0.25 − 0.033 / 1.134) ] = 0.97 d > 0.95d . Thus the
neutral axis depth lies within the flange.
Therefore adopt upper limit of 0.95d and lever arm z = 0.95d = 0.95 × 160 = 152mm
and
M 8.45 × 10 6
As = = = 127.8mm 2
0.87 f yk z 0.87 × 500 × 152
Provide two H10 bars in the ribs, As = 157mm 2 .
2. At the end interior support design as a rectangular section for the solid slab:
M = 0.086 Fl = 0.086 × 19.65 × 5.0 = 8.45 KNm as in 1.
and As = 128mm 2 as at mid-span
Provide two H10 bars in each 0.4m width of slab, As = 157mm 2 .
Page 17 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
3. At the section where the ribs terminate: this occurs 0.6m from the centerline of the support and the moment may
be hogging so that 125mm ribs must provide the concrete area in compression to resist the design moment. The
maximum moment of resistance of the concrete is
M = 0.167 f ck bd 2 = 0.167 × 25 × 125 × 160 2 × 10 −6 = 13.36 KNm
which must be greater than the moment at this section, therefore compression steel is not required.
Shear
Maximum shear in the rib 0.6m from the support centerline (end span)
V Ed = 0.6 F − 0.6 × 3.93 = 0.6 × 19.65 − 0.6 × 3.93 = 9.43KN
As 157
ρ1 = = = 0.0079
bd 125 × 160
From table 8.1, the shear resistance without reinforcement V Rd ,c = v Rd ,c bd where v Rd ,c = 0.68 N / mm 2 and, from
table 8.2, the strength modification factor = 0.94 . Hence:
VRd ,c = v Rd ,c bd = 0.94 × 0.68 × 125 × 160 = 12.78 KN
As V Rd ,c is greater than V Ed then no shear reinforcement is required provided that the bars in the ribs are securely
located during construction.
As the slab has the same span in each direction the moment coefficients, β sx , β sy are taken from table 8.7 with
l y / l x = 1.0 . Calculations are given for a single 0.4m wide beam section and in both directions of span.
Bending
1. At mid-span: design as a T-section.
Positive moment at mid-span = m sx = β sx nl x2 = 0.024 × 11.85 × 6 2 = 10.24 KNm / m
Moment carried by each rib = 0.4 × 10.24 = 4.10 KNm
M 4.1 × 10 6
= = 0.016
bd 2 f ck 400 × 160 2 × 25
where the effective breadth is 400mm as in the previous example.
From the lever arm equation
Page 18 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
z = d [0.5 + (0.25 − K / 1.134) ] = d [0.5 + (0.25 − 0.016 / 1.134) ] = 0.98d > 0.95d . Thus the neutral axis
depth lies within the flange and
M 4.1 × 10 6
As = = = 62 mm 2
0.87 f yk z 0.87 × 500 × 0.95 × 160
Provide two H10 bars in each rib at the bottom of the beam, As = 157mm 2 to satisfy minimum requirement of
0.13bd % = 0.0013 × 400 × 160 = 83mm 2 / rib . Note that since the service stress in the steel will be reduced, this
lead to a higher span-effective depth ratio thus ensuring that the span-effective depth ratio of the slab is kept within
acceptable limits.
3. At the section where the ribs terminate: the maximum hogging moment of resistance of the concrete ribs is
13.36 KNm as in the previous example. This is greater than the moment at this section, therefore compression steel
is not required.
Shear
From the table 8.9 the shear force coefficient for a continuous edge support is 0.33. Hence, for one rib, the shear at
the support
Vsx = β vx nl x × b = 0.33 × 11.85 × 6 × 0.4 = 9.38 KN
Maximum shear in the rib 0.6m from the centerline is
VEd = 9.38 − 0.6 × 11.85 × 0.4 = 6.54 KN
At this position, V Rd ,c = v Rd ,c × 125 × 160 and
100 As 100 × 157
ρ1 = = = 0.79%
bd 125 × 160
Hence from table 8.1, v Rd ,c = 0.68 N / mm 2 and, from table 8.2, the strength modification factor = 0.94 . Hence:
VRd ,c = v Rd ,c bd = 0.94 × 0.68 × 125 × 160 = 12.8 KN
Therefore the unreinforced section is adequate in shear, and no links are required provided that the bars in the ribs
are securely located during construction.
