Classification of the Building
Case No. 2: Buildings Less Than 60 m High Note that for structures less than 60 m high the risk
of flashes to the sides of the building is low, and therefore protection is not required for the
vertical sides directly below protected areas.
AIR TERMINAL BASE
Specifications
Material: Copper
Weight: 20gm
Diameter: 14.2mm
Description: Copper Air Terminal Base
Reference:
https://www.indiamart.com/proddetail/terminal-base-
13439207597.html
Tripod Support
The tilting support placed on the base of each of the legs allows
Specifications:
Type: Stranded (Copper)
Electrical resistivity <0,018 μΩm.
Diameter: 8.9mm
Cross Section Area (mm2): 50
Electrical resistance ≤0,391 Ω/km.
Tensile strength 200 – 450 N/mm2.
BONDING
Pressure Connector for Main Conductor and Secondary Conductor
A device that establishes a connection between two or more conductors or between one or more
conductors and a terminal by means of mechanical pressure and without the use of solder.
13 132 +1.42
X1= 11.27; Y1 = − 1.4 (11.27) + 2(1.4) = − 43.59
13 132 +1.42
X2 =1.73; Y1 = − 1.4 (1.73) + 2(1.4) = 44.99
Coordinates of the Center: (1.73, 44.99)
19 192 +72
X1= 24.30; Y1 = − 7 (24.30) + 2(7) = − 36.67
19 192 +72
X2 =-4.51; Y1 = − 7 (−4.51) + 2(7) = 44.77
d = 19 meters
𝟏𝟗𝟐
𝒑 = 𝟒𝟓 − √𝟒𝟓𝟐 − = 𝟏. 𝟏𝟎𝟏𝟒 𝒎𝒆𝒕𝒆𝒓𝒔
𝟐
The height of the air-termination rods h should always be greater than the value of the
penetration depth p determined to ensure that the rolling sphere does not touch the structure to be
protected.
FINAL DESIGN