The NOVA Elevator Controller User Manual provides comprehensive information on the controller's features, terminal descriptions, and programming instructions. It supports various lift control modes, is user-friendly with built-in diagnostics, and allows for extensive parameterization. The manual includes detailed sections on wiring, input/output connections, and error codes, ensuring proper installation and operation of the elevator system.

Uploaded by

Laly
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
43 views38 pages

NOVA Card Manual

The NOVA Elevator Controller User Manual provides comprehensive information on the controller's features, terminal descriptions, and programming instructions. It supports various lift control modes, is user-friendly with built-in diagnostics, and allows for extensive parameterization. The manual includes detailed sections on wiring, input/output connections, and error codes, ensuring proper installation and operation of the elevator system.

Uploaded by

Laly
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 38

NOVA

ELEVATOR CONTROLLER

USERSS MANUAL
CONTENTS

1. General description……………………...........................................................................04-05
1.1. General Features…………………………………………...........................................................04
1.2. Overview...................................................................................................................04
1.3. Technical data...........................................................................................................05
2. Terminal Description...............................................................................................06-10
2.1. Terminal Layout........................................................................................................06
2.2. Input Supply voltage Terminal..................................................................................06
2.3. Input Terminals.........................................................................................................07
2.4. Output Terminals......................................................................................................08
2.5. Call Terminals...........................................................................................................09
2.6. Indication Terminals.................................................................................................09
2.7. Terminals for Duplex................................................................................................10
2.8. Terminal for Extension.............................................................................................10
3. Shaft Information...................................................................................................11-14
3.1. For reed scheme1.....................................................................................................11
3.2. For reed scheme2.....................................................................................................12
3.3. For reed scheme3.....................................................................................................13
3.4. For reed scheme4.....................................................................................................14
4. Parameterization....................................................................................................15-19
4.1. Overview of Keypad.................................................................................................15
4.2. How to do programming..........................................................................................15
4.3. How to Set the New password.................................................................................15
4.4. Use of ARD input .....................................................................................................16
4.5. Parameter Table.......................................................................................................17
4.6. Factory Default..........................................................................................................19
4.7. Procedure To Be Followed For Assigning Desired Floor Indication...........................20
5. Status and Position Information..................................................................................21
5.1. Input/ Output status LED for VVVF mode.................................................................21
5.2. Input/ Output status LED for 2-speed mode.............................................................21
5.3. Input/ Output status LED for Hydraulic mode..........................................................22

USER MANUAL Page 2


6. Connection Details Of Output Terminal.......................................................................23
7. Connection Details Of Input Terminal..........................................................................24
8. Connections Details Of Call.....................................................................................25-27
8.1 8 Stops (G+7) Down collective mode (without Extension Board)................................25
8.2 6-Stops (G+5) Full Collective mode (without Extension Board)...................................26
8.3 Connection Details of Extension Boards......................................................................27
8.4 All possible combinations with 2 extension boards.....................................................28
9. Connection details of Display.....................................................................................29
9.1. Binary/ Gray code Display.......................................................................................... 29
9.2. Seven Segment display................................................................................................29
10. Connection Details for Duplex...............................................................................30-32
11. Connection details of Extension Board for Serial LOP-COP.....................................33-34
12. Errors Code Description.............................................................................................35
13. Important Instructions...............................................................................................36

USER MANUAL Page 3


1. General description

1.1. Features
• Application: Suitable for VVVF, 2 Speed and Hydraulic Lift control
• Control Mode: Full collective (6 stop) / Down Collective (8 stop)
• No. Of stops: Max up to 8 stop but extendable up to 16 with extension board.
• Door type: Suitable for both Auto Door/ Manual Door
• Group Operation: Simplex & Duplex,
• Floor Indicator O/P: Binary/ Gray/ Seven Segment.
• Self diagnostic: Two line LCD display is used for status/ Fault
• User friendly: Built in LED indicators for all input & output; hence easy for
troubleshooting
• Flexibility in operation: All operating parameters (like door open time, close time,
Reed switch scheme, parking floor etc) are programmable at site with inbuilt keypad
• Protection: All parameters are password protected
• Special Features: Compatible with 60V AC-DC and 110V AC-DC safety voltages, Lift
Lock, Attendance, Fireman, Stop, Overload, ARD, PTC and Arrival Gong, Compatible
with 12V & 24V COP’s and LOP’s etc.
1.2. Overview