Page 19 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
Table 8.9 Shear force coefficients for uniformly loaded rectangular panels supported
on four sides with provision for torsion at corners
β vx for values of l y / l x β vy
Type of panel and location 1.0 1.1 1.2 1.3 1.4 1.5 1.75 2.0
Four edges continuous
continuous 0.33 0.36 0.39 0.41 0.43 0.45 0.48 0.50 0.33
One short edge discontinuous
Continuous edge 0.36 0.39 0.42 0.44 0.45 0.47 0.50 0.52 0.36
Discontinuous edge - - - - - - - - 0.24
One long edge discontinuous
Continuous edge 0.36 0.40 0.44 0.47 0.49 0.51 0.55 0.59 0.36
Discontinuous edge 0.24 0.27 0.29 0.31 0.32 0.34 0.36 0.38 -
Two adjacent edges discontinuous
Continuous edge 0.40 0.44 0.47 0.50 0.52 0.54 0.57 0.60 0.40
Discontinuous edge 0.26 0.29 0.31 0.33 0.34 0.35 0.38 0.40 0.26
Two short edges discontinuous
Continuous edge 0.40 0.43 0.45 0.47 0.48 0.49 0.52 0.54 -
Discontinuous edge - - - - - - - - 0.26
Two long edges discontinuous
Continuous edge - - - - - - - - 0.40
Discontinuous edge 0.26 0.30 0.33 0.36 0.38 0.40 0.44 0.47 -
Three edges discontinuous
(one long edge discontinuous)
Continuous edge 0.45 0.48 0.51 0.53 0.55 0.57 0.60 0.63 -
Discontinuous edge 0.30 0.32 0.34 0.35 0.36 0.37 0.39 0.41 0.29
Three edges discontinuous
(one short edge discontinuous)
Continuous edge - - - - - - - - 0.45
Discontinuous edge 0.29 0.33 0.36 0.38 0.40 0.42 0.45 0.48 0.30
Four edges discontinuous
Discontinuous edge 0.33 0.36 0.39 0.41 0.43 0.45 0.48 0.50 0.33
CL
Light mesh
Page 21 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
Landing Landing
H12-400
H1
Open well 0-4
00
1.5m
H12-300
H12-400
Span 3.0m
Span
The permanent load is calculated along the slope length of the stairs but the variable load is based on the plan area.
If the total design load on the stair is F and the staircase is cast monolithically with the floor slab, then positive
moment at mid span, M = Fl / 10 , and negative moment at supports, M = Fl / 10 . If the staircase is precast, the
positive design moment, M = Fl / 8 . The shear force in both cases, SF = F / 2 .
When the staircase is built monolithically at its ends into a structural member spanning at right angles to its span,
the effective span is given by
Leff = Ln + a1 + a 2
where
Ln is the clear horizontal distance between supporting members
a1 is half the breadth of supporting member at one end
a 2 is half the breadth of supporting member at other end
The thickness of the waist is taken as the slab thickness.
The design procedure is the same as that of slabs.
Bending reinforcement
Page 22 of 23
CE311 STRUCTURAL DESIGN I CHAPTER VIII
M 13.16 × 10 6
= = 0.034
bd 2 f ck 1000 × 115 2 × 30
From the lever arm equation
z = d [0.5 + (0.25 − K / 1.134) ] = d [0.5 + (0.25 − 0.034 / 1.134) ] = 0.97 d > 0.95d .
M 13.46 × 10 6
As = = = 283 mm 2 / m
0.87 f yk z 0.87 × 500 × 0.95 × 115
Maximum allowable spacing is 3h = 3 × 140 = 420mm with an upper limit of 400mm.
Provide H12 bars at 300mm centres, As = 377 mm 2 / m .
Secondary reinforcement
Transverse distribution steel ≥ 0.2 As ,min = 0.2 × 377 = 75.4mm 2 / m
This is very small, and adequately covered by H10 bars at the maximum allowable spacing of 400mm centres, area
= 174mm 2 / m .
Continuity bars at the top and bottom of the span should be provided and, whereas about 50per cent of the main
steel would be reasonable, the maximum spacing is limited to 400mm. Hence provide, say, H12 bars at 400mm
centres as continuity steel.
