Ems II Unit 1&2 Notes
Ems II Unit 1&2 Notes
Stator
Rotor
The rotor and stator are separated by a small air gap ranges from 0.5 mm to 4 mm
depending on the power rating of the motor.
The 3-phase stator windings are wound for a definite number of poles depending
upon the requirement of speed, i.e., greater the number of poles, lesser is the speed
of the motor and vice-versa.
When a balanced 3-phase supply is fed to the stator winding a rotating magnetic
field (RMF) of constant magnitude is produced and this RMF induces currents in the
rotor circuit by electromagnetic induction.
This rotor is not connected electrically to the supply but has currents induced in it by
the electromagnetic induction from the stator.
Those 3-phase induction motors which employed squirrel cage rotor are known
as squirrel cage induction motors. Most of the 3-phase induction motors in the
industries use squirrel cage rotor because it has simple and robust construction
enabling it to operate in the most adverse environment. Although, it suffers from a
disadvantage of low starting torque.
The skewing of squirrel cage rotor conductors offers following advantages −
1. Explain the operation of slip ring induction motor with neat sketch and list out the
difference between squirrel cage rotor and slip ring rotor.
1. The stator of the 3 - phase induction machine consists of normal distributed AC
windings.
2. Balanced three phase voltages impressed on the stator, cause balanced three
phase currents to flow in the stator.
3. These stator currents cause a rotating flux pattern (the pattern is a flux
distribution which is sinusoidal with respect to the space angle) in the air gap.
4. The rotating flux pattern causes three phase induced EMFs in rotor windings
(again normal ac windings). These windings, if shorted, carry three phase-balanced
currents. Torque is produced as a result of interaction of the currents and the air gap
flux.
5. The rotor may also take the form of a squirrel cage arrangement, which behaves in
a manner similar to the short-circuited three phase windings.
In actual practice, the three coils form three windings distributed over several slots.
These windings may be connected in star or delta and three terminations are brought
out. These are conventional three phase windings which are discussed in greater detail
in the chapters on alternators. Such windings are present n the stator as well as rotor
2. A 40 A, 50 Hz induction motor runs at 576 rpm at full load. Determine: (a) the
synchronous speed and the number of poles. (b) the frequency of rotor currents (c) the
rotor speed relative to the revolving field.
(a) ns = 600 rpm , P = (120 X 50) / 600 = 10
(b) s = (600 – 576) / 600 X 100 = 4
F2 = 0.04 X 50 = 2 Hz
(c) Rotor speed relative to the revolving field = 6000 – 576 = 24 rpm
3. A 3-phase induction motor runs at a speed of 940 rpm at full-load when supplied
with power at 50 Hz, 3-phase. (a) How many poles does the motor have? (b) What is
its slip at full-load? (c) What is the corresponding speed of : (i) the rotor field wrt the
rotor surface (ii) the rotor field wrt the stator (iii) what is the rotor speed at twice full-
load slip?
(a) ns = 1000 rpm, P = (120 X 50) / 1000 = 6
(b) s = (1000 – 940)/1000 X 100 = 6%
(c) (i) 1000 – 940 = 60 rpm (ii) 960 + 40 = 1000 rpm (iii) 2s = 12 %
n = 1000 – (12 X 1000)/100 = 880 rpm
the principle of operation of a synchronous motor, assume that the armature winding
(laid out in the stator) of a 3-phase synchronous machine is connected to a suitable
balanced 3-phase source and the field winding to a D.C source of rated voltage. The
current flowing through the field coils will set up stationary magnetic poles of alternate
North and South. On the other hand, the 3-phase currents flowing in the armature
winding produce a rotating magnetic field rotating at synchronous speed. In other
words there will be moving North and South poles established in the stator due to the
3-phase currents i.e. at any location in the stator there will be a North Pole at some
instant of time and it will become a South Pole after a time period corresponding to
half a cycle. (After a time = 1/2f , where f = frequency of the supply). Assume that the
stationary South pole in the rotor is aligned with the North pole in the stator moving in
clockwise direction at a particular instant of time, as shown in Figure below. These
two poles get attracted and try to maintain this alignment (as per Lenz’s law) and
hence the rotor pole tries to follow the stator pole as the conditions are suitable for the
production of torque in the clockwise direction. However, the rotor cannot move
instantaneously due to its mechanical inertia, and so it needs some time to move. In
the mean time, the stator pole would quickly (a time duration corresponding to half a
cycle) change its polarity and becomes a South Pole. So the force of attraction will no
longer be present and instead the like poles experience a force of Repulsion as shown
in Figure below. In other words, the conditions are now suitable for the production of
torque in the anticlockwise direction. Even this condition will not last longer as the
stator pole.