Display
Keypad

USER MANUAL Page 4


1.3. Technical Data:

Board supply: 18VAC & 12VAC


Supply voltage
Peripheral supply: 24VDC
Safety Circuit voltage 60VAC/DC or 110VAC/DC

Control Input Voltage 24VDC

Control Output Voltage Potential free relay contact

Floor Indicator display Voltage 24VDC (Common Anode)

Direction Arrow Voltage 24VDC (Common Anode)

USER MANUAL Page 5


89
88
87
86
85
84
83
82
1 VDD (24V) GND 81
2 GND VDD (24V) 80
3 P1 AC2 (18V) 79

BB
AA

VDD
VDD

GND
GND

TXDO
RXDO
4 P2 AC1(0V) 78
5 P3

USER MANUAL
6 P4 AC2 (12V) 77
7 P5 AC1 (0V) 76

79
78
77
76
8 P6

Terminal no
2.1. Terminal Layout

9 P7 COM2 75
2. Terminal description

10 P8 SPR3 74
11 P9 SPR2 73

AC2
AC1
AC2
AC1
12 P10 DTL 72
13 P11 UTL 71
14 P12 EL-CH 70

Description
2.2. Input Supply Voltage Terminal:
15 PB3 LG 69
16 P14 CG 68
17 P15 RDY 67
18 P16 COM1 66

19 SPARE DO/ COM 65


20 SLW-RD BZ NO 64
21 STP-RD RC/ COM 63
22 UPSL DC NO 62

AC Supply 18V
AC Supply 12V
23 DNSL COM 61
FAN/
24 OL NO 60
MTR

Supply Requirement
25 DOB NC 59
26 DCB COM 58
BB/
27 ATT NO 57
STAR
28 STP NC 56
29 ARD COM 55
HIGH
30 FIRE NO 54
31 INS COM 53
SLOW
32 INS UP NO 52
33 INS DN REV 51
COM 50
F
E

C
B
A
D
G
B1
OL

UP
AG

DN

34 PTC+ FWD 49
35 PTC- NOT USED 48
36
37
38
39
40
41
42
43
44
45
46
47

Page 6
2.3. Input Terminal
2.3.1. Shaft Information input (24Vdc)

Terminal no Description Features LED


20 SLW-RD Slowing reed input D27
21 STP-RD Stopping/Level reed D28
22 UPSL UP Slowing Limit (P58) D29
23 DNSL Down Slowing Limit (P58) D30
71 UTL UP Terminal limit (Optional P30) D22
72 DTL Down Terminal Limit
D23
(Optional P30)

2.3.2. Control Input (24Vdc)

Terminal no Description Features LED


24 OL Overload D31
25 DOB Door Open Button D32
26 DCB Door Close Button D33
27 ATT Attendance key switch D34
28 STP Emergency STOP button in COP D36
29 ARD ARD (Automatic Rescue Input) D37
30 FIRE Fireman D73
31 INS Inspection Mode D74
32 INS UP Inspection Up D75
33 INS DN Inspection Down D76

2.3.3. PTC Input

Terminal no Description Features


34 PTC+ Motor PTC connection
35 PTC-

2.3.4. Safety Input (60V & 110V AC or DC)

Terminal no Description Features LED


66 COM Com1 -
67 RDY Final Limit safety input D18
68 CG CAR Gate Switch D19
69 LG Landing Gate Switch D20
70 Element Check Element Check D21

USER MANUAL Page 7


2.4. Output Terminals (Potential free Relay Contact)

Terminal no Description Features LED


49 FWD Forward D66
50 COM Common -
51 REV Reverse D67
52 NO
Slow speed Relay D65
53 COM
54 NO
High speed Relay D68
55 COM
56 NC
BB(Base Block)/STAR (In
57 NO D69
Hydraulic) Relay
58 COM
59 NC
FAN(In vvvf mode)/MTR(In
60 NO D70
Hydraulic) Relay
61 COM
62 NO RC/DC (Retiring CAM for
manual door/ Door Close D71
63 COM
for Auto Door) Relay
64 NO DO/BZ (Door Buzzer for
manual door/ Door Open D72
65 COM
for Auto door) Relay
80 VDD(24V) 24 VDC Output for
D63
81 GND Peripherals

