02 - Overview of Protection Fundamentals
02 - Overview of Protection Fundamentals
1.0 INTRODUCTION
Relays are compact devices that are connected throughout the power
system to detect intolerable or unwanted conditions within an assigned
area. They are in effect, a form of active insurance designed to maintain
a high degree of service continuity and limit equipment damage. They
are “Silent Sentinels”. While protective relays will be the main emphasis of
this chapter, other types of relays, applied on a more limited basis or used
as part of a total protective relays system will also be covered.
(i) Input
¾ Current
¾ Voltage
¾ Power
¾ Pressure
¾ Frequency
¾ Temperature
¾ Flow
¾ Vibration
The above classification and definitions are based on the ANSI Standard
37.90 (IEEE 313).
The third and fourth considerations are perhaps better expressed as the
“personality of the system and the relay engineer”.
A complex relaying system may result from poor system design or the
economic need to use fewer circuit breakers. Considerable savings can
be realized by using fewer circuit breakers and a more complex relay
system. Such systems usually involve design compromises requiring careful
evaluation, if acceptable protection is to be maintained.
The application logic of protective relays divides the power system into
several zones, each requiring its own group of relays. In all cases, the five
design criteria listed below are common to any well-designed and
efficient protective system or system segment:
4.1 Reliability
System reliability consists of two elements – dependability and security.
Dependability is the certainty of correct operation in response to system
trouble, while security is the ability of the system to avoid mis-operation
between faults. Unfortunately, these aspects of reliability tend to counter
one another: increasing security tends to decrease dependability and
vice versa. In general, however, modern relaying systems are highly
reliable and provide practical compromise between security and
dependability.
Protective relay system must perform correctly under adverse system and
environmental conditions. Regardless of whether other systems are
momentarily blinded during this period, the relays must perform
accurately and dependably. They must either operate in response to
trouble in their assigned area or block correctly if the trouble is outside
their designated area.
4.2 Speed
Relays that could anticipate a fault would be utopian. But, even if
available, they would doubtlessly raise the question of whether or not the
fault or trouble really required a trip-out. The development of faster relays
must always be measured against the increased probability of more
unwanted or unexplained operations. Time, no matter how short, is still the
best method of distinguishing between real and counterfeit trouble.
Applied to a relay, high speed indicates that the operating time usually
does not exceed 50 ms (3 cycles on a 60-hertz base). The term
instantaneous indicates that no delay is purposely introduced in the
operation. In practice, the terms high speed and instantaneous are
frequently used interchangeably.
4.4 Simplicity
As in any other engineering discipline, simplicity in a protective relay
system is always the hallmark of a good design. The simplest relay system,
however, is not always the most economical. As previously indicated,
major economies are possible with a complex relay system that uses a
minimum number of circuit breakers. Other factors being equal, simplicity
of design improves system reliability – if only because there are fewer
elements that can malfunction.
(1) Correct
(2) No conclusion
(3) Incorrect
Incorrect tripping of circuit breakers not associated with the trouble area
is often as disastrous as a failure to trip. Hence, special care must be
taken in both application and installation to ensure against the possibility
of incorrect tripping.
i) Generators
ii) Transformers
iii) Buses
iv) Transmission and distribution circuits
v) Motors
A typical power system and its zones of protection are shown in Fig1. The
purpose of the protective system is to provide the first line of protection,
within the guide-lines outlined above. Since failures do occur, however
some form of backup protection is provided to trip out the adjacent
breakers or zones surrounding the trouble area. Protection in each zone is
overlapped to avoid the possibility of unprotected areas
a. System configuration
b. Existing systems protection and its difficulties
c. Existing operating procedures and practices; possible future
expansions
d. Degree of protection required
e. Fault study
f. Maximum load and current transformer ratios
g. Voltage transformer locations, connections and ratios
h. Impedance of the lines and transformers.
fault study should include zero sequence voltage and negative sequence
currents and voltages. These quantities are easily obtained during the
course of a fault study and are often extremely useful in solving a difficult
relaying problem.
Obviously, not all the above data are necessary in every application. It is
desirable, however, to at least review the system with respect to the
above points and wherever applicable, to compile necessary data.
Lower case (small) suffix letters are used in practically all instances on
electrical diagrams for the auxiliary, position, and limit switches. Capital
letters are generally used for all other suffix letters. The letters should
generally form part of the device function designation, are usually written
directly after the device function number, as for example, 52CS, 71W, or
49D. When it is necessary to use two types of suffix letters in connection
with one function number, it is often desirable for clarity to separate them
by a slanted line or dash, as for example, 20D/CS or 20D-CS.
The suffix letters which denote parts of the main device, and those which
cannot or need not form part of the device function designation, are
generally written directly below the device function number on drawings,
as for example, 52/CC or 43/A.
(1) These may be speed, voltage, current, load, or similar adjusting devices comprising
rheostats, springs, levers, or other components for the purpose.
(2) These electrically operated devices are of the non-latched-in type, whose contact
position is dependent only upon the degree of energisation of the operating or
restraining or holding coil or coils which may or may not be suitable for continuous
energisation. The de-energised position of the device is that with all coils de-
energised.
(3) The energising influences for these devices are considered to be, respectively, rising
temperature, rising level, increasing flow, rising speed, increasing vibration, and
increasing pressure.
The simple designation “a” or “b” is used in all cases where there is no
need to adjust the contacts to change position at any particular point in
the travel of the main device or where the part of the travel, where the
contacts change position is of no significance in the control or operating
scheme. Hence the ”a” or “b” designations usually are sufficient for
circuit breaker auxiliary switches.
9.0 CLASSIFICATION OF RELAYS ON TECHNOLOGY
1. Electromechanical
2. Static.
In practice these terms are used loosely and ends up being wrongly
interpreted and understood. Though the reason for these different types
of relays is the continuous change in electronic technology, each of these
types have their own distinct advantage over the other.
The static relays, as said above are mainly relays designed using
electronics, thus due to the evolution of electronics, the static relays also
used different techniques in their design as listed below,
Relays
Electromechanical Static
Analogue Digital
Numerical
©ALSTOM Limited, Energy Automation & Information