Stator Defect
Stator Defect
This article examines four alternatives used for core and winding repair when localized
damage occurs due to a failure. It shows examples where some of these techniques were
used, as well as the technical aspects of these repairs.
The most likely component of a hydroelectric plant to fail is the generator, according to a
study by SINTEF.1 A second study by Enel on 250 machines shows that stator faults,
although less frequent than other faults, are responsible for longer outages.2 Other studies on
this topic have drawn similar conclusions.3
The conventional solution for these faults involves replacing the stator core and
winding. This solution has many benefits, but it is costly and requires a long outage.
In some cases, the conventional solution is not preferred due to the cost and/or outage
limitations. A solution must be found to allow for at least temporary operation of the unit
until a permanent repair is performed. Developing an efficient repair method for these cases
by reducing the cost and outage time of the machine is essential. This can make sense if there
is localized damage that affected the core and stator winding, for example due to a short
circuit and/or damage caused by a part that broke in the rotor.
This article compares the various repair methods used when one of these faults occurs,
evaluating the benefits and impacts of each solution:
1. The conventional solution is to completely replace the core and winding. This
solution is used when the damage affected a significant area, making the repair
difficult, or when possible, fixes are only temporary, limiting the use or reliability of
the generator. It is also used when components are at the end of their useful life and/or
design improvements are necessary.
2. Another solution is partial replacement of the core and winding, meaning the core is
partially disassembled and the damaged laminations are replaced. The winding in the
affected area is also replaced. Other parts that have not been affected significantly are
only repaired. This solution is typically used when the damage has affected a
relatively small area, although sometimes such repair can make sense for relatively
large damaged areas. For this case, this article presents an example where this
solution allowed the replacement of damaged stator laminations and reinstallation of
the stator winding in a short time.
3. A third solution is core repairs and winding (without disassembly). The core is
repaired without disassembly, while the winding can be partially disassembled and/or
repaired. This solution is used when the damage affected a relatively small area, or in
the case of a relatively large area, when economic factors such as operation
requirements and repair reliability are important. This article presents an example
where significant damage was fixed without core disassembly.
4. Finally, cosmetic repairs are used typically when the damage is localized and minor.
In some cases, they are also used to fix serious damage. The repair is necessary to
prevent additional heating that will gradually affect the winding and core, leading to a
significant failure over time. The term “cosmetic” is used because the damaged area is
replaced by one insulating material, acting as a cosmetic component. The affected
core area is removed by cutting, sanding and straightening the laminations. Usually
such a repair is followed by an EL CID test to determine if a short between
laminations remains. If the stator laminations are short-circuited, acid etching can be
used to remove the shorts. A high capillary resin is then applied, and an insert is
added to act as a cosmetic component.
The photos above provide an example of a cosmetic repair to a damaged winding and core.
Table 1 provides a comparison summary of these methods, including the outage duration,
advantages and disadvantages of each.
A visual inspection is the first logical step of the damage investigation, to localize the damage
and assess its extent and severity. Effectiveness of the visual inspection depends on physical
access to the core and winding, so some disassembly may be required.
Most of the time, removal of generator cover plates will be necessary to access the winding
end-turns. The removal of a cooler or the opening of cover plates on the generator frame can
give access to the back of the core to assess possible deep-seated damage. It might be
possible to look at the stator winding wedging system with the rotor in place, from the space
available between two rotor poles. When this is not possible, removal of two to four,
depending on the size of the unit, can facilitate access to the stator bore surface.
Depending on the type of damage (deep-seated damage after a short circuit or significant
damage on the core air gap surface), it might also be required to remove the rotor before an
inspection. Tools such as a set of mirrors or a borescope can ease the inspection. A borescope
can be used to assess the condition of the stator winding radial wedging system in the air gap
or to detect deep-seated damage from ventilation ducts.
During an inspection after a forced outage, attention should be paid to any unusual signs on
and around the winding, such as foreign materials and debris. In one example described in
this article, aluminum debris was found in the end-turns and ventilation ducts. Particular
attention should be paid to unit cleanliness (contamination). Black dust may indicate
overheating and help to localize a ground fault. Evidence of looseness, overheating, electrical
deterioration, mechanical damage, dusting and corrosion could be signs that can help locate
the fault and identify its root cause. The inspection should not be limited to the winding end-
turns but also include the stator connections (group, serial and circuit ring connections),
winding circular, phase and neutral busses, bracing elements (ties, bracing ring, etc.) and
wedging system. The inspection should also include the ventilation ducts, bore and back
surface of the core to help identify in-slot damages.