49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65

DIRECTION SLOW HIGH BB/ STAR FAN/ MTR RC/DC DO/BZ

FWD CM REV NO CM NO CM NC NO CM NC NO CM NO CM NO CM

COM

To the Drive (in case of VVVF)


Or
To the Contactors

USER MANUAL Page 8


2.5. Call Terminals

Terminal Feature Feature


Description
No (In Down Collective) (In Full Collective)
1 VDD +24V for Call Lamp +24V for Call Lamp
2 GND GND for Call Register GND for Call Register
3 P1 C0 C0
4 P2 C1 C1
5 P3 C2 C2
CAR CALL
6 P4 C3 C3
CAR CALL
7 P5 C4 C4
8 P6 C5 C5
TH
9 P7 C6 0 FLOOR 0U
10 P8 C7 1U
1ST FLOOR
11 P9 L0 1D
12 P10 L1 2U
2ND FLOOR
13 P11 L2 HALL 2D
14 P12 L3 CALL 3U
HALL CALL 3RD FLOOR
15 P13 L4 3D
16 P14 L5 4U
4TH FLOOR
17 P15 L6 4D
TH
18 P16 L7 5 FLOOR 5D

2.6. Indication Terminals

Terminal No. Description Feature


36 A Indication for A
37 B Indication for B
38 C Indication for C
39 D Indication for D
40 E Indication for E
41 F Indication for F
42 G Indication for G
43 B1 Indication for 1 in Double Digit Display
44 UP Indication for Up
45 DN Indication for Down

USER MANUAL Page 9


46 OL Indication for Overload
47 AG Indication for Arrival gong

2.7. Terminals for Duplex

Terminal No. Description Feature


82 VDD
Power supply
83 GND
84 AA
Serial Communication Signal
85 BB

2.8. Terminals for Extension or Serial Connections

Terminal No. Description Feature


86 VDD
Power supply
87 GND
88 TXDO
Serial Communication Signal
89 RXDO

USER MANUAL Page 10


3. Shaft Information
3.1. For Reed Scheme 1
3.2. For Reed Scheme 2
3.3. For Reed Scheme 3
3.4. For Reed Scheme 4
4. Parameterization

4.1. Overview of Keypad:

ENTR INC

Enter Decrement Increment

4.2. How to do Programming


 To go to programming mode, double click on INCREMENT key. The display will show
"Program Mode...."
"P000=08"

 Cursor is at parameter number P000. To increase the parameter numbers press


INCREMENT key.
 Cursor will shift to the value as shown below, if ENTER key is pressed.
"P000=08"
 To increase the value of the parameter press INCREMENT key and to shift the cursor
press DEC key. To save the values of that parameter press ENTER key. The parameter
number automatically increases by one as shown below. Now the cursor shifts to
parameter number as shown below
"P001=01".

4.3. How to set new the Password


 To set Password, Double click on DECREMENT key, it will ask for current password
and after Entering that, use INCREMENT key to increment the value and to shift
cursor press DECREMENT, then finally Press ENTER. New password will be set.

 While entering into the programming mode, it will ask for new password.
4.4. Use of ARD input of Card-
 If 24V DC input is provided to the pin no 29, then card itself gives slow command or
only slow relay will operate and will wait for nearest door zone signal. Card will be in
ARD mode till pin no 29 has 24V DC input and controller will not accept any calls.
 If lift is at floor level and passenger enters into the cabin and before anyone will give
call and power gets Off then card should get the ARD signal (24V DC at pin no. 29)
then card will give Door Open command itself(In auto door mode).