Page 23 of 23
CE311 STRUCTURAL DESIGN I CHAPTER IX
The columns in a structure carry the loads from the beams and slabs down to the foundations, and therefore they
are primarily compression members, although they may also have to resist bending forces due to the continuity of
the structure.
Columns carrying only axial forces can be designed based on the equations.
Columns carrying axial forces plus bending moments are designed with the aid of design charts.
Columns may be square, rectangular, circular, elliptical, cruciform or of other shapes.
Initial dimensions are normally determined by taking into account requirements for durability and fire resistance
(table 9.1).
Table 9.1 Minimum dimensions and axis distance for RC columns and walls for fire resistance
Minimum dimensions (mm)
Column width bmin /axis distance, a, of the Wall thickness/axis distance, a, of the main
Standard fire
main bars bars
resistance
Columns exposed on Columns exposed on Wall exposed on one Wall exposed on two
more than one side one side side sides
R60 250/46 155/25 130/10 140/10
350/40
R90 350/53 155/25 140/25 170/25
450/40
R120 350/57 175/35 160/35 220/35
450/51
R240 600/70 295/70 270/60 350/60
Page 1 of 14
CE311 STRUCTURAL DESIGN I CHAPTER IX
In this chapter only the design of the most common types of columns found in building structures, namely braced
columns, will be described. A column may be considered to be braced in a given plane if the bracing element or
system (e.g. core or shear walls) is sufficiently stiff to resist all the lateral forces in that plane. Thus braced columns
are assumed to not contribute to the overall horizontal stability of a structure and as such are only designed to resist
axial load and bending due to vertical loading.
9.2 Slenderness ratio, Effective height and Limiting slenderness ratio of column
k1 k2
l 0 = 0.5l 1 + 1 + (9.2)
0.45 + k1 0.45 + k 2
k ×k
l 0 = l 1 + 10 1 2 (9.3.a)
k1 + k 2
and
k k
l 0 = l 1 + 1 1 + 2 (9.3.b)
1 + k1 1 + k 2
In the above formulae, k1 and k 2 are the relative flexibilities of the rotational restraints at ends ‘1’ and ‘2’
of the column respectively. At each end k1 and k 2 can be taken as:
Page 2 of 14
CE311 STRUCTURAL DESIGN I CHAPTER IX
Page 3 of 14
CE311 STRUCTURAL DESIGN I CHAPTER IX
The limiting value of λ for a braced column will depend on the relative value of the column’s end moments that
will normally act in the same clockwise or anti-clockwise direction as in case (b) above. If these moments are of
approximately equal value then rm = −1, C = 1.7 + 1 = 2.7 and a typical, approximate limit on λ will be given
by:
λ min = 20 × A × B × C / n = 20 × 0.7 × 1.1 × 1.7 / N Ed /( Ac f cd )
= 26.2 / N Ed /( Ac f cd )
If the actual slenderness ratio is less than the calculated value of λ min then the column can be treated as short.
Otherwise the column must be treated as slender and second order effects must be accounted for in the design of
the column.
Beam 500
700
Length=6.0m Length=4.0m
400
h col =3.0m
300
Y Y
Beam
It can be seen that the column will have the highest slenderness ratio for bending about YY where h = 300mm
and also the end restraints are the less stiff 300 × 500 beams.
Slenderness ratio λ
I bh 3 / 12 h 300
Radius of gyration, i = col = = = = 86.6mm
Acol bh 3.464 3.464
Slenderness ratio λ = l 0 / i = 1.77 × 10 3 / 86.6 = 20.4
For a braced column the minimum limiting value of λ will be given by
λ min = 26.2 / N Ed /( Ac f cd )
where
Page 4 of 14
CE311 STRUCTURAL DESIGN I CHAPTER IX
Longitudinal steel
1. A minimum of four bars is required in a rectangular column (one bar in each corner) and six bars in a circular
column. Bar diameter should not be less than 12mm.
2. The minimum area of steel is given by
0.10 N Ed
As = ≥ 0.002 Ac
0.87 f yk
3. The maximum area of steel, at laps is given by
As ,max
< 0.08
Ac
where As is the total area of longitudinal steel and Ac is the cross-sectional area of the column.
As ,max
Otherwise, in regions away from laps: < 0.04 .