During the inspection, aspects such as generator history, previous maintenance and outages,
and the unit’s condition before failure should be taken into account. Useful guidelines of
aspects to be considered during an inspection, inspection forms and recommended tools are
available.4 Additionally, IEEE Std 492-1999 provides more information on generator
inspections.5
Description of tests
The main tests involved in this type of repair are basic and similar to tests done to evaluate
the condition of the unit.6 A brief description of each test is below:
EL CID: This test was developed to overcome the need for a high power supply
required for rated flux testing. Usually, a variable transformer supplied from an
electrical outlet is all that is required to excite the stator. Even if a low flux density
excitation does not induce heat generation in EL CID, the faulty current created near
laminations with short circuits is directly detected. The basis for the detection is that
fault currents will have a mainly resistive component in respect to the supply voltage
and will be shifted by 90 degrees in respect to the supply current. The currents are
detected using a sensor (called Chattock coil) and phase separator. An advantage of
EL CID is that it can be carried out with the rotor in place, by removing two or three
poles. The results are in the form of traces that can be interpreted by skilled personnel.
In general, a 100 mA reading requires close examination and possible rated flux
testing to verify damage. The shape of the measured current also helps to locate a
fault, whether it is on a stator tooth or deep-seated inside the lamination stack. Theory
and more information about the test setup and its interpretation is available.7
Core loop: The core loop test, also called core magnetization test, consists in applying
1 Tesla or nominal flux to the stator core using a toroidal winding. Heat develops at
any point where the insulation is damaged. The temperature of the stator core is
monitored using infrared camera and/or thermocouples. As a generally accepted
criterion, a core is considered damaged and needing repair if a hot spot is detected,
with temperature being 5 to 10 degrees Celsius higher than the surrounding area.
Theory and more information about the test setup and its interpretation is available.8
Insulation resistance: The insulation resistance test measures the ohmic value between
a conductor (part of the winding) and the ground (stator core). The insulation
resistance of a winding in good condition usually reads in Megaohm as insulation
restrains the current flow from the conductor to ground. The lower the resistance, the
higher the chance of insulation defect. This is probably one of the most widely used
tests in diagnostics and maintenance. This test is usually done at a voltage that is
lower than the generator rated voltage (usually 5 or 10 kV DC). The polarization
index, which is the variation of resistance over time, also helps to identify
contamination problems. Theory and more information about the test setup and its
interpretation is available.9
D.C. ramp: This test is a variation of the DC high potential test. The main difference
is that the voltage is increased progressively, usually at a constant rate of 1 or 2
kV/minute. The evolution of the leakage current over the voltage/time is recorded and
displayed continuously for direct interpretation. Analysis of the curve helps identify
existing or imminent winding faults as well as characterize it, as shown in section
7.8.2 of IEEE Std 95.10. The main advantage of the DC ramp test over the traditional
DC high potential test is that it allows detection of an imminent failure, while giving
the opportunity to stop the test before the failure, to avoid a puncture or damaging a
winding even more. In the context of winding troubleshooting, this test can be used in
conjunction with the insulation resistance test to detect hidden faults while avoiding
additional winding damage. By comparing phases, circuits or equal portions of a
winding, winding defaults can also be located. However, as this is a high-voltage test,
the number of repeat tests should be limited to reduce stress on the insulation.
D.C. resistance (or conductivity): The purpose of this test is to find damaged copper
conductors or joints by resistance or conductivity measurements. A low-resistance
ohmmeter or Kelvin bridge can be used. By comparing the resistance of phases,
circuits or portions of a winding, differences observed will help locate a fault. If it is
possible to easily “open and divide” a stator winding, this test can be used iteratively
to locate a fault in a short amount of time (one or two days of site work) Temperature
should be taken into account as the DC resistance is strongly affected by temperature.
Continuity: This test consists of supplying the damaged winding with an AC current
while measuring the current though a portion of the winding where a fault is
suspected. A significant current drop should be measured on a bar/coil where the
insulation is damaged. This test is particularly useful when it is not possible to easily
“open and divide” a winding. The use of a flexible current probe enables measuring
the current through a bar, coil, group or serial jumper without opening the electrical
circuit. An AC source or even a welding machine can be used as only a small current
is required. An insulation resistance test might be done before performing this test on
separate phases/circuit to identify the faulty phase/circuit first. The tester should have
a good knowledge of the winding diagram before performing the test. Care should be
taken during this test, as additional damage could be caused to the winding. If the
insulation is significantly damaged, a direct path to ground for the current could burn
the insulation even more. For this purpose, several people should be distributed
around the winding and specifically at the suspicious portion of winding to look for
signs of smoke or a burning smell immediately after the winding has been energized.