USER MANUAL Page 16


4.5. Parameter Table

Default
Parameter Description Mode Unit
Value
P00 No of Stops e.g. 8 for G+7 Nor Number 8
P01 Mode of lift operation, 1 for Simplex, 2 for Duplex master and 3 for Duplex slave Nor-ins Number 1
P02 Mode of door. 0 for Manual door, 1 for Auto door, 3 for Semi-Automatic door Nor-ins Number 1
P03 Mode of lift operation, 1 for V3F, 2 for 2 Speed, 3 for Hydraulic Nor-ins Number 1
P04 Retention CAM On Time in case of manual door lift Nor 0.1 Sec 10
P05 Retention CAM Off Time in case of manual door lift Nor 0.1 Sec 35
No of cycles of RCAM on and off if landing door is open in case of manual door lift. No of cycles of
P06 Nor-ins Cycles 3
Door open and close in case of auto door lift
P07 Door open time when the lift stops at floor level Nor Sec 10
P08 Door open time when the DO button or same floor LOP/COP call is given Nor Sec 5
P09 Door close time (Expected maximum) Nor Sec 5
Stoppage time at the floor level. If no activity during this time, lift will automatically start for the
P10 Nor 0.1 Sec 60
next registered call.
Parking Floor No 1. 99 means no homing floor. In simplex mode if no activity during home time
P11 Nor Floor no 99
(settable), lift automatically goes to this floor.
Parking Floor No 2. In duplex mode if no activity during home time (settable), both the lifts will go
P12 Nor Floor no 99
to nearest parking floors.
P13 Parking time. If no activity during this time, lift(s) will automatically will go to set home floor(s). Nor Mins 10
P14 Fireman Floor No. If fire switch is activated, lift will go to this floor no. Nor-ins Floor no 0
P15 Fan/Tube off time when the last call gets completed. Nor 1 Sec 30
Door zone mode. 1 - Doors will open only when Door Zone signal is ON , 0 - Doors can open even if
P16 Nor Number 1
level signal is not ON.
P17 Reed Scheme. Possible values are 1,2,3 or 4 Nor Number 2

USER MANUAL Page 17


P18 Slowing reed type , 0 for NO and 1 for NC Nor Flag 0
Slowing reed out time. If the slowing reed pulse doesn't come during this time the lift will declare
P19 Nor Sec 20
Slowing Reed fault.
P20 Stopping reed type , 0 for NO and 1 for NC Nor Flag 0
Stopping reed out time. If the stopping reed pulse doesn't come during this time the lift will declare
P21 Nor-ins Sec 20
Stopping Reed fault.
P22 MTR off delay in hydraulic mode in Up direction after call complete Nor-ins 0.1 Sec 0
Stop button mode. For NO stop push button, 1 to Clear all calls if stop button pressed. 0 to stop the
P23 lift till the stop is activated. For NC stop push button, 3 to Clear all calls if stop button pressed. 2 to Nor-ins Number 0
stop the lift till the stop is activated.
P24 1 - Two push button full collective logic enabled. 0 means down collective logic enabled. Nor Number 0
P25 1 - One push button full collective logic enabled. 0 means down collective. Nor Number 0
Display 'C' or 'L' on LOP/COP display if Car gate or Landing gate is open. 0 means disabled and 1
P26 Nor Number 0
means enabled, in manual door.
P27 Fault detection mode. 1 means faults are activated and 0 means fault detection is disbaled. Nor Number 1
P28 Display mode. 7 Segment, binary or grey. (1,2 or 3 respectively) Nor-ins Number 1
Landing and Car PB LED mode. 1- landing call is displayed in car push button and 0 means
P29 Nor Number 0
individual LED logic for landing and car call LED’s.
P30 Up-DN terminal inputs enabled or disabled (1 or 0 respectively) Nor Number 0
ARD Door Mode If 0, door will close after door open time and if 1, door will remain open in ARD
P31 Nor Number 0
mode .
ARD mode direction. If 0, lift will carry ARD cycle in down direction and if 1, lift will carry ARD
P32 Nor Number 0
operation in up direction.
P33 No. of Lock Cycles Nor 10 cycles 0
P34 Buzzer mode. 0 - buzzer will continuously be ON when active and 1 - buzzer will tick if active. Nor Number 1
P35 Approaching floor button LED mode. 1 - blinking led for approaching floor, 0 - disabled Nor Number 1
Duplex home logic flag, In duplex keep it 0- meaning that after inactive period both the lifts will
P36 Nor Number 0
move to nearest home floors. 1 in Simplex mode means duplex logic is active else inactive