Ac
Links
1
1. Minimum size = × size of the compression bar but not less than 6mm.
4
2. Maximum spacing should not exceed the lesser of 20 × size of the smallest compression bar or the least
lateral dimension of the column or 400mm. This spacing should be reduced by a factor of 0.60.
(a) for a distance equal to the larger lateral dimension of the column above and below a beam or slab, and
(b) at lapped joints of longitudinal bars > 14mm diameter.
3. Where the direction of the longitudinal reinforcement changes, the spacing of the links should be calculated,
while taking account of the lateral forces involved. If the change in direction is less than or equal to 1 in 12
no calculation is necessary.
4. Every longitudinal bar placed in a corner should be held by transverse reinforcement.
5. No compression bar should be further than 150mm from a restrained bar.
Design charts
The basic equations derived for a rectangular section as shown in figure 9.3 and with a rectangular stress block are:
Page 5 of 14
CE311 STRUCTURAL DESIGN I CHAPTER IX
N Ed = Fcc + Fsc + Fs
(9.5)
= 0.567 f ck bs + f sc As′ + f s As
h s h h
M Ed = Fcc − + Fsc − d ′ − Fs d − (9.6)
2 2 2 2
N Ed = design ultimate axial load
M Ed = design ultimate moment
s = the depth of the stress block = 0.8 x
As′ = the area of longitudinal reinforcement in the more highly compressed face
As = the area of reinforcement in the other face
f sc = the stress in reinforcement As′
f s = the stress in reinforcement As , negative when tensile.
b
0.0035 0.567fck
d'
Fsc
s/2
A's x s=0.8x
d sc Fcc
h neutral
As axis
s Fs
These equations are not suitable for direct solution and the design of a column with symmetrical reinforcement in
each face is best carried out using design chart as illustrated in figure 9.4.
Page 6 of 14
CE311 STRUCTURAL DESIGN I CHAPTER IX
4.0m
Plan
P
3rd floor
3.0m
2nd floor
3.0m
1st floor
400
ground 3.0m
floor 300 400 columns
Q
6.0m 4.0m
1.35G k + 1.5 Q k
k column
Maximum ultimate load at each floor = 4.0(1.35 g k + 1.5q k ) per meter length of beam
= 4(1.35 × 10 + 1.5 × 15)
= 144 KN / m
Minimum ultimate load at each floor = 4.0 × 1.35 g k per meter length of beam
= 4.0 × 1.35 × 10
= 54 KN / m per metre length of beam
Consider first the design of the centre column at the underside (u.s.) of the first floor. The critical arrangement of
load that will cause the maximum moment in the column is shown in figure 9.6a.
Column loads
Second and third floors = 2 × 144 × 10 / 2 = 1440 KN
First floor = 144 × 6 / 2 + 54 × 4 / 2 = 540 KN
Column self-weight, say 2 × 14 = 28 KN
N Ed = 2008 KN
Similar arrangement of load will give the axial load in the column at the underside (u.s.) and top side (t.s.) of each
floor level and these values of N Ed are shown in table 9.3.
Table 9.3
N Ed M Ed N Ed M Ed As f yk
Floor As (mm 2 )
(KN ) (KNm) bhf ck bh 2 f ck bhf ck
3rd u.s. 540 82.6 0.18 0.07 0 240
2nd t.s. 734 68.4 0.24 0.06 0 240
+ 540
2nd u.s. 1274 68.4 0.42 0.06 0 240
1st t.s. 1468 68.4 0.49 0.06 0.10 600
+ 540
1st u.s. 2008 68.4 0.67 0.06 0.30 1800
Column moments
The loading arrangement and the substitute frame for determining the column moments at the first and second
floors are shown in figure 9.6c.
Member stiffness are
k AB 1 bh 3 1 0.3 × 0.7 3
= × = × = 0.71 × 10 −3
2 2 12 L AB 2 12 × 6
k BC 1 bh 3 1 0.3 × 0.7 3
= × = × = 1.07 × 10 −3
2 2 12 LBC 2 12 × 4
0.3 × 0.4 3
k col = = 0.53 × 10 −3
12 × 3.0
therefore
∑ k = (0.71 + 1.07 + 2 × 0.53)10 −3
= 2.84 × 10 −3
and
k col 0.53
distribution factor for the column = = = 0.19
∑ k 2.84
Fixed end moments at B are
144 × 6 2
F.E. M . BA = = 432 KNm
12
54 × 4 2
F.E. M . BC = = 72 KNm
12
Thus
Page 8 of 14
CE311 STRUCTURAL DESIGN I CHAPTER IX
4H25 4H16
(a) Ground to 1st Floor (b) 1st to 3rd Floor
Fig.9.7 Column section in design example
Cover for the reinforcement is taken as 50mm and d 2 / h = 80 / 400 = 0.2 . The minimum area of reinforcement
allowed in the section is given by:
As = 0.002bh = 0.002 × 300 × 400 = 240mm 2
and the maximum area is
As = 0.08bh = 0.008 × 300 × 400 = 9600mm 2
and the reinforcement provided is within these limits.