An EL CID test is highly recommended, and it helps during the repair work but is often not
seen as sufficient. As a final test (after the repair has been carried out), a loop test or core
magnetization test may be performed to detect hot spots in the core. In cases where the
winding is installed and a magnetization test is performed, it is advisable to reduce the flux
density in the yoke. Normally a flux density of 1.0 T or less is recommended. This level of
flux density can help mitigate or avoid vibration risks in the machine, reducing the risk of
damaging the winding while still producing reasonable results.
The most common tests involve DC resistance, continuity, DC Hi pot test (bars replaced),
insulation resistance in the winding and a final DC ramp test (same voltage level as the one
used during maintenance).
To validate the repair methods proposed in the article, two examples are shown:
Two interpolar aluminum supports broke and caused rotor/stator contact. The stator core was
heavily contaminated by aluminum debris, mainly in the first and last packages (upper and
lower). About 25% of the core was damaged (~130 m2). In addition, 67 upper bars were
damaged, to varying degrees. Damage also occurred in the rotor and air deflectors.
The first step performed was a detailed visual inspection of the damage. Thereafter, the core
and winding were cleaned, and preliminary tests were performed to verify the extent of the
damage. These tests included insulation resistance and Hi pot (ramp DC), Ohmic winding
resistance and EL CID (full core). In the EL CID test, 25% of the core surface had a current
measured above 100 mA. The test performed showed that despite the significant area, the
damage was superficial.
The photos above are from the visual inspection of the stator bars with conductor damage
One of the damaged areas was chosen to determine and validate the best repair
process. Brushes, magnifiers, and belt and rotating sanders were used for cleaning of each
spot damaged.
A damaged stator core is visually inspected and sanded
After sanding, an EL CID test was done in the selected area and acid etching was used to
remove the short between laminations. Another EL CID test was performed, and the process
was repeated until the shorts between laminations were eliminated.
Figure 1: EL CID initial results (at top) and stator core repair (at bottom)
Once the method was validated, a complete core repair was started. After the rework, a core
magnetization test was performed, and hot spots were observed (where the temperature was
more than 10 K above the surrounding areas). Localized repairs and EL CID were performed
again at these areas and magnetization tests were repeated. This process was repeated until all
spots were treated.
Bar damages were also repaired, with seven bars replaced. All winding wedges were
replaced. The total unit outage period for repairs was five months. The unit has been in
operation since 2012.
Example 2 – Repair with partial disassembly
The machine suffered a phase to ground short circuit (fault near the end of the stator
core). This short quickly became a two-phase short circuit due to a failure in the cable
between the ground cubicle and the neutral of the generator. The failure resulted in two
separate and prolonged high-intensity discharges with significant damage to the core and
winding.
In addition to the core, four stator bars were damaged beyond repair and several bars suffered
damages in the insulation. Group connections, circuit rings, neutral terminals and current
transformers were also affected.
The first step was to perform a detailed visual inspection of the damaged area. Soon after, a
core and winding cleaning was performed, and preliminary tests were carried out to verify the
extent of the damage. These tests included insulation resistance and Hi-pot (DC ramp test)
and ohmic resistance of the winding. Based on this assessment, a repair with partial
disassembly was the best option.
The first step in the repair was the removal of the bars, end plates and pressure fingers
between slots 34 and 74 (damaged area, see photos below). A support was installed and the
laminations on the end were hoisted, allowing removal of the overlapped laminations. This
process continued until all damaged laminations were replaced with new laminations.
Figure 2: Diagram (at top) and photo (at bottom) of the area where the laminations were
removed
To verify and validate the repair, a core magnetization test was performed. No hot spots were
detected (see Figure 3). The test could also have been done by means of EL CID, but a
magnetization test was the best option due to the location of the fault (extremity of the core).
After installation of the circuit rings, group connections and repairs in the neutrals leads, the
final tests were performed (insulation resistance, Hi pot and ohmic resistance) and the
machine was returned to operation.
The total outage period for repairs was a month. The unit has been in operation since 2015.
Conclusion
While the conventional solution for replacing the core and stator winding has many benefits,
sometimes it is not the most effective one when cost and/or outage limitations are taken into
account. In the two examples, the repair outages were five months and one month. A typical
winding and core replacement outage would have taken 18 to 24 months from notice to
proceed.
Alternative solutions such as localized core repair with partial lamination replacement or
repair without lamination replacement should be reviewed because they reduce the machine’s
outage time and cost. This is especially true if there was localized damage that affected the
core and winding of the stator, for example after a short circuit and/or damage caused by a
part that has broken in the rotor. It is important to emphasize that such fixes are challenging
and need an in-depth understanding of the machine and a skilled repair crew.