Now, the stator poles are revolving with synchronous speed (let’s say clockwise). If
the rotor position is such that, N pole of the rotor is near the N pole of the stator (as
shown in first schematic of above figure), then the poles of the stator and rotor will
rotating with synchronous speed, and they rotate around very fast and interchange their
position. But at this very soon, rotor cannot rotate with the same angle (due to inertia),
and the next position will be likely the second schematic in above figure. In this case,
poles of the stator will attract the poles of rotor, and the torque produced will be
to a rapidly reversing torque, and the motor
will not start. But, if the rotor is rotated up to the synchronous speed of the stator by
means of an external force (in the direction of revolving field of the stator), and the
rotor field is excited near the synchronous speed, the poles of stator will keep attracting
the opposite poles of the rotor (as the rotor is also, now, rotating with it and the
position of the poles will be similar throughout the cycle). Now, the rotor will undergo
unidirectional torque. The opposite poles of the stator and rotor will get locked with
each other, and the rotor will rotate at the synchronous speed.
5. Explain the speed control methods used in induction motor with neat sketch.
Speed control by changing applied voltage From the torque equation of the induction
machine given in eqn.17, we can see that the torque depends on the square of the
applied voltage. The variation of speed torque curves with respect to the applied
voltage is shown in fig. 18. These curves show that the slip at maximum torque sˆ
remains same, while the value of stall torque comes down with decrease in applied
voltage. The speed range for stable operation remains the same.
Further, we also note that the starting torque is also lower at lower voltages. Thus,
even if a given voltage level is sufficient for achieving the running torque, the machine
may not start. This method of trying to control the speed is best suited for loads that
require very little starting torque, but their torque requirement may increase with
speed.
The variation of torque with speed is such that T ∝ ω2. Here one can see that it may
be possible to run the motor to lower speeds within the range ns to (1 − sˆ)ns. Further,
since the load torque at zero speed is zero, the machine can start even at reduced
voltages. This will not be possible with constant torque type of loads.
One may note that if the applied voltage is reduced, the voltage across the magnetizing
branch also comes down. This in turn means that the magnetizing current and hence
flux level are reduced. Reduction in the flux level in the machine impairs torque
production
The slip at maximum torque eqn.18 is dependent on the rotor resistance. Therefore, we
may expect that if the rotor resistance is changed, the maximum torque point shifts to
higher slip values, while retaining a constant torque. Figure 28 shows a family of
torque-speed characteristic obtained by changing the rotor resistance.Rotor resistance
variation
Cascade control The power drawn from the rotor terminals could be spent more
usefully. Apart from using the heat generated in meaning full ways, the slip ring output
could be connected to another induction machine. The stator of the second machine
would carry slip frequency currents of the first machine which would generate some
useful mechanical power. A still better option would be to mechanically couple the
shafts of the two machines together. This sort of a connection is called cascade
connection and it gives some measure of speed control as shown below.
Let the frequency of supply given to the first machine be f1 , its number poles be p1,
and its slip of operation be s1 . Let f2, p2 and s2 be the corresponding quantities for the
second machine. The frequency of currents flowing in the rotor of the first machine
and hence in the stator of the second machine is s1f1. Therefore f2 = s1f1. Since the
machines are coupled at the shaft, the speed of the rotor is common for both. Hence, if
n is the speed of the rotor in radians,
Note that while giving the rotor output of the first machine to the stator of the second,
the resultant stator mmf of the second machine may set up an air-gap flux which
rotates in the same direction as that of the rotor, or opposes it.