0.567fck
d' fsc A's
e
A's x s
h/2 d neutral 0.567f ck bs
axis
h/2 As
d2 fs As
b
1. Select a depth of neutral axis, x (for this design method where the moments are relatively large, x would
generally be less than h).
2. Determine the steel strains ε sc and ε s from the strain distribution.
3. Determine the steel stresses f sc and f s from the equations relating to the stress-strain curve for the reinforcing
bars.
Page 9 of 14
CE311 STRUCTURAL DESIGN I CHAPTER IX
d '=80
A's x
neutral
400
340
axis sc
As
d 2=60
s
Section Strains
Fig.9.9 Unsymmetrical column design example
1. Select a depth of neutral axis, x = 190mm .
2. From the strain diagram
0.0035 0.0035
steel strain ε sc = ( x − d ′) = (190 − 80) = 0.00203
x 190
and
0.0035 0.0035
steel strain ε s = (d − x) = (340 − 190) = 0.00276
x 190
3. From the stress-strain curve and the relevant equations of section 5.1 yield strain, ε y = 0.00217 for grade 500
steel
ε s > 0.00217; therefore f s = 500 / 1.15 = 435 N / mm 2
and
ε sc < 0.00217; therefore f sc = E s ε sc = 200 × 10 3 × 0.00203 = 406 N / mm 2 , compression.
4. In equation 9.7
h
N Ed e + − d 2 = 0.567 f ck bs (d − s / 2) + f sc As′ (d − d ′)
2
M 230 × 10 6
e = Ed = = 209mm
N Ed 1100 × 10 3
s = 0.8 x = 0.8 × 190 = 152mm
To allow for the area of concrete displaced
f sc becomes 406 − 0.567 f ck = 406 − 0.567 × 25 = 392 N / mm 2
and from equation 9.7
Page 10 of 14
CE311 STRUCTURAL DESIGN I CHAPTER IX
A's + As
3000
2900
2800
2700
180 190 200 210 220 230
Depth of neutral axis, x
Fig.9.10 Design chart for unsymmetrical column example
Page 11 of 14
CE311 STRUCTURAL DESIGN I CHAPTER IX
etot = e0 + ea + e2
e0 is an equivalent first-order eccentricity
ea is an accidental eccentricity which accounts for geometric imperfections in the column
e2 is the second-order eccentricity.
Page 12 of 14
CE311 STRUCTURAL DESIGN I CHAPTER IX
M 1 10 × 10 3
e01 = = = 5.9mm
N Ed 1700
M 2 − 70 × 10 3
e02 = = = −41.2mm
N Ed 1700
where e02 is negative since the column is bent in double curvature.
Z
M 2 =70kNm
M
'
d=60
d=240
h=300
Y Y
M 1 =10kNm
Z
The limiting slenderness ratio can be calculated from equation 9.4 where:
A = 1 /(1 + 0.2φef ) = 1 /(1 + (0.2 × 0.87)) = 0.85
B = the default value of 1.1
C = 1.7 − M 01 / M 02 = 1.7 − (−10 / 70) = 1.84
34.41
∴ λmin = 20 × A × B × C / n = 20 × 0.85 × 1.1× 1.84 / n =
n
N Ed 1700 × 10 3
n= = = 0.89
Ac f cd (300 × 450) × 0.567 × 25
34.41
∴ λmin = = 36.47
0.89
Actual slenderness ratios are
ley 6.75
λy = = × 3.46 = 77.85 > 36.47
iy 0.3
lez 8.0
λz = = × 3.46 = 61.55 > 36.47
i z 0.45
Therefore the column is slender, and λ y is critical.