USER MANUAL Page 18


Manual Landing door lock type. 1 - RC is required to check landing door signal. 0 - RC is not
P37 Nor Number 1
required for checking landing door signal .
P39 Fireman switch type, 0- NO and 1 - NC Nor Number 1
P40 Floor 0 status. If 0 floor is disabled. If 3 enabled (Binary status) Nor Number 3
P41 Floor 1 status. If 0 floor is disabled. If 3 enabled Nor Number 3
P42 Floor 2 status. If 0 floor is disabled. If 3 enabled Nor Number 3
P43 Floor 3 status. If 0 floor is disabled. If 3 enabled Nor Number 3
P44 Floor 4 status. If 0 floor is disabled. If 3 enabled Nor Number 3
P45 Floor 5 status. If 0 floor is disabled. If 3 enabled Nor Number 3
P46 Floor 6 status. If 0 floor is disabled. If 3 enabled Nor Number 3
P47 Floor 7 status. If 0 floor is disabled. If 3 enabled Nor Number 3
P48 Floor 8 status. If 0 floor is disabled. If 3 enabled Nor Number 3
P49 Floor 9 status. If 0 floor is disabled. If 3 enabled Nor Number 3
P50 Floor 10 status. If 0 floor is disabled. If 3 enabled Nor Number 3
P51 Floor 11 status. If 0 floor is disabled. If 3 enabled Nor Number 3
P52 Floor 12 status. If 0 floor is disabled. If 3 enabled Nor Number 3
P53 Floor 13 status. If 0 floor is disabled. If 3 enabled Nor Number 3
P54 Floor 14 status. If 0 floor is disabled. If 3 enabled Nor Number 3
P56 1-To enable Serial communication & 0-disable Nor Number 0
Door Open/Close at the floor level till next call is not given, 0-Door Open & 1-Door Close in Auto
P57 Nor Number 1
door mode
P58 Up-Dn Slowing input Enable/Disable in Inspection Mode (0 or 1 respectively) INS Number 1
P59 PTC Enable (1)/ Disable (0) Nor-Ins Number 0

4.6. Factory Default

P60 Put 99, to set the default values Nor-ins 0

USER MANUAL Page 19


4.7 Procedure To Be Followed For Assigning Desired Floor Indication-

Default status of NOVA card.


Sr. Default Programmable
Parameter Floor
No Valve Character
1 P68(LSD) "0" (A-Z)(0-9)(' ' , '-') 0th
2 P69(MSD) "" (A-Z)(0-9)(' ' , '-') Floor
3 P70(LSD) "1" (A-Z)(0-9)(' ' , '-') 1st
4 P71(MSD) "" (A-Z)(0-9)(' ' , '-') Floor
5 P72(LSD) "2" (A-Z)(0-9)(' ' , '-') 2nd
6 P73(MSD) "" (A-Z)(0-9)(' ' , '-') Floor
7 P74(LSD) "3" (A-Z)(0-9)(' ' , '-') 3rd
8 P75(MSD) "" (A-Z)(0-9)(' ' , '-') Floor
9 P76(LSD) "4" (A-Z)(0-9)(' ' , '-') 4th
10 P77(MSD) "" (A-Z)(0-9)(' ' , '-') Floor
11 P78(LSD) "5" (A-Z)(0-9)(' ' , '-') 5th
12 P79(MSD) "" (A-Z)(0-9)(' ' , '-') Floor
13 P80(LSD) "6" (A-Z)(0-9)(' ' , '-') 6th
14 P81(MSD) "" (A-Z)(0-9)(' ' , '-') Floor
15 P82(LSD) "7" (A-Z)(0-9)(' ' , '-') 7th
16 P83(MSD) "" (A-Z)(0-9)(' ' , '-') Floor

For Example: - If I want to set ‘-1’ instead of ‘0’ in ground floor.

Step 1 :- Keep elevator in inspection mode.

Step 2 :- Go to programming mode and set parameter “P68=’1’” and “P69=’-‘(dash).

Step 3 :- Make a connection between NOVA card terminal no ‘43’ and ‘2g’ input of Display.

Note:-

1. Follow similar procedure for different floor.

USER MANUAL Page 20


5. Status and Positions Information Power ON LED

These LED must always be ON, as soon as you switch ON the power supply of the NOVA
PCB.