UNIT 2
1. With neat sketch explain about the protection circuit for induction motor.
Overcurrent Protection
Overload Protection
Overcurrent Protection:
Overcurrent faults occur mostly and mainly due to ground faults and short circuit
faults. When such type of fault occurs at any place a large amount of leakage current
start to flow from the circuit and can cause huge damage to not only in the system but
also someone’s life. Therefore, fuses and circuit breakers are used that show quick
response towards fault when such type of fault (large) current passes from the system.
That’s why to protect the system from the short-circuiting and also from the overload
current we use MCCB’s or Fuses of specific ratings.
When the amount of current larger than the rated current of the device passed through
the system such devices operates and open the circuit until the fault is removed from
the system. We can also say that when a little higher amount of current beyond the
rating of motor pass Overload protection starts operating and prevent the machine from
any hazard. If the overload current persists for a long span of time then things and
machines get damaged. Overload protection doesn’t trip even if a high value of current
flows for a short span of time such as the starting of the motor. Overcurrent protection
rating is always selected with so much care that it must provide
Overload Protection:
Whenever motor draws too much amount of current to fulfil the load demand and if
load demand goes beyond the allowable limit, such condition or situation is called as
Overload. An electric overload occurs when an excessive amount of current passes
through electric wires or from motor windings. The wires or windings can heat and
melt, with the risk of starting a fire. Therefore, overload protection is used in it. It is
basically a type of safety protection when the motor draws too much current or
overload current and causing the overheating of the electrical machine. So that’s why
we use a different kind of overload relays to avoid the system or machine from
overheating due to the excessive amount of current drawn for a too long period.
Sometimes motor starters come with built-in overload relay.
Overload relays are classified on the base of different tripping classes. Tripping class is
a term used in overload relay designing which means how much seconds an overload
relay takes to trip. Overload protections are provided with the help of an overload
relay.
enough protection against high current and also it must allow enough current without
operating the overcurrent protection for the motor to operate under heavy mechanical
load.
2. With the neat sketch explain about the ground fault protection
.
In an isolated neutral system (see Figure 1), the neutral has no intentional connection
to ground: the system is connected to ground through the line-to-ground capacitances.
Single line-to-ground faults shift the system-neutral voltage but leave the phase-to-
phase voltage triangle intact. 3 A B C Ground fault G CA CB CC CAB CAC CBC N
Figure 1 Isolated Neutral System For these systems, two major ground fault current
magnitude-limiting factors are the zerosequence line-to-ground capacitance and fault
resistance. Because the voltage triangle is relatively undisturbed, these systems can
remain operational during sustained, low-magnitude faults. Self-extinction of ground
faults in overhead-ungrounded lines is possible for low values of ground fault current.
At higher magnitudes of fault current, faults are less likely to selfextinguish at the fault
current natural zero-crossing because of the high transient recovery voltage. Later, we
discuss how a resonant-grounded system damps this recovery voltage rise, thereby
increasing the likelihood of causing the ground fault to self-extinguish. Zero-sequence
[9], or three-phase voltage relays can detect ground faults in ungrounded systems. This
method of fault detection is not selective and requires sequential disconnection or
isolation of the feeders to determine the faulted feeder. A sensitive, directional ground
varmetric element is the typical alternative to sequential disconnection [2]. These
elements respond to the quadrature component of the zero-sequence current with
respect to the zero-sequence voltage. Later we introduce a new directional element that
uses the measured impedance as the measurand for differentiating forward and reverse
ground faults
3. With the neat sketch explain about the phase fault protection.
fault current limiters (FCLs) have been utilized in order to obtain optimum settings of
suitable to protect microgrid with islanded and grid-connected operating capabilities.
Similarly, several other studies have been proposed with or without utilizing FCLs
[23,24] . This scheme is cheaper as it does not need any additional piece of equipment
unlike in adaptive protection scheme. ...
... It is to be noted that the values of fault currents are relatively lower in microgrids as
compared to that in the main grid which is mostly protected by using standard IDMT
type characteristic curves of DOCRs. Therefore, adopting the same characteristic
curves for protection of microgrids will result in higher operating times of the relays
[22][23][24] . So, the microgrids may be forced to be under stress for a longer period
during faults which may damage the entire system.
Since the input to an ac regulator is ac, it is always line commutated. Therefore, forced
commutation is not required. As such the circuits of ac regulators are quite simple.
