Io Spec K-Pos Dp-12

The document is the IO Specification for the K-Pos DP-12 system installed on the Saipem PLV Yantai, detailing the input/output configurations and changes made over various revisions. It includes historical changes from the first issue in 2008 to the latest revision in 2013, along with specific technical details about the equipment and connections. The document is part of a larger project and consists of 5 pages.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4 views5 pages

Io Spec K-Pos Dp-12

The document is the IO Specification for the K-Pos DP-12 system installed on the Saipem PLV Yantai, detailing the input/output configurations and changes made over various revisions. It includes historical changes from the first issue in 2008 to the latest revision in 2013, along with specific technical details about the equipment and connections. The document is part of a larger project and consists of 5 pages.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

IO Specification

K-Pos DP-12

Saipem PLV Yantai

Project: 38223 Saipem PLV Yantai

Product: K-Pos DP-12

Synopsis: This is the IO Specification for the DP system installed on


Saipem PLV Yantai. The information in this document is
extracted from IO database number 1065467 revision L

Document number: 1065476 Revision: H

Customer doc number: Document version: 8.0

Contract number: Number of pages: 5

Rev. Date Reason for issue Made by Checked Approved

A 08.02.2008 First issue. OGK QHLV QHLV

B 09.06.2009 New Net cabels added OGØK NF NF

C 10.09.2009 Add new Tunnel Thruster DA QHLV OCS

D 05.03.2010 Correction after yard comments TG TG TG

E 17.03.2010 Removing IO TG TG OCS

F 13.07.2010 Revised because archived, with the NF NF NF


wrong subtitle, need to be updated

G 10.01.2012 Adding UPS 5 TG NF NF

H 18.02.2013 As Built DT KMW MA


Kongsberg Maritime AS

History
Revision Description of Change

A No change information.

B New Net cabels added

C Add new Tunnel Thruster

D Correction after yard comments

E Removing IO

F F

G Adding UPS 5

H As Built

KONGSBERG MARITIME AS
Kirkegårdsveien 45, Carpus Telephone: +47 32 28 50 00
P.O.Box 483 N-3601 Telefax: +47 32 28 50 10

3616 Kongsberg www.kongsberg.com

Norway
Kongsberg Maritime AS

I/O card Pos : 32


IO - PCB (Location) : RSER200-4
TB - PCB :
WU - No : WU3
Zero
Ch Unit No Equipment Terminal Polarity Signal Force
2 U 32 GYRO (3) NMEA X2 : 1 rx+ RS-422, Baud 4800, 8, N, 1

2 U 32 GYRO (3) NMEA X2 : 2 rx- RS-422, Baud 4800, 8, N, 1

3 U 32 DGPS (1) NMEA X3 : 1 rx+ RS-422, Baud 9600, 8, N, 1

3 U 32 DGPS (1) NMEA X3 : 2 rx- RS-422, Baud 9600, 8, N, 1

1065476 / H / Page 3 of 5
Kongsberg Maritime AS

I/O card Pos : 34


IO - PCB (Location) : RMP201-8
TB - PCB :
WU - No : WU3
Zero
Ch Unit No Equipment Terminal Polarity Signal Force
1 U 34 GYRO (3) OK X1 : 1 s DI

1 U 34 GYRO (3) OK X1 : 3 c DI

2 U 34 Fire Backup Sw - X1 : 4 s DI
DPC-1 NO(BU)
2 U 34 Fire Backup Sw - X1 : 6 c DI
DPC-1 NO(BU)
4 U 34 UPS 4 Earth Failure X2 : 4 s DI

4 U 34 UPS 4 Earth Failure X2 : 6 c DI

5 U 34 UPS 4 Alarm X3 : 1 s DI

5 U 34 UPS 4 Alarm X3 : 3 c DI

6 U 34 Fire Backup Sw - X3 : 4 s DI
DPC-1 NC(Main)
6 U 34 Fire Backup Sw - X3 : 6 c DI
DPC-1 NC(Main)

1065476 / H / Page 4 of 5
Kongsberg Maritime AS

I/O card Pos : 35


IO - PCB (Location) : RMP201-8
TB - PCB :
WU - No : WU3
Zero
Ch Unit No Equipment Terminal Polarity Signal Force
3 U 35 MRU (1) Roll com X2 : 2 c AI ± 10V

3 U 35 MRU (1) Roll X2 : 3 s AI ± 10V

4 U 35 MRU (1) Pitch com X2 : 5 c AI ± 10V

4 U 35 MRU (1) Pitch X2 : 6 s AI ± 10V

5 U 35 MRU (1) Heave com X3 : 2 c AI ± 10V

5 U 35 MRU (1) Heave X3 : 3 s AI ± 10V

6 U 35 UPS 5 Alarm X3 : 4 s DI

6 U 35 UPS 5 Alarm X3 : 6 c DI

7 U 35 MRU (1) OK X4 : 1 s DI

7 U 35 MRU (1) OK X4 : 3 c DI

8 U 35 UPS 5 Earth Failure X4 : 4 s DI

8 U 35 UPS 5 Earth Failure X4 : 6 c DI

1065476 / H / Page 5 of 5