24V VDD VCC


D64 D63 D8

5.1 Input/ Output status LED for VVVF mode-

INSDN
INSUP

SLOW
EL-CH

DNSL

HIGH
UPSL

MODE 2

FWD
RDY

REV
CGS
UTL

DTL

LGS

INS
MODE
D22 D23 D21 D20 D19 D18 D29 D30 D74 D75 D76 D66 D67 D68 D65

UP
INSPECTION
DN

HIGH
UP
SLOW
NORMAL
HIGH
DN
SLOW

5.2 Input/ Output status LED for 2-speed mode-


INSDN
INSUP

SLOW
EL-CH

DNSL

HIGH
UPSL

MODE 2

FWD
RDY

REV
CGS
UTL

DTL

LGS

INS

MODE
D22 D23 D21 D20 D19 D18 D29 D30 D74 D75 D76 D66 D67 D68 D65

UP
INSPECTION
DN

HIGH
UP
SLOW
NORMAL
HIGH
DN
SLOW

USER MANUAL Page 21


5.3 Input/ Output status LED for Hydraulic mode -

INSDN

DELTA
INSUP
EL-CH

DNSL

STAR

HIGH
UPSL

FWD

MTR
RDY
CGS

REV
UTL

DTL

LGS

INS
MODE 2
MODE
D22

D23

D21

D20

D19

D18

D29

D30

D74

D75

D76

D66

D67

D69
D70

D68
D65
UP
INSPEC
TION
DN

HIGH
UP
SLOW
NORM
AL
HIGH
DN
SLOW

Note-

This indicates LED is continuously ON


This indicates LED Gets ON for short interval of time at starting

USER MANUAL Page 22


6. Connection Details For Output Terminal

48
OUTPUTS FOR CONTROL

RL2
49 FORWARD

50
51 REVERSE

RL3
53

RL1
S1
52

OUTPUT RELAYS, MAX 220VAC 1A


55
RL4 S2
54
ULN 2804

58
RL5

56 BB/STAR
57

61
RL6

59 FAN/MTR
60

63
RL7

RC/DC
62

65
RL8

BZ/DO
64

NOVA +24V DC

USER MANUAL Page 23


7. Connection Details For Input Terminals
8. Connections Details For Call Registration
8.1 8 Stops (G+7) Down collective mode (without Extension Board):
8.2 6-Stops (G+5) Full Collective mode (without Extension Board)
8.3 Connection Details of Extension Boards:

DIP Switch selection

SW-1 SW-2 Remark


When connected
ON OFF
as EX-1
When connected
OFF ON
as EX-2

86 11 NOVA-
87 12 FL-EXT1
NOVA
88 13 ON

89 14

MODE NOVA EX - 1 EX - 2 11 NOVA-


FCL - 6 Y N N
DCL - 8 Y N N FL-EXT2
12
FCL - 8 Y Y N
DCL - 12 Y Y N 13 ON
FCL - 11 Y Y Y
DCL - 16 Y Y Y
14

• As per Requirement of the mode & no. Of Stop, Do the connection of


Extension Boards with Nova as shown in the above diagram.
• Set the DIP switch as shown in above as per the use of EX-1 & EX-2.
• Use Shielded cable for connection between Nova main board and Extension
board
8.4 All possible combinations with 2 extension boards:

MODE FULL COLLECTIVE DOWN COLLECTIVE


CALL
STOPS 6-STOP 8-STOP 11-STOP 8-STOP 12-STOP 16-STOP
COP-1 NOVA-3 NOVA-3 NOVA-3 NOVA-3 NOVA-3 NOVA-3
COP-2 NOVA-4 NOVA-4 NOVA-4 NOVA-4 NOVA-4 NOVA-4
COP-3 NOVA-5 NOVA-5 NOVA-5 NOVA-5 NOVA-5 NOVA-5
COP-4 NOVA-6 NOVA-6 NOVA-6 NOVA-6 NOVA-6 NOVA-6
COP-5 NOVA-7 NOVA-7 NOVA-7 NOVA-7 NOVA-7 NOVA-7
COP-6 NOVA-8 NOVA-8 NOVA-8 NOVA-8 NOVA-8 NOVA-8
COP-7 NOVA-9 NOVA-9 NOVA-9 NOVA-9 NOVA-9
CAR CALL

COP-8 NOVA-10 NOVA-10 NOVA-10 NOVA-10 NOVA-10


COP-9 NOVA-11 NOVA-11 NOVA-11
COP-10 NOVA-12 NOVA-12 NOVA-12
COP-11 NOVA-13 NOVA-13 NOVA-13
COP-12 NOVA-14 NOVA-14
COP-13 NOVA-15
COP-14 NOVA-16
COP-15 NOVA-17
COP-16 NOVA-18