Two types of controls are used in ac regulators. These are known as integral cycle
control and phase control.
Direct Online Starter – DOL Starter Wiring Diagram for Motors
DOL Starter for Motors – Direct Online Starter Diagram, Working,
Types & Applications
The induction motor draws a huge amount of current at startup. This starting current
can damage the motor windings. In order to avoid any damage, we use different
techniques to reduce the starting current using Motor Starter. These techniques
depend on the motor ratings and the load connected to the motor. Apart from this,
the motor starter also protects the motor from overloading and overcurrent.
The Direct Online or DOL starter employs full voltage or across the line starting
technique where the motor is directly connected to full voltage through MCCB or
circuit breaker and relays for overload protection. This is why such a starter is used
with induction motors rated below 5 hp.
Following is the basic wiring diagram of a DOL (Direct Online Starter).
The Star Delta Starter is a very common type of starter and is used
extensively as compared to the other type of starting methods of the
induction motor. A star delta is used for a cage motor designed to run
normally on the delta-connected stator winding. The connection of a
three-phase induction motor with a star-delta starter is shown in the
figure below:
Apart from the Power switches & logic circuitry, other protection components such as
the circuit breaker or fuse, magnetic contactor for isolation & an OLR (Overload
relay) for prevention of overcurrent is used.
A bypass switch is also used to resume the full voltage across the motor when it
attains the full rated speed.
Working Principle of Soft Starter
The main component used for controlling the voltage in a soft starter is a thyristor. It
is a controlled rectifier that starts conduction of the current flow in only one direction
when a gate pulse is applied called the firing pulse.
The angle of the firing pulse determine how much of the input voltage cycle should be
allowed through it. Since AC swings between maximum & minimum peak forming a
complete 360° cycle, we can use the angle of firing pulse to switch on the thyristor for a
specific duration and control the supplied voltage.
The firing pulses can vary between 0° to 180°. The decrease in the angle of firing
pulse increases the conduction period of thyristor, thus allowing high voltage through
it.
Two such thyristors are connected in back-to-back formation for each phase. So it can
control the current in both directions. Each half cycle, the firing angle
The three pairs of thyristors, each pair for individual phase are used for controlling the
voltage to start & stop the motor. The thyristor conduction period depends on the firing angle
controlled by the logic circuitry.
Very simple and needs just one More complicated in design and
contactor needs 3 contactors
Suitable for high starting torque Not good for applications with
applications high starting torque
Lower cost, and requires less Costs more, and requires more
maintenance maintenance
It cannot prevent the mechanical There are no mechanical jerks at starting &
jerks at startup. stopping of the motor.
It has a very simple design. It has a complex design with logic circuitry.
It does not offer a soft stop feature. It also offers a soft stop feature.
It is used for starting the motor in It can be used for starting the motor in
unloaded conditions. both loaded & unloaded conditions.
It has a simple design but too many wire It has a complex design but with few
connections. wire connections.
Switching between star & delta causes an The power supply is continuous &
open circuit & momentarily power loss there is no power loss. Hence no such
which causes current transients. transients.
It is cheaper & less efficient than a soft It is expensive but more efficient than
starter. a star-delta starter.
It is used for running large induction It is used for running conveyor belts,
motors in unloaded conditions. cranes, the motor with belts & pulley.
COMPARISON OF DOL, STAR DELTA, AUTO TRANSFORMER AND SOFT STARTERS
Economical
5-10 times the 5-10 times the High in-rush
Direct-on- and Higher
full load current full load torque current
Line (DOL) starting torque.
Inrush current
can be reduced
Starting
2-3 times the 2-3 times the to one-third
Star-Delta torque will
full load current full load torque when
Starter reduce
compared to
DOL.
Inrush current
can be reduced
Starting
2-3 times the 2-3 times the to one-third
Auto- torque will
full load current full load torque when
transformer reduce
compared to
DOL.
Inrush current
can be
1.5-2.5 times Starting
3-5 times the reduced.
the full load torque will be
Soft starter full load current Starting torque
torque less
can be
controlled.
Speed and
1.5-2.5 times torque control,
1.1-1.5 times
Variable the full load communication Higher cost
full load current
Speed drive torque and Energy
saving.