Equivalent eccentricity = 0.6e02 + 0.4e01 ≥ 0.4e02
0.6e02 + 0.4e01 = 0.6 × 41.2 + 0.4 × (−5.9) = 22.35mm
0.4e02 = 0.4 × 41.2 = 16.47mm
Therefore equivalent eccentricity e0 = 22.35mm .
Taking v as 1 / 200 the accidental eccentricity is
ley 1 6750
ea = v = × = 16.88mm
2 200 2
The second-order eccentricity is
K1 K 2 l02 f yk
e2 = 2
π × 103500d
where
Page 13 of 14
CE311 STRUCTURAL DESIGN I CHAPTER IX
f yk λ 25 77.85
K1 = 1 + 0.35 + − φef = 1 + 0.35 + − × 0.87
200 150 200 150
= 0.96 (≥ 1)
K1 K 2 l02 f yk 1× 1× 6750 2 × 500
∴ e2 = = = 92.92mm
π 2 × 103500d π 2 × 103500 × 240
with K 2 = 1.0 for the initial value.
For the first iteration the total eccentricity is
etot = e0 + ea + e2 = 22.35 + 16.88 + 92.92 = 132.15mm
and the total moment is
M t = N Ed etot = 1700 × 132.15 × 10 −3 = 225kNm
N Ed 1700 × 10 3
= = 0.504
bhf ck 450 × 300 × 25
Mt 225 × 10 6
= = 0.222
bh 2 f ck 450 × 300 2 × 25
From the design chart of figure 9.4
As f yk
= 0.80 and K 2 = 0.78
bhf ck
This new value of K 2 is used to calculate e2 and hence M t for the second iteration. The design chart is again
used to determine As f yk / bhf ck and a new value of K 2 as shown in table 9.4.
Table 9.4
(1) (2) (3) (4) (5)
Mt As f yk
K2 Mt bh 2 f ck bhf ck K2
1.0 225 0.222 0.80 0.78
0.78 190 0.187 0.6 0.73
The iterations are continued until the value of K 2 in columns (1) and (5) of the table are in reasonable agreement,
which in this design occurs after two iterations. So that the steel area required is
0.6bhf ck 0.6 × 450 × 300 × 25
As = = = 4050mm 2
f yk 500
and K 2 = 0.74 .
As a check on the final value of K 2 interpolated from the design chart:
N bal = 0.29 f ck Ac
= 0.29 × 25 × 300 × 450 × 10 −3
= 978kN
N Ed = 0.567 f ck Ac + 0.87 f yk As
= (0.567 × 25 × 300 × 450 + 0.87 × 500 × 4050)10 −3
= 3675kN
N ud − N Ed 3675 − 1700
K2 = = = 0.73 (≤ 1.0)
N ud − N bal 3675 − 978
which agrees with the final value in column 5 of table 9.4.
Page 14 of 14
CE311 STRUCTURAL DESIGN I CHAPTER X
10.1 Introduction
A building is generally composed of a superstructure above the ground and a substructure which forms the
foundations below ground.
The foundations transfer and spread the loads from a structure’s columns and walls into the ground. The safe
bearing capacity of the soil must not be exceeded otherwise excessive settlement may occur, resulting in damage to
the building and its service facilities. Foundation failure can also affect the overall stability of a structure so that it
is liable to slide, to lift vertically or even overturn.
(a) (b)
Fig.10.1 Foundation failures: (a) sliding failure; (b) overturning failure
Foundation types
There are many types of foundations which are commonly used, namely strip, pad and raft. The foundations may
bear directly on the ground or be supported on piles. The choice of foundation type will largely depend upon (1)
ground conditions (i.e. strength and type of soil) and (2) type of structure (i.e. layout and level of loading).
Pad footings are usually square or rectangular slabs and used to support a single column (Fig. 10.2). The pad may
be constructed using mass concrete or reinforced concrete depending on the relative size of the loading. Continuous
strip footings are used to support loadbearing walls or under a line of closely spaced columns (Fig. 10.3). Strip
footings are designed as pad footings in the transverse direction and in the longitudinal direction as an inverted
continuous beam subject to the ground bearing pressure.
N N N N
= = =
A B C D
Elevation
Plan
Where the ground conditions are relatively poor, a raft foundation may be necessary in order to distribute the loads
from the walls and columns over a large area. In its simplest form this may consist of a flat slab, possibly
strengthened by upstand or downstand beams for the more heavily loaded structures (Fig. 10.4).