LOP-1 UP NOVA-9 NOVA-11 NOVA-14 NOVA-15 EX1-3


DN NOVA-10 NOVA-12 NOVA-15 NOVA-16 EX1-4
LOP-2
UP NOVA-11 NOVA-13 NOVA-16
DN NOVA-12 NOVA-14 NOVA-17 NOVA-17 EX1-5
LOP-3
UP NOVA-13 NOVA-15 NOVA-18
DN NOVA-14 NOVA-16 EX1-3 NOVA-18 EX1-6
LOP-4
UP NOVA-15 NOVA-17 EX1-4
DN NOVA-16 NOVA-18 EX1-5 EX1-3 EX1-7
LOP-5
UP NOVA-17 EX1-3 EX1-6
DN NOVA-18 EX1-4 EX1-7 EX1-4 EX1-8
LOP-6
UP EX1-5 EX1-8
DN EX1-6 EX1-9 EX1-5 EX1-9
LANDING CALL

LOP-7
UP EX1-7 EX1-10
DN EX1-8 EX2-3 EX1-6 EX1-10
LOP-8
UP EX2-4
DN EX2-5 EX1-7 EX2-3
LOP-9
UP EX2-6
DN EX2-7 EX1-8 EX2-4
LOP-10
UP EX2-8
DN EX2-9 EX1-9 EX2-5
LOP-11
UP
DN EX1-10 EX2-6
LOP-12
UP
DN EX2-7
LOP-13
UP
DN EX2-8
LOP-14
UP
LOP-15 DN EX2-9

USER MANUAL Page 28


9. Connection Details of Display:
9.1 Binary/ Gray code Display:

9.2 Seven Segment display:

A, B, C, D, E ,
NOVA F, G ARE
SINKING
TLP 291-4

COM

36 37 38 39 40 41 42 44 45
DATA D
DATA C
DATA A

DATA E
DATA B

DATA G
DATA F

DN
UP

+24V

7 SEG INDICATOR
10. Connection Details for Duplex:

FOR COMMON LOP FOR SEPERATE LOP

NOVA NOVA NOVA NOVA


DUPLEX DUPLEX
(MASTER) (SLAVE) (MASTER) (SLAVE)

CONTROLLER A CALL CONTROLLER B CONTROLLER A CALL CONTROLLER B

82 D 82
U
83 P 83
NOVA-M NOVA-S
L
84 E 85
X
85 84
11. Connection details of Extension Board for Serial LOP-COP:

Pin No Description Remark


1 24V
2 GND Signal from
3 RX NOVA card
4 TX

17 24V
18 GND To Serial
19 A LOP/ COP
20 B

86 1

87 2
NOVA
NOVA-
88 3
SERIAL
89 4

17 18 19 20

To CAN based COP/ LOP


12. Error Code Description

LCD Display List of operational faults (Lower Priority)


SAFETY SIG. CUT RDY open during run (safety input)
CAR GATE OPEN CG open during run
CARGATE SW OPEN CG open too long
LANDING SW OPEN OS open during run
LANDING SW OPEN OS open too long
UP TERMINAL CUT Lift over travelled in Up Direction
DN TERMINAL CUT Lift over travelled in Dn Direction
STOP ACTIVATED. Stop input activated
LIFT OVERLOADED Overload device activated
PTC ACTIVATED... PTC temp exceeds set limit
ELE-CHK FAILED.. Contactor stuck

List of system faults (Higher Priority)


SLOWING REED FLT Slowing Reed fault
STOPING REED FLT Stopping Reed fault
CAR GATE SHORTED CG shorted
LANDING SW SHORT OS shorted
BRAKE FAULT Lift movement in no call condition
UP SLOW LS FLT Up slow safety absent
DN SLOW LS FLT Dn slow safety absent
If the programmed cycles to Gnd floor are
LOCK MODE
over

Status Meaning
SF If Ready signal absent (Safety Input)
CG If Car Gate signal absent
DS If Landing signal is absent
SL If slowing reed is activated
LV If stopping reed is activated
FR Fire mode activated
AR If ARD mode is activated
DO If IR door sensor is activated
AT If lift is in attendant mode

USER MANUAL Page 35


13.Important Instructions
 Note- If anyone wants to shut down / off the controller for long time so he
must shut off the UPS first and then Main Supply.
 Use shielded cable between Nova main board and Extension board.
 To avoid false call registration, short GND of 24V DC and C- ( 2 number Pin)
of nova card.

USER MANUAL Page 36


USER MANUAL Page 37
USER MANUAL Page 38