Where the ground conditions are so poor that it is not practical to use strip or pad footings but better quality soil is
present at lower depths, the use of pile foundations should be considered (Fig. 10.5).
Soft strata
Hard strata
The piles may be made of precast reinforced concrete, prestressed concrete or in-situ reinforced concrete. Loads are
transmitted from the piles to the surrounding strata by end bearing and/or friction. End bearing piles derive most of
their carrying capacity from the penetration resistance of the soil at the toe of the pile, while friction piles rely on
the adhesion or friction between the sides of the pile and the soil.
Foundation design
Foundation failure may arise as a result of (a) allowable bearing capacity of the soil being exceeded, or (b) bending
and/or shear failure of the base.
The first condition allows the plan-area of the base to be calculated, being equal to the design load divided by the
bearing capacity of the soil, i.e.
design load
Ground pressure = < bearing capacity of soil
plan area
Since the settlement of the structure occurs during its working life, the design loadings to be considered when
calculating the size of the base should be taken as those for the serviceability limit state (i.e. 1.0Gk + 1.0Qk ). The
calculations to determine the thickness of the base and the bending and shear reinforcement should, however, be
based on ultimate loads (i.e. 1.35Gk + 1.5Qk ).
Page 2 of 7
CE311 STRUCTURAL DESIGN I CHAPTER X
M M
D D Y/3 e
Centroid
p2
p p1 p
Y
e=0 e ≤ D/6 e > D/6
N N 6M 2N
p= p= ± p=
B× D B × D B × D2 B ×Y
D
where: Y = 3 − e
2
(a) (b) (c)
Fig.10.6 Pad-footing- pressure distributions
or
D
Y = 3 − e
2
therefore in the case of e > D / 6
2N
maximum pressure p = (10.4)
3 B ( D / 2 − e)
Requirements
A typical arrangement of the reinforcement in a pad footing is shown in figure 10.7. With a square base the
reinforcement to resist bending should be distributed uniformly across the full width of the footing. For a
rectangular base the reinforcement in the short direction should be distributed with a closer spacing in the region
under and near the column, to allow for the fact that the transverse moments must be greater nearer the column. It
is recommended that at least teo-thirds of the reinforcement in the short direction should be concentrated in a band
width of (c + 3d ) where c is the column dimension in the long direction and d is the effective depth. If the footing
should be subjected to a large overturning moment so that there is only partial bearing, or if there is a resultant
uplift force, then reinforcement may also be required in the top face.
Dowels or slarter bars should extend from the footing into the column in order to provide continuity to the
reinforcement. These dowels should be embedded into the footing and extend into the columns a full lap length.
Sometimes a 75mm length of the column is constructed in the same concrete pour as the footing so as to form a
'kicker' or support for the column’s shutters. In these cases the dowel’s lap length should be measured from the top
of the kicker.
The critical sections through the base for checking shear, punching shear and bending are shown in figurc 10.8. The
shearing force and bending moments are caused by the ultimate loads from the column and the weight of the base
should not be included in these calculations.
The thickness of the base is often goverened by the requirements for shear resistance.
Dowels
lap length
d h
h
D
Maximum
shear 2.0d Punching shear perimeter
= column perimeter +4pd
B As Shear
Bending 1.0d
Fig.10.7 Pad footing reinforcement details Fig.10.8 Critical sections for design
8. Where applicable, both foundations and the structure should be checked for overall stability at the ultimate limit
state.
9. Reinforcement to resist bending in the bottom of the base should extend at least a full tension anchorage length
beyond the critical section for bending.
d=520
h=600
12H16@225 e.w.
2.8m. sq
VEd
Punching shear stress v Ed =
perimeter × d
626 × 10 3
= = 0.15 N / mm 2
8134 × 520
This ultimate shear stress is not excessive,(see table 8.1) therefore h = 600mm will be a suitable estimate.
5. Bending reinforcement-see figure 10.10(a).
At the column face which is the critical section
1.2
M Ed = (239 × 2.8 × 1.2) × = 482 KNm
2
1.2 m 0.68 m 1.0d=0.52 m
2.8 m
Page 6 of 7
CE311 STRUCTURAL DESIGN I CHAPTER X
Page 7 of 7